You are on page 1of 2

PG-2V600

2 Volt 600 A.H.


UPS / TELECOM BATTERY

FEATURES PRODUCT
Long Service Life
Thick plate design and efficient gas recombination yield a service
life expectancy of 15 years in standby mode.

Low Internal Resistance


Superb high-rate discharge characteristics ensure reliable
performance in UPS and Telecom applications.

Maintenance-Free, Non-Spillable
Proven VRLA technology guarantees safe operation without
maintenance and 'non-restricted article' status for transportation.

Low Self-Discharge
Lead-calcium alloy grids and use of high purity lead account for
superior shelf-life characteristics permitting storage for extended
periods of time.

Designed-In Reliability
Cutting-edge manufacturing and process control combined with
meticulous quality assurance procedures guarantee consistent
and dependable performance.

SPECIFICATIONS
Nominal Voltage 2 Volt (1 cell)
Nominal Capacity
20-hr. rate ( 32.5A to 1.80V ) 650AH
10-hr. rate ( 60.0A to 1.80V ) 600AH
5-hr. rate ( 105.0A to 1.75V ) 525AH
3-hr. rate (159.0A to 1.75V ) 477AH
1-hr. rate ( 390.0A to 1.60V ) 390AH
Approximate Weight 88.3 lbs. (400 kg)
Energy Density ( 10-hr. rate ) 1.13 W-hrs/in3 (69.3 W-hrs/l)
Specific Energy ( 10-hr. rate ) 13.6 W-hrs/lb (30.0 W-hrs/kg)
Internal Resistance .26 millohms
5-min. Discharge Current to 1.60V/cell 1800 A
Terminals threaded insert w. 8 mm stud fastener
Shelf Life — ( % of nominal capacity at 68° F (20° C) )
1 Month 97%
3 Months 91%
6 Months 83%
Operating Temperature Range
Charge -4°F (-20°C) to 122°F (50°C)
Discharge -4°F (-20°C) to 140°F (60°C)
Case Material ABS plastic
TECHNICAL DETAIL: PG-2V600

CONSTANT POWER DISCHARGE RATINGS

WATTS PER CELL @ 25°C


Model Final
5 min 10 min 15 min 20 min 30 min 45 min 60 min
1.80V 2076 1790 1578 1266 1179 857 696
1.75V 2338 1913 1697 1547 1243 928 695
PG-2V600
1.67V 2443 2122 1886 1622 1072 912 700
1.60V 2988 2313 1920 1609 1141 906 769

PERFORMANCE CHARACTERISTICS SELF-DISCHARGE & STORAGE


Discharge Time vs. Discharge Current 100 Charging is not
necessary unless

Capacity Retention Ratio (%)


100% of capacity
10 is required.
9 80
5ºC Charging before
use is necessary
8 (41ºF) to help recover
full capacity.
7
(h)

60
6 Charging may fail
30ºC to restore full
5 40ºC 20ºC capacity. Do not
4 40 (104ºF) (86ºF) (68ºF) let batteries reach
this state.
Discharge Time

3 0
2 0 2 4 6 8 10 12 14 16 18 20
Standing Period (Months)
60
50
40
30
CHARGING
20
(min)

10
Cycle Applications: Limit initial current to 180A. Charge until battery voltage (under
40°C (104°F) charge) reaches 2.40 to 2.45 volts at 68°F (20°C). Hold at 2.40 to 2.45 volts until
6 25°C ( 77°F) current drops to approximately 6A (0.01C).
3 0°C ( 32°F)
“Float” or “Stand-By” Service: Hold battery across constant voltage source of
2 2.25 to 2.30 volts continuously.

50 60 70 82 100 125 150 200 300 540 660 1350 1800


PHYSICAL DIMENSIONS
Discharge Current (A)
20mm

Discharge Characteristics M8
6.89 (175)

7mm

2.1

2.0

1.9
11.81 (300)
1.8
60A 32.5A
Voltage (V)

1.75
1.6 159A 105A
390A
1.3 Sealed Long Life

600A UPS/TELECOM BATTERY

POWER-GUARD SERIES ®
12.99 (330)

13.78 (350)

PG-2V600
2 Volt 600 A.H.
@ 10-hr. rate to 1.80V

0
2 3 10 20 25 60 2 3 5 10 20 M
UST BE R
EC
TTERY

YCL ED

Power-Sonic Corporation Pb
BA

www.power-sonic.com NONSPILLABLE

(min) (h)

Discharge Time

SALES & MARKETING ISO 9001-2000 CUSTOMER SERVICE


3106 Spring Street 9163 Siempre Viva Road
Redwood City, CA 94063 USA FM39170 San Diego, CA 92154 USA
Tel: 650-364-5001 Fax: 650-366-3662 Tel: 619-661-2030 Fax: 619-661-3648
battery@power-sonic.com www.power-sonic.com customer-service@power-sonic.com
PRINTED IN THE U.S.A. 04/04 1M