EXCESS CABLE TO BE COILED AND BURIED JUST BELOW G.L.

MAX. 300mm ABOVE GROUND. CABLE ENDS TO BE PROTECTED


WITH ELECTRICAL INSULATION TAPE.
(RED FOR REFERENC ELECTRODE & YELLOW FOR COUPON)
MARK ON TAPE TAG, 'RE' OR 'CN' TO SUIT 09.04.2020

ELECTRICAL WARNING ELECTRICAL WARNING


GROUND LEVEL TAPE GROUND LEVEL TAPE

VARIABLE ACCORDING TO DEPTH OF

TRENCH BACKFILL
PIPE. SEE PIPELINE REF. DWG N°
000-TCN1800523-PL-DR,
000-TCN1800524-PL-DR

1 REFERENCE ELECTRODE
NATIVE SOIL WITH 1 CORE 10mm²
CABLE (BLACK) COUPON WITH 2 CORE 6mm²
XLPE/PVC/SWA/PVC CABLE
1 CORE 10mm² XLPE/PVC (BLACK)
CABLE (BLACK) [LARGEST
COMPATIBLE CABLE]
PIN BRAZE PIPE
2 CORE 6mm² XLPE/PVC/SWA/PVC
CONNECTION C/W ROYSTON
Pb CABLE (BLACK)
PIN BRAZE PIPE HANDYCAP REPAIR
CONNECTION C/W ROYSTON
HANDYCAP REPAIR

INCLUDE TYPICAL
STRESS RELIEF LOOP

RE
REFERENCE COUPON
ELECTRODE Cn

RE Cn
100mm

PIPE TRENCH DEPTH LEVEL


27.01.2020

2 07-APR-2019 CarlosVieira José Faria Pedro Silva ISSUED FOR CONSTRUCTION

UPDATES ACCORDING 000-BCL1901251-DR-0_CMT01_FIA01 /


1 05-DEC-2019 Chris Coley Rui Pintado Pedro Silva
000-BCL1901251-EL-DR-0_CMT03

Pb Index Date Issued Reviewed Released Revision Details

OWNER: OWNER'S ENGINEER:

PLAN VIEW

27.01.2020
100mm

100mm

PROJECT: PROJECT No.:

SARIR GAS UTILIZATION Project J-22 OKP037


Date Name Title Supplier
CATHODIC PROTECTION -

BAC
®
10" OR 12" PIPELINE TYPICAL REFERENCE ELECTRODE & POLARISATION
REFERENCE RE Cn Issued
100mm COUPON
ELECTRODE
1 COUPON INSTALLATION. TYPICAL TEST STATION C O R R O S IO N C O NTROL
Reviewed

INSTALLATION. GC-2 TO GC-1 & GC-2 TO GC-3


Released Supplier Doc. No.
LEGEND DESCRIPTION MATERIAL REFERENCE CR34982-015
Document No. Revision Status
RE REFERENCE ELECTRODE (RE). Cu/CuSO4 2
000-BCL1901251-EL-DR AP
Owner Document No.
Cn POLARISATION TEST COUPON. 50cm² EXPOSED SURFACE. CARBON STEEL. Format Scale

Sr-J22-E-24548 A3 NTS
1 PIN BRAZE - DIRECT BRAZED PIN CONNECTION.
Pb BAC STANDARD ITEM Sheet Sheets
PROPRIETRY ITEM
DRAWINGS REF: NUMBER: 1 2
COPPER CORE. Internal Status list: IE - In Edition; IP - In progress; CH - Checked; RF - Refused; AC - Approved with comments; NA - Not approved; AP - Approved; EL - Eliminated; AB - As built;
TYPICAL TEST POST INSTALLATION DETAIL 000-BCL1901251-EL-DR-SH2 CABLE - 2 CORE 6mm² Cu/XLPE/PVC/SWA/PVC. INS. OB - Obsolete; AA - Awaiting for External Approval; AE - Approved by External Entity; ACE - Approved with Comments by External Entity; REE - Refused by External Entity;
XLPE/PVC/SWA/PVC
MATERIAL / EQUIPMENT DATA SHEETS 000-BCL1900654-EL-DS COLOUR BLACK © PROMANEC, Lda. No part of this document may be copied, photocopied, reproduced, transmitted or otherwise duplicated on any medium without the prior written consent ofPROMANEC, Lda.
INSULATION The information contained in this document is proprietary and may not be used for any purpose other than that for which it has been supplied byPROMANEC, Lda. nor may such information be
disclosed to third parties without the prior written consent of, and upon such terms as may be stipulated byPROMANEC, Lda. This document and all copies made thereof shall be returned on demand.
Ø114
TEST POST COVER Co

