50HJ006-014

Single-Package Rooftop Cooling Units


50 Hz

Installation, Start-Up and


Service Instructions
CONTENTS INSTALLATION
Page Unit is shipped in the vertical configuration. To convert to
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1 horizontal configuration, remove side duct opening covers.
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-34 Using the same screws, install covers on vertical duct openings
Step 1— Provide Unit Support. . . . . . . . . . . . . . . . . . . . 1 with the insulation-side down. Seals around duct openings
• ROOF CURB must be tight.
• SLAB MOUNT Step 1 — Provide Unit Support
Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 1 ROOF CURB — Assemble and install accessory roof curb in
Step 3 — Install Condensate Drain Line
and External Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 accordance with instructions shipped with curb. See Fig. 1 and
2. Install insulation, cant strips, roofing, and counter flashing as
Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 4 shown. Ductwork must be attached to curb.
• POSITIONING
Step 5 — Make Electrical Connections . . . . . . . . . . 10 If accessory thru-the-bottom connections are used, refer to
• FIELD POWER SUPPLY accessory installation instructions for installation information.
• FIELD CONTROL WIRING
• HEAT ANTICIPATOR SETTINGS IMPORTANT: The gasketing of the unit to the roof curb
Step 6 — Adjust Factory-Installed Options . . . . . . 13 is critical for watertightness. Install gasket supplied with
• APOLLO CONTROL the roof curb as shown in Fig. 1 and 2. Improperly
• DISCONNECT SWITCH applied gasket can also result in air leaks and poor unit
• OPTIONAL DURABLADE ECONOMIZER performance.
• OPTIONAL ECONOMI$ER
Step 7 — Adjust Evaporator-Fan Speed . . . . . . . . . 21 Curb should be level. Unit leveling tolerances are shown in
Fig. 3. This is necessary for unit drain to function properly.
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Refer to Accessory Roof Curb Installation Instructions for
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-37 additional information as required.
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-42 SLAB MOUNT (Horizontal Units Only) — Provide a level
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 43-50 concrete slab that extends a minimum of 152 mm (6 in.)
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . CL-1 beyond unit cabinet. Install a gravel apron in front of condenser
coil air inlet to prevent grass and foliage from obstructing
SAFETY CONSIDERATIONS airflow.
Installation and servicing of air-conditioning equipment can NOTE: Horizontal units may be installed on a roof curb if
be hazardous due to system pressure and electrical compo- required.
nents. Only trained and qualified service personnel should Step 2 — Field Fabricate Ductwork — On verti-
install, repair, or service air-conditioning equipment. cal discharge units, secure all ducts to roof curb and building
Untrained personnel can perform basic maintenance func- structure. Do not connect ductwork to unit. For horizontal
tions of cleaning coils and filters and replacing filters. All other applications, field-supplied flanges should be attached to hori-
operations should be performed by trained service personnel. zontal discharge openings and all ductwork attached to the
When working on air-conditioning equipment, observe precau- flanges. Insulate and weatherproof all external ductwork,
tions in the literature, tags and labels attached to the unit, and joints, and roof openings with counter flashing and mastic in
other safety precautions that may apply. accordance with applicable codes.
Follow all safety codes. Wear safety glasses and work Ducts passing through an unconditioned space must be
gloves. Use quenching cloth for unbrazing operations. Have insulated and covered with a vapor barrier.
fire extinguisher available for all brazing operations. If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applica-
ble fire codes.
A minimum clearance to combustibles is not required
Before performing service or maintenance operations on around ductwork on vertical discharge units. On horizontal
unit, turn off main power switch to unit and install lockout discharge units, a minimum clearance of 25 mm (1 in.) is re-
tag. Electrical shock could cause personal injury. quired for the first 305 mm (12 in.) of ductwork.
Cabinet return-air static shall not exceed –.35 in. wg with
Durablade economizer, or –0.30 in. wg with EconoMi$er, or
–.45 in. wg without economizer.
Ensure voltage listed on unit rating plate agrees with elec-
trical supply provided for the unit.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Catalog No. 005-006 Printed in U.S.A. Form 50HJ-C7SI Pg 1 10-00 Replaces: 50HJ-C5SI
Tab 1b 6b
D ALT
“E” “F” “G” CONNECTOR
B C DRAIN
GAS POWER CONTROL PKG. ACCY.
HOLE
3/4″ 3/ ″ [19] NPT) 1/2″ CRBTMPWR001A00
4
[19] NPT 11/4″ [31.7] [12.7] NPT CRBTMPWR002A00
1′-911/16″ 1′-4″ 13/4″ 1/ ″
2 3/4″
[551] [406] [44.5] [19] NPT 1/ ″
CRBTMPWR003A00
[12.7] NPT 2
3/4″ [12.7] NPT
11/4″ [31.7] CRBTMPWR004A00
[19] NPT

ROOF CURB UNIT SIZE


“A”
ACCESSORY 50HJ
CRRFCURB001A00 1′-2″ [356]
006,007
CRRFCURB002A00 2′-0″ [610]

NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on
curb).
6. Service clearance 4 ft on each side.
7. Direction of airflow.
8. Connector packages CRBTMPWR001A00 and
2A00 are for thru-the-curb type. Packages
CRBTMPWR003A00 and 4A00 are for the
thru-the-bottom type connections.

Fig. 1 — Roof Curb Details; 50HJ006,007

2
D ALT ROOF CURB UNIT SIZE
“E” “F” “G” CONNECTOR “A”
B C DRAIN ACCESSORY 50HJ
GAS POWER CONTROL PKG. ACCY.
HOLE CRRFCURB003A00 1′-2″ [356]
3/ ″ 3/4″[19] NPT) 1/ ″ CRBTMPWR001A00 008-014
4 2
CRRFCURB004A00 2′-0″ [610]
[19] NPT 11/4″ [31.7] [12.7] NPT CRBTMPWR002A00
2′-87/16″ 1′-1015/16″ 13/4″ 1/2″
3/4″
[827] [583] [44.5] [19] NPT 1/2″
CRBTMPWR003A00 NOTES:
[12.7] NPT 1. Roof curb accessory is shipped disassembled.
3/ ″ [12.7] NPT
4
11/4″ [31.7] CRBTMPWR004A00 2. Insulated panels: 1-in. thick polyurethane foam,
[19] NPT 13/4 lb density.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16 gage steel.
5. Attach ductwork to curb (flanges of duct rest on
curb).
6. Service clearance 4 ft on each side.
7. Direction of airflow.
8. Connector packages CRBTMPWR001A00 and
2A00 are for thru-the-curb connections. Pack-
ages CRBTMPWR003A00 and 4A00 are for
the thru-the-bottom type connections.

PLACE UNIT AS CLOSE TO


THIS END OF CURB AS POSSIBLE

PLACE UNIT AS CLOSE TO


THIS END OF CURB AS POSSIBLE

Fig. 2 — Roof Curb Details; 50HJ008-014

3
All units must have an external trap for condensate drain-
age. Install a trap at least 4-in. deep and protect against freeze-
up. If drain line is installed downstream from the external trap,
pitch the line away from the 50HJ unit at 1 in. per 10 ft of run.
Do not use a pipe size smaller than the unit connection (3/4 in.).
Step 4 — Rig and Place Unit — Inspect unit for
transportation damage. File any claim with transportation
agency. Keep unit upright and do not drop. Spreader bars are
50HJ006,007 50HJ008-014 not required if top crating is left on unit. Rollers may be used to
move unit across a roof. Level by using unit frame as a
MAXIMUM ALLOWABLE DIFFERENCE mm (in.) reference. See Tables 1A and 1B and Fig. 5 for additional in-
A-B B-C A-C formation. Operating weight is shown in Tables 1A and 1B and
13 (0.5) 25 (1.0) 25 (1.0) Fig. 5.
Fig. 3 — Unit Leveling Tolerances Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
Step 3 — Install Condensate Drain Line and POSITIONING — Maintain clearance around and above unit
External Trap — Condensate drain connections are locat- to provide proper airflow and service access. See Fig. 6 and 7.
ed at the bottom and side of the unit. Unit discharge connec- Position unit on roof curb so that the following clearances
tions do not determine the use of drain connections; are maintained: 7 mm (1/4-in.) clearance between roof curb and
either drain connection can be used in vertical or horizontal base rails on each side and duct end of unit; for sizes 006,007 =
applications. 6 mm (1/4-in.) and sizes 008-014 = 84 mm (35/16-in.) clearance
When using the standard side drain connection, make sure between roof curb and condenser coil end of unit (see Fig. 1
the plug (Red) in the alternate bottom connection is tight before and 2 section C-C).
installing the unit. Do not install unit in an indoor location. Do not locate unit
To use the bottom drain connection for a roof curb installa- air inlet near exhaust vents or other sources of contaminated
tion, relocate the factory-installed plug (Red) from the bottom air.
connection to the side connection. See Fig. 4. The piping for Although unit is weatherproof, guard against water from
the condensate drain and external trap can be completed after higher level runoff and overhangs.
the unit is in place. After unit is in position, remove polyethylene shipping
wrapper and rigging skid.
To remove center drain plug use 1/2-in. drive ratchet exten-
sion in plug fitting opening.

DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 — Condensate Drain Connection
(Side View)

4
50HJ006,007

50HJ008-014

NOTES: OPERATING
1. Dimension in ( ) is in millimeters. A B C
50HJ WEIGHT
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in
base rails are centered around the unit center of gravity. Use wooden top skid Lb Kg in. mm in. mm in. mm
when rigging to prevent rigging straps from damaging unit. 006 465 211 73.69 1872 35.50 902 33.31 847
3. See Tables 1A and 1B for economizer weights.
007 520 236 73.69 1872 35.50 902 33.31 847
008 755 342 77.42 1967 41.50 1054 42.12 1070
009 760 345 77.42 1967 41.50 1054 42.12 1070
012 915 415 77.42 1967 41.50 1054 50.12 1273
All panels must be in place when rigging.
014 930 422 77.42 1967 41.50 1054 50.12 1273

Fig. 5 — Rigging Details

5
Table 1A — Physical Data (SI)
UNIT SIZE 50HJ 006 007 008 009 012 014
NOMINAL CAPACITY (kW) 15.8 19.0 22.9 25.0 29.2 35.9
OPERATING WEIGHT (kg)
Unit 211 236 342 345 415 422
Unit with Durablade Economizer 226 251 362 365 435 442
Unit with EconoMi$er 232 257 370 373 443 450
Roof Curb 52 52 65 65 65 65
COMPRESSOR Scroll
Quantity 1 1 2 2 2 2
Oil (ml) (each compr) 1479 1774 1567 1567 1479 1774
REFRIGERANT TYPE R-22
Operating Charge (kg)
Circuit 1 4.5 4.4 3.5 3.6 4.2 4.3
Circuit 2 — — 3.7 3.8 4.6 4.2
CONDENSER FAN Propeller Type
Qty...Diameter (mm) 1...559 1...559 2...559 2...559 2...559 2...559
Normal Airflow Rate (L/s) 1650 1650 2600 2600 2645 2645
Motor Output...Speed (kW...r/s) 0.34...16 0.34...16 0.34...16 0.34...16 0.34...16 0.34...16
CONDENSER COIL Enhanced Copper Tubes, Lanced Aluminum Fins
Rows...Fins/m 2...670 2...670 2...670 2...670 2...670 2...670
Total Face Area (sq m) 1.53 1.53 1.90 1.90 2.32 2.32
EVAPORATOR FAN Centrifugal Type
Size (mm) 254 x 254 254 x 254 381 x 381 381 x 381 381 x 381 381 x 381
Type Drive Belt Belt Belt Belt Belt Belt
Nominal Airflow Rate L/s 800 1040 1180 1415 1700 1980
Maximum Continuous BkW 1.80 1.80 2.2 2.2 2.8 2.8
Motor Frame 56 56 56 56 56 56
Fan Speed Range (r/s) 15.3-21.8 15.3-21.8 11.5-14.8 11.5-14.8 11.5-14.8 11.5-14.8
Motor Bearing Type Ball Ball Ball Ball Ball Ball
Maximum Fan Speed (r/s) 29.2 29.2 29.2 29.2 29.2 35
Motor Pulley Pitch Diameter A/B (mm) 61.0/86.4 61.0/86.4 86.4/111.8 86.4/111.8 101.6/127.0 101.6/127.0
Fan Pulley Pitch Diameter (mm) 101.2 94.0 178 178 203 203
Belt — Type...Length (mm) A...1016 A...1016 A...1295 A...1295 A...1295 A...1295
Pulley Center Line Distance (mm) 373.4-393.7 373.4-393.7 425.5-489.0 425.5-489.0 402.6-444.5 402.6-444.5
Speed Change per Full Turn of 1.05 1.05 .667 .667 .600 .600
Moveable Pulley Flange (r/s)
Moveable Pulley Maximum Full Turns
5 5 5 5 5 5
From Closed Position
Factory Setting — Full Turns Open 3 3 5 5 5 5
Factory Speed Setting (r/s) 17.2 18.00 11.5 11.5 11.8 11.8
Fan Shaft Diameter at Pulley (mm) 15.9 15.9 25.4 25.4 25.4 25.4
EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins Acutrol™ Feed Device
Rows...Fins/m 4...591 4...591 3...591 3...591 3...591 4...591
Total Face Area (sq m) 0.51 0.51 0.83 0.83 1.03 1.03
HIGH-PRESSURE SWITCH (kPa)
Cutout 2950
Reset (Auto.) 2205
LOSS-OF-CHARGE/LOW-PRESSURE
SWITCH (Liquid Line) (kPa)
Cutout 48.3 ± 20.7
Reset (Auto.) 151.7 ± 48.3
FREEZE PROTECTION THERMOSTAT (C)
Cutout –1
Reset (Auto.) 7
OUTDOOR-AIR INLET SCREENS Cleanable
1...508 x 635 x 25
Qty...Size (mm) 1...508 x 635 x 25 1...406 x 635 x 25
RETURN-AIR FILTERS Throwaway
Qty...Size (mm) 2...406 x 635 x 51 4...406 x 508 x 51 4...508 x 508 x 51

6
Table 1B — Physical Data (English)
UNIT SIZE 50HJ 006 007 008 009 012 014
NOMINAL CAPACITY (tons) 5 6 71 / 2 81/2 10 121/2
OPERATING WEIGHT (kg)
Unit 465 520 755 760 915 930
Unit with Durablade Economizer 499 554 799 804 959 974
Unit with EconoMi$er 512 567 817 822 977 992
Roof Curb 115 115 143 143 143 143
COMPRESSOR Scroll
Quantity 1 1 2 2 2 2
Oil (ml) (each compr) 50 60 53 53 50 60
REFRIGERANT TYPE R-22
Operating Charge (lb)
Circuit 1 10.0 9.6 7.6 7.9 9.2 9.5
Circuit 2 — — 8.1 8.3 10.2 9.3
CONDENSER FAN Propeller Type
Qty...Diameter (in.) 1...22 1...22 2...22 2...22 2...22 2...22
Normal Cfm 3500 3500 5500 5500 5600 5600
1/ 1/ ...920 1/ ...920 1/ ...920 1/ ...920 1/ ...920
Motor Hp...Rpm 4...920 4 4 4 4 4
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in. 2...17 2...17 2...17 2...17 2...17 2...17
Total Face Area (sq ft) 16.5 16.5 20.5 20.5 25.0 25.0
EVAPORATOR FAN Centrifugal Type
Size (in.) 10 x 10 10 x 10 15 x 15 15 x 15 15 x 15 15 x 15
Type Drive Belt Belt Belt Belt Belt Belt
Nominal Cfm 1700 2200 2500 3000 3600 4200
Maximum Continuous Bhp 2.4 2.4 2.9 2.9 3.7 3.7
Motor Frame 56 56 56 56 56 56
Fan Rmp Range 920-1310 920-1310 690-890 690-890 710-890 710-890
Motor Bearing Type Ball Ball Ball Ball Ball Ball
Maximum Fan Rpm 1750 1750 1750 1750 1750 2100
Motor Pulley Pitch Diameter A/B (in.) 2.4/3.4 2.4/3.4 3.4/4.4 3.4/4.4 4.0/5.0 4.0/5.0
Fan Pulley Pitch Diameter (in.) 4.0 3.7 7.0 7.0 8.0 8.0
Belt — Type...Length (in.) A...40 A...40 A...51 A...51 A...51 A...51
Pulley Center Line Distance (in.) 14.7-15.5 14.7-15.5 16.75-19.25 16.75-19.25 15.85-17.50 15.85-17.50
Speed Change per Full Turn of 63 63 40 40 36 36
Moveable Pulley Flange (rpm)
Moveable Pulley Maximum Full Turns
5 5 5 5 5 5
From Closed Position
Factory Setting — Full Turns Open 3 3 5 5 5 5
Factory Speed Setting (rpm) 1033 1087 690 690 710 710
Fan Shaft Diameter at Pulley (in.) 5/ 5/ 1 1 1 1
8 8
EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double-Wavy Fins Acutrol™ Feed Device
Rows...Fins/in. 4...15 4...15 3...15 3...15 4...15 4...15
Total Face Area (sq ft) 5.5 5.5 8.9 8.9 11.1 11.1
HIGH-PRESSURE SWITCH (psig)
Cutout 428
Reset (Auto.) 320
LOSS-OF-CHARGE/LOW-PRESSURE
SWITCH (Liquid Line) (psig)
Cutout 7±3
Reset (Auto.) 22 ± 7
FREEZE PROTECTION THERMOSTAT (F)
Cutout 30
Reset (Auto.) 45
OUTDOOR-AIR INLET SCREENS Cleanable
1...20 x 25 x 1
Quantity...Size (in.) 1...20 x 24 x 1 1...16 x 25 x 1
RETURN-AIR FILTERS Disposable
Qty...Size (in.) 2...16 x 25 x 2 4...16 x 20 x 2 4...20 x 20 x 2

7
BOTTOM POWER CHART, THESE HOLES REQ’D
DURABLADE CORNER CORNER CORNER CORNER FOR USE WITH ACCESSORY PACKAGES —
STD UNIT ECONOMI$ER
ECONOMIZER WEIGHT WEIGHT WEIGHT WEIGHT
UNIT WEIGHT WEIGHT WEIGHT (A) (B) (C) (D) CRBTMPWR001A00 (1/2″, 3/4″) OR
50HJ
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg CRBTMPWR002A00 (1/2″, 11/4″)
006 465 211 34 15.4 47 21.3 133 60.3 113 51.3 101 45.8 118 53.5 THREADED REQ’D HOLE
WIRE
007 520 236 34 15.4 47 21.3 149 67.6 127 57.6 112 50.8 132 59.9 CONDUIT SIZES
USE
SIZE (Max.)
1/2″ 24 V 7/8″ [22.2]
A 13/8″ Dia. [35] Field Power Supply Hole
3/ ″ Power* 11/8″ [28.4]
B 2″ Dia. [51] Power Supply Knockout 4

C 13/4″ Dia. [44] Charging Port Hole 11/4″ FPT Power* 13/4″ [44.4]
D 7/ ″ Dia. [22] Field Control Wiring Hole
8 *Select either 3/4″ or 11/4″ for power, depending on wire
E 3/ ″ — 14 NPT Condensate Drain size.
4
F 2 /2″ Dia. [64] Power Supply Knockout
1
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of gravity.

3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces (when not using curb) 0 inches, on horizontal discharge units with
electric heat 1 in. clearance to ductwork for 1 ft.
b. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater
clearance is optional.
c. Overhead, 60 in. to assure proper condenser fan operation.
d. Between units, control box side, 42 in. per NEC (National Electrical Code).
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
f. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. per
NEC.
g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil as stated in Notes 5b, a removable fence or
barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material.
8. The vertical center of gravity is 1′-61/2″ [470] up from the bottom of the base rail.

Fig. 6 — Base Unit Dimensions; 50HJ006,007

8
DURABLADE CORNER CORNER CORNER CORNER
STD UNIT ECONOMI$ER
UNIT ECONOMIZER WEIGHT WEIGHT WEIGHT WEIGHT “H” “J” “K”
WEIGHT WEIGHT
50HJ WEIGHT (A) (B) (C) (D)
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in. mm Ft-in. mm
008 755 342 44 20 62 28 164 74 140 64 208 94 243 110 2- 07/8 632 3-55/16 1050 2-911/16 856
009 760 345 44 20 62 28 165 75 141 64 209 94 245 111 1- 27/8 378 3-55/16 1050 2-911/16 856
012 915 415 44 20 62 28 199 90 170 77 252 114 294 134 2-107/8 885 4-15/16 1253 3-03/8 924
014 930 422 44 20 62 28 202 92 172 78 256 116 300 136 1- 27/8 378 4-15/16 1253 3-03/8 924

BOTTOM POWER CHART, THESE HOLES REQ’D


A 13/8″ Dia. [35] Field Power Supply Hole
FOR USE WITH ACCESSORY PACKAGES —
B 21/2″ Dia. [64] Power Supply Knockout
CRBTMPWR001A00 (1/2″, 3/4″) OR
C 13/4″ Dia. [44] Charging Port Hole CRBTMPWR002A00 (1/2″, 11/4″)
D 7/ ″ Dia. [22] Field Control Wiring Hole
8
E 3/4″ — 14 NPT Condensate Drain THREADED REQ’D HOLE
WIRE
F 2″ Dia. [51] Power Supply Knockout CONDUIT SIZES
USE
SIZE (Max.)
1/2″ 24 V 7/8″ [22.2]

3/4″ Power* 11/8″ [28.4]


11/4″ FPT Power* 13/4″ [44.4]
NOTES:
1. Dimensions in [ ] are in millimeters. *Select either 3/4″ or 11/4″ for power, depending on wire
2. Center of gravity. size.

