Electromagnetic Compatibility

chapter 7
7.1 Reasons for Electromagnetic 7.3 EMC-friendly Power Supplies –
Interference Practical Issues and Requirements
7.2 Coupling Mechanisms 7.4 EMC in Standards
7 Electromagnetic Compatibility (EMC)
Electromagnetic compatibility is
relevant in all fields of electrical Source of Potentially suscepti-
Coupling mechanism
engineering. For this reason, every interference ble equipment
(route)
expert should be familiar with this (emitter) (receiver)
subject. Electromagnetic compatibility
means that electrical equipment, Fig. 7/1: Interference model
plant and systems can be operated
simultaneously without unpermissibly
high interference being generated
which might cause malfunction or
Cause of interference Coupling mechanism
even destruction of equipment.

7.1 Reasons for Switching operations


Electromagnetic Electrostatic discharge
Periodic parasitic frequencies
Lightning current arrester
Surge arrester
Interference Strike of lightning Filters
Nuclear blast Equipotential bonding
Electric current flows within an elec- System perturbations
EMC Grounding
tric appliance (emitter) and causes a Corona discharge Screening
magnetic field surrounding it. Addi- Galvanic
tionally, the voltage that drives the Inductive
current causes an electric field. The Capacitive
emitter can also cause electromagne- Interference by waves
tic waves. These magnetic, electric Interference by radiation
and electromagnetic fields can gen-
erate voltages and currents in other
electrical appliances which might Precautions against interference
cause malfunction, damage or even
destruction of these appliances Fig. 7/2: Parameters affecting EMC
(Fig. 7/1). There are three points of
lever-age where you can act upon the
ered and precautions should be taken
system to ensure electromagnetic
to prevent such interference or keep it EMC according to
compatibility:
at a level which does not cause any DIN VDE 0870 is:
 Emitter (e.g. screening, spectral disturbance to the whole system (Fig.
7/2). Subsequent rework to ensure
The capacity of an electrical
limitation)
 Coupling route (e.g. no PEN system EMC gives rise to considerable appliance to function in a
conductor, filtering, optical extra costs. satisfactory manner in its
waveguides) electromagnetic
 Receiver (e.g. screening, filtering) environment without
When an electrical system is planned,
7.2 Coupling impermissibly disturbing this
any possible generation, propagation
Mechanisms environment which may also
and introduction of electromagnetic There are basically three coupling include other appliances.
interference should already be consid- mechanisms how electromagnetic

7/2 Totally Integrated Power by Siemens


Electromagnetic Compatibility (EMC)

interference may be transmitted:


Source A Device A
 Galvanic coupling A

 Capacitive coupling
 Inductive coupling
Source B Device B
The following is derived:
B
 Electromagnetic line coupling
 Radiation coupling

7.2.1 Galvanic Coupling


Galvanic coupling is caused by the
U X A/B
connection of two or more circuits
through common impedances. Exam-
ples of such common impedances are ZK
the internal resistance of power
supply units, joint supply and zero Fig. 7/3: Galvanic coupling of two circuits
potential leads, or protective conduc-
tor or grounding systems of facilities.
Fig. 7/3 shows the possible galvanic Zq
coupling in supply and signal circuits.
Circuits A and B are coupled by a
common impedance ZK. Currents IA
and IB flow through the common U St ZS
impedance and cause a voltage drop
UX A/B, which is superimposed on the
signal voltages in the circuits A or B,
ZL
and may there result in interference
A B
or destruction.
U A/B
A further source of electromagnetic
interference as a result of galvanic
St
coupling is the coupling of several
Point A Point B
circuits by so-called ground loops or
ring ground conductors (Fig. 7/4).
Fig. 7/4: Ground loop between two devices A and B
In order to prevent direct contact with
live parts, the casings of both devices
are connected to the grounding Zq and through the receiver impe-
system. Both devices are connected dance Zs, which causes a voltage
by a signal line whose screening is drop in the source and receiver, which
also grounded. A potential difference in turn is superimposed on the signal
UAB between points A and B may arise voltage. With sine-shaped parameters,
either as a result of ground currents the interference voltage may be
(ground-fault currents, lightning calculated as follows:
currents) or by induction. This poten-
tial difference drives a parasitic cur- ZS
U St = U AB -------------------
rent ISt through the source impedance ZS + ZQ

7/3 7
Examples:
 PEN conductor in the building
 Suppression devices connected
against PE
U1
 Measuring circuits/screenings Circuit 1 Z1
grounded on both sides
Countermeasures: 1

 Isolating transformers
 Neutralizing transformers
 Optocouplers 2
 Optical waveguides

