Professional Documents
Culture Documents
By Design
BERKSHIRE
A Standard Guide
Berkshire Accessibility
by Design
Accessibility
By Design
(Now includes Changing Places)
BERKSHIRE
A Standard Guide
A LABC Publishing Publication
1
Foreword
This design guide seeks to present the promoters cannot accept any responsibility for
requirements of the Building Regulations 2010, incorrect information. Building Regulations are
Approved Document M – Access to and Use of subject to change and if in doubt you should
Buildings and BS8300 - Design of buildings and contact your Local Authority Building Control office
their approaches to meet the needs of disabled to check if the information is still current.
people, in terms of good building design. Material from the Building Regulations, Approved
This guide does not encompass every aspect, or Document M, and BS8300 is as far as possible
taken from the most current versions.
have all the answers, but covers the main design
considerations. We hope this guide will raise The Council gratefully acknowledges LABC and
awareness, and prove especially useful as a RIBA Publications for permission to reproduce their
practical tool, providing a better understanding of material in this publication.
accessibility issues in the Built Environment. © Crown Copyright 1991
Whilst every care has been taken to compile the Reproduced with the permission of the controller
information in this guide, the publishers and of TSO.
2
Contents
DWELLINGS ..................................................................................................................... 44
Accessibility ............................................................................................................................. 44
Circulation ............................................................................................................................... 45
3
Berkshire Building Control
Staff Development
● Qualified staff to deal with all types of buildings
and projects.
● Continuing Professional Development for staff
to ensure they keep up to date with changes.
● Working in partnership within the county and Alternative Languages and Formats
at national level
● Would you or anyone you know like to receive
● A national service with local delivery. this document in an alternative format? If so,
Part of the Development Team please contact your local area Building Control
office.
● Early involvement in the project reduces the
potential for design problems arising during
construction. The Building Regulations
● Provision of good and timely advice on The Building Regulations, when first introduced,
technical and procedural matters. were very prescriptive. This made enforcement of
● One stop shop for access to other council the Regulations easier for Building Control
services and the Fire Authority. professionals, however it stifled the design of
buildings.
Partnerships
● Partner agreements with developers, architects Modern Building Regulations are non-prescriptive
etc to provide a consistent approach in plan and allow for more innovative design. Although
checking across the country. methods of complying with the requirements are
detailed in the Approved Documents, they
Customer Focus demonstrate only one or a limited number of ways
● Inspection regimes to suit customers with same of compliance.
day inspections available in most cases. This style of Regulations has increased the role of
● Advice on the changes to Regulations. Building Control. We are no longer enforcers of
● Technical guidance sheets, design guides and the Regulations but contributors to the overall
other related information. design of buildings.
4
Berkshire Building Control Contacts
Windsor Slough
&
Maidenhead
West Reading
Berkshire Bracknell
Wokingham Forest
Tel: 01635 519356 Tel: 0118 937 2449 Tel: 0118 974 6376
Fax: 01635 519888 Fax: 0118 937 2109 Fax: 0118 974 6385
Email: buildingcontrol@westberks.gov.uk Email: building.control@reading.gov.uk Email: building.control@wokingham.gov.uk
Web: www.westberks.gov.uk Web: www.reading.gov.uk Web: www.wokingham.gov.uk
To help us work more effectively with designers and developers, we produce a number of publications that are
These include general basic advice through to technical solutions and design guides for the more technically
minded customers.
If you wish to find out more about Building Control in your area, please contact your local office. We look
5
Design & Access Statements (DAS)
6
Design & Access Statements (DAS)
Applications requiring a full DAS include new and ● Visibility of signage – size and contrast for
substantially extended buildings, or changes of use people with impaired vision.
where the intended use is:
● Interpretation and Braille facilities.
● Shops and commercial uses, restaurants, public
houses and bars, offices, banks, public buildings, ● Internal corridors – widths, obstructions,
leisure, assembly and recreation facilities, mixed gradients.
use developments, churches, schools/colleges, ● Internal steps/ramps – height, width, guarding,
hotels, industrial, storage and general, listed rise and going.
buildings etc.
● Lifts – size, height of controls.
● Residential purposes such as flats, houses and
bungalows, nursing or old people’s homes, ● WC accommodation – size, layout, number.
student accommodation etc. ● Spectator seating – number of spaces, choice
Applications will not generally require a DAS if the of viewing point, other facilities.
works are for altered or extended dwellings, i.e.
● Access to special facilities – meeting rooms,
houses, bungalows and flats. Similarly, minor
alterations or extensions to other uses may not swimming pools, sports equipment, etc.
require a statement where it can clearly be seen ● Usability of the building/facilities – to meet the
that the accessibility of the building is not affected. DDA.
● Management arrangements – for assisted
Matters for consideration
access and means of escape.
These include but are not exclusively:
● Special considerations need to be given to
● Disabled parking provision or setting down
listed buildings, development in conservation
points or garaging.
areas and other buildings or spaces of special
● Approach routes to building – way finding interest.
signage, gradient, width, surface finish.
● External hazards/features – hard landscaping, Ongoing obligations for owners/occupiers
projections, furniture. The DAS should be amended to reflect any
● External steps/ramps – gradient, width, subsequent decisions reached on site so that any
guarding and heights. new owner or occupier can be aware of the
● Entrances – primary and secondary. rationale used in making decisions which impact on
accessibility and their ongoing obligations under the
● Doors – operation, size, level threshold,
DDA. An up to date DAS can form part of the
automatic, controls.
