Dampers

Combination Fire/Smoke Damper CFSD Series


Motorized Smoke Damper

CFSD FOR USE IN DYNAMIC SYSTEMS

FIRE RESISTANCE: 1 ½ HR AND 3 HRS


LEAKAGE RESISTANCE: CLASS I - 350° F & CLASS II - 250° F
DYNAMIC CLOSURE RATINGS: 2000FPM AND 4000FPM AIR VELOCITY
CLOSED DAMPER PRESSURE RATING: 4 inch W.G.
UL FILE NO: R22165

Product Description
Combination Fire / Smoke dampers provide an automatic means of localizing areas of smoke and or fire in
ventilation systems that is greatly contribute to the safety of life and property in the early stage of fire. It prevents
the spread of fire and or smoke through ventilation ductworks or wall openings. These type of dampers offer an
effective fire or smoke barrier maintaining the integrity in a fire situation and it is combined with low leakage
characteristic for smoke management. It is suitable for installation in sheet metal ductworks, openings in walls or
floor slabs made from concrete, bricks and in lightweight partition walls.

"SAFID" introducing "ERL" Thermoelectric Tripping Device (heat sensor) to replace the existing high torque spring
/ fusible link fire closure mechanism in all Combination Fire & Smoke dampers and blade type Fire dampers. The
"ERL" is thermally responsive bimetal disc / sensor that open and close the electrical contacts at a specific factory
calibrated temperature setting. The "ERL" is available in fixed temperature setting at 165°F (74 °C) only.The "ERL"
requires factory installation and wiring together with the qualified actuator to meet "UL" requirements.

Dampers which allow remote resetting of the damper from a remote location are dangerous. All damper moving
parts must be inspected and cycled at every six months and in accordance with "NFPA90A & 92A" latest edition
and local codes.

Right to alterations reserved. Page 1/19


Dampers
Combination Fire/Smoke Damper CFSD Series
Types
Motorized Smoke Damper
Galvanized Steel Construction as Standard.
1. Sleeve Type, Model: CFSD-40-100
2. Circular Type, Model: CFSD-50-100
3. Oval Type, Model: CFSD-60-100
4. With factory installed Sleeve, Model: CFSD-80-100

OPTIONAL CONSTRUCTION:

Same as the standard construction but blades, stub shaft (latch) with 4 pieces Ø6mm bolts &
nuts, axles and linkage brackets with axle in stainless steel Grade 304.
OPTIONAL: Blades from stainless steel Grade 316 or 316L.
1. Sleeve Type, Model: CFSD-40-110
2. Circular Type, Model: CFSD-50-110
3. Oval Type, Model: CFSD-60-110
4. With factory installed Sleeve, Model: CFSD-80-110

Same as the standard construction but frame, blades, installation sleeve and all accessories in
stainless steel Grade 304.
OPTIONAL: Frame, blades and installation sleeve from stainless steel Grade 316 or 316L.
1. Sleeve Type, Model: CFSD-40-120
2. Circular Type, Model: CFSD-50-120
3. Oval Type, Model: CFSD-60-120
4. With factory installed Sleeve, Model: CFSD-80-120

Standard Construction
Finish Mill galvanized
Sleeve 1.2mm thick (Ga.18) galvanized steel sheet.
Frame 130 x 24.5 x 1.5mm thick (Ga.16) galvanized steel hat channel.
Blades 1.5mm thick (Ga.16) galvanized steel "Triple Vee" (3V) groove type (standard).
Blade stop 1.5mm thick (Ga.16) galvanized steel sheet bend at 45° angle.
Linkage Side linkage concealed in frame (Standard).
Linkage bar Stainless steel type 304, 15mm x 3mm thick.
Galvanized steel Rectangle Stamping Part 50mm x 60mm x 3mm thick, fixed with 1 square axle 9.5 x
Linkage bracket
9.5 mm and Ø6.3mm Pin.
Crank 3mm thick galvanized steel sheet 32mm x 107mm with 6.6mm wide slot.
Axle Zinc plated steel square bar 9.5 x 9.5 mm.
Stub shaft (Latch) Die pressed galvanized steel sheet, 58mm x 68mm x 1.5mm thick (Ga.16).
Bearings Sintered bronze oilite type
Compression type stainless steel grade 304, 0.3mm thick fastened between case and blades by
Side Seal (Jamb seal)
blade axles.
Blade tip seal Blade tip seals are high temperature Durometer Dense Silicone.
Galvanized steel rod Ø12mm across the blade length with 10 x 10mm square end x 25mm long to
Jack shaft
suit with the actuator.
Die pressed galvanized steel sheet 152.9mm x 82.2mm x 1.5mm thick (Ga.16) with Ø12.7mm ball
Jack shaft holder
bearing.
Minimum Size 200W x 150H mm with single blade construction up to 250mm height.
Maximum Size 914W x 914H mm - Single section and 1828W x 1828H - Multiple Section
Mounting Vertical

UL Test Ratings
Fire Resistance 1½ Hour and 3 Hours
Air Leakage test Class I and Class II
Elevated temp. test 350°F and 250°F
Dynamic closure test Rated at 2000FPM and 4000FPM air velocity.
Rated Pressure Rated at 4 inch W.G.
Right to alterations reserved.
Page 2/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Types

Sleeve Type
Model CFSD-40

130 1

3
7 1. Casing (Frame)
10
5 2. Linkage bracket
3. Blade
8
4. Linkage bar
2
11 5. Bearings
6. Blade stop
9
6 7. Side seal
8. Blade tip seal
4
9. Lock washer and GI round washer
10. Kneelock
11. Jackshaft
W-5
H-5

Circular Type Flat Oval Type


Model CFSD-50 Model CFSD-60

275 + WALL THICKNESS 275 + WALL THICKNESS

DIA - 3

H-3

W-3

DIA + 25
W + 25 H + 25
DIA + 25

Right to alterations reserved.

Page 03/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Types Motorized Smoke Damper

CFSD with factory installed Sleeve, ERL and Actuator


Model: CFSD-80

1. Sleeve
2. Damper frame
3. Blade
4. Linkage bracket
5. Lock washer and galvanized round washer
6. Kneelock
7. Crank
8. Linkage bar
9. Actuator
10. Auxiliary swicht cable for indicating damper blades position
11. Thermoelectric Tripping Device (ERL)
12. Power supply
13. Blade stop
14. Stainless steel side seal
15. Blade tip seal
16. Stub shaft (Latch)
17. Jackshaft
18. Axle
19. Bearing

Right to alterations reserved.


Page 4/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Dimensions Single Section

CFSD with factory installed Sleeve, ERL and Actuator


Model: CFSD-80
Height: Up to 220 mm

FRONT VIEW SIDE VIEW

Thermoelectric Tripping Device (ERL)


Model: SF74 (165ºF Klixon)
Bimetallic manual reset type.
165°F (74°C) rated
UL Classified components

Schedule of Damper Sizes and Actuator Types


a. Single section damper with two position (open/close) spring retrun type actuators:
1. BELIMO Model: FSLF-S-US (24 / 230VAC) with built-in auxiliary switch.
Torque: 3.5Nm for W = 610 mm maximum.
2. Model: MS8104F1210 / MS4604F1210 (24 / 230VAC) with built-in auxiliary switch.
Torque: 3.5Nm for W = 610 mm maximum.
3. BELIMO Model: BF-S-ME (24 / 230VAC) with built-in auxiliary swith.
Torque: 15 Nm for W = 914 mm maximum.

Refer to technical data sheet of actuator or contact SAFID for the actuator specifications.

Right to alterations reserved. Page 5/19


Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Dimensions Single Section

CFSD with factory installed Sleeve, ERL and Actuator


Model: CFSD-80
Height: Up to 914 mm

FRONT VIEW SIDE VIEW

Thermoelectric Tripping Device (ERL)


Model: SF74 (165ºF Klixon)
Bimetallic manual reset type.
165°F (74°C) rated
UL Classified components
Schedule of Damper Sizes and Actuator Types
a. Single section damper with two position (open/close) spring retrun type actuators:
1. BELIMO Model: FSLF-S-US (24 / 230VAC) with built-in auxiliary switch.
Torque: 3.5 Nm
Damper size: W=610mm maximum, H=406mm maximum
2. Model: MS8104F1210/MS4604F1210 (24 / 230VAC) with built-in auxiliary switch.
Torque: 3.5 Nm
Damper size: W=610mm maximum, H=406mm maximum
3. BELIMO Model: FSNF-S-US (24 / 230VAC) with built-in auxiliary switch.
Torque: 8 Nm
Damper size: W=610mm maximum, H=610mm maximum
4. BELIMO Model: BF-S-ME (24 / 230VAC) with built-in auxiliary swith.
Torque: 15 Nm
Damper size: W= 914mm maximum, H= 914mm maximum

Refer to technical data sheet of actuator or contact SAFID for the actuator specifications.
Right to alterations reserved. Page 6/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Dimensions Multiple Section

CFSD with factory installed Sleeve, ERL and Actuator


Model: CFSD-80
Sizes:
Width : Up to 1200
Height : Up to 914

FRONT VIEW SIDE VIEW

Thermoelectric Tripping Device (ERL)


Model: SF74 (165ºF Klixon)
Bimetallic manual reset type.
165°F (74°C) rated
UL Classified components
Schedule of Damper Sizes and Actuator Types
a. Multiple section dampers with two position (open/close) spring retrun type actuators:
1. Model: MS4620F1203 (230VAC) with built-in auxiliary switch.
MS8120F1200 (24VAC) with built-in auxiliary switch.
Torque: 20 Nm

NOTE: Location of the actuator can be INSIDE or OUTSIDE the airstream.

Refer to technical data sheet of actuator or contact SAFID for the actuator specifications.

Right to alterations reserved.


Page 7/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Dimensions Multiple Section

CFSD with factory installed Sleeve, ERL and Actuator


Model: CFSD-80
Sizes:
Width : Up to 1828
Height : Up to 914

FRONT VIEW SIDE VIEW

Thermoelectric Tripping Device (ERL)


Model: SF74 (165ºF Klixon)
Bimetallic manual reset type.
165°F (74°C) rated
UL Classified components
Schedule of Damper Sizes and Actuator Types
a. Multiple section dampers with two position (open/close) spring retrun type actuators:
1. Model: MS4620F1203 (230VAC) with built-in auxiliary switch.
MS8120F1200 (24VAC) with built-in auxiliary switch.
Torque: 20 Nm

NOTE: Location of the actuator can be INSIDE or OUTSIDE the airstream.

Refer to technical data sheet of actuator or contact SAFID for the actuator specifications.

Right to alterations reserved.


Page 8/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Dimensions Multiple Section

CFSD with factory installed Sleeve, ERL and Actuator


Model: CFSD-80
Sizes:
Width : Up to 1200
Height : Up to 1828

FRONT VIEW SIDE VIEW

Thermoelectric Tripping Device (ERL)


Model: SF74 (165ºF Klixon)
Bimetallic manual reset type.
165°F (74°C) rated
UL Classified components
Schedule of Damper Sizes and Actuator Types
a. Multiple section dampers with two position (open/close) spring retrun type actuators:
1. Model: MS4620F1203 (230VAC) with built-in auxiliary switch.
MS8120F1200 (24VAC) with built-in auxiliary switch.
Torque: 20 Nm

NOTE: Location of the actuator can be INSIDE or OUTSIDE the airstream.

Refer to technical data sheet of actuator or contact SAFID for the actuator specifications.

Right to alterations reserved.


Page 9/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Dimensions Multiple Section

CFSD with factory installed Sleeve, ERL and Actuator


Model: CFSD-80
Sizes:
Width : Up to 1828
Height : Up to 1828

FRONT VIEW SIDE VIEW

Thermoelectric Tripping Device (ERL)


Model: SF74 (165ºF Klixon)
Bimetallic manual reset type.
165°F (74°C) rated
UL Classified components
Schedule of Damper Sizes and Actuator Types
a. Multiple section dampers with two position (open/close) spring retrun type actuators:
1. Model: MS4620F1203 (230VAC) with built-in auxiliary switch.
MS8120F1200 (24VAC) with built-in auxiliary switch.
Torque: 20 Nm

NOTE: Location of the actuator can be INSIDE or OUTSIDE the airstream.

Refer to technical data sheet of actuator or contact SAFID for the actuator specifications.

Right to alterations reserved.


Page 10/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Dimensions

Model: CFSD Series


Blades Profiles:

Right to alterations reserved. Page 11/19


Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Dimensions

Model: CFSD Series


Linkage Assembly:

Right to alterations reserved.


Page 12/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Installation Details

CFSD with factory installed Sleeve, ERL and Actuator


Model: CFSD-80
Typical Installation

NOTES:
1. Airflow can be at opposite direction.
2. The actuator and ERL can be located in either side of the wall.
3. Refer to installation manual for further installation detail.

Right to alterations reserved.


Page 13/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Actuators

BELIMO Actuator BELIMO Actuator BELIMO Actuator Honeywhell Actuator Thermoelectric


Model: FSLF Model: FSNF Model: BF Model: MS4620F1203 Tripping Device (ERL)
MS4604F1210 , MS4609F1210 (230V)
MS8104F1210,MS8109F1210 & MS8120F1200(24V) SF74 (165ºF) Klixon
Sequence of operation
Fire Mode: The ERL (Thermoelectric Tripping Device) resettable link has a thermal sensor
switch that interrups the power supply to the fire & smoke control actuator as soon as the duct
temperature exceeds 165ºF caused by a fire. When the power supply is interrupted, the energy
stored in the spring of the fire & smoke damper actuator moves the damper back to its safe
position. The damper can be open again by pressing the reset button on ERL after the
temperature cooled down below 165ºF.
Smoke Mode: When a signal detected through normally closed smoke detector (by others)
connection, the power supply to the fire & smoke damper actuator will be interrupted. The energy
stored in the damper actuator moves the damper back to its safe position and remain closed until
the smoke signal close down. The system will reset after power is reapplied to the actuator and
damper will open. By placing an optional control switch (by others), the damper blades at open
position can be closed at any time if required.