U2
7.2.2 Capacitive Coupling Z2 Circuit 2

Capacitive (electrical) coupling may


occur between conductors of different
potential (Fig. 7/5). The potential
difference creates an electrical field
Fig. 7/5: Capacitive coupling
between the conductors, which
means that unwanted capacities are
present between the conductors. The
7.2.3 Inductive Coupling Examples:
following current flow will result from
a voltage change: Inductive (magnetic) coupling is  Transformers, motors, electric
dU caused by the interlinking of the welding devices
i = C K ⋅ ---------1- magnetic flux in two or more circuits  Power lines routed in parallel
dt
(Fig. 7/6). Any change in the magnetic  Unfavorable arrangement of
This creates an undesired voltage in
flux induces interference voltages in conductors in power lines
circuit 2:
the conductor loops of the circuits.  Cabling systems with different phase
The value of the coupling capacity CK This means that even a single circuit and return currents
depends on the geometry and topo- may be affected by transient magnetic  Lines in which currents are
logy of the conductors. fields (lightning discharge, electrosta- frequently switched
dU tic discharge).  Signal lines with high frequencies
u 2 = i ⋅ Z 2 = C K ⋅ Z 2 ⋅ ---------1-
dt As a result of the coupling inductance,  Unconnected coils
Examples:
any current change in circuit 1 will Countermeasures:
 Coupling of interferences between induce a voltage in circuit 2. This
parallel lines voltage depends on the rate of the  Reduction of the coupling
 Static discharge from operator current change and the coupling inductance M by keeping parallel
 Contactors inductance MK: cable routes as short as possible and
Countermeasures: by maintaining large clearances
di
U 2 = M K ⋅ ----- between interfering and unaffected
 Screening of signal lines dt
systems
 Ground-symmetrical design of the  Orthogonal arrangement of
MK depends on the magnetic flux and
signal line conductor loops for the purpose of
the conductivity of the magnetic field.
 Use of optical waveguide systems magnetic decoupling
 Twisted cables
 Screening of the affected system

7/4 Totally Integrated Power by Siemens


Electromagnetic Compatibility (EMC)

U1 Circuit 1 Z1

M1 1

M2 2

Z2 Circuit 2 U2

Fig. 7/6: Inductive coupling

7.2.4 Electromagnetic 7.2.5 Radiation Coupling


Line Coupling Radiation coupling means that circuits
Electromagnetic line coupling occurs are affected by electromagnetic
when electrical and magnetic inter- waves which originate from other
ference is simultaneously present circuits and travel with the speed of
between two or more electrically long light. As long as you are within a close
lines. In electrically long lines, cur- range of the interfering system, the
rents and voltages are not independ- electric field and the magnetic field
ent of each other, but they are firmly are encountered as separate entities
interrelated. A line is considered (inductive and capacitive coupling).
electrically long if the rise time of But as soon as you are within a
transmitted pulses is in the order of remote range, these two fields are
magnitude of the run time through coupled and we speak of radiation
the line. For a calculation of the coupling.
resulting electromagnetic field, a
differential analysis of the electric and
magnetic fields must be performed,
i.e. the fields are superimposed for
differential elements of an infinitely
short length of line.

7/5 7
installation, part of the return current
7.3 EMC-friendly might be distributed through all
7.3.1 Effects of
Conductor Design on EMC
Power Supplies – grounding systems and equipotential
Fig. 7/7 demonstrates which problems
Practical Issues and conductors. Current flows back to the
voltage source through the smallest must be expected if the PE and N
Requirements resistors, so that unwanted currents conductors are combined to form a
might even flow through metal pipes PEN conductor. The illustration shows
For several years, increasing malfunc- a device through which the current IL
and screens of data lines. These
tion of and damage to electrical and flows during operation. Normally, this
“stray” currents may give rise to strong
electronic equipment has been not- current should be taken back to the
electromagnetic fields which cause
iced, for example source through the PEN conductor.
strange failures and malfunction of
 Unaccountable faults in data trans- electronic equipment. They may also This return current, however, causes a
mission networks cause corrosion in water pipes. Since voltage drop in the PEN conductor,
 Desktop and server crashes higher currents may be present in the which acts as an interference voltage
 Printer failure N conductor, as explained above, care on all systems connected to the PEN
 Slowdown of data transmission in must be taken not to reduce the cross conductor, resulting in a parasitic
local networks, even to complete section of the N conductor as com- current ISt through the device screen-
standstill pared to that of the phase conductors, ing and a parasitic current Ibuilding
 Triggering of alarm systems and fire but even to increase it. in the building. The parasitic currents
detectors flowing through the cable screens
 Corrosion in piping and ground interfere with or destroy equipment
conductors which is susceptible to overvoltages.
Moreover, the parasitic currents in the
The reasons for these effects often lie
in an old-style power supply system
where the N conductor and the PE
conductor are combined to form a
single PEN conductor. This wasn’t a
PEN L
problem as long as the number of Distributor

