PG -12V200

12 Volt 200 A.H.


UPS / TELECOM BATTERY

FEATURES PRODUCT
Long Service Life
Thick plate design and efficient gas recombination yield a service
life of up to 10 years in standby mode.

Low Internal Resistance


Superb high-rate discharge characteristics ensure reliable
performance in UPS and Telecom applications.

Maintenance-Free, Non-Spillable
Proven VRLA technology guarantees safe operation without
maintenance and 'non-restricted article' status for transportation.

Low Self-Discharge
Lead-calcium alloy grids and use of high purity lead account for
superior shelf-life characteristics permitting storage for extended
periods of time.

Designed-In Reliability
Cutting-edge manufacturing and process control combined with
meticulous quality assurance procedures guarantee consistent
and dependable performance.

SPECIFICATIONS
Nominal Voltage 12 Volt (6 cells)
Nominal Capacity
20-hr. rate ( 11.30A to 10.8V ) 226.0AH
10-hr. rate ( 21.00A to 10.8V ) 210.0AH
5-hr. rate ( 37.80A to 10.8V ) 189.0AH
3-hr. rate (55.30A to 10.8V ) 166.0AH
1-hr. rate ( 136.00A to 10.5V ) 136.0AH
Approximate Weight 141.2 lbs. (64.0 kg)
Energy Density ( 10-hr. rate ) 1.44 W-hrs/in3 (87.9 W-hrs/l)
Specific Energy ( 10-hr. rate ) 17.0 W-hrs/lb (37.5 W-hrs/kg)
Internal Resistance 2.8 millohms
30-sec. Discharge Current to 1.60V/cell 1200 A
Terminals threaded insert w. 6 mm stud fastener
Shelf Life — ( % of nominal capacity at 68° F (20° C) )
1 Month 97%
3 Months 91%
6 Months 83%
Operating Temperature Range
Charge -4°F (-20°C) to 122°F (50°C)
Discharge -4°F (-20°C) to 140°F (50°C)
Case Material ABS plastic
TECHNICAL DETAIL: P G -12V200

CONSTANT POWER DISCHARGE RATINGS

Final WATTS PER CELL @ 25°C


Model
Voltage
10 min 20 min 30 min 60 min 120 min 180 min 240 min
1.80V 685 475 407 248 148.3 108.8 85.5
PG-12V200 1.75V 758 540 431 260 155.2 117 97.7
1.60V 905 599 464 275 163 121.6 98.5

PERFORMANCE CHARACTERISTICS SELF-DISCHARGE & STORAGE

Discharge Time vs. Discharge Current 100 Charging is not


necessary unless

Capacity Retention Ratio (%)


100% of capacity
10 is required.
80
9 Charging before
5ºC
use is necessary
(41ºF) to help recover
8 full capacity.
7 60
(h)

Charging may fail


6 to restore full
40ºC 30ºC 20ºC
5 capacity. Do not
40 (104ºF) (86ºF) (68ºF) let batteries reach
4 this state.
Discharge Time

3 0
0 2 4 6 8 10 12 14 16 18 20
2
Standing Period (Months)
60
50
40
30
CHARGING
20
Cycle Applications: Limit initial current to 60A. Charge until battery voltage (under
(min)

10 40°C (104°F) charge) reaches 14.40 to 14.70 volts at 68°F (20°C). Hold at 14.40 to 14.70 volts
8 25°C ( 77°F) until current drops to approximately 2A.
6 0°C ( 32°F) “Float” or “Stand-By” Service: Hold battery across constant voltage source of
4 13.50 to 13.80 volts continuously.

0 4 8 12 18 21 25 27 40 65 130 205 420 630 800


PHYSICAL DIMENSIONS
Discharge Current (A)

Discharge Characteristics 20mm


Sealed Long Life
M6
Ambient Temperature: 25°C(77°F)
UPS/TELECOM BATTERY
9.45 (240)

13 6mm
POWER-GUARD SERIES ®
12 M
UST BE R

PG-12V200
EC
TTERY

YCL ED

Pb
BA

NONSPILLABLE
12 Volt 200 A.H. Power-Sonic Corporation
@ 10-hr. rate to 10.8V www.power-sonic.com

11
Voltage (V)

10.8
55.3A 37.8A 21A 11.3A
10 136A
20.55 (522)
9.6
600A 400A 200A
9

8
8.81 (224)
8.58 (218)

0 1.5 3 5 10 20 30 60 2 3 5 10 20

(min) (h)

Discharge Time

SALES & MARKETING ISO9001 CUSTOMER SERVICE


3106 Spring Street 9163 Siempre Viva Road
Redwood City, CA 94063 USA FM39170 San Diego, CA 92154 USA
Tel: 650-364-5001 Fax: 650-366-3662 Tel: 619-661-2030 Fax: 619-661-3648
battery@power-sonic.com www.power-sonic.com customer-service@power-sonic.com
PRINTED IN THE U.S.A. 06/03 1M