You are on page 1of 3

D ATA SH EET SOLAR SSIG 06 235

MODEL SSIG 06 235


VOLTAGE 6
CAPACITY 235Ah @ 100Hr
MATERIAL Polypropylene
BATTERY Deep-Cycle Flooded/Advanced Lead Acid Battery
COLOR Maroon
WATERING HydroLink (Optional)

6 VOLT
PHYSICAL SPECIFICATIONS
MODEL NAME TERMINAL TYPE D DIMENSIONS B INCHES (mm) WEIGHT E LBS. (kg) HYDROLINK OR SPWK HANDLES

LENGTH WIDTH HEIGHT C

SSIG 06 235 1 58 (26) HydroLink Embedded


10.30 (262) 7.13 (181) 10.74 (273)

ELECTRICAL SPECIFICATIONS
VOLTAGE CAPACITY A AMP-HOURS (Ah) ENERGY (kWh)

10-Hr 20-Hr 48-Hr 72-Hr 100-Hr 100-Hr


6
196 214 220 228 235 1.42

CHARGING INSTRUCTIONS CHARGING TEMPERATURE COMPENSATION


CHARGER VOLTAGE SETTINGS (AT 77°F/25°C) ADD SUBTRACT

SYSTEM VOLTAGE 6V 12V 24V 48V


0.005 volt per cell for every 1°C below 25°C 0.005 volt per cell for every 1°C above 25°C
0.0028 volt per cell for every 1°F below 77°F 0.0028 volt per cell for every 1°F above 77°F
Maximum Charge Current (% of C20 Rate)* 13%

Maximum Absorption Phase Time (hours) 4 OPERATIONAL DATA


Absorption Voltage ** 7.35 14.70 29.40 58.80
OPERATING TEMPERATURE SELF DISCHARGE
Float Voltage 6.75 13.50 27.00 54.00
-4°F to 113°F (-20°C to +45°C). At
5 – 15% per month depending on storage
temperatures below 32°F (0°C) maintain a
Equalization Voltage 8.10 16.20 32.40 64.80 temperature conditions.
state of charge greater than 60%.
Do not install or charge batteries in a sealed or non-ventilated compartment. Constant under or
overcharging will damage the battery and shorten its life as with any battery. STATE OF CHARGE MEASURE OF OPEN-CIRCUIT VOLTAGE
*If charging time is limited contact Trojan Technical Support for assistance.
**In cases where controller has a bulk voltage setting, use absorption voltage setting above. PERCENTAGE CHARGE SPECIFIC GRAVITY CELL 6 VOLT

100 1.277 2.122 6.37


RECYCLE RESPONSIBLY
90 1.258 2.103 6.31
80 1.238 2.083 6.25

6V 70 1.217 2.062 6.19


Flooded 60 1.195 2.040 6.12
50 1.172 2.017 6.05
40 1.148 1.993 5.98
30 1.124 1.969 5.91
20 1.098 1.943 5.83
10 1.073 1.918 5.75
DOD VS CYCLE LIFE IN PERCENT CAPACITY
A STATIONARY APPLICATION VS. TEMPERATURE
5500 140 60

120 50
5000

40
100
4500
30
80

Temperature (F)
4000

(C)
20

Temperature (C)
Temperature (F)
60

Temperature
3500 10
40
Number of Cycles

0
Number of Cycles

3000 20
-10

2500 0
-20

-20 -30
2000

-40 -40
1500 0% 20% 40% 60% 80% 100% 120%

Percentof
Percent of Available
Available Capacity
Capacity
1000

500

0
20% 30% 40% 50% 60% 70% 80%

Depth of Discharge
EXPECTED LIFE VS. TEMPERATURE
Depth-of-Discharge

Chemical reactions internal to the battery are driven by voltage and


temperature. The higher the battery temperature, the faster chemical
reactions will occur. While higher temperatures can provide improved
Self Discharge vs. Time discharge performance the increased rate of chemical reactions will
SELF DISCHARGE VS. TIME* result in a corresponding loss of battery life. As a rule of thumb, for every
100 2.12 10°C increase in temperature the reaction rate doubles. Thus, a month of
operation at 35°C is equivalent in battery life to two months at 25°C. Heat
90
42°F (6°C)
2.10 is an enemy of all lead acid batteries, FLA, AGM and gel alike and even
small increases in temperature will have a major influence on battery life.
80 2.08

Recharge Threshold @ 70% SOC


Open Circuit Voltage Per Cell

70 2.06
State of Charge %

60 2.04
*PERIODIC CHARGE
50 2.02
75°F (24°C) FREQUENCY
40 1.99
Provide a periodic freshening charge to maintain a SOC greater than the
30 1.97 threshold of 70%.