Typical Wiring Diagram

          24 VAC OR 240 VAC 
               FUSED CIRCUIT 

Right to alterations reserved.


Page 14/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Air Performance

Pressure Drop
The test method for pressure drop of Combination Fire/Smoke Damper was conducted as per ANSI / AMCA
Standard 500-D, Figure 5.3 which simulate the actual site condition when installed in ventilation, supply and return
air conditioning ductworks.

AMCA Test Figure 5.3

Pressure Drop at Face Area Velocity


Damper Size: 12in. x 12in. - Fully open blades

Right to alterations reserved.

Page 15/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Air Performance

Pressure Drop
The test method for pressure drop of Combination Fire/Smoke Damper was conducted as per ANSI / AMCA
Standard 500-D, Figure 5.3 which simulate the actual site condition when installed in ventilation, supply and return
air conditioning ductworks.

AMCA Test Figure 5.3

Pressure Drop at Face Area Velocity


Damper Size: 24in. x 24in. - Fully open blades

Right to alterations reserved.


Page 169
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Air Performance

Pressure Drop
The test method for pressure drop of Combination Fire/Smoke Damper was conducted as per ANSI / AMCA
Standard 500-D, Figure 5.3 which simulate the actual site condition when installed in ventilation, supply and return
air conditioning ductworks.

AMCA Test Figure 5.3

Pressure Drop at Face Area Velocity


Damper Size: 36in. x 36in. - Fully open blades

Right to alterations reserved.


Page 17/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Order Details

Order Code: CFSD-80 - 100 - 3V - PB - R - A1S - V1 - ER 500 x 500

Variants Duct Size


CFSD-40 = Sleeve Type Width x Height or
CFSD-50 = Circular Spigot Diameter. All damper's
CFSD-60 = Oval Spigot spigot sizes (slip-in
CFSD-80 = Factory Installed Sleeve type) will be
manufactured less than
duct size to fit inside the
ductwork connections.

Types
100 = Galvanized Steel Construction
110 = Blades of Stainless Steel Grade 304
OPTIONAL: Grade 316 or 316L
120 = Stainless Steel Construction
S/S Grade 304 Type of Sensor
OPTIONAL: Grade 316 or 316L ERL = Thermoelectric
Tripping Device
Model::SF74 (165ºF Klixon)

Type of Blades Power Supply


3V = V Groove Type V1 = 24VAC
V2 = 230VAC
Linkage
PB = Side linkage Parallel Blades Operation
Actuators
External Controls BELIMO, BF-S-ME
R = Right hand (Standard Supply) BELIMO, FSNF-S-US
L = Left hand BELIMO, FSLF-S-US
Honeywell, MS4620F1203
MS4604F1210 , MS4609F1210 (230V)
MS8104F1210,MS8109F1210 & MS8120F1200(24V)

Right to alterations reserved.


Page 18/19
Dampers
Combination Fire/Smoke Damper CFSD Series
Motorized Smoke Damper
Specification Text Order Example
Combination Fire/Smoke Dampers with the following SAFID Combination Fire/Smoke Damper, galvanized
specifications shall be used in Heating, Ventilating and steel construction, 3V groove blade for parallel blades
Air Conditioning (HVAC) Duct Systems passing operation, 500mm width X 500mm height duct size
through openings in masonry walls, concrete floor and right hand side external controls. Damper shall
slabs, and in gypsum walls or partitions which required
be with factory installed sleeve and 230 VAC BELIMO
to have a fire resistance rating to restrict the spread of
fire. It shall be also used in Smoke Control Systems actuator with built-in auxiliary switch and with
and in Smoke Proof Stair Enclosure if the wall thermoelectric tripping device (ERL) with temperature
penetrations required to be fire rated in accordance rating of 165°F (74°C).
with NFPA 90A Standard for Installation of Air
Conditioning and Ventilating Systems, and with NFPA
101 Life Safety Code. Make : SAFID
Combination Fire/Smoke Dampers shall be tested and
Type : CFSD-80-100-3V-PB-R-A1S-V2-ERL
classified by Underwriters Laboratories Inc. (UL) in Size : 500 W x 500 H
accordance with the standards; UL 555 Standard for Qty. : 1
Safety, Fire Dampers and UL 555S Standard for
Safety, Smoke Dampers.

Combination Fire/Smoke Dampers with Fire


Resistance Rating of 1½ hour shall be used in fire
barrier with Fire Resistance Rating of less than 3 `
hours, and dampers with 3 hours Fire Resistance
Rating shall be used in fire barrier with Fire Resistance
Rating of 3 hours or more. Leakage Resistance Rating
shall be Class I at 350°F or Class II at 250°F elevated
temperature. It shall be UL Certified for dynamic
closure test with airflow velocity of minimum 2000 FPM
and maximum 4000 FPM with rated Pressure Class of
4 inch of Water Gauge (W.G.).

Combination Fire/Smoke Dampers shall be fitted with


UL Listed spring return actuator and Thermoelectric
Tripping Device (ERL) with temperature rating of 165°F
(74°C). ERL shall cut-off power supply to the actuator
in case of fire that will activate the built-in spring return
to close the damper blades.

Damper blades shall be with external linkage and


parallel action, Ga.16 galvanized steel with 3V groove
type for longitudinal reinforcement. Blade's tip seal
shall be Type 60 Durometer Dense Silicone, meets
gasket requirements in accordance with UL 555S.
Blade's axel shall be 9.5 X 9.5 mm square forced-fit to
one stub shaft, secured to blade with 4 pieces of bolt &
nut, and with sintered bronze oilite axle bearing. Jamb
seal/side seal shall be stainless steel to fill gap
between blade's end and vertical frame. Jackshaft
shall be Ø12 mm galvanized steel with a crank and
kneelock secured to the linkage bracket. Damper
frame shall be Ga.16 galvanized steel formed into hat
channel shape.

Right to alterations reserved.


Page 19/19
Fire and Smoke Spring Return Actuator FSLF230(-S) US
• Meet requirement of UL555(S) when tested as an assembly with
suitable dampers
• Torque: 3.5Nm @ 177°C(350°F) for 30 minutes
• Running time: 15s
• Control: Open/Close
• 1 wire control

Technical data
Electrical data Nominal voltage AC 230V 50/60Hz
Nominal voltage range AC 207...253V
Power consumption 17VA @ running / 6.5VA @ holding
Fusing 0.125A slow blow
Connection -Motor 1m, 18ga, 3 colour coded leads
-Auxiliary Switch 1m, 18ga, 4 appliance leads
1/2” conduit connector
Functional data Torque 3.5Nm (0°C to 177°C) @ nominal voltage
Direction of rotation Selectable by CW/CCW installation
Angle of rotation Max. 95°
Auxiliary switch -FSLF230-S 2 SPST, 1mA @ DC 5V, 3(0.5)A, 120/250V
fixed at 10° , 85°
Running time -Motor <15s at rated voltage and torque
-Spring Return <15s
Position indicator Mechanical
Safety Protection class Grounded enclosure
Degree of protection IP30 / NEMA type 1
Mode of operation Type 1.AA.B
Agency listed cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1,
CSA C22.2 No. 24-93
Ambient -Normal Duty 0...+50°C
temperature -Safety Duty 3 Open/Close cycles after 1/2hr @177°C
Storage temperature -40...+80°C
Humidity test 5...95% RH, non-condensing
Maintenance Maintenance-free
Dimensions / weight Dimensions (L x M x H) 179 x 98 x 82mm
Shaft diameter 12.7...20mm*
Weight -FSLF230 Approx. 1.8kg
-FSLF230-S Approx. 1.95kg
* For damper spindles ø16...20mm, use K6-1

Dimensions [mm/inches]
V3.6 08.2015• Subject to modification

27
Wiring Diagrams FS.. Series

Wiring diagram: FS.. Series Fail-Safe Open/Close Actuators


Notes:
• Parallel connection of several actuators is possible.
• Power consumption must be observed.

(for FSTF230 US) (for FSTF230-S US)


(for FSTF120 US) (for FSTF120-S US)

FSTF24 US FSTF24-S US
FSTF120 US FSTF120-S US
FSTF230 US FSTF230-S US

(for FSLF230 US) (for FSLF230-S US)

FSLF24 US FSLF24-S US
FSLF230 US FSLF230-S US

(for FSNF230 US, FSAF230A) (for FSNF230-S US, FSAF230A-S)


(for FSAF120A) (for FSAF120A-S)

FSNF24 US FSNF24-S US
FSNF230 US FSNF230-S US
FSAF24A FSAF24A-S
FSAF120A FSAF120A-S
FSAF230A FSAF230A -S

(for FSAF230 US) (for FSAF230-S US)


V3.6 08.2015• Subject to modification

FSAF24 US FSAF24-S US
FSAF230 US FSAF230-S US

46
71820-00001 FSNF230-S US
On/Off, Spring Return, 350°F [177°C] for half hour, 230VAC, 15 Seconds Cycle Time

Fire & Smoke damper actuator

Application
The type FSNF spring-return actuator is intended for the operation of smoke
and combination fire and smoke dampers in ventilation and air-conditioning
systems. The actuator will meet requirements of UL555 and UL555S when
tested as an assembly with the damper and will meet requirements of UBC
for 15 second opening and closing. Square footage of damper operated will
depend on make and model and the temperature required.

Operation
Mounting of the actuator to the damper shaft or jackshaft (3/8” to 1.05”) is via
a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both solid
Technical Data 1451 and hollow shafts maintaining a perfect connection. The specially designed
Power Supply 230 VAC ± 14%, 50/60 Hz clamp will not crush hollow shafts. The bottom end of the actuator is held by an
anti-rotation strap or by a stud provided by the damper manufacturer.
Power Consumption Running 50/60 Hz, 23 VA 
Power Consumption Holding 9 VA, End stop 58 VA, 0.25 A slow blow fuse The actuator is mounted in its fail safe position with the damper blade(s) closed.
*  Upon applying power, the actuator drives the damper to the open position. The
Shaft Diameter 1/2” to 1.05” round, centers on 1/2” and 3/4” internal spring is tensioned at the same time. If the power supply is interrupted,
with insert, 1.05” without insert the spring moves the damper back to its fail-safe position.
Electrical Connection 3 ft [1m], 18 GA, 3 color coded leads
Overload Protection electronic throughout 0° to 95° rotation Dimensions (Inches[mm])
Electrical Protection grounded enclosure, 230V 0.65" [16.5]

0.19"
[5]
Angle of Rotation 95° Standard:

3.25" [82.7]
Torque 70 in-lbs [8 Nm] minimum from 32°F to 1/2" to 1.05"

2.24"
[57]
350°F [0°C to 177°C]
Optional*
Direction of Rotation (Motor) can be selected by CCW/CW mounting 3/8" to 3/4"
Direction of Rotation (Fail-Safe) can be selected by CCW/CW mounting 0.19" [5]
Position Indication visual indicator, 0° to 95° (0° is full spring 0.39" [10] 2.64"
10.20" [259]
5.85" [148.5]
return position) 0.35" [9] [67]
0.26" [6.5]
Manual Override No

1.93"
ø1.62"

[49]
3.86" [98]
3.15" [80]
[ø41.2]
Running Time (Motor) <15 seconds at rated voltage and torque 32°F

[73.5]
2.89"
to 122°F [0°C to 50°C]
Date created, 12/15/2015 - Subject to change. © Belimo Aircontrols (USA), Inc.