“Seller’s Pack” which will help to inform future
● Entrance lobbies – size, manoeuvrability. owner/occupiers of the access provision in the
● Reception – counter height. building.
● Aids for hearing impaired people – induction Examples of DAS templates can be found on
loop. Berkshire Building Control webpages.
7
ACCESS TO BUILDINGS
● For disabled people, car access is vital. In car ● Guidance on designated parking, ticket
parks, provision should be made for disabled dispensing machines, vehicular control barriers
drivers and cars carrying disabled passengers. and multi-storey car parks can be found in BS
Parking should be provided as near to the 8300.
principal entrance as possible and under cover ● The recommended numbers of reserved
is desirable. If payment is required, provide
spaces vary in accordance with the type and
level and unobstructed access to pay and
capacity of car parks as follows:
display units.
● The surface of a designated parking bay should Car parks associated with
be firm and level, slip resistant and have a employment premises and provided
1200mm transfer zone alongside and at the for employees and visitors.
rear of the vehicle.
● One space for each disabled employee plus
● If people need to obtain tickets for pay and 5% disabled visiting motorists. BS 8300
display parking, the ticket dispensing machines 4.2.1.2.
need to be accessible to wheelchair users and
people of short stature. They should be Car parks associated with shopping
adjacent to the designated parking and have areas, leisure or recreational facilities.
controls between 750mm and 1200mm from
ground level. ● One space for each disabled employee plus
6% of the total capacity for visiting disabled
motorists. A further 4% of the total capacity
should be enlarged standard spaces. BS
8300 4.2.1.1.
● Designated disabled car parking spaces should
be signposted using the international symbol
of disability, which should also be painted on
the ground.
● Signage with its lower edge 1000mm above
the ground to identify parking space when
road markings obscured e.g. by snow or
fallen leaves, with the words ‘Blue Badge
Holders Only’.
Fig. 1
8
ACCESS TO BUILDINGS
External Travel
● Routes of travel across grass or paved areas ● At changes in level and to slopes steeper than
should be highlighted. This can be achieved by 1:15 a handrail and kerb should be provided.
contrasting colour, texture or by directional A lower rail and kerb should be provided as a
paving. guide for partially sighted people using canes.
● Covers and gratings should be flush with
paving, slots in gratings should be no more
than 13mm wide. Diameter of circular holes in
gratings should not be more than 18mm.
BS 8300 5.6.
Fig. 2
uncontrolled crossings.
800
Fig. 4
9
ACCESS TO BUILDINGS
External Hazards
Fig. 5
Fig. 8
Fig. 6
10
ACCESS TO BUILDINGS
● There should be a convenient access into the ● Clearly signposted steps should be provided
building for disabled people, whether they are when the rise of the ramp exceeds 300mm.
visitors to the building or work in it and The surface of the ramp should be slip resistant
whether they arrive on foot or in a wheelchair. and of a colour that contrasts visually with that
● If space outside the principal entrance is of the landings.
restrictive, an alternative accessible entrance in
common use should be provided. Fig. 9 Relationship of ramp gradient to the
● Car parking spaces should be provided going of a flight
adjacent to the principal entrance or the
accessible entrance in common use.
11
ACCESS TO BUILDINGS
Stepped Access
● A corduroy hazard warning surface should be ● Going of each step should be between
provided at top and bottom landings of a series 280mm and 425mm.
of flights to give advance warning of a change ● Rise and going of each step should be
in level. consistent throughout the flight.
● Rise of each step should be between ● Width of the flight should not be less
150mm and 170mm. than 1.2m.
For schools the preferred dimensions are 150mm rise and 280mm going
Fig. 11 Stepped access – key dimensions and use of hazard warning surface
12
ACCESS TO BUILDINGS
Stepped Access
HANDRAILS
Fig. 12 External steps and stairs –
key dimensions ● Should be between 900mm and 1000mm above the
surface of the ramp.
● Should be continuous along the flights and landings of
steps and ramps.
● Should extend at least 300mm beyond the top and
bottom of ramps and a flight or flights of steps whilst not
projecting onto an access route.
● Should contrast visually from the background without
being reflective.
● The surface should be slip resistant and not cold to
Fig. 13 Examples of acceptable step the touch.
profiles and key dimensions for
external stairs ● The profile should be circular with a diameter of
between 40mm and 45mm or oval, preferably with a
diameter of 50mm.
● Should protrude no more than 100mm into the surface
width of ramp or stairs where this would impinge on
the stair width
requirement of
Approved Fig. 14 Handrail design
Document B
(Fire Safety).
● Should have a
clearance of
between 60mm
and 75mm
between the
handrail and any
adjacent wall
surface.
● For all buildings
used by the general
public and buildings
designed principally
for children; a
second rail should
be installed with its
top surface 600mm
from the ramp
surface or pitch line.
BS 8300
13
ACCESS TO BUILDINGS
Accessible Entrances
14
ACCESS TO BUILDINGS
Accessible Entrances
15
ACCESS WITHIN BUILDINGS
Entrance Lobbies
● Where entrance lobbies are incorporated in ● The door opening widths should apply to the
buildings, adequate space must be provided inner doors as well as the outer doors.
between doors. There should also be space ● Lighting to reduce the contrast between the
for someone assisting the wheelchair user and outside and the building’s interior should be
for someone passing in the opposite direction. considered.
