chapter 7
7.1 Reasons for Electromagnetic 7.3 EMC-friendly Power Supplies –
Interference Practical Issues and Requirements
7.2 Coupling Mechanisms 7.4 EMC in Standards
7 Electromagnetic Compatibility (EMC)
Electromagnetic compatibility is
relevant in all fields of electrical Source of Potentially suscepti-
Coupling mechanism
engineering. For this reason, every interference ble equipment
(route)
expert should be familiar with this (emitter) (receiver)
subject. Electromagnetic compatibility
means that electrical equipment, Fig. 7/1: Interference model
plant and systems can be operated
simultaneously without unpermissibly
high interference being generated
which might cause malfunction or
Cause of interference Coupling mechanism
even destruction of equipment.
Capacitive coupling
Inductive coupling
Source B Device B
The following is derived:
B
Electromagnetic line coupling
Radiation coupling
7/3 7
Examples:
PEN conductor in the building
Suppression devices connected
against PE
U1
Measuring circuits/screenings Circuit 1 Z1
grounded on both sides
Countermeasures: 1
Isolating transformers
Neutralizing transformers
Optocouplers 2
Optical waveguides
U2
7.2.2 Capacitive Coupling Z2 Circuit 2
U1 Circuit 1 Z1
M1 1
M2 2
Z2 Circuit 2 U2
7/5 7
installation, part of the return current
7.3 EMC-friendly might be distributed through all
7.3.1 Effects of
Conductor Design on EMC
Power Supplies – grounding systems and equipotential
Fig. 7/7 demonstrates which problems
Practical Issues and conductors. Current flows back to the
voltage source through the smallest must be expected if the PE and N
Requirements resistors, so that unwanted currents conductors are combined to form a
might even flow through metal pipes PEN conductor. The illustration shows
For several years, increasing malfunc- a device through which the current IL
and screens of data lines. These
tion of and damage to electrical and flows during operation. Normally, this
“stray” currents may give rise to strong
electronic equipment has been not- current should be taken back to the
electromagnetic fields which cause
iced, for example source through the PEN conductor.
strange failures and malfunction of
Unaccountable faults in data trans- electronic equipment. They may also This return current, however, causes a
mission networks cause corrosion in water pipes. Since voltage drop in the PEN conductor,
Desktop and server crashes higher currents may be present in the which acts as an interference voltage
Printer failure N conductor, as explained above, care on all systems connected to the PEN
Slowdown of data transmission in must be taken not to reduce the cross conductor, resulting in a parasitic
local networks, even to complete section of the N conductor as com- current ISt through the device screen-
standstill pared to that of the phase conductors, ing and a parasitic current Ibuilding
Triggering of alarm systems and fire but even to increase it. in the building. The parasitic currents
detectors flowing through the cable screens
Corrosion in piping and ground interfere with or destroy equipment
conductors which is susceptible to overvoltages.
Moreover, the parasitic currents in the
The reasons for these effects often lie
in an old-style power supply system
where the N conductor and the PE
conductor are combined to form a
single PEN conductor. This wasn’t a
PEN L
problem as long as the number of Distributor
St
The phases were loaded nearly sym-
metrically, and consequently the PEN L
Screen
G
with a high proportion of harmonic
contents in the third order (switched
power supply units), the phases are St
G =0
TN-S system, i.e. with distributed
N-conductor function and separate
PE and N conductors. 3-pole and
4-pole switching devices may be used.