*with K4 US clamp
Running Time (Fail-Safe) <15 seconds
Humidity 5 to 95% RH non-condensing 1.97" -S models only
[50]
7.54" [191.6]
Ambient Temperature Range 32°F to 122°F [0°C to 50°C]
Storage Temperature Range -40°F to 176°F [-40°C to 80°C]
Safety Notes
Housing NEMA type 1 / IP40
* Neither UL nor Belimo require local over-current protection. The FSNF
Housing Material zinc coated steel actuators draw higher peak current when driving against any type of stop. If
Gears steel, permanently lubricated used, this requires the value of a local fuse or breaker to be increased to avoid
Agency Listings† cULus listed to UL873 and CAN/CSA C22.2 nuisance opening or tripping. A 2.5 amp slow blow should be used for 24VAC.
No.24, UL 2043 Listed for air plenum A 0.5 amp slow blow should be used for 120 VAC. A 0.25 amp slow blow
installation per NEC 300.22 and IMC Section should be used for 230V and a 0.3 amp slow blow for 208 VAC. Transformers:
602 Note that while a 24V 100VA transformer would handle 2 actuators, a 4 A
NYC Department of Buildings MEA 197-07-M. breaker or plug fuse is insufficient. A 5 amp slow blow would be required.
California State Fire Marshal Listing 3210-
1593:101. Belimo Fire & Smoke actuators have passed the AMCA 520 and UL 555S Long
Noise Level (Motor) 45 db(A) motor, 62 db(A) spring, inaudible Term Holding test. No special cycling is required during prolonged periods
holding  when actuator is driven open and held there. Periodic testing of dampers and
Servicing maintenance free actuators per local codes and NFPA 80 and NFPA 105 are required.
Quality Standard ISO 9001
Weight 7.2 lbs. (3.25 kg.) The actuator contains no components which the user can replace or repair.
A 1/2” threaded connector is standard. FSNFxx-FC models have a 3/8” Flex
Auxiliary Switch 2 x SPDT, 7A resistive, 2.5A inductive at 120V
Connector. Other than the connector, these actuators are identical to the
or 250V, double insulated, one switch at 10°,
conduit connector version.
one at 85°
† UL File XAPX.E108966

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


FSNF230-S US
On/Off, Spring Return, 350°F [177°C] for half hour, 230VAC, 15 Seconds Cycle Time

Accessories
AF-P Anti-rotation bracket AF/NF.
IND-LF LF position indicator.
K4-1 US Classic AF/NF jackshaft clamp (up to 1.05”).
KH-AF Classic AF/NF crankarm for Shafts to 3/4”.
KH-AF-1 US Classic AF/NF crankarm for Jackshaft to 1.05”.
SH8 Push rod for KG6 & KG8 ball joints (36” L, 5/16” diameter).
ZDB-AF2 US Angle of rotation limiter for Classic AF/NF.
ZG-100 Univ. right angle bracket (17” H x 11-1/8” W x 6” base).
ZG-101 Univ. right angle bracket (13” H x 11” W x 7-7/16” base).
ZG-AF US Classic AF/NF crankarm adaptor kit.
ZG-AF108 Classic AF/NF crankarm adaptor kit with ZG-108.
ZG-DC1 Damper clip for damper blade, 3.5” width. 230 VAC
ZG-DC2 Damper clip for damper blade, 6” width.
ZS-100 Weather shield - galvaneal (13” L x 8” W x 6” D). Detector or relay F&S Damper
ZS-150 Weather shield - PC w/ foam seal (16” L x 8-3/8” W x 4” D).
ZS-260 Explosion proof housing. 165°F
N, L2,
ZS-300 NEMA 4X, 304 stainless steel enclosure. HOT 2 1 or COM
BAE165 US 165° F electric thermal sensor, SPST, normally closed.
S2A-F US Auxiliary switch, 2x SPDT, 3A (0.5A inductive) @250 VAC max.

Manual Actuator
Typical Specification reset
All smoke and combination fire and smoke dampers shall be provided To alarm
with Belimo FSTF, FSLF, FSNF, or FSAF actuators. All substitutions must be system
approved before submission of bid. Damper and actuator shall have UL 555S
Listing for 250°F (350°F). Actuator shall have been tested to UL 2043 per Typical containment damper control wiring
requirements of IMC 602.2 and NEC 300.22 (c). Where position indication is
required -S models with auxiliary switches or damper blade switches will be
provided per code requirements.

Wiring Diagrams
INSTALLATION NOTES

Date created, 12/15/2015 - Subject to change. © Belimo Aircontrols (USA), Inc.


Provide overload protection and disconnect as required.
Actuators may be powered in parallel. Power consumption must be Parallel Actuator Wiring
45
observed.

72 S4 makes to S6 when actuator is powered open.

73 Auxiliary switches are for end position indication or interlock control. S1


Double insulated.
74
NC
75 Ground present on some models. S2

S3 10°
NO 73
S4
NC
S5
85° 74
S6
NO 72
Auxiliary Switch

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


Technical data sheet BF230-S-ME

Spring-return actuator for fire and


smoke dampers 90° in ventilation and
air-conditioning systems.
• Torque 15 Nm
• Nominal voltage AC 230 V
• Control: Open-close
• Damper rotation: 12 mm form-fit
• Integrated auxiliary switch
• Designed to meet UL555S

Technical Data
Electrical data Nominal voltage AC 230 V, 50/60 Hz
Nominal voltage range AC 198 ... 264 V
Power consumption Motoring 11 W @ nominal torque
Holding 3.5 W
For wire sizing 12 VA / lmax. 500 mA @ 5 ms
Auxiliary switch 2 x SPDT
Contact rating (contacts gold plate on silver) 1 mA ... 6 A (3 A), DC 5 V ... AC 250 V
Switching points 5° / 80°
Connecting Motor Cable 1 m, 2 x 0.75 mm2 (halogen-free)
Auxiliary switch Cable 1 m, 6 x 0.75 mm2 (halogen-free)
Functional data Torque Motor Min. 15 Nm
Spring-return Min. 15 Nm
Direction of rotation Selected by mounting L/R
Angle of rotation Max. 95° (incl. 5° spring pretensioning)
Running time Motor <75 s
Spring-return <20 s (tamb = 20°C)
Sound power level Motor Max. 45 dB (A)
Spring-return ~62 dB (A)
Damper rotation Form-fit 12 mm (10 with adapter supplied)
Position indication Mechanical with pointer
Service life Min. 60’000 safe positions
Safety Protection class II totally insulated
..
Degree of protection IP54 in all mounting positions ..
..

NEMA2, UL Enclosure Type 2 ..


..
..
EMC CE according to 2004/108/EC ..
..
..
Low-voltage directive CE according to 2006/95/EC ..
..
..
Certification cULus according to UL873 and CAN/CSA C22.2 No. 24 ..
..
Designed to meet UL555S ..
..
..
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14 ..

Mode of operation Type 1.AA.B


Rated impulse voltage 4 kV
Control pollution degree 3
Ambient temperature –30 ... +50°C
Non-operating temperature –40 ... +80°C
Ambient humidity range 95% r.H., non-condensating
Maintenance Maintenance-free
Dimensions / weight Dimensions See «Dimensions» on page 2
Weight Approx. 3.1 kg

Safety notes
• The actuator is not allowed to be used outside the specified field of application, especially in
! aircraft or in any other airborne means of transport.
• Caution: Power supply voltage!
• The actuator is adapted and mounted to the fire and smoke damper by the damper manufac-
turer. For this reason, the actuator is only supplied direct to safety damper manufacturers.
The manufacturer then bears full responsibility for the proper functioning of the damper.

www.belimo.com T3-BF230-S-ME • en • v1.1 • 06.2008 • Subject to changes 1/2


Spring-return actuator 90° , AC 230 V, 15 Nm,
BF230-S-ME integrated auxiliary switch, designed to meet UL555S

Safety notes (Continue)


• The device may only be opened at the manufacturer’s site. It does not contain any parts that
can be replaced or repaired by the user.
• The device contains electronic and electrical components and may not be disposed of with
the household waste. Observe local regulations and valid laws.

Product features
Mode of operation The actuator moves the damper to its normal working position while tensioning the return spring
at the same time. If the power supply is interrupted, the energy stored in the spring moves the
damper back to its safe position.

Signalling Two microswitches with fixed settings are installed in the actuator for indicating the damper end
positions. The position of the damper blade can be read off on a mechanical position indicator.

Manual operation Without power supply, the damper can be operated manually and fixed in any required position.
Release of the locking mechanism can be achieved manually or automatically by applying the
supply voltage.

Accessories
Description Type
Electrical accessories Auxiliary switch, 1 x SPDT 6 A (2.5 A), AC 250 V SN1
Auxiliary switch, 2 x SPDT 6 A (2.5 A), AC 250 V SN2
Mechanical accessories Adapter with clamp for rotary axes up to 20 mm for BF.. and BLF.. ZK-BF
Adapter with DM18 rotary axis, L = 33 mm, for BF.. and BLF.. ZA18-BF
Adapter 12/8 mm for BF.. and BLF.. ZA8-BF
Adapter 12/11 mm for BF.. and BLF.. ZA11-BF
Bracket for SN1 and SN2 auxiliary switches for BF.. ZSN-BF

Electrical installation
Wiring diagram N L1

Note
• Caution: Main power supply voltage! !
• A device that disconnects the pole conductors
(minimum contact gap 3 mm) is required for
isolation from the power supply.
• Parallel connection of several actuators possible. 1 2 S1 S2 S3 S4 S5 S6
Power consumption must be observed!

<5° <80°

Dimensions [mm]
Dimensional diagrams
17

ø 5.2
58.6
17
1

6.5
5.1

40
.2

80
98
12

40

27.2 40
175.6

10 188 50
248

2/2 T3-BF230-S-ME • en • v1.1 • 06.2008 • Subject to changes www.belimo.com


Fire and Smoke Spring Return Actuator FSLF24(-S) US
• Meet requirement of UL555(S) when tested as an assembly with
suitable dampers
• Torque: 3.5Nm @ 177°C(350°F) for 30 minutes
• Running time: 15s
• Control: Open/Close

Technical data
Electrical data Nominal voltage AC 24V 50/60Hz, DC 24V*
Nominal voltage range AC 19.2...26.4V, DC 24...36V*
Power consumption 15VA @ running / 3.5VA @ holding
For transformer sizing 25VA
Fusing 1A slow blow
Connection -Motor 1m, 18ga, 2 colour coded leads
-Auxiliary Switch 1m, 18ga, 4 appliance leads
1/2” conduit connector
Functional data Torque 3.5Nm (0°C to 177°C) @ nominal voltage
Direction of rotation Selectable by CW/CCW installation
Angle of rotation Max. 95°
Auxiliary switch -FSLF24-S 2 SPST, 1mA @ DC 5V, 3(0.5)A, 120/250V
fixed at 10° , 85°
Running time -Motor <15s at rated voltage and torque
-Spring Return <15s
Position indicator Mechanical
Safety Protection class Class 2 supply
Degree of protection IP30 / NEMA type 1
Mode of operation Type 1.AA.B
Ambient -Normal Duty 0...+50°C
temperature -Safety Duty 3 Open/Close cycles after 1/2hr @177°C
Storage temperature -40...+80°C
Humidity test 95% RH, non-condensing
Maintenance Maintenance-free
Dimensions / weight Dimensions (L x M x H) 179 x 98 x 82mm
Shaft diameter 12.7...20mm**
Weight -FSLF24 Approx. 1.6kg
-FSLF24-S Approx. 1.7kg
Safety note AC 24V: Connect via safety isolating transformer,
class 2 supply

* Filtered and regulated DC 24V power supplies is needed.


** For damper spindles ø16...20mm, use K6-1

Dimensions [mm/inches]
V3.6 08.2015• Subject to modification

26
Wiring Diagrams FS.. Series

Wiring diagram: FS.. Series Fail-Safe Open/Close Actuators


Notes:
• Parallel connection of several actuators is possible.
• Power consumption must be observed.

(for FSTF230 US) (for FSTF230-S US)


(for FSTF120 US) (for FSTF120-S US)

FSTF24 US FSTF24-S US
FSTF120 US FSTF120-S US
FSTF230 US FSTF230-S US

(for FSLF230 US) (for FSLF230-S US)

FSLF24 US FSLF24-S US
FSLF230 US FSLF230-S US

(for FSNF230 US, FSAF230A) (for FSNF230-S US, FSAF230A-S)


(for FSAF120A) (for FSAF120A-S)

FSNF24 US FSNF24-S US
FSNF230 US FSNF230-S US
FSAF24A FSAF24A-S
FSAF120A FSAF120A-S
FSAF230A FSAF230A -S

(for FSAF230 US) (for FSAF230-S US)


V3.6 08.2015• Subject to modification

FSAF24 US FSAF24-S US
FSAF230 US FSAF230-S US

46
71816-00001 FSNF24-S US
On/Off, Spring Return, 350°F [177°C] for half hour, 24VAC only, 15 Seconds Cycle Time

Fire & Smoke damper actuator

Application
The type FSNF spring-return actuator is intended for the operation of smoke
and combination fire and smoke dampers in ventilation and air-conditioning
systems. The actuator will meet requirements of UL555 and UL555S when
tested as an assembly with the damper and will meet requirements of UBC for
15 second opening and closing at 350°F. Square footage of damper operated
will depend on make and model and the temperature required.

Operation
Mounting of the actuator to the damper axle shaft or jackshaft (3/8” to 1.05”) is
via a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both
Technical Data 1447 solid and hollow shafts maintaining a perfect connection. The specially designed
Power Supply 24 VAC ± 20%, 50/60 Hz clamp will not crush hollow shafts. The bottom end of the actuator is held by an
anti-rotation strap or by a stud provided by the damper manufacturer.
Power Consumption Running 50/60 Hz, 24 VA 
Power Consumption Holding 6.5 VA, End stop 67 VA, 2.5 A slow blow fuse *  The actuator is mounted in its fail safe position with the damper blade(s) closed.
Transformer Sizing 40VA (class 2 power source) Upon applying power, the actuator drives the damper to the open position. The
Shaft Diameter 1/2” to 1.05” round, centers on 1/2” and 3/4” internal spring is tensioned at the same time. If the power supply is interrupted,
with insert, 1.05” without insert the spring moves the damper back to its fail-safe position.
Electrical Connection 3 ft [1m], 18 GA, 2 color coded leads
Dimensions (Inches[mm])
Overload Protection electronic throughout 0° to 95° rotation
Electrical Protection actuators are double insulated 0.65" [16.5]

0.19"
[5]
Angle of Rotation 95° Standard:

3.25" [82.7]
Torque 70 in-lbs [8 Nm] minimum from 32°F to 350°F 1/2" to 1.05"

2.24"
[57]
[0°C to 177°C] Optional*
Direction of Rotation (Motor) can be selected by CCW/CW mounting 3/8" to 3/4"
Position Indication visual indicator, 0° to 95° (0° is full spring 0.19" [5]
return position) 0.39" [10] 10.20" [259]
2.64" 5.85" [148.5]
[67]
Manual Override No 0.35" [9] 0.26" [6.5]
Running Time (Motor) <15 seconds at rated voltage and torque 32°F to

1.93"
ø1.62"

[49]
3.86" [98]
3.15" [80]
[ø41.2]
122°F [0°C to 50°C]

[73.5]
2.89"
Date created, 12/14/2015 - Subject to change. © Belimo Aircontrols (USA), Inc.