● Thresholds should be flush, 15mm maximum, ● The floor surface should be level, slip resistant
at both doorsets. and not impede the movement of wheelchair
or crutch users. Avoid coir matting and ensure
● Mat wells should be flush (including the any changes in floor materials do not create
surrounds), close fitting and firm. potential trip hazards.
16
ACCESS WITHIN BUILDINGS
Entrance Hall and Reception Area
17
ACCESS WITHIN BUILDINGS
Internal Doors
Design considerations similar to those for entrance doors apply to internal doors
Refer to Table 2 and Fig. 15.
● The force needed to open the door manually ● Incorporate low-level protection from
should not exceed 30 Newtons at any point in wheelchairs. Thresholds should be level with
the full opening cycle. adjacent floor finishes.
● Doors should be distinguishable from the ● Fire doors particularly those in corridors should
adjacent facades, as should be ironmongery be held open with an electro-magnetic device,
(i.e. pull handles) from the actual door itself. but self-close when:
● Lever handles are preferable to knob sets. ■ Activated by a smoke alarm or
fire alarm.
■ Power supply fails.
■ Activated by a hand operated switch.
● Fire doors to individual rooms should be fitted
with swing-free devices that close when
activated by smoke detectors, fire alarms and
power failure.
For guidance on fire doors and
Fig. 17 self-closers see Approved Document M
and BS 8300
18
ACCESS WITHIN BUILDINGS
19
ACCESS WITHIN BUILDINGS
Internal Stairs
Guidance as for stepped access except: ● The going of each step should be at least
● It is not reasonable to require a hazard warning 250mm.
surface at the head of internal stairs (since there ● The provision for handrails is the same as
is no recognised warning surface for use for stepped access.
internally, which can be guaranteed not to
● Landings should be of an adequate size to allow
constitute a trip hazard when used alongside
persons to rest between flights whilst not
flooring surfaces with different frictional
causing an obstruction to other people (width
resistance characteristics).
and length should be as great as the smallest
● A flight between landings normally contains no width of the flight).
more than 12 risers, but in very exceptional
● Landings should be clear of permanent
circumstances 16 risers in small premises may
obstruction.
be provided where the plan area is restricted.
● The rise of each step should be between
150mm and 170mm.
20
ACCESS WITHIN BUILDINGS
Vertical Circulation within the Building
A passenger lift is the most suitable means ● For new developments where due to site
of vertical access and should be provided constraints a full passenger lift cannot be
wherever possible. provided, a lifting platform may be acceptable.
However given the space constraints in some ● Existing buildings may in exceptional
buildings it may not always be possible to provide a circumstances have a wheelchair platform
full passenger lift. stairlift.
● Signs indicating the location of a lifting device
accessible by mobility-impaired people should Passenger Lifts
be clearly visible from the building entrance. ● Minimum dimensions of the car should be
Additionally a sign indicating the floor reached 1100mm wide and 1400mm deep.
should be provided on each landing that can
easily be seen from the lifting device and is ● For a lift that does not have room for a
visually contrasting. wheelchair user to turn around, a mirror
should be provided to allow the user to see
● Whatever lifting device is chosen, internal stairs the space behind the wheelchair.
should always be provided, designed to suit the
ambulant disabled and the visually impaired. ● Power operated sliding doors should provide a
minimum clear opening of 800mm and be
fitted with timing and re-opening activators to
Provision of Lifting Devices
allow time for people and assistance dogs to
● New developments should have a full enter or exit.
passenger lift serving all storeys.
● Controls should be located between 900mm
and 1200mm from the car floor and be at least
400mm from any return wall.
● Landing call buttons should be
Fig. 20 Key dimensions associated with passenger lifts
located between 900mm and
1100mm from the floor and at
least 500mm from any return
wall.
● Lift landing and car doors should
contrast visually from adjoining
walls.
● Audible and visual indication of lift
arrival and location should be
provided in the lift car and lift
lobby. If the lift is to be used
in an emergency it should
conform with the relevant
recommendations of BS 5588
part 8 (Code of Practice for
Means of Escape for Disabled
People).
21
ACCESS WITHIN BUILDINGS
Vertical Circulation within the Building
Lifting Platforms
● Vertical travel distance should be no more than
2m where there is no liftway enclosure and no
floor penetration.
● Controls should be located between 800mm and
1100mm from the floor of the lifting platform and
be at least 400mm from any return wall.
● Continuous pressure controls should be provided,
with landing call buttons the same as for a passenger
lift, capable of operation by persons with reduced
manual dexterity.
1250mm deep.
22
ACCESS WITHIN BUILDINGS
It is clearly the intention of Part M of the Building The government has inferred that it is not their
Regulations to make as much of the built intention to prevent small development through
environment as possible accessible to all. the additional financial burden of providing a lift,
Therefore, the provision of lifts must be seen as but this is a difficult reason to substantiate the
the obvious solution for vertical travel. acceptance of reduced standards.