3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces (when not using curb) 0 inches, on horizontal discharge units with
electric heat 1 in. clearance to ductwork for 1 ft.
b. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater
clearance is optional.
c. Overhead, 60 in. to assure proper outdoor fan operation.
d. Between units, control box side, 42 in. per NEC (National Electrical Code).
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
f. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. per
NEC.
g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil as stated in Notes 5b, a removable fence or
barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material.
8. The vertical center of gravity is 1′-71/2″ [495] for 008 and 009, 2′-0″ [610] for 012 and 014 up from the
bottom of the base rail.

Fig. 7 — Base Unit Dimensions; 50HJ008-014

9
Step 5 — Make Electrical Connections 2. Install power lines to terminal connections as shown in
Fig. 8.
3. For units with accessory electric heat, refer to the acces-
sory installation instructions to determine appropriate
Unit cabinet must have an uninterrupted, unbroken electri- power wiring figure for wiring single point box.
cal ground to minimize the possibility of personal injury if 4. Run control wires from heater module(s) (where applica-
an electrical fault should occur. This ground may consist of ble) to the control wire terminal block located next to the
electrical wire connected to unit ground lug in control com- heater module(s). Connect the control wires as shown in
partment, or conduit approved for electrical ground when accessory electric heater installation instructions.
installed in accordance with NEC (National Electrical
Code, U.S.A. standard) and local electrical codes. Failure During operation, voltage to compressor terminals must be
to follow this warning could result in the installer being lia- within voltage range indicated on unit nameplate (see Table 2).
ble for personal injury of others. On 3-phase units, voltages between phases must be balanced
within 2%, and the current within 10%. Use the formula shown
FIELD POWER SUPPLY — Refer to unit label diagram for in Table 2, Note 3 on page 11 to determine the percent voltage
additional information. Pigtail leads are provided for field wire imbalance. Operation on improper line voltage or excessive
connections. phase imbalance constitutes abuse and may cause damage to
electrical components. Such operation invalidates any applica-
All field wiring must comply with local requirements. In- ble Carrier warranty.
stall field wiring as follows:
When accessory electric heat is installed, remove knockouts
1. Install conduit through side panel openings. For units for appropriate size conduit from unit block-off panel and sin-
without accessory electric heat, install conduit between gle point box. Install conduit (rigid or electro-metallic tubing)
disconnect and control box. through conduit drip boot. Drip boot eliminates the need for
water-tight conduit fittings at the single point box.

50HJ006,007 50HJ008-014
400-3-50 220-3-50,
400-3-50

LEGEND

C — Contactor Terminal
COMPS — Compressors Field Wiring
IFC — Indoor (Evaporator) Fan Contactor Factory Wiring
NEC — National Electrical Code (U.S.A. Standard)
TRAN — Transformer Splice Connection (Factory-Supplied)

Fig. 8 — Power Wiring Connections

10
Table 2 — Electrical Data
VOLTAGE COMPR OFM
NOMINAL IFM ELECTRIC HEAT* POWER SUPPLY DISCONNECT SIZE†
UNIT RANGE (Each) (Each)
50HJ VOLTATE
(50 Hz) FLA FLA Nominal
Min Max RLA LRA FLA MCA MOCP†† FLA LRA
kW**
— — 14.5 20 14
4.2 6.0 14.5 20 14
006 400 360 440 9.0 62.0 0.6 2.6 8.0 11.5 17.6 20 16
(3-phase) 84
9.7 14.0 20.8 25 19
16.0 23.0 32.0 35 29
17.7 25.5 35.2 40 32
— — 15.2 20 15
4.2 6.0 15.2 20 15
400 8.0 11.5 17.6 20 16
007 360 440 9.6 70.0 0.6 2.6 92
(3-phase) 9.7 14.0 20.8 25 19
16.0 23.0 32.0 35 29
17.7 25.5 35.2 40 32
— — 38.2 45 40
8.7 22.9 38.2 45 40
220 13.4 35.3 53.5 60 49
180 242 12.4 88.0 1.4 7.5 242
(3-phase) 20.8 54.7 77.7 80 71
26.9 70.5 97.6 100 90
35.6 93.5 126.2 150 116
008
— — 19.0 25 20
9.7 13.9 21.7 25 20
400 11.5 16.5 24.9 25 23
360 440 6.4 44.0 0.6 3.4 121
(3-phase) 19.3 27.8 39.1 40 36
22.9 33.1 45.6 50 42
28.9 41.8 56.5 60 52
— — 44.1 50 46
8.7 22.9 44.1 50 46
220 180 242 15.0 99.0 1.4 7.5 13.4 35.3 53.5 60 49 264
(3-phase) 20.8 54.7 77.7 80 71
26.9 70.5 97.6 100 90
35.6 93.5 126.2 150 116
009
— — 23.1 30 24
9.7 13.9 23.1 30 24
400 11.5 16.5 24.9 25 24
360 440 8.2 49.5 0.6 3.4 132
(3-phase) 19.3 27.8 39.1 40 36
22.9 33.1 45.6 50 42
28.9 41.8 56.5 60 52
— — 56.8 70 60
8.7 22.9 56.8 70 60
220 13.4 35.3 57.3 60 60
180 242 19.3 123.0 1.4 10.6 337
(3-phase) 26.9 70.5 101.4 110 93
35.6 93.5 130.1 150 120
42.0 110.2 151.0 175 139
012
— — 26.3 30 28
11.5 16.5 26.7 30 28
400 360 440 9.0 62.5 0.6 3.4 19.3 27.8 40.8 45 38 171
(3-phase) 22.9 33.1 47.3 50 44
28.9 41.8 58.2 60 54
34.7 50.1 68.6 70 63
— — 71.7 80 75
8.7 22.9 71.7 80 75
220 180 242 25.9 156.0 1.4 10.6 13.4 35.3 57.3 60 75 403
(3-phase) 26.9 70.5 101.4 110 93
35.6 93.5 130.1 150 120
42.0 110.2 151.0 175 139
014
— — 35.0 40 37
11.5 16.5 35.0 40 37
400 19.3 27.8 40.8 45 38
360 440 12.9 72.0 0.6 4.8 190
(3-phase) 22.9 33.1 47.3 50 44
28.9 41.8 58.2 60 54
34.7 50.1 68.6 70 63

LEGEND Example: Supply voltage is 400-3-50.


FLA — Full Load Amps AB = 393 v
HACR — Heating, Air Conditioning and Refrigeration BC = 403 v
IFM — Indoor (Evaporator) Fan Motor AC = 396 v
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps 393 + 403 + 396
Average Voltage =
MOCP — Maximum Overcurrent Protection 3
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps 1192
=
*Heaters are field installed only. 3
†Used to determine minimum disconnect per NEC (U.S.A. standard). = 397
**Heater capacity (kW) is based on heater voltage of 240 v or 400 v. If power
distribution voltage to unit varies from rated heater voltage, heater kW will Determine maximum deviation from average voltage.
vary accordingly. (AB) 397 – 393 = 4 v
††Fuse or HACR circuit breaker. (BC) 403 – 397 = 6 v
NOTES: (AC) 397 – 396 = 1 v
1. MCA and MOCP values are calculated in accordance with NEC (National Maximum deviation is 6 v.
Electric Code) (U.S.A. standard), Article 440. Determine percent of voltage imbalance.
2. Motor RLA and FLA values are established in accordance with UL
(Underwriters’ Laboratories) Standard 465 (U.S.A. standard). 6
% Voltage Imbalance = 100 x
3. Unbalanced 3-Phase Supply Voltage 397
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percentage of = 1.5%
voltage imbalance. This amount of phase imbalance is satisfactory as it is below the maxi-
% Voltage Imbalance mum allowable 2%.
max voltage deviation from average voltage IMPORTANT: If the supply voltage phase imbalance is more than
= 100 x
average voltage 2%, contact your local electric utility company immediately.

11
FIELD CONTROL WIRING — Install a Carrier-approved
accessory thermostat assembly according to installation in-
structions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense aver-
age temperature in accordance with thermostat installation
instructions.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals to low-voltage terminal strip on
unit (shown in Fig. 9) as described in Steps 1 through 4 below.
NOTE: For wire runs up to 15.2 m (50 ft), use no. 18 AWG
(American Wire Gage) insulated wire (35 C minimum). For
15.2 to 22.9 m (51 to 75 ft), use no. 16 AWG insulated wire
(35 C minimum). For over 22.9 m (75 ft), use no. 14 AWG
insulated wire (35 C minimum). All wire larger than no. 18
AWG cannot be directly connected to the thermostat and will
require a junction box and splice at the thermostat. (See Table
3 for wire conversions.)
LEGEND
Table 3 — American/European Wire Conversions AHA — Adjustable Heat Anticipator Field Wiring
CC — Cooling Compensator Factory Wiring
AMERICAN EUROPEAN
NOTE: On 006 and 007 units: Y2 is connected when using an
Industry American Conversion Industry Standard economizer.
Standard Size (mm2) Size (mm2)
18 AWG 0.82 1.0 Fig. 9 — Low-Voltage Connections With or
16 AWG 1.30 1.5 Without Economizer or Two-Position Damper
14 AWG 2.08 2.5
12 AWG 3.30 4.0
10 AWG 5.25 6.0
8 AWG 6.36 10.0
6 AWG 13.29 16.0
4 AWG 21.14 25.0
3 AWG 26.65 —
2 AWG 33.61 35.0 TERMINAL
1 AWG 42.39 50.0 STRIP
1/0 AWG 53.49 —
2/0 AWG 67.42 70.0
3/0 AWG 85.00 95.0
4/0 AWG 107.19 120.0
250 kcmil 126.64 150.0 RACEWAY
300 kcmil 151.97 —
350 kcmil 177.90 185.0
400 kcmil 202.63 240.0
500 kcmil 253.29 300.0
600 kcmil 303.95 —
COMPRESSOR
LEGEND NO. 2
AWG — American Wire Gage
kcmil — Thousand Circular Mils CONTAINS OIL

1. If unit is mounted on roof curb and accessory thru-the- COMPRESSOR


NO. 1
curb service plate connection is used, route wire through
connection plate.
NOTE: If accessory thru-the-bottom connections are
used, refer to the accessory installation instructions for
power wiring procedures and installation. Refer to Fig. 6 Fig. 10 — Field Control Wiring Raceway
and 7 for drilling holes in basepan. (Size 008-014 shown)
2. Pass control wires through the hole provided on unit (see
connection D in Connection Sizes tables in Fig. 6 and 7). 4. Connect thermostat wires to screw terminals of low-
3. Feed wire through the raceway built into the corner post voltage terminal strip (see Fig. 9).
to the 24-v barrier located on the left side of the control HEAT ANTICIPATOR SETTINGS — For 50HJ006 and
box. See Fig. 10. The raceway provides the required 007 units set both first and second stages to .14 amp. For
clearance between the high- and low-voltage wiring. 50HJ008-014 units with electric heat, set heat anticipator set-
NOTE: If unit is equipped with electric heating elements, tings as shown in Table 4.
thermostat must energize “G” (fan) on call for heating
(W1 and /or W2).
Table 4 — Heat Anticipator Settings
UNIT VOLTAGE
230 400
UNIT Configuration Configuration
Heater Heater
kW 1 Stage 2 Stage 1-Stage 2-Stage
kW
Stage 1 Stage 1 Stage 2 Stage 1 Stage 1 Stage 2
8.7, 13.4 0.3 NA NA
9.6, 11.5, 19.3, 28.9 0.3 NA NA
50HJ 20.8, 26.9 0.6 0.3 0.3
35.6, 42.0 0.9 0.6 0.3 22.9, 34.7 0.6 0.3 0.3

12
Step 6 — Adjust Factory-Installed Options aside screen retainer and retainer screw for later assem-
APOLLO CONTROL — The optional Apollo control is used bly. Do not attach hood to unit at this time.
to actively monitor all modes of operation as well as indoor 4. On size 012 and 014 units, install vertical discharge
(evaporator) fan status, filter status, and indoor-air quality. The block-off plate over duct openings. See Fig. 14.
Apollo control is designed to work with Carrier TEMP and 5. Slide economizer into unit and secure with screws. See
VVT® (Variable Volume and Temperature) systems. Fig. 15.
The thermostat must be wired to the Apollo control before NOTE: Be sure to engage rear economizer flange under tabs in
starting the unit. Refer to the Apollo control installation vertical return-air opening. See Fig. 16.
instructions for information on installing the thermostat. See
Fig. 11 for Apollo location.
DISCONNECT SWITCH — The optional disconnect switch
is non-fused. The switch has the capability of being locked in
place for safety purposes.
OPTIONAL DURABLADE ECONOMIZER — The option-
al economizer hood assembly is packaged and shipped in the
filter section. Damper blades and control boards are installed at
the factory and the economizer is shipped in the vertical dis-
charge position.
NOTE: Horizontal discharge block-off plate is shipped with
the air hood package. If unit is to be used for vertical discharge
application, discard this plate.
Assembly
1. Determine if ventilation air is required in building. If so,
determine the minimum amount to be supplied by each
unit and record quantity of ventilation air needed for use
in Step 8.
2. Remove filter access panel by raising panel and swinging
panel outward. Panel is now disengaged from track and
can be removed. No tools are required to remove filter ac-
cess panel. Remove outdoor-air opening panel. Save pan-
els and screws. See Fig. 12. Remove optional economizer
to allow outdoor-air damper hood package to be removed
from filter section.
3. Assemble outdoor-air hood top and side plates as shown Fig. 12 — Panel Locations (Size 012, 014 shown)
in Fig. 13. Install seal strips on hoop top and sides. Put

CONTROL
WIRING

APOLLO
CONTROL

WIRING TO
THERMOSTAT

COMPRESSOR
NO. 2

COMPRESSOR
NO. 1

Fig. 13 — Outdoor-Air Hood Details


Fig. 11 — Apollo Control Factory-Installed
in Typical Unit (Size 014 shown)

13
6. To convert to horizontal discharge application:
a. Rotate the economizer 90 degrees until the econo-
mizer motor faces the condenser section (see
Fig. 17).
b. Remove shipping screw and tape then rotate the
barometric relief damper hinge 90 degrees. Baro-
metric relief damper should open vertically to
operate properly.
c. Install horizontal discharge block-off plate over
the opening on the access panel. (Block-off plate
MUST be installed before installing hood assem-
bly.) See Fig. 18.
7. Remove and store 12-pin plug with blue and yellow wire
from factory harness in upper left side of return-air cabi-
net. Insert economizer plug into economizer harness. Re-
move shipping screw and tape from barometric relief
Fig. 14 — Vertical Discharge Block-Off Plate damper. See Fig. 15.
(Sizes 012,014 Only)
8. If ventilation air is not required, proceed to Step 9. If ven-
tilation air is required, determine the minimum position
setting for required airflow. See Fig. 19 or 20. Adjust
minimum position setting by adjusting the screws on the
position setting bracket. See Fig. 21. Slide bracket until
the top screw is in the position determined by Fig. 19 or
20. Tighten screws.

ECONOMIZER
PLUG
LOCATION

BAROMETRIC
RELIEF
DAMPER

BAROMETRIC
RELIEF
SHIPPING DAMPER
SCREW
ECONOMIZER SHIPPING
MOUNTING SCREW
SCREWS

ECONOMIZER
MOTOR
POSITION TOP
SETTING BRACKET SCREW

Fig. 15 — Durablade Economizer Installed in Unit


CONDENSER
SECTION

Fig. 17 — Horizontal Durablade Economizer


Installation

UNIT FILTER ECONOMIZER CLIP


RACK HVAC UNIT

ECONOMIZER
UNIT BASE

ECONOMIZER REAR
FLANGE

Fig. 16 — Rear Durablade Economizer


Flange Installation

BLOCK-OFF PLATE

Fig. 18 — Horizontal Discharge Block-Off Plate

14
9. Remove tape from outdoor-air thermostat (OAT). Fasten
OAT to inside of hood using screws and speed clips pro-
vided. See Fig. 22. Make sure OAT terminals are posi-
tioned up.
10. Replace outdoor-air opening panel using screws from
Step 2. Replace filter access panel. Ensure the filter
access panel slides along the tracks and is securely
engaged.

Example:
Given —
Return-Air Negative Static Pressure . . . . . . . 50 Pa (0.2 in. wg)
Outdoor Airflow . . . . . . . . . . . . . . . . . . . . . . . 425 L/s (900 cfm)
Determine —
Setting = 125 mm (5 in.)
Fig. 19 — Durablade Economizer Minimum
Position Setting, 50HJ006 and 007

*Includes pressure drop for filters and hoods.


Fig. 20 — Durablade Economizer Minimum
Position Setting (50HJ008-014)

ENTHALPY
CONTROL
0
1

REV. B
B
POSITION
MINIMUM 3

TR
OPEN

D
SO
S
2

1
T
P

HOOD
2
T1

4
P1
3

CONTACTS SHOWN IN HIGH ENTHALPY


CONTACT RATINGS: 1.5A RUN, 3.5A IN
OR UNPOWERED STATE
RUSH AT 24VAC
% 90

198818A
H
U 70
M
D
I 60
T
I 30
Y 10

ENTHALPY CONTROL
3
4

CW–SETPOINTS–CCW

TR
D
50 55 60 65 70 75 80 85

DAMPER

24VAC
OUTDOOR TEMP.

OPEN

B A

2
3 mA MIN. AT 11 VDC

TR1
5

1
DAMPER
CLOSED
°F

97-3672
REV.
6
7
8
9

*Outdoor-Air Thermostat or Enthalpy Control can be attached to


either side inside hood.
Fig. 21 — Durablade Economizer Minimum Fig. 22 — Durablade Outdoor-Air Thermostat
Position Damper Setting Enthalpy Control Installation
15
11. Fasten hood top and side plate assembly to outdoor-air ECONOMI$ER CONTROLLER
opening panel with screws provided. PLUG
GEAR-DRIVEN
12. Place knob supplied with economizer on OAT. See DAMPER
Fig. 22. Set for 3° F below indoor room thermostat set-
ting. If accessory enthalpy control (EC) is used in place of
OUTDOOR AIR
OAT, see instructions shipped with EC for installation TEMPERATURE
and adjustment. See Fig. 22. SENSOR
13. Connect OAT per Fig. 23.
14. Slide outdoor-air inlet screen(s) into screen track on hood
side plate. On size 008-014 units, slide screen clasp over ACTUATOR
outdoor-air inlet screens to hold screens together. While
holding screen(s) in place, fasten screen retainer to hood
using screws provided. OPTIONAL POWER EXHAUST,
BAROMETRIC RELIEF DAMPERS 24 VAC,3-PIN CONNECTOR
NOTE: Refer to Fig. 24 for economizer barometric relief
damper characteristics. Fig. 25 — 5 and 6 Ton EconoMi$er
Component Locations

ECONOMI$ER CONTROLLER GEAR-DRIVEN


PLUG DAMPER

ACTUATOR

Fig. 23 — Wiring Connections for Outdoor-Air


Thermostat

OUTDOOR AIR
TEMPERATURE
SENSOR

OPTIONAL POWER
EXHAUST 24 VAC, BAROMETRIC
3-PIN CONNECTOR RELIEF DAMPERS

Fig. 26 — 71/2 to 121/2 Ton EconoMi$er


Component Locations

3. Install the 1/8 x 3/4 in. seal strip on the exhaust air hood top
panels and the bottom bracket. Assemble the exhaust air
hood to the outdoor air opening panel as shown in
Fig. 28, using the screws provided. Do not attach hood
assembly to the unit at this time.
4. Install the 1/8 x 7/8 in. seal strip on the outdoor air hood top
and side panels. Assemble the outdoor air hood to the
outdoor air opening panel as shown in Fig. 29, using the
screws provided. Do not attach hood assembly to the unit
at this time.
Fig. 24 — Durablade Economizer Barometric 5. Slide the outdoor air inlet screens into the screen track on
Relief Damper Characteristics the hood side panels. While holding the screens in place,
fasten the screen retainer to the hood using the screws
provided. Repeat the process for the barometric exhaust
OPTIONAL ECONOMI$ER — See Fig. 25 and 26 for air screen. Do not attach completed (Fig. 30) hood
EconoMi$er component locations. assembly to unit at this time.
1. To remove the existing unit filter access panel, raise the 6. For 5 and 6 ton units, proceed to Step 7. For 71/2 and
panel and swing the bottom outward. The panel is now 121/2 ton units, install the return air block-off plate over
disengaged from the track and can be removed. Remove the return air duct opening. See Fig. 31.
the indoor coil access panel and discard. See Fig. 27. 7. Slide the EconoMi$er assembly into the rooftop unit. See
Controller should be mounted in vertical position as Fig. 32-34.
shown in Fig. 25 and 26. NOTE: Be sure to engage rear EconoMi$er flange under tabs in
2. Assemble the hood assembly as follows: return air opening of the unit base. See Fig. 32.
Remove the EconoMi$er hood from its packaging.
Locate the outdoor air opening panel. See Fig. 28.

