Operation Manual
AMC2100 Series
AMC3100 Series
Index
1. Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1
1.1 AMF900 Flange Type - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1
1.2 AMF500 Wafer Type - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2
1.3 AMF300 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2
1.4 AMF500 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2
1.5 AMF601 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3
1.6 AMF900 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3
2.Installation- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4
2.1 Install position - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4
2.2 Remove the interference of magnetic field - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4
2.3 Straight tube length - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4
2.4 Install method - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4
3. Converter AMC2100 and AMC3100 Operate Manual - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6
3.1 Converter AMC2100 Operate Manual- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6
3.1.1 Power and signal output connected line (Compact and separate mode) - - - - - - - - - - - 6
3.1.2 Separate wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7
3.1.3 AMC2100 Panel deploy - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7
3.2 Converter AMC3100 Operate Manual - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8
3.2.1 Power and signal output connected line (Compact and separate mode) - - - - - - - - - - - 8
3.2.2 Separate wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 9
3.2.3 AMC3100 Panel deploy - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 9
3.3 Survey mode setting- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 10
3.4 Example- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 10
3.5 Totalizer Rest - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 10
3.6 Auto zero Adjustment- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 11
3.7 Check for power off message- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 11
3.8 Operate flow chart - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 12
3.9 User operate description - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 14
3.10 System Mode- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 18
3.11 Advance Mode- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 19
3.12 Batch Control - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 21
4. Common Alarm Code Indication - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 23
1.1.6ENG
1. Sensor
EM Flowmeter composed by sensor and Converter, be compact version or separate version, there are several
specification of sensor as follow:
92 92
L D
Standard
Size Liner Material Dimensions (mm)
Pressure
(mm) Kg/cm2 FEP / PFA Neoprene Polyurethane PTFE L D H
6
90 145
10
15 95 155
20 150 105 160
25 115 166
40
32 140 180
40 150 190
50 165 201
65 200 185 220
80 200 235
100 220 254
250
125 16 250 284
150 300 285 314
200 350 340 369
250 400 395 430
300 445 480
450
350 505 540
400 500 565 600
450 550 615 640
10
500 670 700
600
600 780 800
700 700 895 910
800 800 1015 1020
900 900 1115 1120
1000 1000 1230 1230
1200 1200 1405 1450
1400 1400 1630 1560
1600 6 1600 1830 1770
1800 1800 2045 2040
2000 2000 2265 2250
1
1.2 AMF500 Wafer Type
Size: 25mm ~ 200mm (1” ~ 8”)
Liner: FEP
Protection: IP68
Max.Temp.: 180 Deg. C
Installation: Wafer
Tie-rod
NUT
Packing
Flange
2
1.5 AMF601 Installation
3
2. Installation
When you design the tube, please consider following items:
2.1 Install position
Please avoid the sunlight when you install the flowmeter, the ambient temperature between-25~60 Deg.C will be great.
2.2 Remove the interference of magnetic field
Please DO NOT install flowmeter near motor-driven machine, transformer, frequency transformer etc. for it will cause interference
of magnetic field..
2.3 Straight tube length
In order to guarantee the EM Flowmeter accuracy, upstream and downstream of the installation should satisfied the following
conditions(Picture).
T - Tube
ELBOW 90°
> 5D
> 5D
Grove Valve
< 7 . 5°
>10D
Generally tube installation, the flowmeter Upstream could try to stay 5D-10D ,Downstream 2D-5D.
c. Pipe design should make sure no air bubble in the flowmeter position.
Grove Valve
4
d. Electrode position should parallel with ground
EM Flowmeter installed by horizontal or slanting the electrode position(A.B) should match the 2 side( right/left)of
tube, converter(wiring box)should be top of the tube.
Exhaust valve
>300mm
Horizontal install, the electrode position A.B should on the right and left side.
e. Transportation
When you moving, please remember DO NOT use rope through the flowmeter tube, it may cause Liner inside
broken.
Please DO NOT use your hand or rope to hang on Converter or wiring box, if Flowmeter size is bigger than 80mm,
because the material of converter and wiring box is tender aluminum, it can’t stand huge weight.
f. Grounding measure
Grounding Ring
5
3. Converter AMC2100 and AMC3100 Operate Manual
3.1 Converter AMC2100 Operate Manual
3.1.1 Power and signal output connected line(compact and separate model)
Open the 4 screws of the converter, and you can see terminal, decide if you need to connect according to your
needs.
F
U
S
E
I+ P+ R+ A C X L N PE
I- P- R-
P- B Y
1 .4 ~ 20mA output +
2.4~ 20mA output -
3 . Pulse output + + -
4. Pulse output -
Cable from sensor Power supply
5 . RS485 output +
90 ~ 260V AC
6. RS485 output -
50/60Hz
or
24VDC
1 2 3 4 5 6
+ -
+ +
mA
Load Load
6
3.1.2 Separate Wiring
Converter
AMC2100
Series
A B C X Y
Electorde
Coil
Sensor
AMF300 / AMF500
AMF601 / AMF900
Series A B C X Y
70 mm
Σ 123.456 m3
+0.000 m3/h
150 mm
150 mm
ENT Login parameter setting level Save presently settled parameter. Jump to next
Setting parameter setting
Selected one of 4 display line Change present digit, dot and survey unit.
Up Up/Down movement
7
3.2 Converter AMC3100 Operate Manual
3.2.1 Power and signal output connected line(compact and separate model)
Open the rear cover, and you can see terminal, according to your needs decide if you need to connect.