As there is no floor area rule to be guided by, it is When deciding if a scheme is reasonable, the use
important to recognise that whilst the provision of of the building must be taken into consideration. If
a passenger lift (or, in certain situations a lifting no public access is required on upper floors and it
platform) is the preferred option, each application can be demonstrated that work activity precludes
should be looked at individually, as each situation persons with disability through a reasoned DAS,
will differ in some way. this may be deemed satisfactory. However, these
This is why the concept of a Design and Access types of decision cannot be made without knowing
Statement (DAS) has been introduced. It is an the building occupier and usage.
opportunity for a designer to give a reasoned Useful checklist of considerations
argument as to why full compliance is not possible ● Access is to one floor only and the area is
in a particular case or where new technologies or
limited in comparison with the floor below.
alternative solutions are to be used. The
obligations of employers and service providers ● The cost of a passenger lift if the overall project
under the DDA should be pointed out to cost is modest.
designers wishing to submit a DAS. ● Floor space does not contain a unique facility.
In new buildings, it is undesirable for designers to ● Layout of the building, particularly if it is of
put forward an argument for non-compliance. It is historical interest.
more likely that problems in making a building fully
accessible will be put forward for an existing ● Means of escape provision may not be
building. This is why, whilst determining what is achieved due to floor space/layout constraints.
reasonable in each case, it must be remembered ● Members of the public are not permitted on
that it is the intention of the Building Regulations the floor.
for all new buildings and existing non-domestic
buildings that are materially altered or extended to Remember
be accessible to all.
Whatever form of access to floors above the
Inevitably there will be occasions when reduced ground floor is provided, an ambulant disabled stair
standards that are supported by DAS will be should be provided.
considered reasonable. These projects may relate
to small-scale developments for example, where The above list is not conclusive, nor is it
there may not be adequate space for a full size lift, authoritative in that in those situations a passenger
and a platform lift or some other alternative lift is not required. It merely gives guidance for
solution may be suggested. consideration of particular situations.
In such circumstances, consideration should be
given to special design for landings etc. and refuges
if necessary.
23
MEANS OF ESCAPE
Means of Escape/Egress
This publication deals primarily with access into and The refuge need not be located within the stair
around a building, and the use of facilities within enclosure but should enable direct access to
the building but the safe evacuation of all potential the stair.
users of the building is also vitally important. A refuge should be located in either:
When considering means of escape in case of fire, ● Protected lobby, or
the ultimate consideration is the amount of time it
will take for a person(s) to travel from a place ● Protected corridor, or
threatened by fire to a place of safety. ● Protected stairway
It is worth noting that disability is not an absolute ● A refuge should not encroach into the escape
measure of mobility, for instance, evacuation tests flow space
have shown that wheelchair users were able to
● A refuge should have dimensions of at least
evacuate premises before ambulant people with
1400mm x 900mm
walking aids. The wheelchair users did not generally
impede or impose any delay on the able-bodied ● Refuges should be provided for each stairway
people. It was the ambulant person using a walking on each storey.
frame who was the source of the most serious
impediment to the process of the evacuation.
Fig. 23
General
Routes of travel should be free from any obstacles Refuge formed in a protected stairway
which may impede a person with disabilities,
e.g. thresholds or steps.
Ramps that are designed as shown on page 11,
are suitable for changes in level.
The width of escape routes and exits should be
sufficient to accommodate the evacuation of
Escape
mixed-ability occupancies. flow
Refuges
Most people with disabilities should be able to
reach the safety of a protected escape route, or a by Provision where access to the wheelchair space
final exit independently due to the limitations of is counter to the access flow within the stairway
travel. It is when stairways are encountered that
some people with disabilities will rely on assistance.
Wheelchair space
It is for this reason a waiting area should be
provided in a safe area, so a person requiring
assistance can wait in safety until assisted by a
trained colleague or fire rescue personnel. Occupied by
escape flow
Refuges should be provided for each protected
stairway affording egress from each storey.
24
MEANS OF ESCAPE
Means of Escape/Egress
LIFTS Stairlifts
There are 3 main types of lift: Stairlifts should not be used in an emergency
evacuation; they should be fitted with a battery
● Passenger Lift.
back up system, which will take the lift to the
● Evacuation Lift. ground floor if the power fails.
● Firefighting Lift.
Evacuation Chairs
Passenger Lift Commonly known as Evac Chairs, these are often
used in office buildings where occupants are
Generally to gain access to the upper floors,
familiar with evacuation procedures. It is essential
a passenger lift is required by the Building
that operators are fully trained and the use of the
Regulations. These lifts should not be used as a
evac chairs are integral to the management
means of escape in case of fire.
procedures for evacuation in case of emergency.
Evacuation Lift
Such lifts are often provided in buildings where
there is a high proportion of less mobile occupants.
For example, retirement homes, hospitals and
modern shopping centres.
Their use in case of emergency should be strictly
to well managed procedures (see page 26).
Features of an evacuation lift include:
● Lift well is a fire protecting structure.
● There should be a protected lobby at
each storey.
● There should be a protected route from exit
level to a final exit.
● To override car and landing controls, there
should be a switch marked “Evacuation Lift” at
exit level.
Fire Alarms
● There should be a separate primary electrical
supply, and an alternative secondary supply. The typical fire alarm consists of a bell or siren.
Consideration must be given for alerting occupants
with hearing difficulties.
Firefighting Lift
Similar in design to an evacuation lift but with
Audible Alarms
additional fittings which are generally to aid fire
fighters in their operations. Firefighting lifts should An audible alarm is the most usual way of alerting
not be used by occupants of the building in case people to an alarm, and is the best way of alerting
of fire. someone with a visual impairment.