C/W 3No. S/S


FIXING SCREWS
(3mm WALL) COUPON CONNECTION.
PIPE CONNECTION.
10mm² SC 2 CORE 6mm
XLPE/PVC/SWA/PVC XLPE/PVC/SWA/PVC

TERMINAL SCREWS

250mm
M6 x 30 BRASS C/W
PHENOLIC BOARD REFERENCE
NUTS & WASHERS
155 x 75 x 3mm TB ELECTRODE. 1 x 10mm²
XLPE/PVC

SECTION A~A

2250mm
NOTES:
TEST POST TP
3" NB SCH 10 CONCRETE BASE. 325 x
325 x 1000mm 1. POST AND COVER HOT DIP GALVANISED
(3mm WALL) Ba

AND POWDER COATED.


2. ALL DIMENSIONS IN mm

Index Date Issued Reviewed Released Revision Details

OWNER: OWNER'S ENGINEER:

ؽ" CONCRETE
KEYING BARS
100mm

1
PROJECT: PROJECT No.:

UNDERGROUND CABLES IN TO OKP037


SARIR GAS UTILIZATION Project J-22
SECTION C~C THE TEST POST ARE
Ø89mm SUGGESTED TO INCLUDE A Date Name Title
CATHODIC PROTECTION -
Supplier

BAC
®
STRESS RELIEF LOOP Issued TYPICAL REFERENCE ELECTRODE &
POLARISATION COUPON INSTALLATION. C O R R O S IO N C O NTROL
Reviewed

TYPICAL TEST STATION INSTALLATION. GC-2 TO


Released Supplier Doc. No.
1 GC-1 & GC-2 TO GC-3 CR34982-015
Document No. Revision Status
DRAWINGS REF: NUMBER: LEGEND DESCRIPTION MATERIAL REFERENCE
000-BCL1901251-EL-DR 0 AP
TYPICAL REFERENCE ELECTRODE & POLARISATION COUPON INSTALLATION DETAIL 000-BCL1901251-EL-DR-SH1 HOT DIP GALVANISED & Owner Document No. Format Scale
GC-2 TO GC-1 LINE DRAWING SHOWING TEMPORARY MG ANODE AND PERMANENT R.E. 000-BCL1901249-EL-DR TP TEST POST. 3"NB
POWDER COATED
& COUPON AND TEST POST DISTRIBUTION. Sr-J22-E-24548 A3 NTS
GC-2 TO GC-3 LINE DRAWING SHOWING TEMPORARY MG ANODE AND PERMANENT R.E. 000-BCL1901250-EL-DR HOT DIP GALVANISED &
Co TEST POST COVER Sheet Sheets
& COUPON AND TEST POST DISTRIBUTION. POWDER COATED
POLARISATION COUPON DETAIL 000-BCL1901253-EL-DR 2 2
1 GA TYPICAL TEMPORARY Mg ANODE INSTALLATION 000-BCL1901248-EL-DR TB TERMINAL BOARD. 8 TERMINALS BAC MANUFACTURED ITEM Internal Status list: IE - In Edition; IP - In progress; CH - Checked; RF - Refused; AC - Approved with comments; NA - Not approved; AP - Approved; EL - Eliminated; AB - As built;
MATERIAL / EQUIPMENT DATA SHEETS 000-BCL1900654-EL-DS OB - Obsolete; AA - Awaiting for External Approval; AE - Approved by External Entity; ACE - Approved with Comments by External Entity; REE - Refused by External Entity;
© PROMANEC, Lda. No part of this document may be copied, photocopied, reproduced, transmitted or otherwise duplicated on any medium without the prior written consent ofPROMANEC, Lda.
SPARK GAP INSTALLATION DETAIL AT INSULATION FLANGE. 000-BCL1902161-EL-DR Ba CONCRETE BASE (BY OTHERS). 325 x 325 x 1000mm CONCRETE BASE (BY OTHERS) The information contained in this document is proprietary and may not be used for any purpose other than that for which it has been supplied byPROMANEC, Lda. nor may such information be