16
8. Install the outdoor air block-off plate, then secure the
EconoMi$er with the screws provided. See Fig. 33 and
34.
9. Remove and store the 12-pin jumper plug from the unit
wiring harness located in the upper left corner and insert
the EconoMi$er plug into the unit wiring harness. Refer
to wiring diagram Fig. 35 and 36. Also refer to Fig. 37 if
installing an accessory power exhaust.
10. Install the complete hood assembly on the unit and secure
using the screws provided.
11. Remove the indoor fan motor access panel. See Fig. 38.
12. Mount the supply air temperature sensor to the lower left
portion of the indoor blower housing with the two (2)
screws provided (see Fig. 39). Connect the violet and
pink wires to the corresponding connections on the sup-
ply air temperature sensor. Replace the indoor fan motor
access panel.

OUTDOOR-AIR FILTER ACCESS


OPENING PANEL PANEL

Fig. 27 — Typical Access Panel Locations

OUTDOOR AIR
OPENING PANEL EXHAUST AIR
HOOD TOP
Fig. 30 — EconoMi$er Completed Hood Assembly
SCREEN
RETAINER

EXHAUST AIR
SEAL STRIP HOOD SIDES
BLOWER

EXHAUST AIR SCREEN RETURN AIR FILTER


EXHAUST AIR BLOCK-OFF
BOTTOM BRACKET PLATE

Fig. 28 — EconoMi$er Exhaust Air Hood Assembly

OUTDOOR AIR
BLOCK-OFF PLATE

OUTDOOR AIR SEAL STRIP ECONOMI$ER


OPENING OUTDOOR AIR
PANEL HOOD TOP Fig. 31 — Return Air Block-Off Plate Installation
(71/2 to 121/2 Ton Units Only)
SCREEN UNIT FILTER ECONOMIZER CLIP
RETAINER RACK HVAC UNIT

OUTDOOR AIR
SEAL STRIP INLET
SCREENS
ASSEMBLED ECONOMIZER
EXHAUST HOOD UNIT BASE

OUTDOOR AIR ECONOMIZER REAR


HOOD SIDES FLANGE

Fig. 29 — EconoMi$er Outdoor Air Hood Assembly Fig. 32 — Rear EconoMi$er Flange Installation

17
ECONOMI$ER BROWN
CONTROLLER TEMP
VIOLET
TEMP OUTDOOR
OAT COM AIR
WHITE SENSOR
WIRING COM OUT
HARNESS RED
OAH PWR
-15 V
BROWN
RAT TEMP
VIOLET TEMP RETURN
OUTDOOR COM
AIR WHITE COM AIR
BLOCK-OFF RAH SENSOR
RED OUT
PLATE +15 V PWR
CO2 SENSOR
CO2 (+) V+ 24
CO2 COM COM VAC
DAT
Fig. 33 — EconoMi$er Installed in COM SUPPLY AIR
5 and 6 ton Unit REM POT TEMPERATURE SENSOR
COM PINK
TEMP
LED VIOLET
TEMP
COM

WIRING HARNESS Fig. 36 — EconoMi$er Sensor Wiring

OUTDOOR AIR
BLOCK-OFF PLATE

Fig. 34 — EconoMi$er Installed in


71/2 to 121/2 Ton Unit

Fig. 35 — EconoMi$er Wiring

18
Power Exhaust System (High Voltage)
TO FUSED FAN 1 FAN 2
DISCONNECT CAPACITOR 2
CAPACITOR 1

RED GRAY RED YEL BLU GRAY RELAY 2


RELAY 1
HT01AH859

HT01AH850
H1 H2 H1 H3 H2 H4
(575 VAC)

(460 VAC)
4-PIN 3-PIN
CONNECTOR PLUG CONNECTOR PLUG
(HIGH VOLTAGE) (LOW VOLTAGE)
X4 X2 X3 X1 X4 X2 X3 X1
FIELD SUPPLIED
SECONDARY SECONDARY WIRING
230VAC 230VAC

BLACK
COMPRESSOR 1 BLACK
OR CONTACTOR LT. BLUE
11 21 3 6 9 B
230VAC
13 23 BROWN BLACK
FAN 1 R1
2 5 8 3-PIN
C1 24 VAC CONNECTOR
GREEN/ PLUG
YELLOW 1 4 7 A
4-PIN
2 x 4 IN. CONNECTOR BLUE ORANGE
HANDY BOX PLUG 1
L1 YELLOW 2
BLACK L1 1 1
BLUE L2 2 L2 BROWN
2 3
GREEN GND GND BLACK
3 3
4 4 BLACK
BLUE
230 VAC GREEN LT. BLUE
1 PHASE 3 6 9 B

BROWN BLACK R2
FAN 2 24 VAC
2 5 8
C1
GREEN/
YELLOW 1 4 7 A

BLUE

Fig. 37 — Wiring Diagram for Optional Power Exhaust System

SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION

SUPPLY AIR
TEMPERATURE
INDOOR FAN MOTOR, SENSOR
CONTROL BOX AND BLOWER AND ELECTRIC
COMPRESSOR ACCESS PANEL HEAT ACCESS PANEL
Fig. 39 — Supply Air Sensor Placement
Fig. 38 — Typical Access Panel Locations

19
CO2 Control Set Up — If a CO2 sensor is not being used, pro- % Outdoor air through EconoMi$er
ceed to the next section. If a CO2 sensor is being used, perform Mixture Temp – Return Air Temp
the following: % Outdoor air =
Outdoor Temp – Return Air Temp
1. Determine the value at which you want the minimum
position of the dampers to begin opening to allow a great- b. Divide total CFM by percentage outdoor air, this
er amount of outdoor air to enter. The range is 800 to gives outdoor air volume in CFM.
1,400 ppm. 5. Turn on base unit power.
2. Locate the CO2 SP (PPM) potentiometer and adjust to the NOTE: The EconoMi$er begins operation three min-
desired set point. See Fig. 40. utes after power up.
Mechanical Cooling Lockout — Determine the outdoor-air
temperature at which you want the mechanical cooling (com-
pressors) to be disabled. Locate the mechanical cooling lockout
(MECH CLG LOCKOUT) potentiometer. To disable this fea- Personal Injury Hazard. Avoid possible injury by keep-
ture, turn the potentiometer counterclockwise (CCW) to the ing fingers away from damper blades.
OFF position. Otherwise, set the value between 10 and 60 F.
Mechanical cooling will not operate when the outdoor air tem- 6. See Fig. 41 and 42 for barometric relief damper
perature is below this value. See Fig. 40. characteristics.
Dry Bulb Changeover Set Up — Determine the dry bulb
changeover set point from Table 5. The settings are A, B, C and
D. Locate the ECON SP potentiometer and set the dry bulb
changeover set point. See Fig. 40. When the OAT is above this
set point, the damper is limited to minimum position setting.
Table 5 — Changeover Set Points
SETTINGS A B C D
Dry Bulb (°F) 73 69 66 63
Single Enthalpy* (Btu/lb) 27 25 24 22 Fig. 40 — EconoMi$er Control Adjustment
Differential Temperature*
Potentiometers (Factory Settings)
2 2 2 2
(°F, Not Adjustable)
Differential Enthalpy* 1 1 1 1
(Btu/lb, Not Adjustable) 0.5
STATIC PRESSURE (IN. WG)

*Field-installed accessory.
0.4

If a potentiometer fails, its setting will default to the values 0.3


in Table 6.
0.2
Table 6 — Default Potentiometer Settings
0.1
POTENTIOMETER DEFAULT SETTING
CO2 SP (PPM) 1,000 0
MECH CLG LOCKOUT 47° 0 200 400 600 800 1000 1200 1400 1600
ECON SP D
FLOW (CUBIC FEET/MINUTE)
MIN POS (%) 20
Fig. 41 — EconoMi$er 5 and 6 Ton
Ventilation Air (Minimum Position Setup) — If ventilation Barometric Relief Capacity
air is not required, proceed to Step 5. If ventilation air is re-
quired, perform the following:
1. The indoor fan must be on to set the ventilation air. Either
STATIC PRESSURE (IN.WG)

0.5
put the thermostat in the continuous fan mode or jumper
the R and G terminals at the rooftop unit connection 0.4
board.
0.3
2. Locate the minimum position (MIN POS) potentiometer.
Turn the potentiometer full CCW to fully close the out- 0.2
door air dampers. Turn the potentiometer gradually
clockwise (CW) to the desired position. See Fig. 40. 0.1
3. Replace the filter access panel. See Fig. 27. Ensure the fil- 0
ter access panel slides along the tracks and is securely 0 400 800 1200 1600 2000 2400
engaged.
FLOW (CUBIC FEET/MINUTE)
4. Calculate the minimum airflow across the EconoMi$er.
Fig. 42 — EconoMi$er 71/2 to 121/2 Ton
a. Calculate % of outside air using the following Barometric Relief Capacity
formula.

20
Step 7 — Adjust Evaporator-Fan Speed — Ad-
just indoor-fan speed to meet jobsite conditions.
For units with electric heat, required minimum L/s is 700
(1500) for 50HJ006; 850 (1800) for 50HJ007; 1062 (2250) for
50HJ008; 1062 (2250) for 50HJ009; and 1416 (3000) for
50HJ012 and 014 with the following exceptions in Table 7.
Table 7 — Required Minimum Airflow
UNIT REQUIRED
UNIT UNIT HEATER
50HJ VOLTAGE kW CONFIG- MINIMUM
URATION L/s (CFM)
220 35.6 Horizontal 1510 (3200) MOTOR MOUNTING
012 PLATE NUTS
220 40.0 Horizontal 1510 (3200)
and
014 Horizontal
400 34.7 or Vertical 1510 (3200)

Table 8 shows evaporator-fan motor data. Tables 9 and 10


show fan speed at motor pulley settings for standard motors. Fig. 43 — Typical Belt-Drive Motor Mounting
Refer to Tables 11-30 to determine fan speed settings. Fan mo- For Sizes 006-009
tor pulleys are factory set for speed shown in Tables 1A and
1B.
To change fan speeds:
1. Shut off unit power supply and tag disconnect.
2. Loosen belt by loosening fan motor mounting nuts. See
Fig. 43 and 44.
3. Loosen movable pulley flange setscrew (see Fig. 45).
4. Screw movable flange toward fixed flange to increase
speed or away from fixed flange to decrease speed. In-
creasing fan speed increases load on motor. Do not ex-
ceed maximum speed specified in Tables 1A and 1B.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See Tables 1A and 1B for speed change
for each full turn of pulley flange.)
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from Fig. 44 — Typical Belt-Drive Motor Mounting
mounting plate. For Sizes 012, 014
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Sizes 006-009 — Slide motor mounting plate away from
fan scroll for proper belt tension (13-mm [1/2-in. deflec-
tion with 3.6 to 4.5 mg (8 to 10 lbs) force and tighten
mounting nuts (see Fig. 43).
Size 012, 014 — Slide motor mounting plate downward
to tighten belt tension to 1/2-in. deflection with 2.27 to
4.5 mg (5 to 10 lbs) of force. Secure motor mounting
plate nuts. See Fig. 44.
3. Adjust bolt and nut on mounting plate to secure motor in
fixed position.

Fig. 45 — Evaporator-Fan Pulley Adjustment

21
Table 8 — Evaporator Fan Motor Data
UNIT MAXIMUM CONTINUOUS
50HJ BHP* MAXIMUM OPERATING WATTS UNIT VOLTAGE MAXIMUM AMP DRAW
006 2.4 2120 400 3.0
007 2.4 2120 400 3.0
220 8.6
008 2.9 2615
400 3.9
220 8.6
009 2.9 2615
400 3.9
220 12.2
012 3.7 3775
400 5.5
220 12.2
014 3.7 3775
400 5.5

LEGEND *Extensive motor and electrical testing on these units ensures that
BHP — Brake Horsepower the full horsepower range of the motors can be used with confi-
dence. Using the fan motors up to the horsepower ratings shown in
this table will not result in nuisance breaker tripping or premature
motor failure. Unit warranty will not be affected.

Table 9 — Fan R/s at Fan Pulley Settings (SI)


UNIT MOTOR PULLEY TURNS OPEN
50HJ 0 1/
2 1 11 / 2 2 21/2 3 31 / 2 4 41 / 2 5
006 20.3 19.7 19.1 18.4 17.8 17.2 16.6 16.0 15.3 14.7 14.1
007 21.8 21.2 20.5 19.9 19.2 18.6 18.0 17.3 16.6 16.0 15.3
008,009 14.8 14.5 14.2 13.8 13.5 13.2 12.8 12.5 12.2 11.8 11.5
012,014 14.8 14.5 14.2 13.9 13.6 13.3 13.0 12.7 12.4 12.1 11.8

Table 10 — Fan Rpm at Fan Pulley Settings (English)


UNIT MOTOR PULLEY TURNS OPEN
50HJ 0 1/
2 1 11 / 2 2 21/2 3 31 / 2 4 41 / 2 5
006,007 1310 1271 1232 1193 1154 1115 1076 1037 998 959 920
008,009 890 870 850 830 810 790 770 750 730 710 690
012,014 890 872 854 836 818 800 782 764 746 728 710

Table 11 — Fan Performance 50HJ006 — Horizontal Discharge Units (SI)


EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
(L/s) 25 50 100 150 200 250 300 350 400
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
650 10.3 0.19 11.5 0.22 13.5 0.30 15.2 0.39 16.6 0.49 18.0 0.59 18.3 0.72 18.5 0.75 19.2 0.79
700 11.0 0.22 12.1 0.25 14.0 0.34 15.6 0.44 17.0 0.54 18.4 0.65 19.0 0.78 19.8 0.86 20.2 0.90
750 11.6 0.26 12.7 0.29 14.5 0.39 16.0 0.49 17.4 0.60 18.8 0.72 20.1 0.84 21.1 0.97 21.2 1.06
800 12.3 0.30 13.3 0.35 15.0 0.44 16.5 0.56 17.9 0.66 19.2 0.78 20.4 0.91 21.6 1.05 22.6 1.19
850 12.9 0.35 14.0 0.43 15.6 0.53 17.2 0.65 18.6 0.78 19.7 0.87 20.9 0.94 22.2 0.99 23.2 1.14
900 13.5 0.40 14.6 0.48 16.1 0.60 17.6 0.72 18.8 0.81 20.0 0.88 21.2 1.02 22.4 1.07 23.5 1.19
950 14.2 0.47 15.2 0.55 16.6 0.66 18.0 0.80 19.1 0.83 20.4 0.96 21.6 1.10 22.7 1.14 23.8 1.24
1000 14.8 0.54 15.8 0.62 17.2 0.75 18.5 0.88 19.5 0.89 20.8 1.05 21.9 1.11 23.0 1.25 24.1 1.29
1050 15.4 0.61 16.3 0.69 17.8 0.84 18.9 0.92 20.0 1.00 21.3 1.07 22.3 1.19 23.4 1.34 24.4 1.33
1100 16.0 0.69 16.9 0.77 18.4 0.92 19.3 0.95 20.5 1.09 21.7 1.15 22.7 1.31 23.8 1.45 24.8 1.44
1150 16.7 0.78 17.4 0.85 18.8 0.97 19.8 1.04 21.0 1.19 22.0 1.23 23.2 1.41 24.2 1.50 25.1 1.57
1200 17.3 0.87 18.0 0.95 19.3 1.01 20.3 1.16 21.5 1.22 22.5 1.33 23.5 1.51 24.7 1.55 25.6 1.70
LEGEND fan motors up to the BkW ratings shown will not result in nui-
BkW — Motor Brake (Output) Power (kW) sance tripping or premature motor failure. Unit warranty will not
r/s — Fan Wheel Speed, Revolutions per Second be affected.
3. Values include losses for filters, unit casing, and wet coils.
NOTES: 4. Use of a field-supplied motor may affect wire sizing. Contact
1. Boldface indicates field-supplied drive required. (See Note 5.) Carrier representative to verify.
2. Maximum usable output power (BkW) is 1.80. Extensive motor 5. Motor drive range: 15.3 to 21.8 r/s. All other speeds require
and electrical testing on these units ensures that the full BkW field-supplied drive.
range of the motor can be utilized with confidence. Using the

22
Table 12 — Fan Performance 50HJ007 — Horizontal Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
25 50 100 150 200 250 300 350 400
(L/s)
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
700 11.0 0.22 12.1 0.25 14.0 0.34 15.6 0.44 17.0 0.54 18.4 0.65 19.0 0.78 19.8 0.86 20.2 0.90
750 11.6 0.26 12.7 0.29 14.5 0.39 16.0 0.49 17.4 0.60 18.8 0.72 20.1 0.84 21.1 0.97 21.2 1.06
800 12.3 0.30 13.3 0.35 15.0 0.44 16.5 0.56 17.9 0.66 19.2 0.78 20.4 0.91 21.6 1.05 22.6 1.19
850 12.9 0.35 14.0 0.43 15.6 0.53 17.2 0.65 18.6 0.78 19.7 0.87 20.9 0.94 22.2 0.99 23.2 1.14
900 13.5 0.40 14.6 0.48 16.1 0.60 17.6 0.72 18.8 0.81 20.0 0.88 21.2 1.02 22.4 1.07 23.5 1.19
950 14.2 0.47 15.2 0.55 16.6 0.66 18.0 0.80 19.1 0.83 20.4 0.96 21.6 1.10 22.7 1.14 23.8 1.24
1000 14.8 0.54 15.8 0.62 17.2 0.75 18.5 0.88 19.5 0.89 20.8 1.05 21.9 1.11 23.0 1.25 24.1 1.29
1050 15.4 0.61 16.3 0.69 17.8 0.84 18.9 0.92 20.0 1.00 21.3 1.07 22.3 1.19 23.4 1.34 24.4 1.33
1100 16.0 0.69 16.9 0.77 18.4 0.92 19.3 0.95 20.5 1.09 21.7 1.15 22.7 1.31 23.8 1.45 24.8 1.44
1150 16.7 0.78 17.4 0.85 18.8 0.97 19.8 1.04 21.0 1.19 22.0 1.23 23.2 1.41 24.2 1.50 25.1 1.57
1200 17.3 0.87 18.0 0.95 19.3 1.01 20.3 1.16 21.5 1.22 22.5 1.33 23.5 1.51 24.7 1.55 25.6 1.70
1250 17.9 0.98 18.6 1.05 19.9 1.12 20.9 1.27 22.0 1.33 23.0 1.48 24.1 1.58 25.1 1.66 26.0 1.83
1300 18.6 1.09 19.2 1.12 20.4 1.24 21.3 1.33 22.6 1.45 23.4 1.60 24.6 1.65 25.6 1.83 26.5 1.95
1350 19.0 1.13 19.7 1.19 21.0 1.36 21.8 1.45 22.9 1.58 24.1 1.78 25.1 1.79 26.0 1.96 26.9 2.10
1400 19.3 1.16 20.2 1.31 21.2 1.45 22.3 1.51 23.5 1.72 24.8 1.81 25.4 1.93 26.5 2.10 — —
1450 19.9 1.27 20.6 1.44 21.3 1.54 22.9 1.66 24.0 1.86 25.3 1.95 25.8 2.07 — — — —
LEGEND range of the motor can be utilized with confidence. Using the
BkW — Motor Brake (Output) Power (kW) fan motors up to the BkW ratings shown will not result in nui-
r/s — Fan Wheel Speed, Revolutions per Second sance tripping or premature motor failure. Unit warranty will not
be affected.
NOTES: 4. Values include losses for filters, unit casing, and wet coils.
1. Boldface indicates field-supplied drive required. (See Note 5.) 5. Motor drive range: 15.3 to 21.8 r/s. All other speeds require
field-supplied drive.
2. indicates field-supplied motor and drive required.
6. Use of a field-supplied motor may affect wire sizing. Contact
3. Maximum usable output power (BkW) is 1.80. Extensive motor Carrier representative to verify.
and electrical testing on these units ensures that the full BkW

Table 13 — Fan Performance 50HJ008,009 — Horizontal Discharge Units (SI)


EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW 25 50 100 150 200 250 300 350 400 500
(L/s)
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
850 6.9 0.18 8.4 0.28 9.6 0.43 11.0 0.60 12.0 0.73 12.9 0.98 13.4 1.16 13.4 1.37 12.9 1.57 11.5 1.75
900 7.1 0.21 8.6 0.32 9.8 0.48 11.1 0.65 12.1 0.79 13.0 1.03 13.6 1.22 13.7 1.43 13.3 1.64 12.2 1.83
1000 7.5 0.28 9.0 0.41 10.2 0.58 11.4 0.75 12.4 0.91 13.3 1.14 14.0 1.34 14.3 1.56 14.2 1.78 13.6 1.99
1100 7.9 0.35 9.4 0.50 10.6 0.68 11.7 0.85 12.7 1.03 13.6 1.25 14.4 1.46 14.9 1.69 15.1 1.92 15.0 2.15
1200 8.3 0.42 9.8 0.59 11.0 0.78 12.0 0.95 13.0 1.15 13.9 1.36 14.8 1.58 15.5 1.82 16.0 2.06 16.4 2.31
1300 8.8 0.51 10.2 0.69 11.3 0.88 12.4 1.08 13.3 1.28 14.2 1.49 15.0 1.72 15.8 1.96 16.5 2.21 17.1 2.47
1400 9.2 0.60 10.6 0.80 11.7 0.99 12.7 1.22 13.7 1.42 14.5 1.63 15.3 1.87 16.1 2.12 16.9 2.38 — —
1500 9.7 0.71 11.0 0.91 12.1 1.12 13.0 1.35 14.0 1.59 14.8 1.81 15.6 2.04 16.4 2.30 — — — —
1600 10.1 0.82 11.3 1.04 12.5 1.28 13.4 1.49 14.3 1.75 15.2 2.00 15.9 2.24 — — — — — —
1700 10.6 0.93 11.8 1.20 12.9 1.44 13.8 1.67 14.7 1.92 15.5 2.20 — — — — — — — —
LEGEND range of the motor can be utilized with confidence. Using the
BkW — Motor Brake (Output) Power (kW) fan motors up to the BkW ratings shown will not result in nui-
r/s — Fan Wheel Speed, Revolutions per Second sance tripping or premature motor failure. Unit warranty will not
be affected.
NOTES: 4. Use of a field-supplied motor may affect wire sizing. Contact
1. Boldface indicates field-supplied drive required. (See Note 6.) Carrier representative to verify.
2. indicates field-supplied motor and drive required. 5. Values include losses for filters, unit casing, and wet coils.
6. Motor drive range: 11.5 to 14.8 r/s. All other speeds require
3. Maximum usable output power (BkW) is 2.2. Extensive motor field-supplied drive.
and electrical testing on these units ensures that the full BkW

23
Table 14 — Fan Performance 50HJ012 — Horizontal Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
50 100 150 200 250 300 350 400 450 500
(L/s)
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
1200 — — 9.2 0.38 10.2 0.45 11.2 0.61 12.1 0.72 13.2 0.87 13.8 1.12 14.3 0.99 14.7 0.93 15.3 0.91
1250 — — 9.3 0.42 10.4 0.50 11.4 0.65 12.3 0.77 13.3 0.92 13.9 1.16 14.6 1.09 15.0 1.01 15.5 1.02
1300 6.9 0.06 9.5 0.46 10.5 0.55 11.6 0.69 12.5 0.81 13.4 0.96 14.1 1.19 14.8 1.18 15.2 1.08 15.7 1.12
1350 7.2 0.15 9.7 0.50 10.7 0.59 11.7 0.73 12.6 0.86 13.5 1.01 14.3 1.22 15.0 1.28 15.5 1.16 15.8 1.22
1400 7.5 0.23 9.9 0.54 10.9 0.64 11.9 0.77 12.8 0.91 13.7 1.06 14.5 1.25 15.2 1.37 15.8 1.24 16.0 1.32
1450 7.9 0.32 10.0 0.58 11.1 0.69 12.0 0.81 12.9 0.96 13.8 1.11 14.7 1.28 15.5 1.47 16.0 1.32 16.1 1.43
1500 8.3 0.41 10.2 0.62 11.3 0.74 12.2 0.86 13.1 1.00 13.9 1.15 14.8 1.32 15.7 1.53 16.3 1.41 16.4 1.52
1550 8.6 0.46 10.4 0.67 11.5 0.80 12.4 0.91 13.2 1.06 14.1 1.21 14.9 1.37 15.8 1.56 16.4 1.51 16.6 1.63
1600 8.9 0.51 10.6 0.72 11.7 0.86 12.5 0.96 13.4 1.11 14.2 1.27 15.0 1.43 15.8 1.61 16.6 1.61 16.8 1.72
1650 9.3 0.57 10.8 0.77 11.9 0.92 12.7 1.03 13.6 1.17 14.4 1.33 15.1 1.50 16.0 1.67 16.7 1.73 17.0 1.84
1700 9.9 0.64 11.0 0.82 12.0 0.97 12.9 1.10 13.7 1.23 14.5 1.39 15.3 1.56 16.1 1.73 16.8 1.84 17.3 1.93
1750 10.1 0.72 11.2 0.88 12.2 1.02 13.0 1.16 13.9 1.29 14.7 1.45 15.5 1.62 16.2 1.77 16.9 1.92 17.4 2.04
1800 10.4 0.78 11.4 0.93 12.4 1.08 13.3 1.24 14.0 1.36 14.8 1.51 15.6 1.69 16.3 1.85 17.0 2.01 17.6 2.14
1850 10.6 0.84 11.6 0.98 12.5 1.14 13.5 1.31 14.2 1.43 15.0 1.58 15.7 1.76 16.5 1.93 17.2 2.10 17.8 2.24
1900 10.8 0.90 11.8 1.04 12.7 1.20 13.7 1.39 14.4 1.51 15.1 1.65 15.8 1.83 16.6 2.01 17.3 2.18 18.0 2.34
1950 11.1 0.97 12.0 1.10 12.9 1.28 13.8 1.46 14.5 1.59 15.3 1.73 16.0 1.90 16.7 2.10 17.4 2.27 18.1 2.44
2000 11.3 1.04 12.1 1.17 13.1 1.35 14.0 1.53 14.7 1.68 15.4 1.82 16.2 1.98 16.8 2.18 17.5 2.36 18.2 2.54
2050 11.6 1.11 12.3 1.24 13.2 1.42 14.1 1.60 14.9 1.77 15.6 1.91 16.3 2.07 17.0 2.26 17.6 2.45 18.3 2.63
2100 11.9 1.19 12.5 1.30 13.4 1.51 14.3 1.67 15.1 1.87 15.8 2.00 16.5 2.16 17.1 2.34 17.8 2.54 18.4 2.74
2150 12.0 1.27 12.7 1.38 13.6 1.58 14.5 1.75 15.3 1.96 15.9 2.10 16.6 2.25 17.3 2.42 17.9 2.64 18.6 2.84
2200 12.4 1.36 12.9 1.46 13.8 1.66 14.6 1.83 15.5 2.05 16.1 2.21 16.8 2.36 17.4 2.52 18.1 2.73 18.7 2.95
2250 12.6 1.45 13.1 1.54 14.0 1.74 14.8 1.93 15.6 2.14 16.3 2.32 16.9 2.46 17.6 2.62 18.2 2.83 18.8 3.05
2300 12.9 1.54 13.3 1.63 14.2 1.83 15.0 2.03 15.8 2.22 16.5 2.43 17.1 2.57 17.7 2.74 18.4 2.92 19.0 3.15
2350 13.2 1.63 13.5 1.72 14.4 1.92 15.2 2.13 16.0 2.32 16.7 2.54 17.3 2.69 17.9 2.86 18.5 3.03 19.1 3.25
2400 13.4 1.73 13.8 1.81 14.6 2.01 15.4 2.23 16.1 2.42 16.9 2.65 17.5 2.83 18.1 2.98 18.7 3.15 19.3 3.36
2450 13.7 1.84 14.0 1.92 14.8 2.11 15.5 2.33 16.3 2.52 17.1 2.77 17.7 2.95 18.2 3.11 18.8 3.28 19.4 3.47
LEGEND 4. Use of a field-supplied motor may affect wire sizing. Contact
BkW — Motor Brake (Output) Power (kW) Carrier representative to verify.
r/s — Fan Wheel Speed, Revolutions per Second 5. Maximum usable output power (BkW) is 2.8. Extensive motor
and electrical testing on these units ensures that the full BkW
NOTES: range of the motor can be utilized with confidence. Using the
1. Boldface indicates field-supplied drive required. (See Note 6.) fan motors up to the BkW ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not
2. indicates field-supplied motor and drive required. be affected.
3. Values include losses for filters, unit casing, and wet coils. 6. Motor drive range: 11.8 to 14.8 r/s. All other speeds require
field-supplied drive.

24
Table 15 — Fan Performance 50HJ014 — Horizontal Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
50 100 150 200 250 300 350 400 450 500
(L/s)
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
1400 7.5 0.23 9.9 0.54 10.9 0.64 11.9 0.77 12.8 0.91 13.7 1.06 14.5 1.25 15.2 1.37 15.8 1.24 16.0 1.32
1450 7.9 0.32 10.0 0.58 11.1 0.69 12.0 0.81 12.9 0.96 13.8 1.11 14.7 1.28 15.5 1.47 16.0 1.32 16.1 1.43
1500 8.3 0.41 10.2 0.62 11.3 0.74 12.2 0.86 13.1 1.00 13.9 1.15 14.8 1.32 15.7 1.53 16.3 1.41 16.4 1.52
1550 8.6 0.46 10.4 0.67 11.5 0.80 12.4 0.91 13.2 1.06 14.1 1.21 14.9 1.37 15.8 1.56 16.4 1.51 16.6 1.63
1600 8.9 0.51 10.6 0.72 11.7 0.86 12.5 0.96 13.4 1.11 14.2 1.27 15.0 1.43 15.8 1.61 16.6 1.61 16.8 1.72
1650 9.3 0.57 10.8 0.77 11.9 0.92 12.7 1.03 13.6 1.17 14.4 1.33 15.1 1.50 16.0 1.67 16.7 1.73 17.0 1.84
1700 9.9 0.64 11.0 0.82 12.0 0.97 12.9 1.10 13.7 1.23 14.5 1.39 15.3 1.56 16.1 1.73 16.8 1.84 17.3 1.93
1750 10.1 0.72 11.2 0.88 12.2 1.02 13.0 1.16 13.9 1.29 14.7 1.45 15.5 1.62 16.2 1.77 16.9 1.92 17.4 2.04
1800 10.4 0.78 11.4 0.93 12.4 1.08 13.3 1.24 14.0 1.36 14.8 1.51 15.6 1.69 16.3 1.85 17.0 2.01 17.6 2.14
1850 10.6 0.84 11.6 0.98 12.5 1.14 13.5 1.31 14.2 1.43 15.0 1.58 15.7 1.76 16.5 1.93 17.2 2.10 17.8 2.24
1900 10.8 0.90 11.8 1.04 12.7 1.20 13.7 1.39 14.4 1.51 15.1 1.65 15.8 1.83 16.6 2.01 17.3 2.18 18.0 2.34
1950 11.1 0.97 12.0 1.10 12.9 1.28 13.8 1.46 14.5 1.59 15.3 1.73 16.0 1.90 16.7 2.10 17.4 2.27 18.1 2.44
2000 11.3 1.04 12.1 1.17 13.1 1.35 14.0 1.53 14.7 1.68 15.4 1.82 16.2 1.98 16.8 2.18 17.5 2.36 18.2 2.54
2050 11.6 1.11 12.3 1.24 13.2 1.42 14.1 1.60 14.9 1.77 15.6 1.91 16.3 2.07 17.0 2.26 17.6 2.45 18.3 2.63
2100 11.9 1.19 12.5 1.30 13.4 1.51 14.3 1.67 15.1 1.87 15.8 2.00 16.5 2.16 17.1 2.34 17.8 2.54 18.4 2.74
2150 12.0 1.27 12.7 1.38 13.6 1.58 14.5 1.75 15.3 1.96 15.9 2.10 16.6 2.25 17.3 2.42 17.9 2.64 18.6 2.84
2200 12.4 1.36 12.9 1.46 13.8 1.66 14.6 1.83 15.5 2.05 16.1 2.21 16.8 2.36 17.4 2.52 18.1 2.73 18.7 2.95
2250 12.6 1.45 13.1 1.54 14.0 1.74 14.8 1.93 15.6 2.14 16.3 2.32 16.9 2.46 17.6 2.62 18.2 2.83 18.8 3.05
2300 12.9 1.54 13.3 1.63 14.2 1.83 15.0 2.03 15.8 2.22 16.5 2.43 17.1 2.57 17.7 2.74 18.4 2.92 19.0 3.15
2350 13.2 1.63 13.5 1.72 14.4 1.92 15.2 2.13 16.0 2.32 16.7 2.54 17.3 2.69 17.9 2.86 18.5 3.03 19.1 3.25
2400 13.4 1.73 13.8 1.81 14.6 2.01 15.4 2.23 16.1 2.42 16.9 2.65 17.5 2.83 18.1 2.98 18.7 3.15 19.3 3.36
2450 13.7 1.84 14.0 1.92 14.8 2.11 15.5 2.33 16.3 2.52 17.1 2.77 17.7 2.95 18.2 3.11 18.8 3.28 19.4 3.47
2500 14.0 1.95 14.2 2.02 15.0 2.21 15.7 2.45 16.5 2.63 17.2 2.86 17.9 3.09 18.4 3.24 19.0 3.42 19.6 3.59
2550 14.2 2.06 14.5 2.13 15.2 2.30 15.9 2.55 16.6 2.75 17.4 2.97 18.1 3.21 18.6 3.38 19.1 3.55 19.7 3.74
2600 14.5 2.18 14.7 2.24 15.3 2.42 16.1 2.66 16.8 2.88 17.5 3.09 18.3 3.35 18.8 3.53 19.3 3.69 19.9 3.88
2650 14.8 2.30 15.0 2.36 15.5 2.52 16.3 2.77 17.2 3.01 17.7 3.01 18.4 3.47 19.0 3.68 19.5 3.84 20.0 4.03
2700 15.0 2.43 15.2 2.48 15.7 2.64 16.5 2.89 17.2 3.13 17.9 3.33 18.6 3.59 19.2 3.83 19.7 4.00 20.2 4.18
2750 15.3 2.57 15.4 2.61 15.9 2.76 16.7 3.01 17.4 3.19 18.0 3.46 18.7 3.71 19.4 3.98 19.9 4.17 — —
2800 15.6 2.70 15.7 2.74 16.1 2.89 16.9 3.13 17.6 3.40 18.2 3.61 20.5 3.84 19.6 4.13 — — — —
2850 15.8 2.84 15.9 2.89 16.4 3.02 17.1 3.26 17.8 3.53 18.4 3.76 19.0 3.98 19.7 4.27 — — — —
2900 16.1 2.99 16.2 3.03 16.6 3.15 17.3 3.39 17.9 3.67 18.6 3.91 19.2 4.12 — — — — — —
2950 16.4 3.14 16.5 3.18 16.8 3.30 17.5 3.53 18.1 3.80 18.8 4.06 19.4 4.27 — — — — — —
3000 16.6 3.30 16.7 3.33 17.0 3.45 17.6 3.66 18.3 3.94 18.9 4.22 — — — — — — — —
3050 16.9 3.46 17.0 3.49 17.3 3.60 17.8 3.81 18.5 4.09 — — — — — — — — — —
LEGEND 4. Use of a field-supplied motor may affect wire sizing. Contact
BkW — Motor Brake (Output) Power (kW) Carrier representative to verify.
r/s — Fan Wheel Speed, Revolutions per Second 5. Maximum usable output power (BkW) is 2.8. Extensive motor
and electrical testing on these units ensures that the full BkW
NOTES: range of the motor can be utilized with confidence. Using the
1. Boldface indicates field-supplied drive required. (See Note 6.) fan motors up to the BkW ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not
2. indicates field-supplied motor and drive required. be affected.
3. Values include losses for filters, unit casing, and wet coils. 6. Motor drive range: 11.8 to 14.8 r/s. All other speeds require
field-supplied drive.

Table 16 — Fan Performance 50HJ006 — Vertical Discharge Units (SI)


EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
25 50 100 150 200 250 300 350 400
(L/s)
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
650 11.0 0.19 12.0 0.23 14.1 0.31 15.5 0.40 16.7 0.49 18.3 0.64 19.9 0.75 20.6 1.02 20.9 1.02
700 11.7 0.24 12.7 0.28 14.6 0.37 16.1 0.47 17.4 0.57 18.8 0.70 20.2 0.82 21.2 1.03 22.0 1.10
750 12.4 0.29 13.4 0.33 15.1 0.43 16.7 0.54 18.1 0.65 19.3 0.76 20.5 0.89 21.8 1.04 23.1 1.18
800 13.2 0.34 14.1 0.39 15.7 0.49 17.1 0.59 18.5 0.71 19.7 0.83 20.9 0.97 22.0 1.11 23.4 1.26
850 15.1 0.48 16.1 0.57 18.0 0.77 19.4 0.84 20.8 0.90 22.1 0.97 23.0 1.08 23.8 1.16 25.3 1.28
900 15.8 0.57 17.5 0.75 18.7 0.82 19.8 0.89 21.0 0.97 22.2 1.05 23.5 1.19 24.7 1.28 25.9 1.35
950 16.6 0.66 17.8 0.80 19.3 0.87 20.2 0.94 21.3 0.99 23.1 1.16 24.4 1.31 25.4 1.38 26.2 1.44
1000 17.3 0.75 18.1 0.84 20.0 0.96 21.3 1.07 22.8 1.21 24.0 1.27 25.2 1.43 25.8 1.45 26.7 1.57
1050 18.1 0.86 19.6 0.96 21.0 1.08 22.4 1.19 23.2 1.30 24.6 1.39 25.6 1.51 26.4 1.60 27.3 1.71
1100 19.6 0.99 19.9 1.01 21.3 1.12 22.5 1.26 23.6 1.40 25.1 1.50 25.9 1.59 27.0 1.73 28.0 1.86
1150 19.9 1.04 20.2 1.04 21.5 1.16 23.2 1.40 24.2 1.49 25.8 1.66 26.6 1.76 27.5 1.87 — —
1200 20.2 1.08 21.4 1.18 23.8 1.32 23.9 1.54 24.7 1.58 26.3 1.79 27.4 1.95 28.1 2.03 — —
LEGEND range of the motor can be utilized with confidence. Using the
BkW — Motor Brake (Output) Power (kW) fan motors up to the BkW ratings shown will not result in nui-
r/s — Fan Wheel Speed, Revolutions per Second sance tripping or premature motor failure. Unit warranty will not
be affected.
NOTES: 4. Values include losses for filters, unit casing, and wet coils.
1. Boldface indicates field-supplied drive required. (See Note 5.) 5. Use of a field-supplied motor may affect wire sizing. Contact
2. indicates field-supplied motor and drive required. Carrier representative to verify.
6. Motor drive range: 15.3 to 21.8 r/s. All other speeds require
3. Maximum usable output power (BkW) is 1.80. Extensive motor field-supplied drive.
and electrical testing on these units ensures that the full BkW

25
Table 17 — Fan Performance 50HJ007 — Vertical Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
25 50 100 150 200 250 300 350 400
(L/s)
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
700 11.7 0.24 12.7 0.28 14.6 0.37 16.1 0.47 17.4 0.57 18.8 0.70 20.2 0.82 21.2 1.03 22.0 1.10
750 12.4 0.29 13.4 0.33 15.1 0.43 16.7 0.54 18.1 0.65 19.3 0.76 20.5 0.89 21.8 1.04 23.1 1.18
800 13.2 0.34 14.1 0.39 15.7 0.49 17.1 0.59 18.5 0.71 19.7 0.83 20.9 0.97 22.0 1.11 23.4 1.26
850 15.1 0.48 16.1 0.57 18.0 0.77 19.4 0.84 20.8 0.90 22.1 0.97 23.0 1.08 23.8 1.16 25.3 1.28
900 15.8 0.57 17.5 0.75 18.7 0.82 19.8 0.89 21.0 0.97 22.2 1.05 23.5 1.29 24.7 1.28 25.9 1.35
950 16.6 0.66 17.8 0.80 19.3 0.87 20.2 0.94 21.3 0.99 23.1 1.16 24.4 1.31 25.4 1.38 26.2 1.44
1000 17.3 0.75 18.1 0.84 20.0 0.96 21.3 1.07 22.8 1.21 24.0 1.27 25.2 1.43 25.8 1.45 26.7 1.57
1050 18.1 0.86 19.6 0.96 21.0 1.08 22.4 1.19 23.2 1.30 24.6 1.39 25.6 1.51 26.4 1.60 27.3 1.71
1100 19.6 0.99 19.9 1.01 21.3 1.12 22.5 1.26 23.6 1.40 25.1 1.50 25.9 1.59 27.0 1.73 28.0 1.86
1150 19.9 1.04 20.2 1.04 21.5 1.16 23.2 1.40 24.2 1.49 25.8 1.66 26.6 1.76 27.5 1.87 — —
1200 20.2 1.08 21.4 1.18 23.8 1.32 23.9 1.54 24.7 1.58 26.3 1.79 27.4 1.95 28.1 2.03 — —
1250 21.4 1.21 22.0 1.30 23.8 1.60 24.9 1.66 25.7 1.75 26.7 1.90 28.1 2.13 — — — —
1300 22.0 1.33 22.6 1.42 24.3 1.66 25.4 1.78 26.5 1.93 27.2 2.04 — — — — — —
1350 22.7 1.46 23.7 1.60 24.7 1.72 25.9 1.89 27.2 2.12 27.9 2.23 — — — — — —
1400 23.9 1.71 24.3 1.75 25.3 1.89 26.3 2.01 — — — — — — — — — —
1450 24.0 1.67 24.9 1.84 26.1 2.07 — — — — — — — — — — — —
LEGEND range of the motor can be utilized with confidence. Using the
BkW — Motor Brake (Output) Power (kW) fan motors up to the BkW ratings shown will not result in nui-
r/s — Fan Wheel Speed, Revolutions per Second sance tripping or premature motor failure. Unit warranty will not
be affected.
NOTES: 4. Values include losses for filters, unit casing, and wet coils.
1. Boldface indicates field-supplied drive required. (See Note 5.) 5. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
2. indicates field-supplied motor and drive required.
6. Motor drive range: 15.3 to 21.8 r/s. All other speeds require
3. Maximum usable output power (BkW) is 1.80. Extensive motor field-supplied drive.
and electrical testing on these units ensures that the full BkW