25
MEANS OF ESCAPE
Means of Escape/Egress
26
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Audience and Spectator Facilities
Audience and spectator facilities fall into Table 3 Provision of wheelchair spaces
3 categories: in audience seating
■ Entertainment facilities,
eg. Cinemas and theatres.
■ Sports Stadiums.
■ Lecture & Conference Facilities.
General
● People with mobility or sensory impairments
may need to view from a particular side or sit
in the front to lip read or see sign interpreters.
● Care needs to be taken so that poor lighting or
very bright natural light does not make it
difficult to see the interpreter. LECTURE AND CONFERENCE FACILITIES
● Wheelchair users, people who have difficulty ● Where a podium or stage is provided
using chairs with fixed arms and those with wheelchair users should have access to it by
assistance dogs should have the choice of sitting means of a ramp or a lifting platform.
next to a seated companion or a companion ● A hearing enhancement system should be
wheelchair user. provided for the hearing impaired.
● Consideration should be given to providing Guidance on hearing enhancement systems
space by certain seats for assistance dogs to can be found in BS 8300
rest.
● Greater spacing between rows of seats at
the rear of a block or at the end of rows may
provide extra legroom for people of large Fig. 24 An example of wheelchair spaces
stature. in a lecture theatre
27
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Audience and Spectator Facilities
Fig. 25 Possible location of wheelchair spaces in front of a rear aisle
28
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Refreshment Facilities
29
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Sleeping Accommodation
Sleeping accommodation where provided ● All bedrooms should have a visual fire alarm
for a significant number of people such as signal in addition to the requirements of
hotels, motels and student accommodation, Approved Document B.
should be convenient for everyone. ● Room numbers should be indicated in
● In student accommodation it is beneficial to embossed characters.
provide a wheelchair accessible toilet for visitors. WHEELCHAIR ACCESSIBLE BEDROOMS
This guidance should be followed for ● At least 1 in 20 bedrooms should be
all bedrooms: wheelchair accessible.
● Effective clear width of the door from the ● The wheelchair accessible bedrooms should be
access corridor should comply with Table 2 located to provide a choice of location and be
(page 14). on accessible routes to all the facilities.
● They should be of the same standard as all
● Swing doors on wardrobes etc should open
other bedrooms.
through 180 degrees.
● The entrance door to the bedroom and to
● Handles on hinged and sliding doors should be the en suite facility should comply with Table 2
easy to grip and operate and contrast visually (page 14) and have a maximum opening
from the door. pressure of 30N.
Fig. 28 One example of a wheelchair-accessible hotel bedroom with en suite sanitary
facilities
30
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Sleeping Accommodation
● En suite facilities should comply with the ● Openable windows and window controls
provisions for wheelchair accessible bath and should be located between 800mm and
shower facilities. 1000mm above the floor and be easy to
● The size of the room should allow a operate without the need to use both hands
simultaneously.
wheelchair user to manoeuvre at the side of
the bed and transfer independently. ● On the outside of the room the call signal
● An emergency assistance alarm and reset should be easily seen and heard and linked to
a central control point.
button should be located in the bedroom and
be activated by a pull-cord that can be
operated from the bed or the floor.
● Wall mounted socket outlets, telephone points ● Sockets should be at least 350mm from any
and television sockets should be located room corners.
between 400mm and 1000mm above the ● Light switches for use by the general public
floor with a preference for the lower end of
should be large push pads and align horizontally
the range.
with the door handles within the range
● Switches for permanently wired appliances between 900mm to 1100mm from the floor.
should be located between 400mm and Where this cannot be achieved pull cords
1200mm above the floor. should be provided in the same height range.
● All switches and controls that require precise ● The front plates of sockets should contrast
hand movements should be located between visually from the background and have a clear
750mm and 1200mm above the floor. indication that they are ON.
● Controls that need close vision should be
located between 1200mm and 1400mm from
the floor, so readings can be taken from a
seated or standing position.
31
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Design Considerations for
Sensory Impairments
A high proportion of the population have sensory ● Lecture and Conference facilities –
impairments such as poor sight and hearing loss. A local light should be provided to illuminate
Whilst these impairments are not immediately the lectern/reading surface, where appropriate
visible they need to be considered when designing the speaker’s face should be lit for the benefit
the internal finishes and environment in and of lip readers in the audience. When the lights
around buildings. in the lecture and conference facilities are low,
any sign language interpreter should be
Lighting separately lit (BS 11.4.6).
32
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Design Considerations for
Sensory Impairments
● Differences in Light Reflectance Value (LVR)
should be used to assess the degree of visual
Lux recommendations for lighting contrast between surfaces such as floors, walls,
Area To Be Lit Recommendation doors, and ceilings and between key
Entrances: Halls, Lobbies, 300 Lux fittings/fixtures and surrounding surfaces
Waiting Rooms (BS 9.1.1).
Enquiry Desks 600 Lux
● Floor surfaces. Very shiny finishes should be
Circulation: Corridors, 150 Lux
avoided due to problems with glare and the
Lifts, Stairs
fact that they are perceived as being slippery,
Communal Areas: Lounges, 300 Lux
Staff Rooms even when they have a slip resistant surface.
Kitchens 300 Lux Large repeating patterns that incorporate bold
Bedrooms 150 Lux contrasting colours or simulate steps should
not be used for any floor or wall surface
Offices 500 Lux (BS 9.1.3 , 9.1.4).