20 1.94
85°F (29°C)
10 1.92
0 2 4 6 8 10 12 14 16 18 20

Storage Time in Weeks


F F F
BATTERY DIMENSIONS (shown with ELPT)

7.13 7.13
E E (181) (181) E
10.30 WIDTH
10.30 WIDTH
(262) (262)
5/16"-18 .47 5/16"-18 .47
LENGTH 7 LENGTH
STAINLESS STEEL 6 5 STAINLESS STEEL4 3
NOTES: UNLESS OTHERWISE SPECIFIED ZONE DESCRIPTION
INITIAL RELEASE; ECO2693
1. DIMENSIONS ARE REFERENCE ONLY NEW CASE STYLE; ECO2997
H
D D CORRECT COVER DIMS; MODIFY NOTE 1; ECO3079
D
2.79

1.79
G
C C 10.74 10.74
C
9.69 (273)9.69 (273)
(246) (246)
HEIGHT HEIGHT

F
B
B B

THIS DRAWING AND DATA EMBODY


PROPRIETARY INFORMATION WHICH IS THE
CONFIDENTIAL PROPERTY OF TROJAN
BATTERY COMPANY WHICH SHALL NOT BE

6.97 6.97OR COPIED, REPRODUCED DISCLOSED TO OTHERS


USED IN WHOLE OR PART FOR ANY
10.18 10.18
(177)
PURPOSE
(177)PERMISSION 7.13
WITHOUT THE EXPRESS WRITTEN
OF TROJAN BATTERY CO. THIS
(259) E (259) 1 2 3 8 0 CL ARK ST. SANTA FE SPRI NGS, CA9 0 6 7 0
5194 MINOLA DR. LITHONIA, GA 30038 THE
(181)
DRAWING IS LOANED IN CONFIDENCE WITH
UNDERSTANDING THAT IT SHALL BE
1 2 3 8 0 CL ARK ST
5194 MINOLA DR.

10.30 TITLE
WIDTH
RETURNED ON DEMAND

A A (262)
UNLESS OTHERWISE
SPECIFICED
6V (T105, 5/16"-18T125, T605) BAYONET.47 UNLESS OTH
SPECIFIC

LENGTH
TOLERANCES ARE:
STAINLESS ELPTSTEELBATTERY ASSEMBLY TOLERANCE

BP DP CS
DWN BY SCALE CHK APPVD
X.X ı#0.02" CSIZE=DWG SCALE
X.X ı#0.02"
X.XX ı#0.01" X.XX ı#0.01"
X.XXX ı#0.005" DATE DWG NO REV X.XXX ı#0.005"

7 6 5 7 4 6 3 5
ANGL ES = ı #0 ı 3$0 '
4 03-23-11 720429 3 C
ANGL ES = ı #0 ı 3$0 '

UNCONTROLLED COPY WHEN DOWNLOADED or PRINTED- UNCONTROLLED COPY WHEN DOWNLOADED or PRINTED-
Check MASTER DOCUMENT LOG to verify that this document/drawing is current prior to use D
Check MASTER DOCUMENT LOG to verify that this document/drawing is current prior to use

C 10.74
9.69 (273)
(246) HEIGHT

TERMINAL CONFIGURATIONSD
1 ELPT EMBEDDED LOW PROFILE
B TERMINAL

Terminal Height Inches (mm)


1.22 (31) 6.97
10.18 (177)
Torque Values: in-lb (Nm) (259) 1
5
95 – 105 (11 – 12)
A
Bolt Size
5/16" – 18 X
X
X

7 6 5 4 3
A

UNCONTROLLED COPY WHEN DOWNLOADED or PRINTED-


Check MASTER DOCUMENT LOG to verify that this document/drawing is current prior to use

A. The amount of amp-hours (Ah) a battery can deliver when discharged at a constant rate at 86°F (30°C) for all rates and C. Height taken from bottom of the battery to the highest point on the battery. Heights may vary depending on type of terminal.
maintain a voltage above 1.75 V/cell. Capacities are based on peak performance. D. Terminal images are representative only.
B. Dimensions may vary depending on type of handle or terminal. Batteries should be mounted with 0.5 inches E. Weight may vary.
(12.7 mm) spacing minimum.

TROJAN BATTERY
COMPANY WITH
QUALITY SYSTEM
Designed in compliance with applicable BCI, DIN, BS and IEC standards.
CERTIFIED BY DNV
= ISO 9001:2015 =
Tested in compliance to BCI and IEC standards.

800.423.6569 / +1.562.236.3000 / trojanbattery.com SSIG 06 235_DS_022519

© 2019 Trojan Battery Company, LLC. All rights reserved. Trojan Battery Company is not liable for damages that may result from any information provided in or omitted
from this publication, under any circumstances. Trojan Battery Company reserves the right to make adjustments to this publication at any time, without notice or obligation.

You might also like