Table 18 — Fan Performance 50HJ008,009 — Vertical Discharge Units (SI)


EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW 50 100 150 200 250 300 350 400 450 500
(L/s)
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
850 7.2 0.17 9.1 0.34 9.9 0.45 11.2 0.63 12.1 0.77 13.3 0.90 14.1 1.14 15.2 1.50 15.7 1.72 16.7 2.13
900 7.5 0.22 9.3 0.39 10.1 0.51 11.4 0.69 12.3 0.84 13.4 0.98 14.2 1.21 15.3 1.55 15.8 1.78 16.8 2.17
1000 8.1 0.32 9.7 0.49 10.6 0.63 11.8 0.81 12.7 0.98 13.7 1.14 14.5 1.36 15.5 1.66 16.1 1.90 17.0 2.26
1100 8.7 0.42 10.1 0.59 11.1 0.75 12.2 0.93 13.1 1.12 14.0 1.30 14.8 1.51 15.7 1.77 16.4 2.02 17.2 2.35
1200 9.3 0.52 10.5 0.69 11.6 0.87 12.6 1.05 13.5 1.26 14.3 1.46 15.1 1.66 15.9 1.88 16.7 2.14 17.4 2.44
1300 9.8 0.64 11.0 0.81 12.1 1.01 13.0 1.20 13.9 1.41 14.7 1.63 15.5 1.84 16.2 1.98 16.9 2.29 17.6 2.56
1400 10.4 0.77 11.5 0.94 12.6 1.16 13.5 1.37 14.3 1.58 15.1 1.80 15.9 2.04 16.6 2.27 17.3 2.51 — —
1500 11.0 0.92 12.0 1.10 13.0 1.33 13.9 1.56 14.7 1.78 15.5 2.00 16.3 2.25 17.0 2.50 — — — —
1600 11.6 1.08 12.6 1.28 13.5 1.50 14.4 1.76 15.2 2.00 16.0 2.23 16.7 2.47 — — — — — —
1700 12.2 1.26 13.1 1.48 14.0 1.70 14.9 1.97 15.7 2.23 16.4 2.48 — — — — — — — —
LEGEND range of the motor can be utilized with confidence. Using the
BkW — Motor Brake (Output) Power (kW) fan motors up to the BkW ratings shown will not result in nui-
r/s — Fan Wheel Speed, Revolutions per Second sance tripping or premature motor failure. Unit warranty will not
be affected.
NOTES: 4. Use of a field-supplied motor may affect wire sizing. Contact
1. Boldface indicates field-supplied drive required. (See Note 6.) Carrier representative to verify.
2. indicates field-supplied motor and drive required. 5. Values include losses for filters, unit casing, and wet coils.
6. Motor drive range: 11.5 to 14.8 r/s. All other speeds require
3. Maximum usable output power (BkW) is 2.2. Extensive motor field-supplied drive.
and electrical testing on these units ensures that the full BkW

26
Table 19 — Fan Performance 50HJ012 — Vertical Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
50 100 150 200 250 300 350 400 450 500
(L/s)
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
1200 6.2 0.00 9.5 0.46 10.7 0.51 11.5 0.62 12.4 0.76 13.2 0.91 14.3 1.12 15.4 0.99 15.9 0.95 15.6 1.05
1250 6.5 0.05 9.7 0.50 10.9 0.57 11.6 0.66 12.6 0.81 13.3 0.96 14.4 1.16 15.5 1.09 16.1 1.06 15.8 1.14
1300 6.9 0.14 9.9 0.54 11.1 0.63 11.8 0.71 12.7 0.86 13.5 1.01 14.5 1.20 15.6 1.18 16.2 1.17 16.1 1.23
1350 7.2 0.23 10.1 0.58 11.3 0.68 12.0 0.76 12.9 0.91 13.6 1.06 14.6 1.24 15.6 1.28 16.3 1.28 16.3 1.33
1400 7.5 0.32 10.4 0.62 11.5 0.74 12.2 0.81 13.1 0.95 13.8 1.10 14.7 1.28 15.7 1.37 16.4 1.39 16.5 1.42
1450 7.9 0.40 10.6 0.66 11.6 0.79 12.4 0.85 13.2 1.00 13.9 1.15 14.8 1.32 15.8 1.47 16.6 1.50 16.7 1.52
1500 8.3 0.45 10.7 0.71 11.8 0.85 12.5 0.91 13.4 1.06 14.1 1.20 15.0 1.37 15.8 1.53 16.6 1.60 17.0 1.62
1550 8.6 0.51 10.9 0.76 12.0 0.91 12.7 0.96 13.5 1.11 14.2 1.27 15.1 1.43 16.0 1.56 16.7 1.72 17.2 1.74
1600 8.9 0.57 11.1 0.82 12.2 0.96 12.9 1.02 13.7 1.17 14.4 1.32 15.2 1.49 16.1 1.61 16.8 1.83 17.4 1.83
1650 9.3 0.64 11.3 0.87 12.3 1.02 13.1 1.09 13.9 1.23 14.5 1.38 15.4 1.56 16.2 1.67 16.9 1.87 17.6 1.93
1700 9.9 0.73 11.5 0.93 12.5 1.08 13.3 1.17 14.0 1.28 14.7 1.46 15.6 1.63 16.4 1.73 17.1 1.93 17.6 2.02
1750 10.9 0.84 11.9 0.98 12.8 1.12 13.6 1.25 14.4 1.38 15.1 1.55 15.8 1.69 16.5 1.84 17.2 1.98 17.7 2.10
1800 11.1 0.89 12.1 1.04 13.0 1.19 13.8 1.32 14.6 1.45 15.3 1.63 16.0 1.77 16.7 1.92 17.3 2.07 17.9 2.21
1850 11.4 0.95 12.4 1.11 13.2 1.27 14.0 1.40 14.7 1.53 15.5 1.70 16.2 1.86 16.8 2.01 17.5 2.17 18.1 2.32
1900 11.6 1.02 12.6 1.19 13.4 1.34 14.2 1.48 14.9 1.61 15.6 1.77 16.3 1.95 17.0 2.11 17.7 2.27 18.3 2.42
1950 11.9 1.09 12.8 1.26 13.7 1.42 14.4 1.57 15.1 1.70 15.8 1.86 16.5 2.04 17.2 2.21 17.8 2.37 18.4 2.53
2000 12.1 1.16 13.0 1.34 13.9 1.50 14.6 1.66 15.3 1.80 16.0 1.94 16.7 2.13 17.3 2.31 18.0 2.47 18.6 2.64
2050 12.4 1.24 13.2 1.42 14.1 1.58 14.8 1.75 15.5 1.89 16.2 2.03 16.9 2.21 17.5 2.41 18.1 2.58 18.7 2.75
2100 12.6 1.32 13.5 1.51 14.3 1.67 15.0 1.85 15.7 2.00 16.4 2.13 17.0 2.31 17.7 2.51 18.3 2.69 18.9 2.86
2150 12.8 1.41 13.7 1.60 14.5 1.77 15.3 1.95 15.9 2.10 16.6 2.24 17.2 2.41 17.8 2.62 18.5 2.80 19.1 2.98
2200 13.1 1.49 13.9 1.69 14.7 1.86 15.5 2.05 16.1 2.21 16.8 2.36 17.4 2.51 18.0 2.71 18.6 2.92 19.2 3.11
2250 13.3 1.59 14.2 1.79 15.0 1.96 15.7 2.15 16.4 2.32 17.0 2.48 17.6 2.62 18.2 2.82 18.8 3.03 19.4 3.23
2300 13.6 1.68 14.4 1.89 15.2 2.07 15.9 2.25 16.6 2.44 17.2 2.60 17.8 2.75 18.4 2.93 19.0 3.15 19.5 3.36
2350 13.8 1.78 14.6 1.99 15.4 2.18 16.1 2.36 16.8 2.56 17.4 2.72 18.0 2.89 18.6 3.05 19.2 3.26 19.7 3.49
2400 14.1 1.88 14.9 2.10 15.6 2.30 16.3 2.48 17.0 2.68 17.6 2.85 18.2 3.02 18.8 3.17 19.3 3.38 19.9 3.62
2450 14.3 1.99 15.1 2.20 15.8 2.42 16.6 2.60 17.2 2.80 17.8 2.98 18.4 3.15 19.0 3.32 19.5 3.50 20.1 3.74
2500 14.6 2.10 15.3 2.31 16.1 2.54 16.8 2.72 17.4 2.93 18.0 3.12 18.6 3.30 19.2 3.47 19.7 3.64 20.3 3.86
LEGEND 5. Maximum usable output power (BkW) is 2.8. Extensive motor
BkW — Motor Brake (Output) Power (kW) and electrical testing on these units ensures that the full BkW
r/s — Fan Wheel Speed, Revolutions per Second range of the motor can be utilized with confidence. Using the
fan motors up to the BkW ratings shown will not result in nui-
NOTES: sance tripping or premature motor failure. Unit warranty will not
1. Boldface indicates field-supplied drive required. (See Note 6.) be affected.
6. Motor drive range: 11.8 to 14.8 r/s. All other speeds require
2. indicates field-supplied motor and drive required. field-supplied drive.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.

27
Table 20 — Fan Performance 50HJ014 — Vertical Discharge Units (SI)
EXTERNAL STATIC PRESSURE (Pa)
AIRFLOW
50 100 150 200 250 300 350 400 450 500
(L/s)
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
1400 7.5 0.35 10.4 0.61 11.5 0.73 12.2 0.80 13.1 0.95 13.8 1.10 14.7 1.27 15.7 1.41 16.5 1.40 16.5 1.42
1450 7.9 0.40 10.6 0.66 11.6 0.79 12.4 0.85 13.2 1.00 13.9 1.15 14.8 1.32 15.8 1.47 16.6 1.50 16.7 1.52
1500 8.3 0.45 10.7 0.71 11.8 0.85 12.5 0.91 13.4 1.06 14.1 1.20 15.0 1.37 15.8 1.53 16.6 1.60 17.0 1.62
1550 8.6 0.51 10.9 0.76 12.0 0.91 12.7 0.96 13.5 1.11 14.2 1.27 15.1 1.43 16.0 1.56 16.7 1.72 17.2 1.74
1600 8.9 0.57 11.1 0.82 12.2 0.96 12.9 1.02 13.7 1.17 14.4 1.32 15.2 1.49 16.1 1.61 16.8 1.83 17.4 1.83
1650 9.3 0.64 11.3 0.87 12.3 1.02 13.1 1.09 13.9 1.23 14.5 1.38 15.4 1.56 16.2 1.67 16.9 1.87 17.6 1.93
1700 9.9 0.73 11.5 0.93 12.5 1.08 13.3 1.17 14.0 1.28 14.7 1.46 15.6 1.63 16.4 1.73 17.1 1.93 17.6 2.02
1750 10.9 0.84 11.9 0.98 12.8 1.12 13.6 1.25 14.4 1.38 15.1 1.55 15.8 1.69 16.5 1.84 17.2 1.98 17.7 2.10
1800 11.1 0.89 12.1 1.04 13.0 1.19 13.8 1.32 14.6 1.45 15.3 1.63 16.0 1.77 16.7 1.92 17.3 2.07 17.9 2.21
1850 11.4 0.95 12.4 1.11 13.2 1.27 14.0 1.40 14.7 1.53 15.5 1.70 16.2 1.86 16.8 2.01 17.5 2.17 18.1 2.32
1900 11.6 1.02 12.6 1.19 13.4 1.34 14.2 1.48 14.9 1.61 15.6 1.77 16.3 1.95 17.0 2.11 17.7 2.27 18.3 2.42
1950 11.9 1.09 12.8 1.26 13.7 1.42 14.4 1.57 15.1 1.70 15.8 1.86 16.5 2.04 17.2 2.21 17.8 2.37 18.4 2.53
2000 12.1 1.16 13.0 1.34 13.9 1.50 14.6 1.66 15.3 1.80 16.0 1.94 16.7 2.13 17.3 2.31 18.0 2.47 18.6 2.64
2050 12.4 1.24 13.2 1.42 14.1 1.58 14.8 1.75 15.5 1.89 16.2 2.03 16.9 2.21 17.5 2.41 18.1 2.58 18.7 2.75
2100 12.6 1.32 13.5 1.51 14.3 1.67 15.0 1.85 15.7 2.00 16.4 2.13 17.0 2.31 17.7 2.51 18.3 2.69 18.9 2.86
2150 12.8 1.41 13.7 1.60 14.5 1.77 15.3 1.95 15.9 2.10 16.6 2.24 17.2 2.41 17.8 2.62 18.5 2.80 19.1 2.98
2200 13.1 1.49 13.9 1.69 14.7 1.86 15.5 2.05 16.1 2.21 16.8 2.36 17.4 2.51 18.0 2.71 18.6 2.92 19.2 3.11
2250 13.3 1.59 14.2 1.79 15.0 1.96 15.7 2.15 16.4 2.32 17.0 2.48 17.6 2.62 18.2 2.82 18.8 3.03 19.4 3.23
2300 13.6 1.68 14.4 1.89 15.2 2.07 15.9 2.25 16.6 2.44 17.2 2.60 17.8 2.75 18.4 2.93 19.0 3.15 19.5 3.36
2350 13.8 1.78 14.6 1.99 15.4 2.18 16.1 2.36 16.8 2.56 17.4 2.72 18.0 2.89 18.6 3.05 19.2 3.26 19.7 3.49
2400 14.1 1.88 14.9 2.10 15.6 2.30 16.3 2.48 17.0 2.68 17.6 2.85 18.2 3.02 18.8 3.17 19.3 3.38 19.9 3.62
2450 14.3 1.99 15.1 2.20 15.8 2.42 16.6 2.60 17.2 2.80 17.8 2.98 18.4 3.15 19.0 3.32 19.5 3.50 20.1 3.74
2500 14.6 2.10 15.3 2.31 16.1 2.54 16.8 2.72 17.4 2.93 18.0 3.12 18.6 3.30 19.2 3.47 19.7 3.64 20.3 3.86
2550 14.8 2.21 15.6 2.43 16.3 2.66 17.0 2.85 17.6 3.06 18.2 3.27 18.8 3.45 19.4 3.62 19.9 3.78 20.4 4.00
2600 15.1 2.33 15.8 2.56 16.5 2.80 17.2 2.98 17.9 3.20 18.4 3.41 19.0 3.59 19.6 3.77 20.1 3.94 20.6 4.14
2650 15.3 2.46 16.1 2.68 16.7 2.92 17.4 3.12 18.1 3.33 18.7 3.56 19.2 3.75 19.8 3.93 20.3 4.11 20.8 4.29
2700 15.6 2.59 16.3 2.81 17.0 3.06 17.6 3.27 18.3 3.47 18.9 3.71 19.4 3.91 20.0 4.09 20.5 4.28 — —
2750 15.8 2.72 16.5 2.95 17.2 3.21 17.9 3.42 18.5 3.62 19.1 3.86 19.6 4.07 20.2 4.27 — — — —
2800 16.1 2.86 16.8 3.09 17.4 3.36 18.1 3.57 18.7 3.78 19.3 4.02 19.9 4.24 — — — — — —
2850 16.3 2.98 17.0 3.24 17.7 3.50 18.3 3.74 18.9 3.94 19.5 4.18 — — — — — — — —
2900 16.6 3.15 17.3 3.39 17.9 3.65 18.5 3.90 19.2 4.10 — — — — — — — — — —
2950 16.8 3.30 17.5 3.54 18.2 3.80 18.8 4.06 19.4 4.27 — — — — — — — — — —
3000 17.1 3.45 17.8 3.70 18.4 3.97 19.0 4.24 — — — — — — — — — — — —
3050 17.3 3.62 18.0 3.87 18.6 3.98 — — — — — — — — — — — — — —
LEGEND 5. Maximum usable output power (BkW) is 2.8. Extensive motor
BkW — Motor Brake (Output) Power (kW) and electrical testing on these units ensures that the full BkW
r/s — Fan Wheel Speed, Revolutions per Second range of the motor can be utilized with confidence. Using the
fan motors up to the BkW ratings shown will not result in nui-
NOTES: sance tripping or premature motor failure. Unit warranty will not
1. Boldface indicates field-supplied drive required. (See Note 6.) be affected.
6. Motor drive range: 11.8 to 14.8 r/s. All other speeds require
2. indicates field-supplied motor and drive required. field-supplied drive.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.

Table 21 — Fan Performance 50HJ006 — Horizontal Discharge Units (English)


EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1300 589 0.21 661 0.25 785 0.35 890 0.48 980 0.60 1064 0.73 1013 0.86 1056 0.90 1104 0.94
1400 627 0.26 695 0.30 814 0.41 915 0.54 1003 0.67 1086 0.81 1100 0.98 1129 1.04 1163 1.09
1500 665 0.31 729 0.35 843 0.47 940 0.60 1026 0.74 1108 0.89 1187 1.06 1202 1.18 1222 1.24
1600 703 0.36 763 0.40 872 0.53 965 0.66 1049 0.81 1130 0.97 1206 1.14 1275 1.32 1281 1.44
1700 741 0.40 801 0.47 902 0.60 993 0.75 1077 0.89 1152 1.05 1226 1.23 1298 1.37 1359 1.50
1800 776 0.47 841 0.57 933 0.71 1029 0.87 1113 1.05 1183 1.16 1252 1.26 1334 1.40 1389 1.56
1900 812 0.54 876 0.65 965 0.80 1054 0.96 1129 1.08 1197 1.18 1273 1.37 1342 1.43 1412 1.60
2000 849 0.63 911 0.74 998 0.89 1081 1.07 1145 1.11 1223 1.29 1294 1.47 1363 1.53 1426 1.66
2100 886 0.72 945 0.83 1032 1.00 1111 1.18 1169 1.20 1249 1.41 1316 1.49 1379 1.68 1444 1.73
2200 924 0.82 978 0.92 1066 1.12 1134 1.23 1198 1.34 1278 1.44 1340 1.59 1401 1.80 1462 1.79
2300 962 0.92 1012 1.03 1101 1.24 1156 1.28 1227 1.46 1300 1.54 1364 1.76 1426 1.94 1488 1.93
2400 1000 1.04 1046 1.14 1129 1.30 1187 1.40 1257 1.60 1322 1.65 1389 1.89 1454 2.01 1506 2.10
2500 1038 1.17 1081 1.27 1156 1.36 1220 1.55 1289 1.64 1348 1.78 1412 2.02 1481 2.08 1536 2.28
LEGEND the motor can be utilized with confidence. Using the fan motors
Bhp — Brake Horsepower up to the horsepower ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be
NOTES: affected.
1. Boldface indicates field-supplied drive required. (See Note 4.) 3. Values include losses for filters, unit casing, and wet coils.
2. Maximum usable bhp is 2.4. Extensive motor and electrical 4. Motor drive range: 920 to 1310 rpm. All other speeds require
testing on these units ensures that the full horsepower range of field-supplied drive.