Computer Work Stations 500 Lux
● Service outlets, light switches and other
Tonal Contrast & Colour functional elements on the surface of walls
should be distinguishable from the wall, using
● The entrance door should contrast visually visual and textural contrast (BS 9.1.4).
with its immediate surroundings and should be
● To help blind and partially sighted people
well lit and clearly signed. It should not have a identify key objects within sanitary
mirrored finish (BS 8300 :2009 6.1.2). accommodation, support rails and grab rails
● For easy identification by blind and partially should contrast visually with the wall, the WC
seat and cover should contrast visually with the
sighted people, all door opening furniture
WC pan and cistern, and sanitary fittings and
should contrast visually with the surface of the accessories should contrast visually within the
door (BS 6.5.1). background against which they are seen
● The surface of a ramp should contrast visually (BS 12.2.7).
with that of the landing and of the edge ● The presence of doors, open or closed, should
be apparent to visually impaired people
protection so that its presence is distinguishable
through careful choice of colour and material
by blind and partially sighted people for the door and its surroundings. For example,
(BS 5.8.7). when a door is open, people with impaired
● A lift door should contrast visually with the vision should be able to identify the door
opening within the wall, as well as the leading
adjoining wall of the lift lobby (BS 8.3.3.4).
edge of the door (AD(M)2004, 3.8).
Call buttons should also contrast visually with
● Mirrored, high gloss finishes or very shiny
the surrounding face plate and the face plate
surface finishes should be avoided for large
should similarly contrast with the wall on which areas, e.g. floor, wall, door and ceiling surfaces
it is mounted (BS 8.3.3.3). (BS 9.1.1.).
33
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Design considerations
for sensory impairments
Aids to Communication
Detailed guidance on surface finishes,
visual, audible and tactile signs as well as
the characteristics and appropriate choice
of hearing enhancement systems is given
in BS 8300.
● Provision for a hearing enhancement system
should be installed in rooms and spaces
designed for meetings, lectures, classes,
T
spectator sport or films and at service or
reception counters, particularly in noisy areas
or where they are behind glass screens.
● All facilities should be indicated with the
appropriate symbol and signage. Fig. 29
Fig. 30
34
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Changing Places
Sanitary Accommodation
A Changing Places (CP) facility is a combined toilet, ● The room should have either a mobile or fixed
shower and changing room for use by people with changing bench, in each case, height adjustable,
complex and multiple disabilities who require the and capable of operating at a safe working load
help of up to two assistants. of 125kg.
A CP facility should be provided in larger buildings ● A peninsular WC layout should be provided,
and complexes, where the public have access in with drop-down support rails either side.
numbers or where visitors might be expected to
● Large sanitary disposal bins and waste bins,
spend longer periods of time e.g. large railway
should, where practicable be recessed into the
stations and airports, motorway services, sport &
wall, to avoid being an obstacle to assistants.
leisure facilities, large hotels, museums, concert
halls, art galleries, shopping centres, key buildings ● The CP facility should be heated as users might
within town centres, educational establishments be undressed for long periods.
and health facilities e.g. hospitals. ● A power-operated, height-adjustable wash
● The CP facility should be at least 3m wide and basin should be provided.
4m long, with a ceiling height of 2.4m. ● A CP facility should contain, as minimum, the
● The doorway should have a minimum clear fittings and accessories shown in the example
width of 1000mm, with a level threshold. layout of Figure 31.
● The space needs to be fitted with a full room
cover overhead fixed tracked hoist system.
35
Fig. 31 An example of a Changing
Places facility
36
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Sanitary Conveniences
● A wheelchair user
Fig. 32 Unisex wheelchair-accessible toilet with corner WC should not have to travel
more than 40m on the
same floor or more than
40m combined
horizontal travel if the
toilet is on another floor
of the building and is
accessible by passenger
lift. In buildings with a
lifting platform vertical
travel to the toilet
should be limited to
one storey.
● Heat emitters should be
screened or their surface
temperature kept below
43 degrees centigrade.
● All fittings and grab-rails
should contrast visually
with the background
wall and floor finish,
and there should be
contrast between the
walls and floor.
37
FACILITIES IN BUILDINGS OTHER
THAN DWELLING
Sanitary Conveniences
Fig. 33 Heights and arrangement of fittings in a unisex wheelchair-accessible toilet
(looking towards wall A in Fig. 31)
38
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Sanitary Conveniences
39
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Wheelchair Accessible Changing
and Shower Facilities
● Where more than one unit is provided ● Should provide wall mounted drop down
provision for left or right handed transfer support rails and wall mounted, slip resistant tip
should be made. up seats (not spring loaded).
● In sports facilities individual self-contained
Fig. 36 An example of a self-contained changing shower facilities should be provided in
room for individual use addition to communal separate sex
facilities.
● A shower curtain should be provided that
covers the seat and rails when in the
horizontal position and can be opened
and closed from the shower seat.
● A shelf that can be reached from the seat
or wheelchair should be provided for
toiletries.
● An emergency assistance pull cord should
be easily identifiable and can be reached
from the seat or the floor, the assistance
alarm should be as for sanitary
accommodation.
● Facilities for limb storage should be
included for the benefit of amputees.
● When associated with shower facilities
the floor should be level and slip resistant
when dry or wet.
● There should be a manoeuvring space of
at least 1500mm deep in front of lockers.
