You are on page 1of 2

PG-2V300

2 Volt 324 A.H.


UPS / TELECOM BATTERY

FEATURES PRODUCT
Long Service Life
Thick plate design and efficient gas recombination yield a service
life expectancy of 15 years in standby mode.

Low Internal Resistance


Superb high-rate discharge characteristics ensure reliable
performance in UPS and Telecom applications.

Maintenance-Free, Non-Spillable
Proven VRLA technology guarantees safe operation without
maintenance and 'non-restricted article' status for transportation.

Low Self-Discharge
Lead-calcium alloy grids and use of high purity lead account for
superior shelf-life characteristics permitting storage for extended
periods of time.

Designed-In Reliability
Cutting-edge manufacturing and process control combined with
meticulous quality assurance procedures guarantee consistent
and dependable performance.

SPECIFICATIONS
Nominal Voltage 2 Volt (1 cell)
Nominal Capacity
20-hr. rate ( 17.6A to 1.80V ) 352.0AH
10-hr. rate ( 32.4A to 1.80V ) 324.0AH
5-hr. rate ( 56.7A to 1.75V ) 283.5AH
3-hr. rate (85.9A to 1.75V ) 257.7AH
1-hr. rate ( 210.6A to 1.60V ) 210.6AH
Approximate Weight 42.6 lbs. (19.3 kg)
Energy Density ( 10-hr. rate ) 1.17 W-hrs/in3 (71.74 W-hrs/l)
Specific Energy ( 10-hr. rate ) 14.09 W-hrs/lb (31.09 W-hrs/kg)
Internal Resistance 0.5 millohms
5-min. Discharge Current to 1.60V/cell 900 A
Terminals threaded insert w. 8 mm stud fastener
Shelf Life — ( % of nominal capacity at 68° F (20° C) )
1 Month 97%
3 Months 91%
6 Months 83%
Operating Temperature Range
Charge -4°F (-20°C) to 122°F (50°C)
Discharge -4°F (-20°C) to 140°F (60°C)
Case Material ABS plastic
TECHNICAL DETAIL: PG-2V300

CONSTANT POWER DISCHARGE RATINGS

WATTS PER CELL @ 25°C


Model Final
5 min 10 min 15 min 20 min 30 min 45 min 60 min
1.80V 1027 896 791 635 591.3 430.5 350
1.75V 1169 956.1 849 774 622 464 348
PG-2V300
1.67V 1222 1062 945 813 632 456.5 379
1.60V 1499 1161 966 809 620 455 417

PERFORMANCE CHARACTERISTICS SELF-DISCHARGE & STORAGE

Discharge Time vs. Discharge Current 100 Charging is not


necessary unless

Capacity Retention Ratio (%)


100% of capacity
is required.
80
10 Charging before
5ºC
9 use is necessary
(41ºF) to help recover
8 full capacity.
60
7 Charging may fail
(h)

6 30ºC to restore full


40ºC 20ºC capacity. Do not
5 40 (104ºF) (86ºF) (68ºF) let batteries reach
4 this state.
3 0
Discharge Time

0 2 4 6 8 10 12 14 16 18 20
2
Standing Period (Months)
60
50
40
30 40°C (104°F)
20
25°C ( 77°F)
CHARGING
(min)

10 0°C ( 32°F) Cycle Applications: Limit initial current to 90A. Charge until battery voltage (under
6
charge) reaches 2.40 to 2.45 volts at 68°F (20°C). Hold at 2.40 to 2.45 volts until
current drops to approximately 3A (0.01C).
3
2 “Float” or “Stand-By” Service: Hold battery across constant voltage source of
2.25 to 2.30 volts continuously.
25 30 40 45 50 85 130 180 225 290 360 730 970

Discharge Current (A)


PHYSICAL DIMENSIONS
20mm
Discharge Characteristics M8

7mm
5.91 (150)

2.1

2.0

1.9

1.8 6.69 (170)


32.4A 17.6A
Voltage (V)

1.75
1.6 85.9A 56.7A
210.6A
1.3
300A Sealed Long Life
UPS/TELECOM BATTERY
13.78 (350)

POWER-GUARD SERIES fi
12.91 (328)

PG-2V300
2 Volt 324 A.H.
0 @ 10-hr. rate to 1.80V

2 3 10 20 25 60 2 3 5 10 20
(min) (h)
UST BE R
M
EC
TTERY

YCL ED

Power-Sonic Corporation Pb
BA

www.power-sonic.com NONSPILLABLE

Discharge Time

SALES & MARKETING ISO 9001-2000 CUSTOMER SERVICE


3106 Spring Street 9163 Siempre Viva Road
Redwood City, CA 94063 USA FM39170 San Diego, CA 92154 USA
Tel: 650-364-5001 Fax: 650-366-3662 Tel: 619-661-2030 Fax: 619-661-3648
battery@power-sonic.com www.power-sonic.com customer-service@power-sonic.com
PRINTED IN THE U.S.A. 04/04 1M