28
Table 22 — Fan Performance 50HJ007 — Horizontal Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1500 665 0.31 729 0.35 843 0.47 940 0.60 1026 0.74 1108 0.89 1187 1.06 1202 1.18 1222 1.24
1600 703 0.36 763 0.40 872 0.53 965 0.66 1049 0.81 1130 0.97 1206 1.14 1275 1.32 1281 1.44
1700 741 0.40 801 0.47 902 0.60 993 0.75 1077 0.89 1152 1.05 1226 1.23 1298 1.41 1359 1.60
1800 776 0.47 841 0.57 933 0.71 1029 0.87 1113 1.05 1183 1.16 1252 1.26 1334 1.33 1389 1.53
1900 812 0.54 876 0.65 965 0.80 1054 0.96 1129 1.08 1197 1.18 1273 1.37 1342 1.43 1412 1.60
2000 849 0.63 911 0.74 998 0.89 1081 1.07 1145 1.11 1223 1.29 1294 1.47 1363 1.53 1426 1.66
2100 886 0.72 945 0.83 1032 1.00 1111 1.18 1169 1.20 1249 1.41 1316 1.49 1379 1.68 1444 1.73
2200 924 0.82 978 0.92 1066 1.12 1134 1.23 1198 1.34 1278 1.44 1340 1.59 1401 1.80 1462 1.79
2300 962 0.92 1012 1.03 1101 1.24 1156 1.28 1227 1.46 1300 1.54 1364 1.76 1426 1.94 1488 1.93
2400 1000 1.04 1046 1.14 1129 1.30 1187 1.40 1257 1.60 1322 1.65 1389 1.89 1454 2.01 1506 2.10
2500 1038 1.17 1081 1.27 1156 1.36 1220 1.55 1289 1.64 1348 1.78 1412 2.02 1481 2.08 1536 2.28
2600 1076 1.31 1117 1.41 1191 1.50 1252 1.70 1322 1.79 1377 1.99 1443 2.12 1503 2.22 1562 2.45
2700 1115 1.46 1149 1.50 1224 1.66 1279 1.78 1354 1.95 1403 2.14 1474 2.21 1534 2.45 1588 2.62
2800 1137 1.51 1181 1.59 1259 1.83 1310 1.94 1375 2.12 1446 2.29 1508 2.40 1561 2.63 1616 2.82
2900 1159 1.55 1209 1.76 1270 1.95 1339 2.03 1408 2.31 1489 2.43 1525 2.59 1589 2.82 — —
3000 1194 1.70 1237 1.93 1280 2.06 1373 2.23 1440 2.50 1520 2.62 1547 2.77 — — — —
LEGEND the motor can be utilized with confidence. Using the fan motors
Bhp — Brake Horsepower up to the horsepower ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be
NOTES: affected.
1. Boldface indicates field-supplied drive required. (See Note 5.) 4. Values include losses for filters, unit casing, and wet coils.
2. indicates field-supplied motor and drive required. 5. Motor drive range: 920 to 1310 rpm. All other speeds require
field-supplied drive.
3. Maximum usable bhp is 2.4. Extensive motor and electrical
testing on these units ensures that the full horsepower range of

Table 23 — Fan Performance 50HJ008,009 — Horizontal Discharge Units (English)


EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1800 411 0.31 509 0.46 585 0.59 659 0.82 724 1.07 762 1.29 775 1.58 732 1.84 787 2.05 850 2.09
1900 423 0.34 519 0.50 595 0.65 667 0.88 732 1.13 773 1.37 792 1.66 764 1.92 805 2.15 858 2.25
2000 435 0.36 529 0.54 605 0.71 675 0.94 739 1.19 783 1.44 808 1.73 795 2.00 826 2.25 865 2.40
2100 447 0.39 539 0.58 615 0.77 683 1.00 746 1.25 794 1.51 825 1.80 826 2.08 841 2.35 873 2.55
2200 459 0.42 549 0.62 625 0.83 691 1.06 753 1.31 805 1.58 842 1.87 857 2.16 869 2.45 880 2.70
2250 465 0.43 554 0.64 630 0.86 695 1.09 757 1.34 810 1.62 850 1.91 873 2.20 863 2.50 885 2.78
2300 471 0.45 559 0.66 635 0.89 699 1.12 760 1.37 816 1.65 859 1.94 888 2.24 897 2.55 887 2.85
2400 482 0.50 569 0.71 645 0.95 708 1.18 768 1.44 824 1.72 872 2.01 909 2.32 931 2.64 935 2.96
2500 494 0.54 581 0.76 654 1.01 717 1.25 776 1.51 832 1.79 882 2.09 925 2.40 955 2.72 972 3.06
2550 501 0.57 587 0.79 659 1.05 722 1.29 780 1.55 836 1.83 887 2.13 931 2.45 964 2.77 986 3.11
2600 507 0.59 592 0.82 663 1.08 727 1.32 784 1.58 839 1.87 891 2.17 936 2.49 973 2.82 999 3.16
2700 520 0.65 604 0.89 672 1.14 737 1.40 793 1.66 846 1.95 898 2.26 946 2.58 987 2.91 1019 3.26
2800 533 0.71 615 0.95 683 1.20 747 1.49 802 1.75 855 2.04 906 2.35 954 2.67 997 3.01 1034 3.36
2900 546 0.77 626 1.02 693 1.27 756 1.57 813 1.84 863 2.13 913 2.44 961 2.77 1006 3.12 — —
3000 559 0.83 637 1.09 704 1.35 765 1.66 823 1.94 872 2.22 921 2.54 969 2.88 1014 3.22 — —
3100 572 0.90 648 1.17 715 1.43 775 1.74 832 2.05 882 2.33 930 2.65 976 2.99 1021 3.34 — —
3200 585 0.96 660 1.24 727 1.52 785 1.83 841 2.15 892 2.45 939 2.76 984 3.10 — — — —
3300 598 1.03 671 1.32 739 1.62 795 1.91 851 2.26 902 2.57 948 2.88 993 3.21 — — — —
3400 610 1.10 682 1.41 750 1.72 806 2.01 860 2.36 912 2.69 958 3.01 1002 3.34 — — — —
3500 623 1.17 694 1.50 761 1.82 817 2.11 870 2.47 921 2.82 968 3.15 — — — — — —
3600 636 1.25 707 1.60 772 1.93 828 2.23 880 2.57 930 2.95 978 3.29 — — — — — —
3700 649 1.33 720 1.71 783 2.03 840 2.35 890 2.69 940 3.07 — — — — — — — —
3750 655 1.37 727 1.77 789 2.09 846 2.42 896 2.75 945 3.14 — — — — — — — —
3800 661 1.41 733 1.82 795 2.15 852 2.48 901 2.80 949 3.20 — — — — — — — —
3900 674 1.49 746 1.93 806 2.26 863 2.61 912 2.93 959 3.33 — — — — — — — —
4000 687 1.57 759 2.05 817 2.38 874 2.75 923 3.08 — — — — — — — — — —
4100 699 1.66 772 2.17 828 2.50 885 2.88 935 3.23 — — — — — — — — — —
4200 712 1.75 785 2.30 840 2.64 897 3.03 947 3.39 — — — — — — — — — —
4250 719 1.80 792 2.37 846 2.71 903 3.10 — — — — — — — — — — — —
4300 725 1.85 798 2.43 852 2.77 908 3.17 — — — — — — — — — — — —
LEGEND up to the horsepower ratings shown will not result in nuisance
Bhp — Brake Horsepower tripping or premature motor failure. Unit warranty will not be
affected.
NOTES: 4. Use of a field-supplied motor may affect wire sizing. Contact
1. Boldface indicates field-supplied drive required. (See Note 6.) Carrier representative to verify.
2. indicates field-supplied motor and drive required. 5. Values include losses for filters, unit casing, and wet coils.
6. Motor drive range: 690 to 890 rpm. All other speeds require
3. Maximum usable bhp is 2.9. Extensive motor and electrical field-supplied drive.
testing on these units ensures that the full horsepower range of
the motor can be utilized with confidence. Using the fan motors

29
Table 24 — Fan Performance 50HJ012 — Horizontal Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2550 — — 550 0.50 609 0.59 676 0.81 731 0.97 789 1.17 837 1.49 864 1.44 886 1.23 915 1.25
2600 — — 555 0.53 614 0.63 680 0.84 735 1.00 793 1.20 841 1.52 870 1.49 893 1.29 920 1.31
2700 399 0.02 565 0.58 625 0.69 689 0.89 744 1.06 800 1.26 849 1.56 882 1.59 907 1.39 931 1.44
2800 419 0.13 575 0.63 636 0.75 698 0.94 753 1.12 807 1.32 857 1.60 895 1.69 922 1.49 941 1.57
2900 439 0.24 585 0.69 646 0.82 707 1.00 762 1.18 815 1.38 865 1.65 907 1.79 936 1.60 951 1.70
3000 459 0.35 595 0.74 657 0.88 716 1.05 770 1.24 822 1.44 872 1.69 919 1.88 950 1.70 962 1.82
3100 478 0.46 605 0.79 667 0.94 725 1.10 779 1.30 829 1.50 882 1.73 932 2.00 965 1.80 971 1.95
3200 500 0.57 615 0.85 679 1.01 734 1.16 787 1.36 837 1.56 886 1.78 943 2.06 978 1.91 984 2.07
3300 519 0.62 625 0.90 691 1.08 744 1.23 796 1.43 845 1.63 892 1.85 947 2.10 988 2.05 995 2.20
3400 537 0.69 637 0.97 702 1.16 753 1.30 805 1.50 853 1.71 899 1.93 951 2.17 995 2.17 1008 2.32
3500 561 0.77 647 1.03 712 1.23 762 1.38 814 1.57 862 1.78 907 2.01 959 2.24 1000 2.33 1021 2.47
3600 592 0.86 658 1.10 721 1.30 773 1.47 823 1.65 871 1.86 915 2.09 965 2.32 1005 2.46 1036 2.59
3700 607 0.97 670 1.18 732 1.37 782 1.56 833 1.73 879 1.95 927 2.17 973 2.38 1013 2.57 1046 2.73
3800 621 1.05 681 1.25 742 1.45 795 1.66 842 1.82 889 2.03 934 2.26 980 2.48 1022 2.69 1058 2.87
3900 636 1.13 693 1.32 751 1.53 808 1.76 851 1.92 898 2.12 942 2.36 987 2.59 1030 2.81 1068 3.01
4000 650 1.21 705 1.40 761 1.61 819 1.86 861 2.02 908 2.21 950 2.46 994 2.70 1037 2.92 1077 3.14
4100 665 1.30 717 1.48 772 1.71 830 1.96 871 2.13 917 2.32 960 2.55 1001 2.81 1045 3.04 1085 3.27
4200 680 1.39 728 1.57 783 1.81 839 2.05 883 2.25 925 2.44 969 2.65 1009 2.92 1051 3.17 1092 3.40
4300 696 1.49 739 1.66 794 1.91 848 2.14 896 2.38 935 2.56 979 2.77 1018 3.03 1058 329 1100 3.53
4400 711 1.60 750 1.75 805 2.02 857 2.24 908 2.51 945 2.68 988 2.89 1028 3.14 1066 3.41 1106 3.67
4500 727 1.70 762 1.85 817 2.12 867 2.35 919 2.63 955 2.82 996 3.02 1037 3.25 1074 3.54 1113 3.81
4600 742 1.82 774 1.96 828 2.23 877 2.46 929 2.75 967 2.96 1005 3.16 1046 3.38 1084 3.66 1121 3.95
4700 758 1.94 786 2.07 840 2.34 888 2.59 938 2.87 980 3.11 1015 3.30 1056 3.52 1093 3.79 1129 4.09
4800 773 2.06 799 2.18 852 2.46 899 2.72 947 2.98 992 3.26 1025 3.45 1064 3.67 1103 3.92 1137 4.22
4900 789 2.19 812 2.30 863 2.57 910 2.86 957 3.11 1003 3.41 1036 3.61 1073 3.83 1112 4.07 1147 4.36
5000 805 2.32 826 2.43 875 2.70 921 2.99 966 3.24 1014 3.56 1049 3.79 1083 4.00 1121 4.23 1157 4.50
LEGEND 5. Maximum usable bhp is 3.7. Extensive motor and electrical
Bhp — Brake Horsepower testing on these units ensures that the full horsepower range of
the motor can be utilized with confidence. Using the fan motors
NOTES: up to the horsepower ratings shown will not result in nuisance
1. Boldface indicates field-supplied drive required. (See Note 6.) tripping or premature motor failure. Unit warranty will not be
affected.
2. indicates field-supplied motor and drive required. 6. Motor drive range: 710 to 890 rpm. All other speeds require
3. Values include losses for filters, unit casing, and wet coils. field-supplied drive.
4. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.

30
Table 25 — Fan Performance 50HJ014 — Horizontal Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
3000 459 0.35 595 0.74 657 0.88 716 1.05 770 1.24 822 1.44 872 1.69 919 1.88 950 1.70 962 1.82
3100 478 0.46 605 0.79 667 0.94 725 1.10 779 1.30 829 1.50 882 1.73 932 2.00 965 1.80 971 1.95
3200 500 0.57 615 0.85 679 1.01 734 1.16 787 1.36 837 1.56 886 1.78 943 2.06 978 1.91 984 2.07
3300 519 0.62 625 0.90 691 1.08 744 1.23 796 1.43 845 1.63 892 1.85 947 2.10 988 2.05 995 2.20
3400 537 0.69 637 0.97 702 1.16 753 1.30 805 1.50 853 1.71 899 1.93 951 2.17 995 2.17 1008 2.32
3500 561 0.77 647 1.03 712 1.23 762 1.38 814 1.57 862 1.78 907 2.01 959 2.24 1000 2.33 1021 2.47
3600 592 0.86 658 1.10 721 1.30 773 1.47 823 1.65 871 1.86 915 2.09 965 2.32 1005 2.46 1036 2.59
3700 607 0.97 670 1.18 732 1.37 782 1.56 833 1.73 879 1.95 927 2.17 973 2.38 1013 2.57 1046 2.73
3800 621 1.05 681 1.25 742 1.45 795 1.66 842 1.82 889 2.03 934 2.26 980 2.48 1022 2.69 1058 2.87
3900 636 1.13 693 1.32 751 1.53 808 1.76 851 1.92 898 2.12 942 2.36 987 2.59 1030 2.81 1068 3.01
4000 650 1.21 705 1.40 761 1.61 819 1.86 861 2.02 908 2.21 950 2.46 994 2.70 1037 2.92 1077 3.14
4100 665 1.30 717 1.48 772 1.71 830 1.96 871 2.13 917 2.32 960 2.55 1001 2.81 1045 3.04 1085 3.27
4200 680 1.39 728 1.57 783 1.81 839 2.05 883 2.25 925 2.44 969 2.65 1009 2.92 1051 3.17 1092 3.40
4300 696 1.49 739 1.66 794 1.91 848 2.14 896 2.38 935 2.56 979 2.77 1018 3.03 1058 329 1100 3.53
4400 711 1.60 750 1.75 805 2.02 857 2.24 908 2.51 945 2.68 988 2.89 1028 3.14 1066 3.41 1106 3.67
4500 727 1.70 762 1.85 817 2.12 867 2.35 919 2.63 955 2.82 996 3.02 1037 3.25 1074 3.54 1113 3.81
4600 742 1.82 774 1.96 828 2.23 877 2.46 929 2.75 967 2.96 1005 3.16 1046 3.38 1084 3.66 1121 3.95
4700 758 1.94 786 2.07 840 2.34 888 2.59 938 2.87 980 3.11 1015 3.30 1056 3.52 1093 3.79 1129 4.09
4800 773 2.06 799 2.18 852 2.46 899 2.72 947 2.98 992 3.26 1025 3.45 1064 3.67 1103 3.92 1137 4.22
4900 789 2.19 812 2.30 863 2.57 910 2.86 957 3.11 1003 3.41 1036 3.61 1073 3.83 1112 4.07 1147 4.36
5000 805 2.32 826 2.43 875 2.70 921 2.99 966 3.24 1014 3.56 1049 3.79 1083 4.00 1121 4.23 1157 4.50
5100 821 2.47 840 2.57 887 2.83 932 3.13 976 3.38 1024 3.71 1061 3.96 1093 4.17 1129 4.40 1166 4.66
5200 837 2.61 854 2.71 898 2.96 943 3.28 987 3.53 1033 3.84 1073 4.14 1103 4.34 1138 4.58 1175 4.82
5300 853 2.76 868 2.85 909 3.09 955 3.42 998 3.69 1042 3.98 1084 4.31 1115 4.53 1148 4.76 1184 5.01
5400 869 2.92 882 3.01 920 3.24 967 3.57 1009 3.86 1051 4.14 1095 4.49 1128 4.74 1158 4.95 1193 5.20
5500 885 3.09 897 3.17 932 3.38 978 3.72 1029 4.03 1061 4.03 1105 4.66 1140 4.94 1168 5.15 1202 5.40
5600 901 3.26 911 3.33 943 3.54 990 3.87 1031 4.20 1071 4.46 1114 4.81 1152 5.14 1180 5.36 1211 5.60
5700 917 3.44 926 3.50 956 3.70 1002 4.03 1042 4.38 1081 4.64 1123 4.98 1163 5.34 1193 5.59 — —
5800 933 3.62 941 3.68 968 3.87 1013 4.20 1053 4.56 1092 4.84 1132 5.15 1174 5.54 — — — —
5900 949 3.81 956 3.87 981 4.05 1025 4.37 1065 4.74 1103 5.04 1142 5.34 1183 5.72 — — — —
6000 965 4.01 972 4.06 995 4.23 1037 4.55 1076 4.92 1114 5.24 1152 5.53 — — — — — —
6100 981 4.21 987 4.26 1008 4.42 1047 4.73 1088 5.10 1125 5.45 1162 5.73 — — — — — —
6200 997 4.42 1002 4.46 1022 4.62 1058 4.91 1100 5.29 1136 5.66 — — — — — — — —
6300 1014 4.64 1018 4.68 1036 4.83 1070 5.11 1112 5.49 — — — — — — — — — —
LEGEND 5. Maximum usable bhp is 3.7. Extensive motor and electrical
Bhp — Brake Horsepower testing on these units ensures that the full horsepower range of
the motor can be utilized with confidence. Using the fan motors
NOTES: up to the horsepower ratings shown will not result in nuisance
1. Boldface indicates field-supplied drive required. (See Note 6.) tripping or premature motor failure. Unit warranty will not be
affected.
2. indicates field-supplied motor and drive required. 6. Motor drive range: 710 to 890 rpm. All other speeds require
3. Values include losses for filters, unit casing, and wet coils. field-supplied drive.
4. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.