Running Time (Fail-Safe) <15 seconds *with K4 US clamp

Humidity 5 to 95% RH non-condensing


1.97" -S models only
Ambient Temperature Range 32°F to 122°F [0°C to 50°C] [50]
7.54" [191.6]
Storage Temperature Range -40°F to 176°F [-40°C to 80°C]
Housing NEMA type 1 / IP40
Safety Notes
Housing Material zinc coated steel * Neither UL nor Belimo require local over-current protection. The FSNF
Gears steel, permanently lubricated actuators draw higher peak current when driving against any type of stop. If
Agency Listings† cULus listed to UL873 and CAN/CSA C22.2 used, this requires the value of a local fuse or breaker to be increased to avoid
No.24, UL 2043 Listed for air plenum nuisance opening or tripping. A 2.5 amp slow blow should be used for 24VAC.
installation per NEC 300.22 and IMC Section A 0.5 amp slow blow should be used for 120 VAC. A 0.25 amp slow blow
602 should be used for 230V and a 0.3 amp slow blow for 208 VAC. Transformers:
NYC Department of Buildings MEA 197-07-M. Note that while a 24V 100VA transformer would handle 2 actuators, a 4 A
California State Fire Marshal Listing 3210- breaker or plug fuse is insufficient. A 5 amp slow blow would be required.
1593:101.
Noise Level (Motor) 45 db(A) motor, 62 db(A) spring, inaudible Belimo Fire & Smoke actuators have passed the AMCA 520 and UL 555S Long
holding  Term Holding test. No special cycling is required during prolonged periods
Servicing maintenance free when actuator is driven open and held there. Periodic testing of dampers and
Quality Standard ISO 9001 actuators per local codes and NFPA 80 and NFPA 105 are required.
Weight 6.5 lbs. (3.0 kg.)
The actuator contains no components which the user can replace or repair.
Auxiliary Switch 2 x SPDT, 7A resistive, 2.5A inductive at 120V A 1/2” threaded connector is standard. FSNFxx-FC models have a 3/8” Flex
or 250V, double insulated, one switch at 10°, Connector. Other than the connector, these actuators are identical to the
one at 85° conduit connector version.
† UL File XAPX.E108966

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


FSNF24-S US
On/Off, Spring Return, 350°F [177°C] for half hour, 24VAC only, 15 Seconds Cycle Time

Accessories
AF-P Anti-rotation bracket AF/NF.
IND-AF2 Classic AF/NF position indicator. Com (White) 1 Common
K4-1 US Classic AF/NF jackshaft clamp (up to 1.05”).
KH-AF Classic AF/NF crankarm for Shafts to 3/4”. Hot (Black) 2 Hot
KH-AF-1 US Classic AF/NF crankarm for Jackshaft to 1.05”.
SH8 Push rod for KG6 & KG8 ball joints (36” L, 5/16” diameter).
ZDB-AF2 US Angle of rotation limiter for Classic AF/NF. 1
ZG-100 Univ. right angle bracket (17” H x 11-1/8” W x 6” base).
ZG-101 Univ. right angle bracket (13” H x 11” W x 7-7/16” base).
ZG-AF US Classic AF/NF crankarm adaptor kit. 45
ZG-AF108 Classic AF/NF crankarm adaptor kit with ZG-108.
ZG-DC1 Damper clip for damper blade, 3.5” width. 24 VAC/DC
ZG-DC2 Damper clip for damper blade, 6” width.
ZS-100 Weather shield - galvaneal (13” L x 8” W x 6” D). Detector or relay F&S Damper
ZS-150 Weather shield - PC w/ foam seal (16” L x 8-3/8” W x 4” D).
ZS-260 Explosion proof housing. 165°F
N, L2,
ZS-300 NEMA 4X, 304 stainless steel enclosure. HOT 2 1 or COM
BAE165 US 165° F electric thermal sensor, SPST, normally closed.
S2A-F US Auxiliary switch, 2x SPDT, 3A (0.5A inductive) @250 VAC max.
Manual Actuator
Typical Specification reset
All smoke and combination fire and smoke dampers shall be provided To alarm
with Belimo FSTF, FSLF, FSNF, or FSAF actuators. All substitutions must be system
approved before submission of bid. Damper and actuator shall have UL 555S
Listing for 250°F (350°F). Actuator shall have been tested to UL 2043 per Typical containment damper control wiring
requirements of IMC 602.2 and NEC 300.22 (c). Where position indication is
required -S models with auxiliary switches or damper blade switches will be
provided per code requirements.

Wiring Diagrams
INSTALLATION NOTES

Date created, 12/14/2015 - Subject to change. © Belimo Aircontrols (USA), Inc.


Provide overload protection and disconnect as required.
Actuators may be powered in parallel. Power consumption must be Parallel Actuator Wiring
45
observed.

72 S4 makes to S6 when actuator is powered open.

73 Auxiliary switches are for end position indication or interlock control. S1


Double insulated.
74
NC
75 Ground present on some models. S2
Meets cULus requirements without the need of an electrical ground
connection. S3 10°
NO 73
S4
NC
S5
85° 74
S6
NO 72
Auxiliary Switch

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN


Technical data sheet BF24-S-ME

Spring-return actuator for fire and


smoke dampers 90° in ventilation and
air-conditioning systems.
• Torque 15 Nm
• Nominal voltage AC/DC 24 V
• Control: Open-close
• Damper rotation: 12 mm form-fit
• Integrated auxiliary switch
• Designed to meet UL555S

Technical Data
Electrical data Nominal voltage AC 24 V, 50/60 Hz / DC 24 V
Nominal voltage range AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V
Power consumption Motoring 8 W @ nominal torque
Holding 2W
For wire sizing 11 VA / lmax. 8.3 A @ 5 ms
Auxiliary switch 2 x SPDT
Contact rating (contacts gold plate on silver) 1 mA ... 6 A (3 A), DC 5 V ... AC 250 V
Switching points 5° / 80°
Connecting Motor Cable 1 m, 2 x 0.75 mm2 (halogen-free)
Auxiliary switch Cable 1 m, 6 x 0.75 mm2 (halogen-free)
Functional data Torque Motor Min. 15 Nm
Auxiliary switch Min. 15 Nm
Direction of rotation Selected by mounting L/R
Angle of rotation Max. 95° (incl. 5° spring pretensioning)
Running time Motor <75 s
Auxiliary switch <20 s (tamb = 20°C)
Sound power level Motor Max. 45 dB (A)
Auxiliary switch ~62 dB (A)
Damper rotation Form-fit 12 mm (10 with adapter supplied)
Position indication Mechanical with pointer
Service life Min. 60’000 safe positions
..
Safety Protection class III Safety extra-low voltage / UL Class 2 Supply ..
..
..
Degree of protection IP54 in all mounting positions ..
..

NEMA2, UL Enclosure Type 2 ..


..
..
EMC CE according to 2004/108/EC ..
..
..
Low-voltage directive CE according to 2006/95/EC ..
..
..
Certification cULus according to UL873 and CAN/CSA C22.2 No. 24 ..
..
Designed to meet UL555S ..
..
..
Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14 ..

Mode of operation Type 1.AA.B


Rated impulse voltage 0.8 kV
Control pollution degree 3
Ambient temperature –30 ... +50°C
Non-operating temperature –40 ... +80°C
Ambient humidity range 95% r.H., non-condensating
Maintenance Maintenance-free
Dimensions / Weight Dimensions See «Dimensions» on page 2
Weight Approx. 2.8 kg

Safety notes
• The actuator is not allowed to be used outside the specified field of application, especially in
! aircraft or in any other airborne means of transport.
• The actuator is adapted and mounted to the fire and smoke damper by the damper manufac-
turer. For this reason, the actuator is only supplied direct to safety damper manufacturers.
The manufacturer then bears full responsibility for the proper functioning of the damper.

www.belimo.com T3-BF24-S-ME • en • v1.1 • 06.2008 • Subject to changes 1/2


Spring-return actuator 90° , AC/DC 24 V, 15 Nm,
BF24-S-ME integrated auxiliary switch, designed to meet UL555S

Safety notes (Continue)


• The device may only be opened at the manufacturer’s site. It does not contain any parts that
can be replaced or repaired by the user.
• The device contains electronic and electrical components and may not be disposed of with
the household waste. Observe local regulations and valid laws.

Product features
Mode of operation The actuator moves the damper to its normal working position while tensioning the return spring
at the same time. If the power supply is interrupted, the energy stored in the spring moves the
damper back to its safe position.

Signalling Two microswitches with fixed settings are installed in the actuator for indicating the damper end
positions. The position of the damper blade can be read off on a mechanical position indicator.

Manual operation Without power supply, the damper can be operated manually and fixed in any required position.
Release of the locking mechanism can be achieved manually or automatically by applying the
supply voltage.

Accessories
Description Type
Electrical accessories Auxiliary switch, 1 x SPDT 6 A (2.5 A), AC 250 V SN1
Auxiliary switch, 2 x SPDT 6 A (2.5 A), AC 250 V SN2
Mechanical accessories Adapter with clamp for rotary axes up to 20 mm for BF.. and BLF.. ZK-BF
Adapter with DM18 rotary axis, L = 33 mm, for BF.. and BLF.. ZA18-BF
Adapter 12/8 mm for BF.. and BLF.. ZA8-BF
Adapter 12/11 mm for BF.. and BLF.. ZA11-BF
Bracket for SN1 and SN2 auxiliary switches for BF.. ZSN-BF

Electrical installation
Wiring diagram
T ~
– +
Note
• Supply via safety isolation transformer !
• Parallel connection of several actuators possible.
Power consumption must be observed!

1 2 S1 S2 S3 S4 S5 S6

<5° <80°

Dimensions [mm]
Dimensional diagrams
17

ø 5.2
58.6
17
1

6.5
5.1

40
.2

80
98
12

40

27.2 40
175.6

10 188 50
248

2/2 T3-BF24-S-ME • en • v1.1 • 06.2008 • Subject to changes www.belimo.com


HONEY WELL 230 V
3.4 N.M (230V) 9 N.M (230V)

MS4104, MS4109, MS4604, MS4609, MS8104,


MS8109 Fast-Acting, Two-Position Actuators
FOR FIRE/SMOKE CONTROL APPLICATIONS
PRODUCT DATA

FEATURES
• 30 lb-in. (3.4 N•m) or 80 lb-in. (9 N•m) minimum driving
torque at 350°F (176°C).
• Reversible mounting facilitates use in either clockwise
(cw) or counterclockwise (ccw) spring rotation.
• Integral spring return ensures level of return torque.
• Fifteen-second spring return timing.
• No special cycling required during long-term holding.
(See Operation section.)
• No audible noise during holding.
• Patent pending design eliminates need for limit
switches to reduce power consumption.
• Models available for 24, 120, and 230 Vac.
• Ninety-five degree angle of rotation.
• Actuator holds rated torque at reduced power level.
• Die-cast aluminum housing.
• Housing design allows flush mounting to damper.

APPLICATION • Designed to operate reliably in smoke control systems


requiring Underwriter’s Laboratories Inc. UL555S
ratings up to 350°F.
The MS4104, MS4109, MS4604, MS4609, MS8104 and
MS8109 Fast-Acting, Two-Position Actuators are spring return • Models available with SPST position-indicating
direct coupled actuators (DCA) for Fire and Smoke dampers switches (7°, 85° stroke).
(on/off control). The actuator accepts an on/off signal from a
single-pole, single-throw (SPST) controller. Reversible
mounting allows actuator to be used for either clockwise (cw)
or counterclockwise (ccw) spring rotation.

Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Operation .......................................................................... 6
Checkout .......................................................................... 6

N314 63-2740-05
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS

SPECIFICATIONS Mounting: Round 1/2 inch shaft adapter with 1/4 inch set
screws.
Threads: ¼-20 UNC-2A
Models: See Table 1. Material: Alloy Steel hardened to HRC 45-53
Table 1. Models. Thread Lock: Nylon Patch

Voltage Internal Auxiliary IMPORTANT


Model (Vac) Switches Honeywell does not recommend using linkages with
these actuators because side-loading of the output
MS4104F1010 120 None hub reduces actuator life.
MS4104F1210 120 2 SPSTa
Temperature Ratings:
MS4109F1010 120 None Ambient: 0°F to 130°F (-18°C to 55°C).
MS4109F1210 120 Shipping and Storage: -40°F to 140°F (-40°C to 60°C).
2 SPSTa
MS4604F1010 230 None IMPORTANT
The actuator is designed to meet UL555S standards
MS4604F1210 230 2 SPST a
3.4N.M at 350°F (176°C). The actuator must be tested with
MS4609F1010 230 None the damper to achieve this rating.
MS4609F1210 230 2 SPSTa 9 N.M Humidity Ratings: 5% to 95% RH noncondensing.
MS8104F1010 24 None Noise Rating (Maximum):
MS8104F1210 24 2 SPSTa Driving Open: 75 dBA at 1m.
Holding: 20 dBA at 1m (no audible noise).
MS8109F1010 24 None
MS8109F1210 24 2 SPSTa Controller Type:
MS4104, MS4109: Line voltage (120 Vac),
a two-position, SPST (Series 40).
Internal switches are designed to pass UL555S
requirements (at 350°F for 30 minutes) and are intended for MS4604, MS4609: Line voltage (230 Vac),
use as position indication. two-position, SPST (Series 40).
MS8104, MS8109: Low voltage (24 Vac),
Dimensions: See Fig. 1. two-position, SPST (Series 80).
Minimum Damper Shaft Length: 2 in. (51 mm). Table 2. MS4104, MS4109, MS4604, MS4609, MS8104 and
MS8109 DCA Models.
Device Weight: 5 lb (2.3 kg).
Power Consumption Torque Voltage
Stroke: 95° ± 3°, mechanically limited. in lb-in. Input
Model Running Holding (N•m) in Vac
Electrical Ratings: See Table 2.
MS4104F 0.18A, 18W 0.11A, 9W 30 (3.4) 120 ±10%,
Electrical Connections: MS4109F 0.25A, 23W 0.13A, 7W 80 (9) 50/60 Hz
Power Lead Wires:
MS410xF and MS460xF: 32 inches (0.8m), 18 AWG MS4604F 0.13A, 18W 0.10A, 11W 30 (3.4) 230 ±10%,
MS4609F 0.13A, 23W 0.09A, 7W 80 (9) 50/60 Hz
MS810xF: 39 inches (1m), 18 AWG MS8104F 16 VA 8 VA 30 (3.4) 24Vac/dc +20%,
Switch Lead Wires: 18 inches, 18 AWG, 2 color coded leads MS8109F 23 VA 7 VA 80 (9) -10%, 50/60 Hz

ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:

1.Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2.Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.