+ + +
-
-
-
1 . 4~20mA output +
2 . 4~20mA output -
3 . Pulse output +
4 . Pulse output -
5 . RS485 output +
6 . RS485 output -
+ -
Power supply
90~260VAC
50 / 60Hz
or
24VDC
I+ I- P+ P- R+ R-
+ -
+ +
mA
Load Load
8
3.2.2 Separate Wiring
Converter
AMC3100
Series
A B C X Y
Electorde
Coil
Sensor
AMF300 / AMF500
AMF601 / AMF900
Series A B C X Y
190mm
>
>
20mm
ENT Login parameter setting level Save presently settled parameter. Jump to next
Setting parameter setting
Selected one of 4 display line Change present digit, dot and survey unit.
Up Up/Down movement
9
3.3 Survey mode setting
Flowmeter will enter to normal mode when electrified, every line has several choice as follow:
3.4 Example
If you need Line 1 display from m3/h turn to %
Σ 123.456 m3
+0.0000m3/h
Σ 123.456 m3 In general display, Press or button and select ,make sure enter zero window
+0.0000m3/h
ENT
ENT
Clear Total Select YES for making zero operation and press ENT
to confirm
NO YES
10
3.6 Auto zero Adjustment
When the tube are full pipe, and no flow, flowmeter still show the flowrate, then you could use Auto Zero adjustment
to adjust your flowmeter to Zero, the method as follow:
Σ 123.456 m3 In the normal display, press ENT
button for 5 seconds, then it will go to next setting
+0.1234m3/h
ENT
OPERATIONS In this setting, Press or button till you selected ZERO and press ENT
to confirm
ENT
NO YES
ENT
Zero Adjustment.
Zero Triming …
ENT
Zero Tirm End Zero Adjustment end. Select ESC, press to turn back to the operations select
ENT
-2.624mv (If you want to do Zero Adjustment again, Pls select ZERO )
Zero Esc
ENT
ENT
ENT
11
3.8 Operate flow chart
Σ 123.456 m3
+0.0000m3/h
ENT
OPERATIONS
ENT
Password
ENT
0000
PV Units Communication
ENT ENT
URV
MODBUS Type HART Address
ENT
ENT ENT
Switch Func
ENT
Baudrate
ENT
Liter/Pulse Freq of URV (Hz)
ENT ENT
Data Bit
ENT
Pulse Width Alarm Select
ENT ENT
Parity
ENT
Pulse Level UPPER-Alarm
ENT
Stop Bit
ENT
Low Cutoff(%fs)
ENT
Modbus Address
ENT
Damping(s)
ENT
DATE (yy-mm-dd)
ENT
Hydro-State
ENT
TIME (hh-mm-ss)
Direction ENT
ENT
Indication
12
ENT
Password Password
1111 ****
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ENT ENT
ENT
ENT ENT
ENT
ENT
PGA
ENT
ENT
Zero Factor
ENT
4mA Trim
ENT
20mA Trim
13
3.9 User operate description
Σ 123.456 m3 In the normal display, press ENT
button for 5 seconds, then it will go to next setting
+0.0000m3/h
ENT
ENT
ENT
Language Language
Press or to selected the language
简体 繁體 ENG
ENT
ENT
ENT
ENT
Batch Control When selected “Alarm”, It will display “ Batch Control”
Please read page 22
ENT
14
Pulse Level Pulse Level
Press or to selected Pulse Level
Active L Active H
ENT
ENT
ENT
ENT
ENT
ENT
Direction Direction
Press or button to select the Hydro-state
Fwd. Rev. Bid. 1. Forward 2. Reverse 3. Bidirection
ENT
Indication Indication
Press or button to select the Indication
Forward Reverse 1. Forward 2. Reverse
ENT
ENT
50
ENT
15
Communication Communication
Press or button to select if need to use communication function
OFF ON
ENT
HART Address Please read page 18
00
ENT
ENT
ENT
ENT
ENT
ENT
ENT
17:09:49
16
HART operate description
ENT
ENT
17
3.10 System Mode
OPERATIONS In the normal display, press button for 5 seconds, then it will go to next setting
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ENT
18
3.11 Advance Mode
OPERATIONS In the normal display, press button for 5 seconds, then it will go to next setting
ENT
ENT
ENT
A7082106
ENT
ENT
ENT
ENT
ENT
ENT
ENT
19
ENT
B0000000
ENT
ENT
ENT
ENT
PGA PGA
Press or button to select the gain type
x 1. x 2 . x 4. AUTO Original setting “AUTO”
ENT
0.0
ENT
4.000
ENT
20.000
20
3.12 Batch Control
ENT
ENT
ENT
Language Language
Press or to selected the language
简体 繁體 ENG
ENT
ENT
ENT
ENT
ENT
21
Σ 123.456 m3 In general display, Press or button and select ,make sure enter batch control window
+0.0000m3/h
ENT
1.00000
ENT
ENT
ENT
PAUSE
ENT
SET 1.000m3 At this time, If choose START,It will continue the next flow
RUN 0.000m3 If choose EXIT, It will quit the batch control
ENT
MANUAL EXIT
22
4. Common Alarm Code Indication
32 OV. Freq Exceeding Fmax range Increase the frequency setting range
Exceeding the upper limit value of Turn off alarm output or raise alarm upper limit
64 UPPER
alarm settings value
Exceeding the upper limit value of Increase range
72 OV. Flow ; UPPER alarm settings Turn off alarm output or raise alarm upper limit
Over range value
Under the lower limit value of alarm Turn off alarm output or decrease the alarm
128 LOWER
setting lower limit value
Over range Increase range
136 OV. Flow ; LOWER Under the lower limit value of alarm Turn off alarm output or decrease the alarm
setting lower limit value
256 EMPTY Empty pipe alarm Check the pipe & full the pipe
1024 Coil Exciting Current<40% Check the XY wiring fall off or not
23
Quality we care !