Table 26 — Fan Performance 50HJ006 — Vertical Discharge Units (English)


EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1300 631 0.21 695 0.27 822 0.37 905 0.46 982 0.58 1084 0.81 1177 0.93 1206 1.36 1203 1.29
1400 671 0.27 732 0.33 850 0.44 938 0.55 1017 0.68 1109 0.88 1195 1.02 1241 1.37 1267 1.39
1500 711 0.33 769 0.39 878 0.51 971 0.64 1052 0.78 1134 0.95 1213 1.11 1276 1.38 1331 1.49
1600 751 0.39 806 0.45 906 0.58 1004 0.73 1087 0.88 1159 1.02 1231 1.20 1311 1.39 1395 1.59
1700 791 0.46 845 0.53 941 0.66 1030 0.80 1112 0.96 1184 1.12 1258 1.30 1322 1.49 1403 1.69
1800 904 0.65 968 0.77 1082 1.03 1164 1.12 1246 1.21 1328 1.30 1380 1.45 1425 1.55 1520 1.72
1900 948 0.76 1052 1.01 1120 1.10 1188 1.19 1260 1.30 1332 1.41 1409 1.60 1480 1.71 1551 1.81
2000 993 0.88 1070 1.07 1157 1.17 1211 1.26 1277 1.33 1386 1.56 1461 1.76 1522 1.85 1570 1.93
2100 1038 1.01 1088 1.12 1200 1.29 1278 1.43 1367 1.62 1439 1.70 1512 1.92 1549 1.95 1602 2.10
2200 1083 1.15 1178 1.29 1262 1.45 1345 1.60 1392 1.75 1473 1.86 1533 2.03 1586 2.14 1639 2.29
2300 1177 1.33 1194 1.35 1277 1.50 1347 1.69 1417 1.88 1507 2.01 1554 2.13 1618 2.32 1677 2.50
2400 1195 1.39 1209 1.40 1292 1.56 1391 1.88 1451 2.00 1549 2.23 1597 2.36 1650 2.51 — —
2500 1212 1.45 1284 1.58 1340 1.77 1436 2.06 1484 2.12 1580 2.40 1644 2.61 1684 2.72 — —
LEGEND up to the horsepower ratings shown will not result in nuisance
Bhp — Brake Horsepower tripping or premature motor failure. Unit warranty will not be
affected.
NOTES: 4. Values include losses for filters, unit casing, and wet coils.
1. Boldface indicates field-supplied drive required. (See Note 6.) 5. Use of a field-supplied motor may affect wire sizing. Contact
2. indicates field-supplied motor and drive required. Carrier representative to verify.
6. Motor drive range: 920 to 1310 rpm. All other speeds require
3. Maximum usable bhp is 2.4. Extensive motor and electrical field-supplied drive.
testing on these units ensures that the full horsepower range of
the motor can be utilized with confidence. Using the fan motors

31
Table 27 — Fan Performance 50HJ007 — Vertical Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1500 711 0.33 769 0.39 878 0.51 971 0.64 1052 0.78 1134 0.95 1213 1.11 1276 1.38 1331 1.49
1600 751 0.39 806 0.45 906 0.58 1004 0.73 1087 0.88 1159 1.02 1231 1.20 1311 1.39 1395 1.59
1700 791 0.46 845 0.53 941 0.66 1030 0.80 1112 0.96 1184 1.12 1258 1.30 1322 1.49 1403 1.69
1800 904 0.65 968 0.77 1082 1.03 1164 1.12 1246 1.21 1328 1.30 1380 1.45 1425 1.55 1520 1.72
1900 948 0.76 1052 1.01 1120 1.10 1188 1.19 1260 1.30 1332 1.41 1409 1.60 1480 1.71 1551 1.81
2000 993 0.88 1070 1.07 1157 1.17 1211 1.26 1277 1.33 1386 1.56 1461 1.76 1522 1.85 1570 1.93
2100 1038 1.01 1088 1.12 1200 1.29 1278 1.43 1367 1.62 1439 1.70 1512 1.92 1549 1.95 1602 2.10
2200 1083 1.15 1178 1.29 1262 1.45 1345 1.60 1392 1.75 1473 1.86 1533 2.03 1586 2.14 1639 2.29
2300 1177 1.33 1194 1.35 1277 1.50 1347 1.69 1417 1.88 1507 2.01 1554 2.13 1618 2.32 1677 2.50
2400 1195 1.39 1209 1.40 1292 1.56 1391 1.88 1451 2.00 1549 2.23 1597 2.36 1650 2.51 — —
2500 1212 1.45 1284 1.58 1340 1.77 1436 2.06 1484 2.12 1580 2.40 1644 2.61 1684 2.72 — —
2600 1282 1.62 1320 1.74 1430 2.15 1494 2.23 1542 2.35 1604 2.55 1686 2.86 — — — —
2700 1321 1.79 1356 1.90 1455 2.23 1524 2.39 1587 2.59 1634 2.73 — — — — — —
2800 1360 1.96 1420 2.15 1479 2.31 1554 2.54 1630 2.84 1676 2.99 — — — — — —
2900 1435 2.29 1458 2.35 1517 2.53 1577 2.70 — — — — — — — — — —
3000 1441 2.24 1495 2.47 1568 2.78 — — — — — — — — — — — —
LEGEND up to the horsepower ratings shown will not result in nuisance
Bhp — Brake Horsepower tripping or premature motor failure. Unit warranty will not be
affected.
NOTES: 4. Values include losses for filters, unit casing, and wet coils.
1. Boldface indicates field-supplied drive required. (See Note 6.) 5. Use of a field-supplied motor may affect wire sizing. Contact
2. indicates field-supplied motor and drive required. Carrier representative to verify.
6. Motor drive range: 920 to 1310 rpm. All other speeds require
3. Maximum usable bhp is 2.4. Extensive motor and electrical field-supplied drive.
testing on these units ensures that the full horsepower range of
the motor can be utilized with confidence. Using the fan motors

Table 28 — Fan Performance 50HJ008,009 — Vertical Discharge Units (English)


EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1800 442 0.31 529 0.47 605 0.68 671 0.86 727 1.01 784 1.26 881 1.76 913 2.06 954 2.45 995 2.98
1900 458 0.36 543 0.53 617 0.74 683 0.94 739 1.11 794 1.36 882 1.81 919 2.12 960 2.50 1001 3.01
2000 473 0.40 557 0.59 629 0.80 694 1.01 750 1.20 804 1.45 882 1.85 924 2.18 965 2.54 1007 3.03
2100 488 0.45 571 0.65 641 0.86 705 1.08 761 1.29 814 1.54 883 1.90 929 2.24 972 2.59 1013 3.06
2200 503 0.50 585 0.71 653 0.92 716 1.15 772 1.38 824 1.63 884 1.95 934 2.30 975 2.64 1019 3.09
2250 511 0.52 592 0.74 659 0.95 722 1.19 778 1.43 829 1.68 884 1.97 937 2.33 977 2.66 1022 3.10
2300 518 0.55 599 0.77 665 0.98 727 1.22 783 1.47 834 1.72 885 2.00 939 2.36 979 2.69 1025 3.12
2400 534 0.61 613 0.84 677 1.06 738 1.30 794 1.55 844 1.81 892 2.08 944 2.40 987 2.76 1039 3.20
2500 549 0.67 627 0.90 690 1.14 750 1.38 805 1.64 855 1.91 902 2.18 949 2.48 1002 2.84 1041 3.25
2550 557 0.71 633 0.94 697 1.18 756 1.42 811 1.69 861 1.96 908 2.24 953 2.53 1003 2.87 1045 3.28
2600 565 0.74 639 0.97 703 1.22 761 1.46 816 1.74 866 2.01 913 2.29 957 2.58 1004 2.91 1050 3.31
2700 581 0.81 652 1.04 717 1.31 773 1.55 827 1.83 878 2.12 924 2.41 967 2.70 1010 3.01 1056 3.37
2800 597 0.89 665 1.12 731 1.40 786 1.66 839 1.93 889 2.23 935 2.52 978 2.62 1019 3.13 1061 3.47
2900 613 0.97 679 1.20 745 1.50 799 1.76 850 2.04 900 2.34 946 2.65 989 2.96 1030 3.27 — —
3000 629 1.06 694 1.29 759 1.59 812 1.88 862 2.15 911 2.46 957 2.78 1000 3.09 1040 3.41 — —
3100 646 1.15 709 1.39 772 1.70 825 1.99 875 2.28 923 2.58 968 2.91 1011 3.24 — — — —
3200 662 1.25 724 1.50 785 1.80 840 2.11 887 2.41 934 2.71 980 3.04 1022 3.38 — — — —
3300 679 1.35 740 1.61 798 1.91 854 2.24 900 2.54 946 2.85 991 3.18 — — — — — —
3400 696 1.46 756 1.73 811 2.02 868 2.37 914 2.69 959 3.00 1003 3.32 — — — — — —
3500 712 1.57 771 1.85 824 2.14 881 2.50 928 2.84 971 3.16 1014 3.48 — — — — — —
3600 729 1.69 787 1.98 839 2.27 894 2.64 942 2.99 984 3.32 — — — — — — — —
3700 746 1.82 803 2.12 854 2.42 907 2.78 956 3.15 997 3.49 — — — — — — — —
3750 755 1.89 811 2.20 862 2.49 914 2.85 963 3.23 — — — — — — — — — —
3800 763 1.95 819 2.27 869 2.56 920 2.92 970 3.31 — — — — — — — — — —
3900 780 2.09 835 2.42 884 2.72 933 3.07 983 3.48 — — — — — — — — — —
4000 796 2.23 851 2.56 900 2.89 946 3.23 — — — — — — — — — — — —
4100 813 2.39 867 2.74 915 3.06 960 3.40 — — — — — — — — — — — —
4200 830 2.55 883 2.91 931 3.24 — — — — — — — — — — — — — —
4250 839 2.63 892 3.00 939 3.34 — — — — — — — — — — — — — —
4300 847 2.71 900 3.09 947 3.43 — — — — — — — — — — — — — —
LEGEND up to the horsepower ratings shown will not result in nuisance
Bhp — Brake Horsepower tripping or premature motor failure. Unit warranty will not be
affected.
NOTES: 4. Use of a field-supplied motor may affect wire sizing. Contact
1. Boldface indicates field-supplied drive required. (See Note 6.) Carrier representative to verify.
2. indicates field-supplied motor and drive required. 5. Values include losses for filters, unit casing, and wet coils.
6. Standard motor drive range: 690 to 890 rpm. All other speeds
3. Maximum usable bhp is 2.9. Extensive motor and electrical require field-supplied drive.
testing on these units ensures that the full horsepower range of
the motor can be utilized with confidence. Using the fan motors

32
Table 29 — Fan Performance 50HJ012 — Vertical Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2550 369 0.06 574 0.59 643 0.68 691 0.81 747 1.01 793 1.21 857 1.47 925 1.44 960 1.31 937 1.39
2600 379 0.11 580 0.62 648 0.72 695 0.85 751 1.05 797 1.25 861 1.50 927 1.49 963 1.38 943 1.46
2700 399 0.20 591 0.68 659 0.79 705 0.91 760 1.11 805 1.31 867 1.56 931 1.59 969 1.51 956 1.58
2800 419 0.29 603 0.74 670 0.86 715 0.97 769 1.17 813 1.37 873 1.62 935 1.69 976 1.65 969 1.70
2900 439 0.38 614 0.79 681 0.94 725 1.04 778 1.24 821 1.44 880 1.67 939 1.79 982 1.78 982 1.83
3000 459 0.46 625 0.85 691 1.01 734 1.10 787 1.30 829 1.50 886 1.73 943 1.88 988 1.91 995 1.95
3100 478 0.57 637 0.90 702 1.08 744 1.16 796 1.36 837 1.56 892 1.78 947 2.00 995 2.05 1008 2.07
3200 500 0.62 647 0.97 712 1.16 753 1.23 805 1.43 845 1.63 899 1.85 951 2.06 1000 2.17 1021 2.20
3300 519 0.69 658 1.03 721 1.23 762 1.30 814 1.50 853 1.71 907 1.93 959 2.10 1004 2.33 1036 2.36
3400 537 0.77 669 1.10 731 1.30 773 1.38 823 1.57 862 1.78 915 2.01 966 2.17 1009 2.46 1043 2.47
3500 561 0.86 680 1.17 741 1.37 784 1.47 832 1.65 871 1.86 924 2.09 974 2.24 1015 2.51 1054 2.59
3600 592 0.98 692 1.24 751 1.45 796 1.57 841 1.72 880 1.95 933 2.18 983 2.32 1023 2.58 1058 2.70
3700 654 1.12 714 1.31 767 1.50 815 1.67 861 1.85 906 2.08 950 2.27 991 2.47 1030 2.65 1064 2.82
3800 668 1.20 727 1.40 780 1.60 827 1.77 873 1.95 916 2.18 959 2.38 1001 2.58 1040 2.78 1075 2.96
3900 683 1.28 741 1.49 793 1.70 839 1.88 884 2.05 927 2.28 969 2.50 1010 2.70 1049 2.91 1085 3.11
4000 697 1.37 754 1.59 806 1.80 851 1.99 895 2.16 938 2.38 979 2.62 1020 2.83 1059 3.04 1095 3.25
4100 711 1.46 767 1.69 819 1.90 864 2.10 907 2.28 949 2.49 989 2.74 1029 2.96 1068 3.18 1105 3.39
4200 726 1.56 780 1.80 832 2.01 877 2.22 919 2.41 960 2.60 1000 2.86 1039 3.10 1077 3.31 1114 3.54
4300 741 1.66 794 1.91 845 2.12 889 2.35 931 2.54 971 2.72 1011 2.97 1049 3.23 1087 3.46 1124 3.69
4400 755 1.77 808 2.03 858 2.24 902 2.48 943 2.68 983 2.86 1022 3.10 1059 3.37 1097 3.61 1133 3.84
4500 770 1.89 821 2.15 871 2.37 915 2.61 955 2.82 995 3.01 1033 3.23 1070 3.51 1107 3.76 1143 4.00
4600 784 2.00 835 2.27 884 2.49 928 2.75 968 2.96 1006 3.17 1044 3.37 1081 3.64 1117 3.92 1152 4.17
4700 799 2.13 849 2.40 897 2.63 941 2.88 981 3.11 1018 3.32 1056 3.52 1092 3.78 1127 4.07 1162 4.33
4800 814 2.25 863 2.53 910 2.77 954 3.02 993 3.27 1030 3.48 1067 3.69 1103 3.93 1138 4.23 1172 4.50
4900 829 2.39 877 2.67 923 2.92 967 3.17 1006 3.43 1043 3.65 1079 3.87 1114 4.09 1149 4.37 1182 4.68
5000 843 2.52 892 2.81 937 3.08 980 3.32 1019 3.60 1055 3.82 1091 4.05 1126 4.25 1160 4.53 1193 4.85
LEGEND 5. Maximum usable bhp is 3.7. Extensive motor and electrical
Bhp — Brake Horsepower testing on these units ensures that the full horsepower range of
the motor can be utilized with confidence. Using the fan motors
NOTES: up to the horsepower ratings shown will not result in nuisance
1. Boldface indicates field-supplied drive required. (See Note 6.) tripping or premature motor failure. Unit warranty will not be
affected.
2. indicates field-supplied motor and drive required. 6. Motor drive range: 710 to 890 rpm. All other speeds require
3. Values include losses for filters, unit casing, and wet coils. field-supplied drive.
4. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.

33
Table 30 — Fan Performance 50HJ014 — Vertical Discharge Units (English)
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
(Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
3000 459 0.46 625 0.85 691 1.01 734 1.10 787 1.30 829 1.50 886 1.73 943 1.88 988 1.91 995 1.95
3100 478 0.57 637 0.90 702 1.08 744 1.16 796 1.36 837 1.56 892 1.78 947 2.00 995 2.05 1008 2.07
3200 500 0.62 647 0.97 712 1.16 753 1.23 805 1.43 845 1.63 899 1.85 951 2.06 1000 2.17 1021 2.20
3300 519 0.69 658 1.03 721 1.23 762 1.30 814 1.50 853 1.71 907 1.93 959 2.10 1004 2.33 1036 2.36
3400 537 0.77 669 1.10 731 1.30 773 1.38 823 1.57 862 1.78 915 2.01 966 2.17 1009 2.46 1043 2.47
3500 561 0.86 680 1.17 741 1.37 784 1.47 832 1.65 871 1.86 924 2.09 974 2.24 1015 2.51 1054 2.59
3600 592 0.98 692 1.24 751 1.45 796 1.57 841 1.72 880 1.95 933 2.18 983 2.32 1023 2.58 1058 2.70
3700 654 1.12 714 1.31 767 1.50 815 1.67 861 1.85 906 2.08 950 2.27 991 2.47 1030 2.65 1064 2.82
3800 668 1.20 727 1.40 780 1.60 827 1.77 873 1.95 916 2.18 959 2.38 1001 2.58 1040 2.78 1075 2.96
3900 683 1.28 741 1.49 793 1.70 839 1.88 884 2.05 927 2.28 969 2.50 1010 2.70 1049 2.91 1085 3.11
4000 697 1.37 754 1.59 806 1.80 851 1.99 895 2.16 938 2.38 979 2.62 1020 2.83 1059 3.04 1095 3.25
4100 711 1.46 767 1.69 819 1.90 864 2.10 907 2.28 949 2.49 989 2.74 1029 2.96 1068 3.18 1105 3.39
4200 726 1.56 780 1.80 832 2.01 877 2.22 919 2.41 960 2.60 1000 2.86 1039 3.10 1077 3.31 1114 3.54
4300 741 1.66 794 1.91 845 2.12 889 2.35 931 2.54 971 2.72 1011 2.97 1049 3.23 1087 3.46 1124 3.69
4400 755 1.77 808 2.03 858 2.24 902 2.48 943 2.68 983 2.86 1022 3.10 1059 3.37 1097 3.61 1133 3.84
4500 770 1.89 821 2.15 871 2.37 915 2.61 955 2.82 995 3.01 1033 3.23 1070 3.51 1107 3.76 1143 4.00
4600 784 2.00 835 2.27 884 2.49 928 2.75 968 2.96 1006 3.17 1044 3.37 1081 3.64 1117 3.92 1152 4.17
4700 799 2.13 849 2.40 897 2.63 941 2.88 981 3.11 1018 3.32 1056 3.52 1092 3.78 1127 4.07 1162 4.33
4800 814 2.25 863 2.53 910 2.77 954 3.02 993 3.27 1030 3.48 1067 3.69 1103 3.93 1138 4.23 1172 4.50
4900 829 2.39 877 2.67 923 2.92 967 3.17 1006 3.43 1043 3.65 1079 3.87 1114 4.09 1149 4.37 1182 4.68
5000 843 2.52 892 2.81 937 3.08 980 3.32 1019 3.60 1055 3.82 1091 4.05 1126 4.25 1160 4.53 1193 4.85
5100 858 2.67 906 2.95 950 3.24 993 3.48 1032 3.76 1068 4.00 1103 4.23 1137 4.45 1171 4.70 1204 5.01
5200 873 2.82 920 3.10 963 3.40 1006 3.65 1045 3.93 1081 4.19 1115 4.42 1149 4.65 1182 4.88 1215 5.18
5300 888 2.97 934 3.26 977 3.57 1019 3.82 1058 4.11 1094 4.38 1127 4.62 1161 4.85 1194 5.07 1226 5.36
5400 903 3.13 949 3.43 991 3.75 1032 4.00 1071 4.29 1106 4.57 1139 4.82 1173 5.06 1205 5.29 1237 5.55
5500 918 3.30 963 3.59 1004 3.92 1045 4.18 1084 4.47 1119 4.77 1152 5.03 1185 5.27 1217 5.51 1248 5.75
5600 933 3.47 978 3.77 1018 4.11 1058 4.38 1097 4.66 1132 4.97 1165 5.24 1197 5.49 1229 5.74 — —
5700 948 3.65 992 3.95 1032 4.30 1072 4.58 1110 4.86 1145 5.18 1178 5.46 1209 5.72 — — — —
5800 963 3.83 1006 4.14 1046 4.50 1085 4.79 1123 5.07 1158 5.39 1191 5.69 — — — — — —
5900 978 4.00 1021 4.34 1060 4.69 1098 5.01 1136 5.28 1171 5.60 — — — — — — — —
6000 993 4.22 1035 4.54 1074 4.89 1112 5.23 1149 5.50 — — — — — — — — — —
6100 1008 4.42 1050 4.75 1089 5.10 1125 5.45 1162 5.73 — — — — — — — — — —
6200 1023 4.63 1065 4.96 1103 5.32 1139 5.68 — — — — — — — — — — — —
6300 1038 4.85 1079 5.19 1117 5.54 — — — — — — — — — — — — — —
LEGEND 5. Maximum usable bhp is 3.7. Extensive motor and electrical
Bhp — Brake Horsepower testing on these units ensures that the full horsepower range of
the motor can be utilized with confidence. Using the fan motors
NOTES: up to the horsepower ratings shown will not result in nuisance
1. Boldface indicates field-supplied drive required. (See Note 6.) tripping or premature motor failure. Unit warranty will not be
affected.
2. indicates field-supplied motor and drive required. 6. Motor drive range: 710 to 890 rpm. All other speeds require
3. Values include losses for filters, unit casing, and wet coils. field-supplied drive.
4. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.