40
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Wheelchair Accessible Changing
and Shower Facilities
● Where showers are provided in commercial ● Shower controls in communal showers should
developments for the benefit of staff, at least be positioned between 750mm and 1000mm
one wheelchair accessible shower above the floor.
compartment should be provided.
41
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Wheelchair Accessible Bathrooms
This guidance covers wheelchair accessible ● A choice of left or right handed transfer should
bathing facilities in hotels, motels, student be provided where more than one accessible
accommodation in hospitals.
42
FACILITIES IN BUILDINGS OTHER
THAN DWELLINGS
Wheelchair Accessible Bathrooms
● Doors should open outwards and be fitted ● The room should be fitted with a pull cord and
with a horizontal closing bar fixed to the assistance alarm.
inside face.
43
DWELLINGS
Accessibility
Part M (2004) of the Building Regulations was ● Access to the dwelling or block of flats must be
amended to improve accessibility for visitors to all via an accessible threshold. This should be
new dwellings. Reasonable access is required into designed to take into account the requirements
the dwelling within the boundaries of the plot. of other parts of the Building Regulations
Generally, a level or ramped approach is required including resistance to weather and ground
to the principal entrance, with a gradient not moisture.
exceeding 1:20 and not less than 900mm wide.
Consideration should also be given to the
If site topography prevents this, and the plot Joseph Rowntree Foundation Life Time Homes
gradient exceeds 1:20, a ramp may be required. recommendation (see page 56).
This requires a firm and even surface, a minimum
width of 900mm, 1.2m top, bottom and
intermediate landings, and a gradient no steeper
Timber sill and external concrete slab paving
than 1:12, broken into 5m lengths.
If the plot gradient exceeds 1:15, a stepped
approach will be acceptable, providing the steps
are designed to meet the needs of an ambulant
disabled person (see below).
Fig. 41
Concrete sill and internal transition unit
Fig. 40
44
DWELLINGS
Circulation
The Department for Transport, Local Government ● If a building contains flats, provision must be
and the Regions (DTLR) published a design guide made for disabled people to visit occupants on
for accessible thresholds in new housing, which is any storey. This may be via the installation of
available from The Stationery Office (ISBN 011 a suitably dimensioned and designed lift or via
702333 7). This document provides design common stairways designed for use by
solutions for suitable thresholds in many situations ambulant disabled and visually impaired people.
which minimise the risk of moisture ingress. See Section Vertical Circulation within
Guidance is provided on suitable sill and threshold the Building.
profiles, provision of drainage channels, treatment
of internal floor finishes and external hard
Internal doors, passages and corridors
landscaping.
45
DWELLINGS
WCs within Dwellings
A WC should be provided in the entrance storey The minimum width of the compartment is
of the dwelling. This should be located such that it 900mm, but prescriptive layouts have not been
can be reached from the habitable rooms in that imposed. Consideration should be given to the
storey without using stairs. (If the entrance storey location of the wash basin, particularly in very
contains no habitable rooms the WC may be small rooms.
provided in the principal storey.)
Clear space for frontal access to WC
The door to the WC should
■ open outwards
■ have a clear opening width as
described previously
■ be positioned to enable wheelchair
users to access the WC.
N.B. The compartment does not have to fully
accommodate a wheelchair, and handrails are
not required.
Fig. 46
Fig. 45
46
INTERIOR ERGONOMICS
Wa i t i n g r o o m
Fig. 49
Fig. 48
● Signs should be consistent, thorough and
continuous along routes and should take
account of the need for reassurance.
47
INTERIOR ERGONOMICS
Anthropometric Data
● The formulation of design criteria for buildings ● For example, for the head-height of wheelchair
depends to a considerable extent on the using men, the value of 1:235 for the fifth
dimensional characteristics of people at rest percentile means that five per cent of
and moving and on their range of physical wheelchair using men’s head height when in a
capabilities. In the case of people with wheelchair is at 1:235 or less; the value 1:435
disabilities, these criteria may be modified by for the 95th percentile means that 95 per cent
the use of aids such as sticks, artificial limbs is at 1:435 high or shorter.
and wheelchairs. The figures below show the relevant dimensions.
● To determine appropriate limits for the range
of the population to be accommodated, the
statistical technique of percentile distribution
is used.
MEN
Fig. 50
48
INTERIOR ERGONOMICS
Anthropometric Data
WOMEN
Fig. 51
49
INTERIOR ERGONOMICS
Anthropometric Data
● When data is applied to design problems, it is ● It is not the case that whenever the value for
usually found that there is a limiting factor in the 95th percentile is observed, 95 per cent of
one direction only, e.g. if the problem relates the population will be accommodated; if the
to obstructions at head-height, the measures of critical dimension is in the opposite direction,
short people are not significant. In applying only five per cent will be accommodated and
data, the designer should enquire which the correct course is to apply the 5th
dimension is critical. percentile instead.
Fig. 52
50
INTERIOR ERGONOMICS
Anthropometric Data
AMBULANT PEOPLE
● It is not always economic or practicable to cover
100 per cent of the population by catering for
people at the extremes. It may not be possible
to obtain a solution to a specific design problem,
which is equally efficient for a typical ambulant
person and a person in a wheelchair.
Fig. 53
51
INTERIOR ERGONOMICS
Ergonomic Data
F. Elbow level
F: minus 0.130: preferred level of kitchen surfaces
where sink rim and general work surfaces are at
the same height.
F: minus 0.100: preferred level of sink rim.