63-2740—05 2
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS

Torque Rating (at rated voltage):


Spring Return: 2 (51)
MS4104F, MS4604F, MS8104F: 30 lb-in. (3.4 N•m). 1 (25)

MS4109F, MS4609F, MS8109: 80 lb-in. (9 N•m). 11/16


Stall Maximum: 90° 0°
(17)
MS4104F, MS4604F, MS8104F: 150 lb-in. (17 N•m).
MS4109F, MS4609F, MS8109: 240 lb-in. (27 N•m). 6-3/8
(161)
350°F Driving:
MS4104F, MS4604F, MS8104F: 30 lb-in. (3.4 N•m).
MS4109F, MS4609F, MS8109: 80 lb-in. (9 N•m).

Timing (At Rated Torque and Voltage):


Drive Open: 15 seconds typical.
Spring Close: 15 seconds typical.

Cycling Requirements:
The actuator and the internal spring are designed to require no
special cycling during long-term holding.
Honeywell recommends following all local, state and national 8-15/16
codes for periodic testing of the entire smoke control sys- (227)

tem. Refer to National Fire Protection Association (NFPA)


National Fire Codes®: NFPA90A, NFPA92A and NFPA92B 2 (51) 3-1/4 (83) 1/16
for your application. 4 (102) (2)
NFPA recommends periodic examination of each fire/smoke
damper (semi-annually or annually) to ensure proper perfor-
mance.
9/16 (14)

Design Life (at Rated Voltage): 30,000 full stroke cycles.

Approvals: See Table 3.

Environmental Protection Ratings: See Table 4. 5-1/8 (130) M34622

Accessories: Fig. 1. MS4104, MS4109, MS4604, MS4609, MS8104 and


205649 Mounting Bracket (not supplied with actuator). MS8109 dimensional drawing in in. (mm).
Table 3. Approvals.
MS4104F, MS4604F, MS8104F,
MS4109F MS4609F MS8109F
UL/cUL X X X
UL60730 X X X
CE X X X
C-Tick X X X

Table 4. Environmental Ratings.


MS4104, MS4109, MS4604,
MS4609, MS8104 and
All Devices MS8109
NEMA1 IP40

3 63-2740—05
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS

INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous 90 °
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician. 1

4. After installation is complete, check out product


operation as provided in these instructions.

IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.

WARNING
Electrical Power Hazard.
Line voltage can cause death or serious injury 2
and short equipment circuitry.
Disconnect power supply before installation.

CAUTION
Electrical Shock or Equipment Damage Hazard.
1 ENSURE THAT MOUNTING ASSEMBLY PREVENTS ACTUATOR
ROTATION AND ALLOWS ACTUATOR TO FLOAT ALONG
INDICATED AXIS. WHEN TOO TIGHT, THE RESULTING BINDING
CAN DAMAGE THE ACTUATOR OR REDUCE TORQUE OUTPUT.
Low voltage can shock individuals or short
equipment circuitry. 2 ACCESSORY MOUNTING BRACKET IS NOT SUPPLIED WITH
THE ACTUATOR.
Disconnect power supply before installation. M34623

Location and Mounting Fig. 2. Mounting actuator to damper housing.

The actuators are designed to open a damper by driving the


damper shaft in either clockwise or counterclockwise Preparation
direction. The actuator housing has two slots on the Before mounting the actuator onto the damper shaft,
bottom that, with a 205649 Mounting Bracket, secure it flush to determine the:
a damper box (see Fig. 2). When mounted correctly, these — Damper/valve opening direction for correct spring
slots allow the actuator to float without rotating relative to the return rotation. The actuator can be mounted to provide
damper shaft. clockwise or counterclockwise spring return.
— Damper shaft size (see Specifications section).

CAUTION
Equipment Damage Hazard.
Tightly securing actuator to damper housing can
damage actuator.
Mount actuator to allow it to float along its vertical axis.

63-2740—05 4
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS

Installation IMPORTANT
1. All wiring must comply with local electrical codes,
ordinances and regulations.
2. Voltage and frequency of transformer must corre-
CAUTION spond with the characteristics of power supply and
Device Malfunction Hazard. actuator.
Improper set screw tightening causes device 3. Use wires rated for at least 75°C (167°F).
malfunction. 4. The conduit fittings are designed for use with 3/8 in.
Ensure damper blade is in the correct position and reduced-wall steel or aluminum flexible conduit.
tighten set screws with proper torque to prevent
damper shaft slippage.
L2 ( )
BLACK

CAUTION
24 VAC RED

L1 ( )
Actuator Damage Hazard.
Using actuator as shaft bearing causes device
damage.
Use actuator only to supply rotational torque. Avoid any BLUE
side loads to actuator output coupling bearings. 7° AUXILIARY
BLUE
SWITCH
YELLOW
To install actuator, proceed as follows: 85° AUXILIARY YELLOW
1. Place actuator over damper shaft; and hold mounting SWITCH
bracket in place. See Fig. 2.
2. Mark screw holes on damper housing. M34624
3. Remove actuator and mounting bracket. Fig. 3. Typical 24 Vac wiring.
4. Drill or center-punch holes for mounting screws (or use
no.10 self-tapping sheet metal screws).
5. Turn damper blades to desired normal (closed) position.
6. Place actuator and mounting bracket back into position L2 ( ) WHITE
and secure bracket to damper box with sheet metal 120 VAC BLACK
screws. L1 ( )
GREEN
7. Tighten set screws securely into damper shaft using min-
imum 100 lb-in., maximum 130 lb-in. torque. Use
1/4 in. wrench (see Specifications for details) to tighten
set screws. BLUE
7° AUXILIARY
SWITCH BLUE

Wiring 85° AUXILIARY


YELLOW
YELLOW
SWITCH
See Fig. 3 through 5 for typical wiring diagrams.
M34625

WARNING Fig. 4. Typical 120 Vac wiring.


Electrical Power Hazard.
Line voltage can cause death or serious injury and
short equipment circuitry.
Disconnect power supply before installation. L2 ( ) BLUE
230 VAC
BROWN
L1 ( )

CAUTION
Electrical Shock or Equipment Damage Hazard.
GREEN

Low voltage can shock individuals or short


BLUE
equipment circuitry. 7° AUXILIARY
BLUE
Disconnect power supply before installation. SWITCH
YELLOW
85° AUXILIARY
YELLOW
SWITCH

M34626

Fig. 5. Typical 230 Vac wiring.

5 63-2740—05
OPERATION CHECKOUT
The MS4104, MS4109, MS4604, MS4609, MS8104 and
MS8109 DCA are designed for use in Smoke Control Systems. MS4104F, MS4109F (120 Vac model)
If power fails, the actuator spring returns to the 0° position. The 1. Check damper position.
actuator mounts flush with the damper box. The actuator drives 2. Connect 120 Vac to the black and white leadwires to
from 0° to 95° and spring returns back to 0°. drive the damper to the open position. The actuator
should drive the damper.
The actuators are operated by an spst two-position controller.
3. If the actuator does not spring return, verify that the actu-
When using an spst two-position controller, the actuator drives
ator is properly installed. See Installation section.
to the damper fully open position when controller contact
4. If the actuator is correctly installed but neither runs nor
makes and spring returns to the damper fully closed position
spring returns, replace the actuator.
when controller contact breaks. The actuator drops to holding
power level on detection of stall, independent of hub position.
MS4604F, MS4609F (230 Vac model)
Cycling 1. Check damper position.
2. Connect 230 Vac to the blue and brown leadwires to
The actuator and the internal spring are designed so that no
drive the damper to the open position. The actuator
special cycling during long-term holding is required. Honeywell
should drive the damper.
recommends following all local, state, and national codes for
3. If the actuator does not spring return, verify that the actu-
periodic testing of the entire smoke control system. Refer to
ator is properly installed. See Installation section.
National Fire Protection Association (NFPA) National Fire
4. If the actuator is correctly installed but neither runs nor
Codes®: NFPA90A, NFPA92A, and NFPA92B for your
spring returns, replace the actuator.
application.

NOTE: The actuator is designed to operate for 30 min- MS8104F, MS8109F (24 Vac model)
utes during a one-time excursion to 350°F (176°C).
1. Check damper position.
2. Connect 24 Vac to the red and black leadwires to drive
the damper to the open position. The actuator should
drive the damper.
3. If the actuator does not spring return, verify that the actu-
ator is properly installed. See Installation section.
4. If the actuator is correctly installed but neither runs nor
spring returns, replace the actuator.

National Fire Codes® is a registered trademark of the National Fire Protection Association (NFPA).

63-2740—05 6
20NM (230V)
MS4120F, MS4620F,S;
MS8120F,S; S2024-F; S20230-F
Fast-Acting, Two-Position Actuators
FOR FIRE/SMOKE CONTROL APPLICATIONS N314

The MS4120F; MS4620F,S; MS8120F,S; S2024-F, and SPECIFICATION DATA


S20230-F Fast-Acting, Two-Position Actuators are spring
return direct coupled actuators (DCA) for on/off damper
control. The actuator accepts an on/off signal from a single- FEATURES
pole, single-throw (spst) controller. Reversible mounting
allows actuator to be used for either clockwise (cw) or • Reversible mounting facilitates use in either clockwise
counterclockwise (ccw) spring rotation. (cw) or counterclockwise (ccw) spring rotation.
• No special cycling required during long-term holding.
Designed to operate reliably in smoke control systems • Integral spring return ensures level of return torque.
requiring Underwriter’s Laboratories Inc. UL555S ratings • Stainless steel internal spring.
up to 350°F. • Fifteen-second spring return timing.
• No audible noise during holding.
SPECIFICATIONS • Patent pending design eliminates need for limit
switches to reduce power consumption.
• Models available for 24, 120, and 230 Vac.
Models:
• Ninety-five degree angle of rotation.
Internal • Actuator holds rated torque at reduced power level.
Voltage Auxiliary • Die-cast aluminum housing.
Model in Vac Switches • Housing design allows flush mounting to damper.
• Self-centering shaft adapter (SCSA), patent pending.
MS4120F1006 120 None
• Designed to operate reliably in smoke control systems
MS4120F1204 120 2 SPSTa requiring Underwriter’s Laboratories Inc. UL555S
ratings up to 350°F.
MS4620F1005 230 None
MS4620F1203 230 2 SPSTa
MS4120F, MS4620F, MS8120F
MS8120F1002 24 None • High temperature Teflon® lead wires.
MS8120F1200 24 2 SPST a • Models available with integral high temperature
(350°F) SPST position-indicating switches (7°, 85°).
S2024-F (MS8120S1006) 24 None
S20230-F (MS4620S1009) 230
S2024-F, S20230-F, MS4620S, MS8120S
S2024-F-SW2 (MS8120S1204) 24 2 SPDTa • Double-insulation rating.
S20230-F-SW2 (MS4620S1207) 230 • High-temperature, halogen-free, silicone-free leadwires.
a • Models available with integral SPDT position-
Internal switches are designed to pass UL555S indicating switches (7°, 85°).
requirements (at 350°F).
Dimensions:
! See Fig. 1.
Device Weight: Electrical Connections:
! 7 lb (3.2 kg). ! Lead Wires:
Stroke: ! MS4120F, MS4620F, MS8120F: 1m Teflon wire.
! 95° ± 3°, mechanically limited. ! MS4620S, MS8120S, S2024-F, S20230-F: 1m halogen-
free wire.
Electrical Ratings: ! Two integral 3/8 in. flexible conduit connections.
! Power Input:
! MS4120F: 120 Vac ±10%, 60 Hz. Timing (At Rated Torque and Voltage):
! MS4620F,S, S20230-F: 230 Vac ±10%, 50/60 Hz. ! Drive Open: 15 seconds typical.
! MS8120F,S; S2024-F: 24 Vac +20%, -10%, 50/60 Hz ! Spring Close: 15 seconds typical.
(Class 2). Auxiliary Switches:
! Power Consumption: ! Ratings (maximum load): 250 Vac, 5A resistive,
! MS4120F: Driving: 0.35A, 35W. Holding: 0.15A, 10W. 3A inductive.
! MS4620F,S; S20230-F: ! Settings (fixed): 7° nominal stroke, 85° nominal stroke.
Driving: 0.20A, 35W. Holding: 0.14A, 10W.
! MS8120F,S; S2024-F: Driving: 45 VA. Holding: 10 VA.