electronic equipment connected into ON


L
supply was low. N

St
The phases were loaded nearly sym-
metrically, and consequently the PEN L
Screen

conductor was hardly loaded. Owing Token ring


St

to an increasing number of high- Distributor


power single-phase loads, and loads
U>0

G
with a high proportion of harmonic
contents in the third order (switched
power supply units), the phases are St

loaded extremely asymmetrically, and


the N conductor is sometimes loaded PEN L

with a higher current than the phase


conductors. As the PE conductor is Transformer L = Current in phase conductor L

meant to carry current only in case of N = Neutral conductor current in PEN


G = Stray current in the building
a fault, the PE conductor and the N St = Parasitic currents in screens
conductor must be laid separately in Conductive building structure, U = Voltage drop in PEN conductor
water pipe (external voltage)
new power supply systems (VDE 0100
Part 540 Appendix C.2). If this require-
ment is not observed in an electrical
Fig. 7/7: Current flow for a combined PEN conductor

7/6 Totally Integrated Power by Siemens


Electromagnetic Compatibility (EMC)

 The supplying sources for sections A


PE N L and B may be operated in parallel.
Distributor
 A connection between ground and
ON
L
the PE conductor may only be made
N at one point (central grounding
point), as otherwise the PE conduc-
Screen
tor and the N conductor would be
St = 0 connected in parallel, resulting in
L Token ring
unfavorable EMC conditions as
Distributor shown in Fig. 7/5.
 All load feeders are designed as a
U=0

G =0
TN-S system, i.e. with distributed
N-conductor function and separate
PE and N conductors. 3-pole and
4-pole switching devices may be used.
N L

Network configuration for


distributed supply
Transformer L = Current in phase conductor L
= Neutral conductor current in PEN
N
Fig. 7/10 depicts the recommended
G = Stray current in the building
St = Parasitic currents in screens system for distributed supply. Distri-
Conductive building structure, U = Voltage drop in PEN conductor buted supply is encountered if the
water pipe (external voltage)
following applies to the distance
Fig 7/8: Current flow for separate PE and N conductors between sections A and B:
As short-circuit currents decrease with
building may result in corrosion and Network configuration for central distance from the main equipotential
give rise to magnetic fields which may power supply bonding conductor, and protective
cause further damage. Separate devices require a certain minimum
The network configuration shown in
design of the N conductor and PE
Fig. 7/9 is recommended for central a1 >> a2
conductor will prevent such stray
supply, with EMC being ensured even
currents. Thus, the PE conductor only
when the supplying sources of sec-
carries current in case of a fault (Fig. value for safe tripping in the event of
tions A and B are operated in parallel.
7/8). a fault, and as selective grading must
We recommend that the PEN conduc-
also be taken into account, a second
tor be marked in light blue and,
main equipotential bonding conduc-
additionally, in green-yellow through-
7.3.2 Power Supply Sys- out its course.
tor is installed for distributed supply
tems – Network Configu- of the SPS.
ration The following should be observed for
The following should be observed for
this kind of power supply system:
In order to avoid parasitic currents, the this kind of power supply system:
type of power supply system must be  The PEN conductor must be wired
 The PEN conductor must be wired
carefully selected. The following section separately along its whole course,
separately along its whole course in
explains two typical examples for coup- both in the SPS and in the GPS, as
the GPS.
ling the general power supply (GPS well as in the LVMD.
 There must be no connection be-
network) and the safety power supply  There must be no connection be-
tween the neutral point of the
(SPS network). In the first case, the SPS is tween the neutral points of trans-
transformer and ground or the PE
installed in the immediate vicinity of the former and generator, and ground
or the PE conductor, respectively. conductor, respectively. Between
GPS (central supply system) and in the the neutral point of the generator
second case, the SPS is installed remote  The feeder switches for supply from
from the GPS (distributed supply system). SPS and GPS must be in 3-pole
design.