F: minus 0.150: preferred level of general work
surfaces.
F: minus 0.100: preferred level of wash basin rim.
F: minus 0.250: preferred level of fixed
ironing board.
Fig. 54
G. Knuckle height (comfortable
downward reach)
G: lower level of preferred zone for most-used
articles stored in kitchen.
A. Comfortable vertical reach
G: preferred minimum height of socket outlets and
A: minus 0.070: maximum height of storage
other controls.
shelves, allowing access to front of shelf.
G: preferred height of letter basket and delivery
A: minus 0.150: maximum height of 0.300 deep
shelves adjacent to entrance door.
storage shelves over 0.600 floor units, allowing
access to front of shelf. H. Effective downward reach
H: minimum height of storage shelves, socket
B. Oblique vertical reach
outlets, heater controls and oven floor.
B: maximum height of window and blind controls.
B: minus 0.060: maximum height of 0.200 deep J. Comfortable forward reach
storage shelves over 0.600 floor units, allowing J: plus 0.100: maximum depth of kitchen work
access to front of shelf. surfaces.
B: minus 0.080: maximum height of unobstructed J: preferred maximum dimension, sink fascia to
storage shelves, allowing reach to back of shelf. sink tops.
52
INTERIOR ERGONOMICS
Ergonomic Data
WHEELCHAIR USERS
H. Elbow level
H: plus 0.020: preferred height of letter basket and
delivery shelves adjacent to entrance door.
H: minus 0.030: preferred height of pull-out for
food preparation.
H: minus 0.040: preferred height of fixed
ironing board.
J. Thigh level
J: minimum unobstructed vertical dimension for
knee recesses to tables, desks, kitchen sink,
preparation centre and wash hand basin.
J: plus 0.160: preferred height of kitchen work
surfaces at consistent level assuming 0.150 deep
Fig. 55 sink bowl.
K. Chair seat level, centre front edge (with
MEASUREMENTS
cushion if used)
A. Comfortable vertical reach K: preferred level of WC seat, platform at head
A: minus 0.070: maximum height of unobstructed end of bath and shower seat.
storage shelves with lateral approach, reach to L. Knuckle height
front of shelf. L: plus 0.100: minimum height of heater controls.
B. Oblique vertical reach L: plus 0.050: lower level of preferred zone for
B: maximum height of window and blind controls. most-used articles stored in kitchen.
B: minus 0.120: maximum height of 0.300 deep L: minimum level of oven floor.
storage shelves over 0.600 floor units, allowing M. Comfortable downward reach
reach to front of shelf. M: minimum height of storage shelves.
B: minus 0.160: maximum height of unobstructed
storage shelves with frontal approach, allowing N. Foot height
reach to back of shelves. N: minimum height of toe recesses to kitchen units.
53
The Disability Discrimination
The DDA created rights for any individual, defined information, advice, training and the involvement of
by the Act as a disabled person, not to be members and volunteers, should be making
discriminated against in: reasonable adjustments to all policies, procedures
● Employment. and practices to make their services accessible.
This applies to all sizes of service providers and
● Provision of goods, facilities and services.
organisations.
● The management, buying or renting of land or
From October 2004, all service providers are
property.
required to alter, remove or provide means of
● Education and training. avoiding physical barriers that make it impossible or
● Provision of transport. unreasonably difficult for disabled people, including
The original provisions on education in schools, any volunteers and members, to access their
colleges and universities were significantly amended services by making reasonable adjustments to all
by the Special Educational Needs and Disability their buildings and the environment.
Rights Act 2001, which have become Part lV of the
DDA. All training provision is already covered by The Disability Discrimination
Part lll of the DDA.
From December 1996, employers have had to
Act 2005
make reasonable adjustments for employees, The Act was amended and extended in 2005.
based upon their specific requirements and the N.B. from April 2011 the Equality Act,
nature of the job. This includes adjustments to
which became law in October 2010, will
policies, procedures and practices and to buildings
and the environment. succeed the Disability Discrimination Act
(DDA). The Equality Act will fully
From October 1999, all service providers,
including community and voluntary organisations encompass the DDA, including some areas
providing any service to the public, including which have been expanded upon.
54
Legislation and Bibliography
BIBLIOGRAPHY
LEGISLATION
The following are the most significant Acts of The Building Regulations 2010
Cinematograph Acts 1909 and 1952 Approved Document M Access to and Use
of Buildings
Companies (Employment of Disabled
Persons) Regulations 1980 Approved Document N Glazing Materials
and Protection
Disabled Persons Act 1981
Regulatory Reform (Fire Safety) Order 2005 BS 8300 Design of Buildings and the
Approaches to meet the
Health and Safety at Work, etc Act 1974 needs of Disabled People B.S.I.
Highways Act 1980 Designing for the Disabled – Selwyn Goldsmith
55
Useful Contacts
Bracknell Forest Borough Council Royal National Institute of the Blind (RNIB)
Environment & Leisure Department Tel: 0207 388 1266
Time Square, Market Street www.rnib.org.uk
Bracknell, Berkshire RG12 1JD
Tel: 01344 351106/1208 Royal National Institute of the Deaf (RNID)
Fax: 01344 351193 Tel: 0808 8080123 (freephone)
Email: building.control@bracknell-forest.gov.uk www.rnid.org.uk
56
Martin Butler
Partnership Limited
Architectural Design
& Planning Consultants
DURABUILD