63-2592—5
MS4120F, MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

Torque Rating (at rated voltage): Approvals:


! Typical Holding (minimum at 350°F): 175 lb-in. (20 N•m).
! Spring Return (minimum at 350°F): 175 lb-in. (20 N•m). S20230-F,
! Stall Maximum (fully open at 75°F): 425 lb-in. (48.0 N•m). S2024-F,
! 350°F Minimum Driving: 175 lb-in. (20 N•m). MS4620F, MS4620S,
MS4120F MS8120F MS8120S
Design Life (at Rated Voltage): UL/cUL X X
! 30,000 full stroke cycles.
UL873 Plenum Rating, X X
Minimum Damper Shaft Length: File No. E4436;
! 1 in. (25 mm); 3-1/4 (83 mm) recommended. Guide No. XAPX.a
CE X X
Cycling Requirements:
! Prolonged holding-period (1 year) testing of these C-TICK X X
actuators has been performed with no spring return a Plenum
failures. The actuator and the internal spring are designed applications require that conductors be enclosed in
to require no special cycling during long-term holding. conduit (see Wiring section for conduit details).
! Honeywell recommends following all local, state and
national codes for periodic testing of the entire smoke Controller Type:
control system. Refer to National Fire Protection MS4120F: Line voltage (120 Vac), 2-position, spst (Series 40).
Association (NFPA) National Fire Codes®: NFPA90A, MS4620F,S; S20230-F: Line voltage (230 Vac), 2-position,
NFPA92A and NFPA92B for your application. spst (Series 40).
! NFPA recommends periodic examination of each fire/ MS8120F,S; S2024-F: Low voltage (24 Vac), 2-position, spst
smoke damper (semi-annually or annually) to ensure (Series 80).
proper performance.
3-15/16 (100)
Mounting: 2 (50)
! Self-centering shaft adapter.
! Round Damper Shafts: 0.5 to 1.06 in.
1-9/16
! Square Damper Shafts: 1/2 to 3/4 in. (40)
! Actuator can be mounted with shaft in any position.

IMPORTANT
Honeywell does not recommend using linkages with
these actuators because side-loading of the output
hub reduces actuator life.

Noise Rating (Maximum):


! Driving or Spring Return: 70 dBA. 10-11/16
(271)
! Holding: 20 dBA (no audible noise).

Temperature Ratings: 8-5/8


(220)
IMPORTANT
The actuators are designed to meet UL555S
standards at 350°F (176°C). These actuators must
be tested with the damper to achieve this rating.

! Ambient: -40°F to 130°F (-40°C to 55°C).


! Shipping and Storage: -40°F to 140°F (-40°C to 60°C).

Humidity Ratings:
! 5% to 95% RH noncondensing.

Environmental Protection Ratings:


1/4 (6) 2-15/16 (75)
! NEMA2 and IP54 when mounted on a horizontal shaft. M20051

Accessories: Fig. 1. Dimensions in in. (mm).


! 205649 Mounting Bracket (not supplied with actuator).

63-2592—5 2
MS4120F, MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

MS8120F S2024-F-SW2, MS8120S

L2 ( )
BLACK
L2 ( ) BLUE
24 VAC RED
230 VAC BROWN
L1 ( ) L1 ( )

GREEN GRAY/BLUE
BLUE 85° AUXILIARY GRAY/RED
7° AUXILIARY SWITCH
SWITCH BLUE GRAY/YELLOW
YELLOW BLACK/BLUE
85° AUXILIARY YELLOW BLACK/RED
7° AUXILIARY
SWITCH
SWITCH BLACK/YELLOW
M20053A
M20678A

Fig. 2. Typical 24 Vac wiring (MS Series).


Fig. 5. Typical 24 Vac wiring (S20 Series).
MS4120F
7° SWITCH 85° SWITCH
LESS 7° MORE 7° LESS 85° MORE 85°
L2 ( ) WHITE BLACK/BLUE BLACK/BLUE GRAY/BLUE GRAY/BLUE
120 VAC
BLACK BLACK/RED BLACK/RED GRAY/RED GRAY/RED
L1 ( )
GREEN BLACK/YELLOW BLACK/YELLOW GRAY/YELLOW GRAY/YELLOW
M20679B

BLUE Fig. 6. Auxiliary switch wiring (S20 Series).


7° AUXILIARY
SWITCH BLUE
YELLOW S20230-F-SW2, MS4620S
85° AUXILIARY YELLOW
SWITCH
L2 ( ) BLUE
M20056A
230 VAC
BROWN
L1 ( )
Fig. 3. Typical 120 Vac wiring.

MS4620F
GRAY/BLUE
85° AUXILIARY GRAY/RED
SWITCH GRAY/YELLOW
L2 ( ) BLUE
230 VAC BLACK/BLUE
BROWN
L1 ( ) 7° AUXILIARY BLACK/RED
GREEN SWITCH BLACK/YELLOW

M20680A

BLUE
7° AUXILIARY Fig. 7. Typical 230 Vac wiring (S20 Series).
SWITCH BLUE
YELLOW
85° AUXILIARY
SWITCH YELLOW

M20057A

Fig. 4. Typical 230 Vac wiring (MS Series).

3 63-2592—5
HONEY WELL 24 V
24V,3.4NM

MS4104, MS4109, MS4604, MS4609, MS8104,


24V,9NM
MS8109 Fast-Acting, Two-Position Actuators
FOR FIRE/SMOKE CONTROL APPLICATIONS
PRODUCT DATA

FEATURES
• 30 lb-in. (3.4 N•m) or 80 lb-in. (9 N•m) minimum driving
torque at 350°F (176°C).
• Reversible mounting facilitates use in either clockwise
(cw) or counterclockwise (ccw) spring rotation.
• Integral spring return ensures level of return torque.
• Fifteen-second spring return timing.
• No special cycling required during long-term holding.
(See Operation section.)
• No audible noise during holding.
• Patent pending design eliminates need for limit
switches to reduce power consumption.
• Models available for 24, 120, and 230 Vac.
• Ninety-five degree angle of rotation.
• Actuator holds rated torque at reduced power level.
• Die-cast aluminum housing.
• Housing design allows flush mounting to damper.

APPLICATION • Designed to operate reliably in smoke control systems


requiring Underwriter’s Laboratories Inc. UL555S
ratings up to 350°F.
The MS4104, MS4109, MS4604, MS4609, MS8104 and
MS8109 Fast-Acting, Two-Position Actuators are spring return • Models available with SPST position-indicating
direct coupled actuators (DCA) for Fire and Smoke dampers switches (7°, 85° stroke).
(on/off control). The actuator accepts an on/off signal from a
single-pole, single-throw (SPST) controller. Reversible
mounting allows actuator to be used for either clockwise (cw)
or counterclockwise (ccw) spring rotation.

Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Operation .......................................................................... 6
Checkout .......................................................................... 6

N314 63-2740-05
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS

SPECIFICATIONS Mounting: Round 1/2 inch shaft adapter with 1/4 inch set
screws.
Threads: ¼-20 UNC-2A
Models: See Table 1. Material: Alloy Steel hardened to HRC 45-53
Table 1. Models. Thread Lock: Nylon Patch

Voltage Internal Auxiliary IMPORTANT


Model (Vac) Switches Honeywell does not recommend using linkages with
these actuators because side-loading of the output
MS4104F1010 120 None hub reduces actuator life.
MS4104F1210 120 2 SPSTa
Temperature Ratings:
MS4109F1010 120 None Ambient: 0°F to 130°F (-18°C to 55°C).
MS4109F1210 120 Shipping and Storage: -40°F to 140°F (-40°C to 60°C).
2 SPSTa
MS4604F1010 230 None IMPORTANT
The actuator is designed to meet UL555S standards
MS4604F1210 230 2 SPST a
at 350°F (176°C). The actuator must be tested with
MS4609F1010 230 None the damper to achieve this rating.
MS4609F1210 230 2 SPSTa Humidity Ratings: 5% to 95% RH noncondensing.
MS8104F1010 24 None Noise Rating (Maximum):
MS8104F1210 24 2 SPSTa 24V,3.4NM Driving Open: 75 dBA at 1m.
Holding: 20 dBA at 1m (no audible noise).
MS8109F1010 24 None
MS8109F1210 24 2 SPSTa Controller Type:
24V,9NM
MS4104, MS4109: Line voltage (120 Vac),
a two-position, SPST (Series 40).
Internal switches are designed to pass UL555S
requirements (at 350°F for 30 minutes) and are intended for MS4604, MS4609: Line voltage (230 Vac),
use as position indication. two-position, SPST (Series 40).
MS8104, MS8109: Low voltage (24 Vac),
Dimensions: See Fig. 1. two-position, SPST (Series 80).
Minimum Damper Shaft Length: 2 in. (51 mm). Table 2. MS4104, MS4109, MS4604, MS4609, MS8104 and
MS8109 DCA Models.
Device Weight: 5 lb (2.3 kg).
Power Consumption Torque Voltage
Stroke: 95° ± 3°, mechanically limited. in lb-in. Input
Model Running Holding (N•m) in Vac
Electrical Ratings: See Table 2.
MS4104F 0.18A, 18W 0.11A, 9W 30 (3.4) 120 ±10%,
Electrical Connections: MS4109F 0.25A, 23W 0.13A, 7W 80 (9) 50/60 Hz
Power Lead Wires:
MS410xF and MS460xF: 32 inches (0.8m), 18 AWG MS4604F 0.13A, 18W 0.10A, 11W 30 (3.4) 230 ±10%,
MS4609F 0.13A, 23W 0.09A, 7W 80 (9) 50/60 Hz
MS810xF: 39 inches (1m), 18 AWG MS8104F 16 VA 8 VA 30 (3.4) 24Vac/dc +20%,
Switch Lead Wires: 18 inches, 18 AWG, 2 color coded leads MS8109F 23 VA 7 VA 80 (9) -10%, 50/60 Hz

ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:

1.Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2.Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.

63-2740—05 2
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS

Torque Rating (at rated voltage):


Spring Return: 2 (51)
MS4104F, MS4604F, MS8104F: 30 lb-in. (3.4 N•m). 24V,3.4NM 1 (25)

MS4109F, MS4609F, MS8109: 80 lb-in. (9 N•m). 11/16


Stall Maximum: 90° 0°
(17)
MS4104F, MS4604F, MS8104F: 150 lb-in. (17 N•m).
MS4109F, MS4609F, MS8109: 240 lb-in. (27 N•m). 6-3/8
(161)
350°F Driving:
MS4104F, MS4604F, MS8104F: 30 lb-in. (3.4 N•m).
MS4109F, MS4609F, MS8109: 80 lb-in. (9 N•m).

Timing (At Rated Torque and Voltage):


Drive Open: 15 seconds typical.
Spring Close: 15 seconds typical.

Cycling Requirements:
The actuator and the internal spring are designed to require no
special cycling during long-term holding.
Honeywell recommends following all local, state and national 8-15/16
codes for periodic testing of the entire smoke control sys- (227)

tem. Refer to National Fire Protection Association (NFPA)


National Fire Codes®: NFPA90A, NFPA92A and NFPA92B 2 (51) 3-1/4 (83) 1/16
for your application. 4 (102) (2)
NFPA recommends periodic examination of each fire/smoke
damper (semi-annually or annually) to ensure proper perfor-
mance.
9/16 (14)

Design Life (at Rated Voltage): 30,000 full stroke cycles.

Approvals: See Table 3.

Environmental Protection Ratings: See Table 4. 5-1/8 (130) M34622

Accessories: Fig. 1. MS4104, MS4109, MS4604, MS4609, MS8104 and


205649 Mounting Bracket (not supplied with actuator). MS8109 dimensional drawing in in. (mm).
Table 3. Approvals.
MS4104F, MS4604F, MS8104F, 24V,3.4NM
MS4109F MS4609F MS8109F 24V,9NM
UL/cUL X X X
UL60730 X X X
CE X X X
C-Tick X X X

Table 4. Environmental Ratings.


MS4104, MS4109, MS4604,
MS4609, MS8104 and
All Devices MS8109
NEMA1 IP40

3 63-2740—05
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS

INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous 90 °
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician. 1

4. After installation is complete, check out product


operation as provided in these instructions.

IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.

WARNING
Electrical Power Hazard.
Line voltage can cause death or serious injury 2
and short equipment circuitry.
Disconnect power supply before installation.

CAUTION
Electrical Shock or Equipment Damage Hazard.
1 ENSURE THAT MOUNTING ASSEMBLY PREVENTS ACTUATOR
ROTATION AND ALLOWS ACTUATOR TO FLOAT ALONG
INDICATED AXIS. WHEN TOO TIGHT, THE RESULTING BINDING
CAN DAMAGE THE ACTUATOR OR REDUCE TORQUE OUTPUT.
Low voltage can shock individuals or short
equipment circuitry. 2 ACCESSORY MOUNTING BRACKET IS NOT SUPPLIED WITH
THE ACTUATOR.
Disconnect power supply before installation. M34623

Location and Mounting Fig. 2. Mounting actuator to damper housing.

The actuators are designed to open a damper by driving the


damper shaft in either clockwise or counterclockwise Preparation
direction. The actuator housing has two slots on the Before mounting the actuator onto the damper shaft,
bottom that, with a 205649 Mounting Bracket, secure it flush to determine the:
a damper box (see Fig. 2). When mounted correctly, these — Damper/valve opening direction for correct spring
slots allow the actuator to float without rotating relative to the return rotation. The actuator can be mounted to provide
damper shaft. clockwise or counterclockwise spring return.
— Damper shaft size (see Specifications section).