7/7 7
Section A Section B
Source

Equipotential Equipotential Main equipotential


bonding – bonding – bonding –
transformer transformer generator
Low-voltage main distribution

GPS SPS

L1 L1
L2 L2
L3 L3
PEN
PE

Central
g rounding
p oint Main
for sections e quipotential
A and B b onding

Fig. 7/9: Network configuration for central supply

Section A Section B

Central
g rounding
Source

p oint
for section B
Equipotential
Equipotential bonding – Main
bonding – transformer a1 equipotential
transformer bonding
a2

generator
Low-voltage main distribution

Interlock
GPS SPS

L1 L1
L2 L2
L3 L3
PEN N
PE PE

Central
g rounding
p oint Main
for section A e quipotential
b onding

Fig. 7/10: Network configuration for distributed supply

7/8 Totally Integrated Power by Siemens


Electromagnetic Compatibility (EMC)

and ground or the PE conductor,  All load feeders are designed as a conductor clearance and a suitable
respectively, a connection for an TN-S system, i.e. with distributed conductor arrangement. The following
additional equipotential bonding conductor function and separate PE illustration shows the magnetic flux
conductor is installed. and N conductors. 3-pole and 4-pole density curve and the interference limits,
 A parallel operation between sec- switching devices may be used. to demonstrate when a screen will start
tions A and B is impermissible. The By implementing a central grounding flickering. This illustration shows the
transformers may supply sections A point in the power supply systems minimum conductor clearances, in a
and B at the same time. The gener- given conductor arrangement, for which
described above, suitable measuring
ator, however, may only supply screen interference limits are observed.
devices can be used to make sure that
section B. Flux density is minimized in a symmetri-
no further – impermissible – splitter
cal conductor arrangement of type E, in
bridge between the N conductor and
Note: During changeover from trans- which the clearance between the indivi-
former to generator operation, there the PE conductor was installed. dual conductors should be kept as low as
may occur parallel operation under possible.
unfavorable EMC conditions for a 7.3.3 Interference Limits
short time, for example during back Comparison of conductor arrangements
synchronization. With flux densities above 1 µTesla (14/15 B and C2 shows that even a slightly
 The switches of the changeover inch screens), or 0.5 µTesla (17/21 inch imbalanced load results in a large
connection in the SPS and the gener- screens), a display screen (CRT monitor) increase of magnetic flux density, and
ator supply must be in 4-pole design. starts flickering. In order to observe that the clearance required for observ-
The feeder switches for supply of these limits, the magnetic flux density ing screen interference limits rises in
section A must be in 3-pole design. can be reduced by both increasing consequence.

Conductor arrangements
100
L1
Magnetic flux density B in T

10 cm
L 1 = 1,000 A e -j0∞
B L2 L 2 = 1,000 A e -j120∞
10 cm L = 950 A e -j240∞
3
L3
10
L1
10 cm
L 1= 200 A e -j0∞
C1 L2 L 2= 200 A e -j120∞
10 cm L 3= 200 A e -j240∞
L3 Interference limit for 14/15 inch display screen
1
L1 Interference limit for 17/21 inch display screen
10 cm
L 1 = 1,000 A e -j0∞
C2 L2 L 2 = 1,000 A e -j120∞
10 cm L 3 = 1,000 A e -j240∞
L3
0.1
L1
E L 1 = 1,000 A e -j0∞
3c
m
3c

L 2 = 1,000 A e -j120∞
L 3 = 1,000 A e -j240∞
L3 3 cm L2
0.01
1 5 10 50 100
Distance to source of interference in m

Fig. 7/11: Field strength for different conductor arrangements

7/9 7
The following factors show a favora- and earthing in buildings with infor- Section 444: Protection against elec-
ble impact by reducing magnetic flux mation technology equipment tromagnetic interferences (EMI) in
density: installations of buildings
DIN VDE 0100-443
 Symmetrical conductor arrangement (VDE 0100 Part 443):
 Small clearances between Erection of low-voltage installations –
conductors Part 4: Protection for safety; Chapter
 Symmetrical conductor loads 44: Protection against overvoltages;
 Large clearances between conductors Section 443: Protection against over-
and the potentially susceptible voltages of atmospheric origin or due
equipment to switching
DIN VDE 0100-540
7.4 EMC in (VDE 0100 Part 540):
Erection of power installations with
Standards nominal voltages up to 1,000 V;
DIN EN 50174-2
selection and erection of equipment;
(VDE 0800 Part 174-2):
earthing arrangements, protective
Information technology – Cabling
conductors, equipotential bonding
installation – Part 2: Installation
conductors
planning and practices inside buildings
DIN VDE 0100-444
DIN EN 50310
(VDE 0100 Part 444):
(VDE 0800 Part 2-310):
Electrical installations of buildings –
Application of equipotential bonding
Part 4: Protection for safety; Chapter
44: Protection against overvoltages;

7/10 Totally Integrated Power by Siemens