You are on page 1of 2

PG-2V800

2 Volt 800 A.H.


UPS / TELECOM BATTERY

FEATURES PRODUCT
Long Service Life
Thick plate design and efficient gas recombination yield a service
life expectancy of 15 years in standby mode.

Low Internal Resistance


Superb high-rate discharge characteristics ensure reliable
performance in UPS and Telecom applications.

Maintenance-Free, Non-Spillable
Proven VRLA technology guarantees safe operation without
maintenance and 'non-restricted article' status for transportation.

Low Self-Discharge
Lead-calcium alloy grids and use of high purity lead account for
superior shelf-life characteristics permitting storage for extended
periods of time.

Designed-In Reliability
Cutting-edge manufacturing and process control combined with
meticulous quality assurance procedures guarantee consistent
and dependable performance.

SPECIFICATIONS
Nominal Voltage 2 Volt (1 cell)
Nominal Capacity
20-hr. rate ( 43.4A to 1.80V ) 868AH
10-hr. rate ( 80.0A to 1.80V ) 800AH
5-hr. rate ( 140.0A to 1.75V ) 700AH
3-hr. rate ( 212.0A to 1.75V ) 636AH
1-hr. rate ( 520.0A to 1.60V ) 520AH
Approximate Weight 123.6 lbs. (56.0 kg)
Energy Density ( 10-hr. rate ) 1.11 W-hrs/in3 (67.57 W-hrs/l)
Specific Energy ( 10-hr. rate ) 12.94 W-hrs/lb (28.57 W-hrs/kg)
Internal Resistance 0.18 millohms
5-min. Discharge Current to 1.60V/cell 2400 A
Terminals threaded insert w. 8 mm stud fastener
Shelf Life — ( % of nominal capacity at 68° F (20° C) )
1 Month 97%
3 Months 91%
6 Months 83%
Operating Temperature Range
Charge -4°F (-20°C) to 122°F (50°C)
Discharge -4°F (-20°C) to 140°F (60°C)
Case Material ABS plastic
TECHNICAL DETAIL: PG-2V800

CONSTANT POWER DISCHARGE RATINGS

WATTS PER CELL @ 25°C


Model Final
5 min 10 min 15 min 20 min 30 min 45 min 60 min
1.80V 2622 2386 2103 1687 1573 1143 929
1.75V 3117 2550 2261 2060 1658 1238 927
PG-2V800
1.67V 3258 2829 2517 2162 1680 1219 934
1.60V 3983 3084 2560 2147 1521 1208 1027

PERFORMANCE CHARACTERISTICS SELF-DISCHARGE & STORAGE

Discharge Time vs. Discharge Current 100 Charging is not


necessary unless

Capacity Retention Ratio (%)


100% of capacity
10 is required.
9 80
5ºC Charging before
use is necessary
(41ºF) to help recover
8
full capacity.
7 60
(h)

6 Charging may fail


30ºC to restore full
5 40ºC 20ºC capacity. Do not
40 (104ºF) (86ºF) (68ºF) let batteries reach
4
this state.
Discharge Time

3 0
2 0 2 4 6 8 10 12 14 16 18 20
Standing Period (Months)
60
50
40
30
CHARGING
20
(min)

Cycle Applications: Limit initial current to 240A. Charge until battery voltage (under
10 40°C (104°F) charge) reaches 2.40 to 2.45 volts at 68°F (20°C). Hold at 2.40 to 2.45 volts until
6 25°C ( 77°F) current drops to approximately 8A (0.01C).
3 0°C ( 32°F)
“Float” or “Stand-By” Service: Hold battery across constant voltage source of
2 2.25 to 2.30 volts continuously.

70 80 90 110 150 200 300 400 600 740 880 1800 2400
PHYSICAL DIMENSIONS
Discharge Current (A)

Discharge Characteristics 20mm


M8
6.89 (175)

7mm
2.1

2.0

1.9
16.14 (410)
1.8
80A 43.4A
Voltage (V)

1.75
1.6 212A 140A
520A
1.3 Sealed Long Life

800A
UPS/TELECOM BATTERY

POWER-GUARD SERIES ®
12.99 (330)

13.82 (351)

PG-2V800
2 Volt 800 A.H.
@ 10-hr. rate to 1.80V

0
2 3 10 20 25 60 2 3 5 10 20
UST BE R
M
EC
TTERY

YCL ED

Power-Sonic Corporation Pb
BA

www.power-sonic.com NONSPILLABLE

(min) (h)

Discharge Time

SALES & MARKETING ISO 9001-2000 CUSTOMER SERVICE


3106 Spring Street 9163 Siempre Viva Road
Redwood City, CA 94063 USA FM39170 San Diego, CA 92154 USA
Tel: 650-364-5001 Fax: 650-366-3662 Tel: 619-661-2030 Fax: 619-661-3648
battery@power-sonic.com www.power-sonic.com customer-service@power-sonic.com
PRINTED IN THE U.S.A. 04/04 1M

You might also like