CAUTION
Equipment Damage Hazard.
Tightly securing actuator to damper housing can
damage actuator.
Mount actuator to allow it to float along its vertical axis.

63-2740—05 4
MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 FAST-ACTING, TWO-POSITION ACTUATORS

Installation IMPORTANT
1. All wiring must comply with local electrical codes,
ordinances and regulations.
2. Voltage and frequency of transformer must corre-
CAUTION spond with the characteristics of power supply and
Device Malfunction Hazard. actuator.
Improper set screw tightening causes device 3. Use wires rated for at least 75°C (167°F).
malfunction. 4. The conduit fittings are designed for use with 3/8 in.
Ensure damper blade is in the correct position and reduced-wall steel or aluminum flexible conduit.
tighten set screws with proper torque to prevent
damper shaft slippage.
L2 ( )
BLACK

CAUTION
24 VAC RED

L1 ( )
Actuator Damage Hazard.
Using actuator as shaft bearing causes device
damage.
Use actuator only to supply rotational torque. Avoid any BLUE
side loads to actuator output coupling bearings. 7° AUXILIARY
BLUE
SWITCH
YELLOW
To install actuator, proceed as follows: 85° AUXILIARY YELLOW
1. Place actuator over damper shaft; and hold mounting SWITCH
bracket in place. See Fig. 2.
2. Mark screw holes on damper housing. M34624
3. Remove actuator and mounting bracket. Fig. 3. Typical 24 Vac wiring.
4. Drill or center-punch holes for mounting screws (or use
no.10 self-tapping sheet metal screws).
5. Turn damper blades to desired normal (closed) position.
6. Place actuator and mounting bracket back into position L2 ( ) WHITE
and secure bracket to damper box with sheet metal 120 VAC BLACK
screws. L1 ( )
GREEN
7. Tighten set screws securely into damper shaft using min-
imum 100 lb-in., maximum 130 lb-in. torque. Use
1/4 in. wrench (see Specifications for details) to tighten
set screws. BLUE
7° AUXILIARY
SWITCH BLUE

Wiring 85° AUXILIARY


YELLOW
YELLOW
SWITCH
See Fig. 3 through 5 for typical wiring diagrams.
M34625

WARNING Fig. 4. Typical 120 Vac wiring.


Electrical Power Hazard.
Line voltage can cause death or serious injury and
short equipment circuitry.
Disconnect power supply before installation. L2 ( ) BLUE
230 VAC
BROWN
L1 ( )

CAUTION
Electrical Shock or Equipment Damage Hazard.
GREEN

Low voltage can shock individuals or short


BLUE
equipment circuitry. 7° AUXILIARY
BLUE
Disconnect power supply before installation. SWITCH
YELLOW
85° AUXILIARY
YELLOW
SWITCH

M34626

Fig. 5. Typical 230 Vac wiring.

5 63-2740—05
OPERATION CHECKOUT
The MS4104, MS4109, MS4604, MS4609, MS8104 and
MS8109 DCA are designed for use in Smoke Control Systems. MS4104F, MS4109F (120 Vac model)
If power fails, the actuator spring returns to the 0° position. The 1. Check damper position.
actuator mounts flush with the damper box. The actuator drives 2. Connect 120 Vac to the black and white leadwires to
from 0° to 95° and spring returns back to 0°. drive the damper to the open position. The actuator
should drive the damper.
The actuators are operated by an spst two-position controller.
3. If the actuator does not spring return, verify that the actu-
When using an spst two-position controller, the actuator drives
ator is properly installed. See Installation section.
to the damper fully open position when controller contact
4. If the actuator is correctly installed but neither runs nor
makes and spring returns to the damper fully closed position
spring returns, replace the actuator.
when controller contact breaks. The actuator drops to holding
power level on detection of stall, independent of hub position.
MS4604F, MS4609F (230 Vac model)
Cycling 1. Check damper position.
2. Connect 230 Vac to the blue and brown leadwires to
The actuator and the internal spring are designed so that no
drive the damper to the open position. The actuator
special cycling during long-term holding is required. Honeywell
should drive the damper.
recommends following all local, state, and national codes for
3. If the actuator does not spring return, verify that the actu-
periodic testing of the entire smoke control system. Refer to
ator is properly installed. See Installation section.
National Fire Protection Association (NFPA) National Fire
4. If the actuator is correctly installed but neither runs nor
Codes®: NFPA90A, NFPA92A, and NFPA92B for your
spring returns, replace the actuator.
application.
24V,3.4NM 24V,9NM
NOTE: The actuator is designed to operate for 30 min- MS8104F, MS8109F (24 Vac model)
utes during a one-time excursion to 350°F (176°C).
1. Check damper position.
2. Connect 24 Vac to the red and black leadwires to drive
the damper to the open position. The actuator should
drive the damper.
3. If the actuator does not spring return, verify that the actu-
ator is properly installed. See Installation section.
4. If the actuator is correctly installed but neither runs nor
spring returns, replace the actuator.

National Fire Codes® is a registered trademark of the National Fire Protection Association (NFPA).

63-2740—05 6
MS4120F, MS4620F,S;
24V,20N.M MS8120F,S; S2024-F; S20230-F
Fast-Acting, Two-Position Actuators
FOR FIRE/SMOKE CONTROL APPLICATIONS N314

The MS4120F; MS4620F,S; MS8120F,S; S2024-F, and SPECIFICATION DATA


S20230-F Fast-Acting, Two-Position Actuators are spring
return direct coupled actuators (DCA) for on/off damper
control. The actuator accepts an on/off signal from a single- FEATURES
pole, single-throw (spst) controller. Reversible mounting
allows actuator to be used for either clockwise (cw) or • Reversible mounting facilitates use in either clockwise
counterclockwise (ccw) spring rotation. (cw) or counterclockwise (ccw) spring rotation.
• No special cycling required during long-term holding.
Designed to operate reliably in smoke control systems • Integral spring return ensures level of return torque.
requiring Underwriter’s Laboratories Inc. UL555S ratings • Stainless steel internal spring.
up to 350°F. • Fifteen-second spring return timing.
• No audible noise during holding.
SPECIFICATIONS • Patent pending design eliminates need for limit
switches to reduce power consumption.
• Models available for 24, 120, and 230 Vac.
Models:
• Ninety-five degree angle of rotation.
Internal • Actuator holds rated torque at reduced power level.
Voltage Auxiliary • Die-cast aluminum housing.
Model in Vac Switches • Housing design allows flush mounting to damper.
• Self-centering shaft adapter (SCSA), patent pending.
MS4120F1006 120 None
• Designed to operate reliably in smoke control systems
MS4120F1204 120 2 SPSTa requiring Underwriter’s Laboratories Inc. UL555S
ratings up to 350°F.
MS4620F1005 230 None
MS4620F1203 230 2 SPSTa
MS4120F, MS4620F, MS8120F
MS8120F1002 24 None • High temperature Teflon® lead wires.
MS8120F1200 24 2 SPST a • Models available with integral high temperature
(350°F) SPST position-indicating switches (7°, 85°).
S2024-F (MS8120S1006) 24 None
S20230-F (MS4620S1009) 230
S2024-F, S20230-F, MS4620S, MS8120S
S2024-F-SW2 (MS8120S1204) 24 2 SPDTa • Double-insulation rating.
S20230-F-SW2 (MS4620S1207) 230 • High-temperature, halogen-free, silicone-free leadwires.
a • Models available with integral SPDT position-
Internal switches are designed to pass UL555S indicating switches (7°, 85°).
requirements (at 350°F).
Dimensions:
! See Fig. 1.
Device Weight: Electrical Connections:
! 7 lb (3.2 kg). ! Lead Wires:
Stroke: ! MS4120F, MS4620F, MS8120F: 1m Teflon wire.
! 95° ± 3°, mechanically limited. ! MS4620S, MS8120S, S2024-F, S20230-F: 1m halogen-
free wire.
Electrical Ratings: ! Two integral 3/8 in. flexible conduit connections.
! Power Input:
! MS4120F: 120 Vac ±10%, 60 Hz. Timing (At Rated Torque and Voltage):
! MS4620F,S, S20230-F: 230 Vac ±10%, 50/60 Hz. ! Drive Open: 15 seconds typical.
! MS8120F,S; S2024-F: 24 Vac +20%, -10%, 50/60 Hz ! Spring Close: 15 seconds typical.
(Class 2). Auxiliary Switches:
! Power Consumption: ! Ratings (maximum load): 250 Vac, 5A resistive,
! MS4120F: Driving: 0.35A, 35W. Holding: 0.15A, 10W. 3A inductive.
! MS4620F,S; S20230-F: ! Settings (fixed): 7° nominal stroke, 85° nominal stroke.
Driving: 0.20A, 35W. Holding: 0.14A, 10W.
! MS8120F,S; S2024-F: Driving: 45 VA. Holding: 10 VA.

63-2592—5
MS4120F, MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

Torque Rating (at rated voltage): Approvals:


! Typical Holding (minimum at 350°F): 175 lb-in. (20 N•m).
! Spring Return (minimum at 350°F): 175 lb-in. (20 N•m). S20230-F,
! Stall Maximum (fully open at 75°F): 425 lb-in. (48.0 N•m). S2024-F,
! 350°F Minimum Driving: 175 lb-in. (20 N•m). MS4620F, MS4620S,
MS4120F MS8120F MS8120S
Design Life (at Rated Voltage): UL/cUL X X
! 30,000 full stroke cycles.
UL873 Plenum Rating, X X
Minimum Damper Shaft Length: File No. E4436;
! 1 in. (25 mm); 3-1/4 (83 mm) recommended. Guide No. XAPX.a
CE X X
Cycling Requirements:
! Prolonged holding-period (1 year) testing of these C-TICK X X
actuators has been performed with no spring return a Plenum
failures. The actuator and the internal spring are designed applications require that conductors be enclosed in
to require no special cycling during long-term holding. conduit (see Wiring section for conduit details).
! Honeywell recommends following all local, state and
national codes for periodic testing of the entire smoke Controller Type:
control system. Refer to National Fire Protection MS4120F: Line voltage (120 Vac), 2-position, spst (Series 40).
Association (NFPA) National Fire Codes®: NFPA90A, MS4620F,S; S20230-F: Line voltage (230 Vac), 2-position,
NFPA92A and NFPA92B for your application. spst (Series 40).
! NFPA recommends periodic examination of each fire/ MS8120F,S; S2024-F: Low voltage (24 Vac), 2-position, spst
smoke damper (semi-annually or annually) to ensure (Series 80).
proper performance.
3-15/16 (100)
Mounting: 2 (50)
! Self-centering shaft adapter.
! Round Damper Shafts: 0.5 to 1.06 in.
1-9/16
! Square Damper Shafts: 1/2 to 3/4 in. (40)
! Actuator can be mounted with shaft in any position.

IMPORTANT
Honeywell does not recommend using linkages with
these actuators because side-loading of the output
hub reduces actuator life.

Noise Rating (Maximum):


! Driving or Spring Return: 70 dBA. 10-11/16
(271)
! Holding: 20 dBA (no audible noise).

Temperature Ratings: 8-5/8


(220)
IMPORTANT
The actuators are designed to meet UL555S
standards at 350°F (176°C). These actuators must
be tested with the damper to achieve this rating.

! Ambient: -40°F to 130°F (-40°C to 55°C).


! Shipping and Storage: -40°F to 140°F (-40°C to 60°C).

Humidity Ratings:
! 5% to 95% RH noncondensing.

Environmental Protection Ratings:


1/4 (6) 2-15/16 (75)
! NEMA2 and IP54 when mounted on a horizontal shaft. M20051

Accessories: Fig. 1. Dimensions in in. (mm).


! 205649 Mounting Bracket (not supplied with actuator).

63-2592—5 2
MS4120F, MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

MS8120F S2024-F-SW2, MS8120S

L2 ( )
BLACK
L2 ( ) BLUE
24 VAC RED
230 VAC BROWN
L1 ( ) L1 ( )

GREEN GRAY/BLUE
BLUE 85° AUXILIARY GRAY/RED
7° AUXILIARY SWITCH
SWITCH BLUE GRAY/YELLOW
YELLOW BLACK/BLUE
85° AUXILIARY YELLOW BLACK/RED
7° AUXILIARY
SWITCH
SWITCH BLACK/YELLOW
M20053A
M20678A

Fig. 2. Typical 24 Vac wiring (MS Series).


Fig. 5. Typical 24 Vac wiring (S20 Series).
MS4120F
7° SWITCH 85° SWITCH
LESS 7° MORE 7° LESS 85° MORE 85°
L2 ( ) WHITE BLACK/BLUE BLACK/BLUE GRAY/BLUE GRAY/BLUE
120 VAC
BLACK BLACK/RED BLACK/RED GRAY/RED GRAY/RED
L1 ( )
GREEN BLACK/YELLOW BLACK/YELLOW GRAY/YELLOW GRAY/YELLOW
M20679B

BLUE Fig. 6. Auxiliary switch wiring (S20 Series).


7° AUXILIARY
SWITCH BLUE
YELLOW S20230-F-SW2, MS4620S
85° AUXILIARY YELLOW
SWITCH
L2 ( ) BLUE
M20056A
230 VAC
BROWN
L1 ( )
Fig. 3. Typical 120 Vac wiring.

MS4620F
GRAY/BLUE
85° AUXILIARY GRAY/RED
SWITCH GRAY/YELLOW
L2 ( ) BLUE
230 VAC BLACK/BLUE
BROWN
L1 ( ) 7° AUXILIARY BLACK/RED
GREEN SWITCH BLACK/YELLOW

M20680A

BLUE
7° AUXILIARY Fig. 7. Typical 230 Vac wiring (S20 Series).
SWITCH BLUE
YELLOW
85° AUXILIARY
SWITCH YELLOW

M20057A

Fig. 4. Typical 230 Vac wiring (MS Series).