N L
7/7 7
Section A Section B
Source
GPS SPS
L1 L1
L2 L2
L3 L3
PEN
PE
Central
g rounding
p oint Main
for sections e quipotential
A and B b onding
Section A Section B
Central
g rounding
Source
p oint
for section B
Equipotential
Equipotential bonding – Main
bonding – transformer a1 equipotential
transformer bonding
a2
generator
Low-voltage main distribution
Interlock
GPS SPS
L1 L1
L2 L2
L3 L3
PEN N
PE PE
Central
g rounding
p oint Main
for section A e quipotential
b onding
and ground or the PE conductor, All load feeders are designed as a conductor clearance and a suitable
respectively, a connection for an TN-S system, i.e. with distributed conductor arrangement. The following
additional equipotential bonding conductor function and separate PE illustration shows the magnetic flux
conductor is installed. and N conductors. 3-pole and 4-pole density curve and the interference limits,
A parallel operation between sec- switching devices may be used. to demonstrate when a screen will start
tions A and B is impermissible. The By implementing a central grounding flickering. This illustration shows the
transformers may supply sections A point in the power supply systems minimum conductor clearances, in a
and B at the same time. The gener- given conductor arrangement, for which
described above, suitable measuring
ator, however, may only supply screen interference limits are observed.
devices can be used to make sure that
section B. Flux density is minimized in a symmetri-
no further – impermissible – splitter
cal conductor arrangement of type E, in
bridge between the N conductor and
Note: During changeover from trans- which the clearance between the indivi-
former to generator operation, there the PE conductor was installed. dual conductors should be kept as low as
may occur parallel operation under possible.
unfavorable EMC conditions for a 7.3.3 Interference Limits
short time, for example during back Comparison of conductor arrangements
synchronization. With flux densities above 1 µTesla (14/15 B and C2 shows that even a slightly
The switches of the changeover inch screens), or 0.5 µTesla (17/21 inch imbalanced load results in a large
connection in the SPS and the gener- screens), a display screen (CRT monitor) increase of magnetic flux density, and
ator supply must be in 4-pole design. starts flickering. In order to observe that the clearance required for observ-
The feeder switches for supply of these limits, the magnetic flux density ing screen interference limits rises in
section A must be in 3-pole design. can be reduced by both increasing consequence.
Conductor arrangements
100
L1
Magnetic flux density B in T
10 cm
L 1 = 1,000 A e -j0∞
B L2 L 2 = 1,000 A e -j120∞
10 cm L = 950 A e -j240∞
3
L3
10
L1
10 cm
L 1= 200 A e -j0∞
C1 L2 L 2= 200 A e -j120∞
10 cm L 3= 200 A e -j240∞
L3 Interference limit for 14/15 inch display screen
1
L1 Interference limit for 17/21 inch display screen
10 cm
L 1 = 1,000 A e -j0∞
C2 L2 L 2 = 1,000 A e -j120∞
10 cm L 3 = 1,000 A e -j240∞
L3
0.1
L1
E L 1 = 1,000 A e -j0∞
3c
m
3c
L 2 = 1,000 A e -j120∞
L 3 = 1,000 A e -j240∞
L3 3 cm L2
0.01
1 5 10 50 100
Distance to source of interference in m
7/9 7
The following factors show a favora- and earthing in buildings with infor- Section 444: Protection against elec-
ble impact by reducing magnetic flux mation technology equipment tromagnetic interferences (EMI) in
density: installations of buildings
DIN VDE 0100-443
Symmetrical conductor arrangement (VDE 0100 Part 443):
Small clearances between Erection of low-voltage installations –
conductors Part 4: Protection for safety; Chapter
Symmetrical conductor loads 44: Protection against overvoltages;
Large clearances between conductors Section 443: Protection against over-
and the potentially susceptible voltages of atmospheric origin or due
equipment to switching
DIN VDE 0100-540
7.4 EMC in (VDE 0100 Part 540):
Erection of power installations with
Standards nominal voltages up to 1,000 V;
DIN EN 50174-2
selection and erection of equipment;
(VDE 0800 Part 174-2):
earthing arrangements, protective
Information technology – Cabling
conductors, equipotential bonding
installation – Part 2: Installation
conductors
planning and practices inside buildings
DIN VDE 0100-444
DIN EN 50310
(VDE 0100 Part 444):
(VDE 0800 Part 2-310):
Electrical installations of buildings –
Application of equipotential bonding
Part 4: Protection for safety; Chapter
44: Protection against overvoltages;