3 63-2592—5
Instruction of Installation -Annex 5
COMBINATION FIRE / SMOKE DAMPERS
SERIES: CFSD-40, 50, 60, 80
1½ HOURS & 3 HOURS FIRE RATINGS

INSTALLATION INSTRUCTIONS - A
Revision-6

FIRE / SMOKE DAMPER FOR USE IN DYNAMIC SYSTEMS


FIRE RESISTANCE RATING 1½ HOURS & 3 HOURS
LEAKAGE CLASS I - 350⁰F & CLASS II - 250ºF TEMP. DEGRADATION TEST
2000 & 4000FPM VELOCITY @ 4 IN. W.G. STATIC PRESSURE
FILE NO:R22165

Right to alterations reserved.

Safid-CFSD Installation-REV.6 Page 1 of 10


COMBINATION FIRE / SMOKE DAMPERS
SERIES: CFSD-40, CFSD-50, CFSD-60, CFSD-80
INSTALLATION INSTRUCTIONS

The following installation instructions apply to "SAFID" "CFSD" series Combination Fire / Smoke
Dampers intended for use in HVAC duct systems. These instructions are applicable for installations
through fire resistive masonry walls, block or stud walls, air transfer openings in walls and partitions in
accordance with the standard for Installation of Air-conditioning and Ventilating systems, NFPA-90A.
These 1½ hours and 3 hours "Fire Rated Dampers" shall be used for the protection of openings in walls
and partitions with fire resistive ratings of less than 3 hours or for 3 hours or more as specified with
NFPA-90A.

These dampers are designed and tested by Underwritters Laboratories Inc. (UL) for the installation and
operation in vertical position. The dampers to be installed shall be free from twisting or racking.
Transportation and installation of the dampers shall be handled carefully at the frame or sleeve only. Do
not lift the damper at damper shaft, blades or at damper actuator or operator. This installation
instructions meet the requirements of "UL555 Standard for Safety Fire Dampers" for 1½ hours and 3
hours Fire Ratings and "UL555S Standard for Safety Smoke Dampers" for Leakage Class II Leakage

1. The installation of the damper and all duct connections to the damper sleeve shall conform to
"NFPA-90A" and the "SMACNA" Fire, Smoke and Radiation damper installation guide for HVAC
systems.
2. Dampers shall be supplied with optional factory installed actuators to close the damper blades
automatically when sensing heat or upon interruption of power supply to the actuator (close by
tensioned spring).
3. Expansion Clearance: The clearance between the sleeve and wall or floor opening shall be a
minimum of 1/8" per foot (3.18 mm per 305mm) of width or height of the sleeve. The sleeve may
rest on the bottom of the opening with equal expansion clearance on both sides.
4. Sleeve:
All Combination Fire/Smoke dampers shall be provided with steel sleeve to permit direct
attachment of perimeter mounting angles on the sleeve on each side of the wall or partition.
Attachment or fixing of retaining angle directly to the wall is not allowed.
4.1. Thickness: The minimum sleeve thickness to be used shall be as per below given
specifications:

MINIMUM SLEEVE THICKNESS FOR "CFSD" DAMPERS


Type of Connection Type of Duct Duct Dimension Sleeve Gauge
Breakaway or Round or
1000mm and below 18
without duct Rectangular
Round Ø610mm maximum
Rigid Rectangular 610mm max. height & 16
914mm max. width
Round Over Ø610mm
Rigid Rectangular Over Ø610mm height 14
& over 914mm width

Right to alterations reserved.

Safid-CFSD Installation-REV.6 Page 2 of 10


COMBINATION FIRE / SMOKE DAMPERS
SERIES: CFSD-40, CFSD-50, CFSD-60, CFSD-80
INSTALLATION INSTRUCTIONS

4.2. Fasteners: Damper shall be fastened to sleeve on 4" (100mm) maximum centers with 1/2''
(13mm) long welds (for factory installed sleeve) or ؼ'' (6mm) bolts & nuts or No.10 steel
screws or minimum Ø3/16'' (5mm) steel rivets.
4.3. Sleeve Length:
a. Wall thickness plus maximum 6" (152mm) and minimum 4⅓'' (110mm) on each side for
dampers intended for use without an actuator or without a factory installed access door on
the sleeve.
b. Wall thickness plus maximum 6" (152mm) and minimum 4⅓'' (110mm) on one side and
(220mm) minimum on the opposite side for dampers intended for use with an actuator
factory installed on the sleeve.
c. Wall thickness plus maximum 6" (152mm) and minimum 4⅓'' (110mm) on one side and
16'' (406mm) on the opposite side for dampers intended for use with an actuator and
access door factory installed on the sleeve.

5. Perimeter Mounting Angles: The sleeve shall be retained in the wall or partition opening by
the use of steel mounting angles (retaining angles). The minimum angle size shall be 1½" x
1½" x 0.157'' (40x40x4mm). The mounting angles must overlap the structure opening by 1"
(25mm) minimum. The corners of the mounting angles shall be fully welded to each other.

The mounting angles shall be fastened to sleeve on 5"(127mm) maximum centers with 1/2"
(13mm) long welds or ؼ" (6mm) bolts & nuts or No.10 steel screws or minimum Ø3/16"
(5mm) steel rivets. The fasteners shall not interfere with the operation of the damper blades.

6. Duct connections: (Breakaway connections)


The damper sleeve or frame connecting the ductwork shall be provided with breakaway joints
to allow collapse of the ductwork in case of fire without disturbing the integrity of the installed
damper (CFSD). "The connecting ducts shall not be continuous, and shall terminate at the
sleeve or at the frame".

6.1. SAFID recommend "S" slip type of breakaway connection as shown in Figure 1 for use on
all sides of rectangular ducts.

6.2. The type of breakaway connection shown in Figure 1 shall have a maximum two pieces
of Ø4.8mm aluminum rivets on each side and on the bottom located in the center of the
"S" slip. The rivets shall penetrate both sides of "S" slip pocket. UL tested duct sealant
may be used.

Right to alterations reserved.

Safid-CFSD Installation-REV.6 Page 3 of 10


COMBINATION FIRE / SMOKE DAMPERS
SERIES: CFSD-40, CFSD-50, CFSD-60, CFSD-80
INSTALLATION INSTRUCTIONS

6.3. For joints of round or flat oval spiral ducts attached to round or flat oval collars which are
part of the damper sleeve, Ø4.8mm aluminum rivets shall be fixed equally spaced around
the circumference of the ducts.
1. For duct diameter 22" (558mm) and smaller shall have three aluminum rivets.
2. Duct diameter over 22" (558mm) up to and including 36" (914mm) shall have 5 rivets.

For flat oval ducts, the diameter shall be considered the largest (major) dimension of the duct.
UL listed sealant may be used.

Figure 1
DUCT SLEEVE CONNECTIONS
(Breakaway Connections)

Plain "S" Slip Hemmed "S" Slip

Right to alterations reserved.

Safid-CFSD Installation-REV.6 Page 4 of 10


COMBINATION FIRE / SMOKE DAMPERS
SERIES: CFSD-40, CFSD-50, CFSD-60, CFSD-80
INSTALLATION INSTRUCTIONS

7. Single Section Construction Sizes and Assembly Details:

SIZE LIMITATIONS
SINGLE SECTION - VERTICAL MOUNT
DESCRIPTION
WIDTH HEIGHT
MINIMUM SIZE (mm) 200 150

MAXIMUM SIZE (mm) 914 914

ASSEMBLY DETAILS FOR MODEL: "CFSD-80"

Right to alterations reserved.

Safid-CFSD Installation-REV.6 Page 5 of 10


COMBINATION FIRE / SMOKE DAMPERS
SERIES: CFSD-40, CFSD-50, CFSD-60, CFSD-80
INSTALLATION INSTRUCTIONS

8. Multiple Section Construction Sizes and Assembly Details:

SIZE LIMITATIONS
MULTIPLE SECTION - VERTICAL MOUNT
DESCRIPTION
WIDTH HEIGHT
MINIMUM SIZE (mm) 915 915

MAXIMUM SIZE (mm) 1828 1828

ASSEMBLY DETAILS FOR MODEL: "CFSD-80"

Right to alterations reserved.

Safid-CFSD Installation-REV.6 Page 6 of 10


COMBINATION FIRE / SMOKE DAMPERS
SERIES: CFSD-40, CFSD-50, CFSD-60, CFSD-80
INSTALLATION INSTRUCTIONS

9. Thermoelectric Tripping Device (ERL)


The thermoelectric tripping device is suitable with Belimo "BF" and Honeywell "MS" series damper
actuators for fire damper or combination fire & smoke damper applications. This device can be
integrated with all series of "SAFID" Combination Fire / Smoke Dampers.

The tripping device have built-in thermal "fuse or sensor switch" that disconnect the power supply
to the damper actuator as soon as the duct temperature exceeds 165ºF. If the power supply is
interrupted, the energy stored at the built-in spring-return of the actuator will moves back the
damper blades to its safe position (closed position).

The tripping device can be manually reset by pressing the reset button after the temperature
cooled down below the set point (165°F).

10. Damper Actuator Specification:


1. BELIMO Model: BF-ME (24 - 230VAC).
2. BELIMO Model: BF-S-ME (24 - 230VAC) with built-in Auxiliary switch.
Torque: 15Nm
3. Honeywell Model: MS8104F1210 (24VAC) with built-in auxiliary switch.
MS4604F1210 (230VAC) with built-in auxiliary switch.
  Torque: 3.5Nm
4. Honeywell Model: MS4620F1203 (230VAC) with built-in auxiliary switch.
MS8120F1200 (24VAC) with built-in auxiliary switch.
Torque: 20 Nm

Control: Open / Close


Spring-return type actuator
UL Listed
Steel construction
Simple mounting directly into square drive shaft.
Direction of rotation can be selected by mounting the actuator on left or right position.

Refer to product technical data sheet or contact SAFID for further information.

Right to alterations reserved.

Safid-CFSD Installation-REV.6 Page 7 of 10


COMBINATION FIRE / SMOKE DAMPERS
SERIES: CFSD-40, CFSD-50, CFSD-60, CFSD-80
INSTALLATION INSTRUCTIONS

11. FRAMING DETAILS FOR STEEL AND WOOD STUD WALLS

GYPSUM PANELS MUST BE SCREWED 305MM ON CENTERS MAXIMUM


TO ALL STUD AND RUNNER FLANGES SURROUNDING OPENING

Right to alterations reserved.

Safid-CFSD Installation-REV.6 Page 8 of 10


COMBINATION FIRE / SMOKE DAMPERS
SERIES: CFSD-40, CFSD-50, CFSD-60, CFSD-80
INSTALLATION INSTRUCTIONS

12. Typical Vertical Installations

13. Thermoelectric Tripping Device Specification: Model: BAE165 US or SF74 (165ºF Klixon)
Tripping device set point 165°F
Built-in manual reset button.
Short circuit protected against damage to cable.
Application: The BAE165 US or SF74 (165ºF Klixon) thermoelectric resettable tripping device
(ERL) operates in conjunction with a UL listed safety actuator for use in Fire & Smoke
applications. The tripping device drives a motorized fire damper to its safe position when the
temperature at the sensor exceed the set value. The device is connected in series with the
power supply of the fire & smoke damper actuator. The wiring method must be in accordance
with Class1 field wiring method for plenum application as required by National Electric Code
(NEC). Jacket the cable with suitable flexible conduit. Mount the conduit into the ERL metal
bushing by means of the provided screw.
Refer to product technical data sheet or contact SAFID for further information.
NOTES:
1. Airflow can be at opposite direction.

Right to alterations reserved.

Safid-CFSD Installation-REV.6 Page 9 of 10


COMBINATION FIRE / SMOKE DAMPERS
SERIES: CFSD-40, CFSD-50, CFSD-60, CFSD-80
INSTALLATION INSTRUCTIONS

14. Typical Wiring Diagrams

15. OPERATION:
15.1 Fire Mode:
If detected a high temperature exceeding 165ºF, the ERL (Thermoelectric Tripping Device) will
interrups the power supply to the actuator and the energy stored at the spring-return of the
actuator will moves the damper back to its safe position (closed damper blades).
15.2 Smoke Mode:
If the smoke detector detected a smoke, the power supply to the damper actuator must be
automatically disconnected and the energy stored at the spring-return of the actuator will
moves the damper back to its safe position (closed damper blades).
16. MAINTENANCE:
Dampers shall be maintained at intervals as stated in "NFPA 90A" and 92A. A duct access
door to be located on the jackshaft side of each damper for inspection and maintenance.
Some other maintenance codes includes: UL 864, AMCA 503-03 and local codes.

In general if damper cleaning is required, apply mild detergents or solvents.


If lubrication is required for any moving part such as axle or jackshaft bearing, jamb seals etc.
do not used lubricants that attracts contaminants such as dust.
17. Damper Troubleshooting
Symptom Possible cause Corrective action
Frame is racked Adjust frame such that it is square/plumb
Actuator linkage loose Close damper, off power, adjust/tight linkage
Damper does not fully
Defective actuator Replace
OPEN or CLOSE
Damper linkage screw Damper installed away from designated line
Damper contaminants Clean with non-oil based solvent
TRD Sensor tripped Heat Push the TRD reset button
Damper does not operate No power supply to motor ON (faciliate) the power supply

Right to alterations reserved.

Safid-CFSD Installation-REV.6 Page 10 of 10