34
PRE-START-UP START-UP
Unit Preparation — Make sure that unit has been in-
stalled in accordance with these installation instructions and
Failure to observe the following warnings could result in applicable codes.
serious personal injury: Return-Air Filters — Make sure correct filters are in-
1. Follow recognized safety practices and wear protec- stalled in unit (see Tables 1A and 1B). Do not operate unit
tive eyeglasses when checking or servicing refrigerant without return-air filters.
system.
Outdoor-Air Inlet Screens — Outdoor-air inlet screen(s)
2. Do not operate compressor or provide any electric must be in place before operating unit.
power to unit unless compressor terminal cover is in
place and secured. Compressor Mounting — Compressors are internally
3. Do not remove compressor terminal cover until all spring mounted. Do not loosen or remove compressor hold-
electrical sources are disconnected. down bolts.
4. Relieve and reclaim all refrigerant from system before Internal Wiring — Check all electrical connections in
touching or disturbing anything inside terminal box unit control boxes; tighten as required.
if refrigerant leak is suspected around compressor
terminals. Refrigerant Service Ports — Each refrigerant sys-
tem has 4 Schrader-type service gage ports: one on the suction
5. Never attempt to repair soldered connection while re- line, one on the liquid line, and two on the compressor dis-
frigerant system is under pressure. charge line. Be sure that caps on the ports are tight.
6. Do not use torch to remove any component. System
contains oil and refrigerant under pressure. To remove High Flow Valves — Located on the compressor hot gas
a component, wear protective eyeglasses and proceed and suction tubes are High Flow Valves. Large black plastic
as follows: caps distinguish these valves with o-rings located inside the
caps. These valves cannot be accessed for service in the field.
a. Shut off electrical power to unit. Ensure the plastic caps are in place and tight or the possibility
b. Relieve and reclaim all refrigerant from system of refrigerant leakage could occur.
using both high- and low-pressure ports.
c. Cut component connection tubing with tubing Compressor Rotation — On 3-phase units with scroll
cutter and remove component from unit. compressors, it is important to be certain compressor is rotating
d. Carefully unsweat remaining tubing stubs when in the proper direction. To determine whether or not compres-
necessary. Oil can ignite when exposed to torch sor is rotating in the proper direction:
flame. 1. Connect service gages to suction and discharge pressure
fittings.
Proceed as follows to inspect and prepare the unit for initial 2. Energize the compressor.
start-up:
3. The suction pressure should drop and the discharge pres-
1. Remove all access panels. sure should rise, as is normal on any start-up.
2. Read and follow instructions on all WARNING, CAU- If the suction pressure does not drop and the discharge pres-
TION, and INFORMATION labels attached to or sure does not rise to normal levels:
shipped with unit.
1. Note that the evaporator fan is probably also rotating in
3. Make the following inspections: the wrong direction.
a. Inspect for shipping and handling damages such 2. Turn off power to the unit and tag disconnect.
as broken lines, loose parts, or disconnected wires.
3. Reverse any two of the unit power leads.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates 4. Turn on power to the unit and verify rotation is correct.
a refrigerant leak. Leak-test all refrigerant tubing The suction and discharge pressure levels should now move
connections using electronic leak detector, halide to their normal start-up levels.
torch, or liquid-soap solution. NOTE: When the compressor is rotating in the wrong direc-
c. Inspect all field- and factory-wiring connections. tion, the unit makes an elevated level of noise and does not
Be sure that connections are completed and tight. provide cooling.
Ensure wiring does not come in contact with
refrigerant tubing. Cooling — To start unit, turn on main power supply. Set
system selector switch at COOL position and fan switch at
d. Inspect coil fins. If damaged during shipping and AUTO position. Adjust thermostat to a setting below room
handling, carefully straighten fins with a fin comb. temperature. Compressor starts on closure of contactor.
4. Verify the following conditions: Check unit charge. Refer to Refrigerant Charge section on
a. Make sure that outdoor-fan blades are correctly page 39.
positioned in fan orifice. Refer to Condenser Fan Reset thermostat at a position above room temperature.
Adjustment section on page 39 for more details. Compressor will shut off.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled with TO SHUT OFF UNIT — Set system selector switch at OFF
water to ensure proper drainage. position. Resetting thermostat at a position above room tem-
perature shuts unit off temporarily until space temperature ex-
d. Make sure that all tools and miscellaneous loose ceeds thermostat setting. Units are equipped with Cycle-
parts have been removed. LOC™ protection device. Unit shuts down on any safety trip
e. Make sure that Start-Up Checklist has been per- and remains off; an indicator light on the thermostat comes on.
formed and filled out. Check reason for safety trip.

35
Compressor restart is accomplished by manual reset at the with mechanical cooling, providing second stage cooling. The
thermostat by turning the selector switch to OFF position and compressor and condenser fan will be energized and the position
then ON position. of the economizer damper will be determined by the supply-air
temperature.
Heating — To start unit, turn on main power supply.
When the second stage of cooling is satisfied, the compres-
Set thermostat at HEAT position and a setting above room sor and OFM will be deenergized. The damper position will be
temperature, fan at AUTO position. determined by the supply-air temperature.
First stage of thermostat energizes the first-stage electric When the first stage of cooling is satisfied, there is a
heater elements; second stage energizes second-stage electric 30-second delay before the evaporator fan shuts off on size 006
heater elements if installed. Check heating effects at air supply units. The damper will move to fully closed position.
grille(s).
COOLING, UNITS WITH ECONOMI$ER — When the
If electric heaters do not energize, reset limit switch (located outdoor-air temperature (OAT) is above the ECON SP set point
on evaporator-fan scroll) by depressing button located between and the room thermostat calls for Stage 1 cooling (R to G +
terminals on the switch. Y1), the indoor (evaporator) fan motor (IFM) is energized and
TO SHUT OFF UNIT — Set system selector switch at OFF the EconoMi$er damper modulates to minimum position. The
position. Resetting heating selector lever below room tempera- compressor contactor is energized to start the compressor and
ture temporarily shuts unit off until space temperature falls be- outdoor (condenser) fan motor (OFM). After the thermostat is
low thermostat setting. satisfied, the damper modulates to the fully closed position
when the IFM is deenergized.
Safety Relief — A soft solder joint at the suction line at
the loss-of-charge/low-pressure switch fitting provides pressure When the OAT is below the ECON SP setting and the room
relief under abnormal temperature and pressure conditions. thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
Ventilation (Continuous Fan) — Set fan and system IFM is energized. The EconoMi$er provides Stage 1 of cooling
selector switches at ON and OFF positions, respectively. Evap- by modulating the return and outdoor air dampers to maintain a
orator fan operates continuously to provide constant air 55 F supply air set point. If the supply-air temperature (SAT) is
circulation. greater than 57 F, the EconoMi$er modulates open, allowing a
greater amount of outdoor air to enter the unit. If the SAT drops
Operating Sequence — 50HJ006,007 Units below 53 F, the outdoor air damper modulates closed to reduce
COOLING, UNITS WITHOUT ECONOMIZER — When the amount of outdoor air. When the SAT is between 53 and
the thermostat calls for cooling, terminals G and Y1 are ener- 57 F, the EconoMi$er maintains its position.
gized. The indoor (evaporator) fan contactor (IFC), and com- If outdoor air alone cannot satisfy the cooling requirements
pressor contactor no. 1 (C1) are energized and the indoor of the conditioned space, and the OAT is above the MECH
(evaporator) fan motor (IFM), compressor no. 1, and condenser CLG LOCKOUT set point, the EconoMi$er integrates free
fan start. The outdoor (condenser) fan motor (OFM) runs con- cooling with mechanical cooling. This is accomplished by the
tinuously while unit is cooling. strategies below.
COOLING, UNITS WITH DURABLADE ECONO- NOTE: Compressor has a 2-minute Minimum On, Minimum
MIZER — When the outdoor-air temperature is above the out- Off, and Interstage delay timer.
door-air temperature (OAT) setting and the room thermostat
calls for cooling, the compressor contactor is energized to start 1. If Y1 is energized, and the room thermostat calls for Y2
the compressor and outdoor (condenser) fan motor (OFM). (2-stage thermostat), the compressor and OFM are ener-
The indoor (evaporator) fan motor (IFM) is energized and the gized. The position of the EconoMi$er damper is main-
economizer damper moves to the minimum position. After the tained at its current value.
thermostat is satisfied, the damper moves to the fully closed 2. If Y1 is energized for more than 20 minutes, and Y2 is
position when IFM is deenergized. not energized (whether or not a 2-stage thermostat is
When the outdoor-air temperature is below the OAT setting used), the compressor and OFM are energized. The posi-
and the thermostat calls for Y1 and G (cooling), the economiz- tion of the EconoMi$er damper is maintained at its cur-
er damper moves to the minimum position when the evapora- rent value.
tor fan starts. The first stage of cooling is provided by the econ- 3. If Y1 is energized, and the compressor is already ener-
omizer. If the supply-air temperature is above 57 F, a switch on gized (see Step 2) and the room thermostat calls for Y2,
the supply-air thermostat is closed between the T2 terminal and the compressor continues to operate.
the 24 vac terminal. This causes the damper to continue to 4. If the compressor is energized and the thermostat is satis-
modulate open until the supply-air temperature falls below fied, the compressor, the OFM, and IFM are deenergized
55 F or the damper reaches the fully open position. and the EconoMi$er modulates closed.
When the supply-air temperature is between 55 F and 52 F, When the OAT is below the MECH CLG LOCKOUT set
the supply-air thermostat has open switches between the T2 point, the compressors remain off.
and 24 vac terminals and between the T1 and 24 vac terminals.
This causes the economizer damper to remain in an intermedi- HEATING, UNITS WITHOUT ECONOMIZER — Upon a
call for heating through W1 and “G”, indoor (evaporator) fan
ate open position. contactor (IFC) and heater contactor no. 1 (HC1) are energized.
If the supply-air temperature falls below 52 F, a switch on On units equipped for 2 stages of heat, when additional heat is
the supply-air thermostat is closed between the T1 terminal and needed, heater contactor no. 2 is energized through W2.
the 24 vac terminal. This causes the damper to modulate closed HEATING, UNITS WITH ECONOMIZER — When the
until the supply-air temperature rises above 55 F or the damper
reaches the minimum position. room temperature calls for heat through terminal W1 and “G”,
the indoor (evaporator) fan contactor (IFC) and heater contac-
When the supply-air temperature is between 55 F and 57 F, tor no. 1 (HC1) are energized. On units equipped for 2 stages of
the supply-air thermostat has open switches between the T2 heat, when additional heat is needed, heater contactor no. 2 is
and 24 vac terminals. This causes the economizer damper to re- energized through W2. The economizer damper moves to the
main in an intermediate open position. minimum position. When the thermostat is satisfied, the damp-
If the outdoor air alone cannot satisfy the cooling require- er moves to the fully closed position.
ments of the conditioned space, economizer cooling is integrated

36
Operating Sequence — 50HJ008-014 Units by modulating the return and outdoor air dampers to maintain a
COOLING, UNITS WITHOUT ECONOMIZER — When 55 F supply air set point. If the supply-air temperature (SAT) is
the thermostat calls for cooling, terminals G and Y1 are ener- greater than 57 F, the EconoMi$er modulates open, allowing a
gized. The indoor (evaporator) fan contactor (IFC), and com- greater amount of outdoor air to enter the unit. If the SAT drops
pressor contactor no. 1 (C1) are energized and the indoor below 53 F, the outdoor-air damper modulates closed to reduce
(evaporator) fan motor (IFM), compressor no. 1, and condenser the amount of outdoor air. When the SAT is between 53 and
fans start. The outdoor (condenser) fan motors (OFM) run con- 57 F, the EconoMi$er maintains its position.
tinuously while unit is cooling. If the thermostat calls for a sec- If outdoor air alone cannot satisfy the cooling requirements
ond stage of cooling by energizing Y2, compressor contactor of the conditioned space, and the OAT is above the MECH
no. 2 (C2) is energized and compressor no. 2 starts. CLG LOCKOUT set point, the EconoMi$er integrates free
COOLING, UNITS WITH DURABLADE ECONO- cooling with mechanical cooling. This is accomplished by the
MIZER — When the outdoor-air temperature is above the strategies below.
outdoor-air temperature (OAT) setting and the room thermostat NOTE: Compressor has a two-minute Minimum On, Mini-
calls for cooling, the compressor contactor no. 1 is energized to mum Off, and Interstage delay timer.
start compressor no. 1 and outdoor (condenser) fan motors 1. If Y1 is energized, and the room thermostat calls for Y2
(OFM). The indoor (evaporator) fan motor (IFM) is energized (2-stage thermostat), compressor no. 1 and OFM are en-
and the economizer damper moves to the minimum position. ergized. The position of the EconoMi$er damper is main-
Upon a further call for cooling, compressor contactor no. 2 will tained at its current value.
be energized, starting compressor no. 2. After the thermostat is 2. If Y1 is energized for more than 20 minutes, and Y2 is
satisfied and the IFM is deenergized, the damper moves to the
not energized (whether or not a 2-stage thermostat is
fully closed position. used), compressor no. 1 and OFM are energized. The po-
When the outdoor-air temperature is below the OAT setting sition of the EconoMi$er damper is maintained at its cur-
and the thermostat calls for Y1 and G (cooling), the economiz- rent value.
er damper moves to the minimum position when the evapora- 3. If Y1 is energized, and compressor no. 1 is already ener-
tor fan starts. The first stage of cooling is provided by the econ-
omizer. If the supply-air temperature is above 57 F, a switch on gized (see Step 2) and the room thermostat calls for Y2, the
compressor continues to operate. If Y2 remains energized
the supply-air thermostat is closed between the T2 terminal and for more than 20 minutes, compressor no. 2 is energized.
the 24 vac terminal. This causes the damper to continue to
modulate open until the supply-air temperature falls below NOTE: Compressor no. 2 cannot be energized unless there is a
55 F or the damper reaches the fully open position. signal for Y2 from the space thermostat.
When the supply-air temperature is between 55 F and 52 F, 4. If compressor no. 2 is energized, and the Y2 signal from
the supply-air thermostat has open switches between the T2 the thermostat is satisfied, compressors 1 and 2 are deen-
and 24 vac terminals and between the T1 and 24 vac terminals. ergized. Reasserting Y2 will start compressor no. 1 and
This causes the economizer damper to remain in an intermedi- (after a 20-minute interstage delay) compressor no. 2.
ate open position. 5. If compressor no. 1 is energized and the thermostat is sat-
If the supply-air temperature falls below 52 F, a switch on isfied, compressor no. 1, the OFM, and IFM are deener-
the supply-air thermostat is closed between the T1 terminal and gized and the EconoMi$er modulates closed.
the 24 vac terminal. This causes the damper to modulate closed When the OAT is below the MECH CLG LOCKOUT set
until the supply-air temperature rises above 55 F or the damper point, the compressors remain off.
reaches the minimum position. HEATING, UNITS WITHOUT ECONOMIZER — Upon a
When the supply-air temperature is between 55 F and 57 F, call heating through terminal W1 and “G”, indoor (evaporator)
the supply-air thermostat has open switches between the T2 fan contactor (IFC) and heater contactor no. 1 (HC1) are ener-
and 24 vac terminals. This causes the economizer damper to re- gized. On units equipped for 2 stages of heat, when additional
main in an intermediate open position. heat is needed, HC2 is energized through W2.
If the outdoor air alone cannot satisfy the cooling require- HEATING, UNITS WITH ECONOMIZER — When the
ments of the conditioned space, economizer cooling is integrat- room thermostat calls for heat through terminal W1, the indoor
ed with mechanical cooling, providing second stage cooling. (evaporator) fan contactor (IFC) and heater contactor no. 1
Compressor no. 1 and condenser fans will be energized, and (HC1) are energized. On units equipped for 2 stages of heat,
the position of the economizer damper will be determined by when additional heat is needed, HC2 is energized through W2.
the supply-air temperature. Compressor no. 2 is locked out. The economizer damper moves to the minimum position.
When the second stage of cooling is satisfied, the compres- When the thermostat is satisfied, the damper moves to the fully
sor and OFMs will be deenergized. The damper position will closed position.
be determined by the supply-air temperature. Differential Enthalpy Switchover Strategy —
When the first stage of cooling is satisfied, the IFM shuts off On certain EconoMi$er controller models, the differential
and the damper will move to fully closed position. enthalpy switchover strategy must be enabled manually.
COOLING, UNITS WITH ECONOMI$ER — When the To determine the controller model, refer to the label on the
outdoor-air temperature (OAT) is above the ECON SP set point front of the controller. Models AD-DME1701-0 require no
and the room thermostat calls for Stage 1 cooling (R to G + commissioning for differential enthalpy switchover strategy.
Y1), the indoor (evaporator) fan motor (IFM) is energized and Models AD-DME1701-1 or AD-DME1711-1 require manual
the EconoMi$er damper modulates to minimum position. The configuration. To enable differential enthalpy:
compressor contactor is energized to start the compressor and
outdoor (condenser) fan motor (OFM). After the thermostat is Press and hold the CONFIG button for more than 30 sec-
onds, then release. The LED flashes twice and the controller re-
satisfied, the damper modulates to the fully closed position sumes normal operation.
when the IFM is deenergized.
When the OAT is below the ECON SP setting and the room To return to single enthalpy mode, press and hold the CON-
FIG button for more than 30 seconds, then release. The LED
thermostat calls for Stage 1 cooling (R to G + Y1), the flashes once and the controller resumes normal operation.
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling

37
SERVICE

When servicing unit, shut off all electrical power to unit


and tag disconnect to avoid shock hazard or injury from
rotating parts.
Cleaning — Inspect unit interior at the beginning of each
heating and cooling season or as operating conditions require.
EVAPORATOR COIL — Inspect whenever filters are
checked (see Filters section), and clean evaporator coil annu-
ally or as required. Clean with commercial coil cleaner.
1. Turn unit power off and install lockout tag. Remove
evaporator coil access panel.
2. If accessory economizer is installed, remove economizer
by disconnecting 12-pin Molex plug and removing econo-
mizer mounting screws (see Fig. 15 or 26). Refer to Acces- Fig. 47 — Cleaning Condenser Coil (Sizes 008-014)
sory Economizer Installation Instructions for more details.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canister. Wash both sides
of coil and flush with clean water. For best results,
backflush toward return-air section to remove debris.
5. Flush condensate pan after completion.
6. Reinstall economizer and filters.
7. Reconnect wiring.
8. Replace access panels.
CONDENSER COILS — Inspect coils monthly. Clean con-
denser coils annually, and as required by location and outdoor-
air conditions.
Clean coils as follows: Fig. 48 — Propping Up Top Panel (Sizes 006,007)
1. Turn off unit power and install lockout tag.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 46 or 47. To
hold top panel open, place coil corner post between top
panel and center post. See Fig. 48 or 49.
4. Remove screws securing coil to center post.
5. Remove fastener holding coil sections together at return
end of condenser coil. Carefully separate the outer coil
section 76 to 102 mm (3 to 4 in.) from the inner coil sec-
tion. See Fig. 50 or 51.
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and de-
bris. Clean the outer surfaces with a stiff brush in the nor-
mal manner.

Fig. 49 — Propping Up Top Panel (Sizes 008-014)

7. Secure inner and outer coil rows together with a field-


supplied fastener.
8. Reposition the outer coil section, and remove the coil cor-
ner post from between the top panel and center post. In-
stall the coil corner post, coil center post and replace all
screws.
CONDENSATE DRAIN — Check and clean each year at
start of cooling season. In winter, keep drain dry or protect
against freeze-up.
FILTERS — Clean or replace at start of each heating and cool-
ing season, or more often if operating conditions require it. Re-
placement filters must be same dimensions as original filters.
OUTDOOR-AIR INLET SCREEN — Clean screen annual-
ly and clean as necessary. Clean screens with steam or hot
water and a mild detergent. Do not use disposable filters in
place of screens.
Fig. 46 — Cleaning Condenser Coil (Sizes 006,007)

38
Economizer Adjustment — Refer to Optional Econo-
mizer sections on pages 13 and 16.
High-Pressure Switch — The high-pressure switch
contains a Schrader core depressor, and is located on the com-
pressor hot gas line. This switch opens at 428 psig and closes at
320 psig. No adjustments are necessary.
Loss-Of-Charge Switch — The loss-of-charge switch
contains a Schrader core depressor, and is located on the com-
pressor liquid line. This switch opens at 7 psig and closes at
22 psig. No adjustments are necessary.
Freeze-Stat — The freeze-stat is a bimetal temperature-
sensing switch that is located on the “hair-pin” end of the evap-
orator coil. The switch protects the evaporator coil from freeze-
up due to lack of airflow. The switch opens at 30 F and closes
at 45 F. No adjustments are necessary.
Cycle-LOC™ Device — The system is protected with a
Cycle-LOC device so that the compressor will not start or con-
tinue to run should a high pressure, loss of charge or freeze-stat
open. To reset the Cycle-LOC device, set the thermostat to
eliminate cooling demand, then return to original set point.
This should be done only once, and if system shuts down due
Fig. 50 — Separating Coil Sections (Sizes 006,007) to the same fault, determine the problem before attempting to
reset the Cycle-LOC device.
Overload Relay (OLR) — This relay is a 24-volt tem-
perature sensing switch embedded into the evaporator motor
windings. Should the motor winding develop excessive heat
for any reason, the switch will open the “R” (red wire) from the
low voltage transformer. When this switch opens the low volt-
age circuit is deenergized. The switch is automatically reset.
Refrigerant Charge — Amount of refrigerant charge is
listed on unit nameplate (also refer to Tables 1A and 1B). Refer
to Carrier Refrigerant Service Techniques Manual, Chapter 1,
Refrigerants section.
Unit panels must be in place when unit is operating during
charging procedure. Unit must operate a minimum of 10 min-
utes before checking or adjusting charge.
NO CHARGE — Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refriger-
ant (refer to Tables 1A and 1B).
LOW CHARGE COOLING — Use Cooling Charging Charts,
Fig. 53-58. Vary refrigerant until the conditions of the appropri-
Fig. 51 — Separating Coil Sections (Sizes 008-014) ate chart are met. Note that charging charts are different from
the type normally used. Charts are based on charging the units
Blower Belt Adjustment — Inspect blower belt for to the correct superheat for the various operating conditions.
Accurate pressure gage and temperature sensing device are re-
wear and proper belt tension, and pulley alignment as condi- quired. Connect the pressure gage to the service port on the
tions require, or at the beginning of each heating and air condi-
tioning season. Refer to step 7 — Adjust Evaporator Fan suction line. Mount the temperature sensing device on the suc-
tion line and insulate it so that outdoor ambient temperature
Speed on page 21 for adjustment and alignment procedures. does not affect the reading. Indoor-air L/s (cfm) must be within
Lubrication the normal operating range of the unit.
COMPRESSORS — Each compressor is charged with correct TO USE COOLING CHARGING CHART — Take the out-
amount of oil at the factory. door ambient temperature and read the suction pressure gage.
Refer to appropriate chart to determine what the suction tem-
FAN MOTOR BEARINGS — Fan motor bearings are per- perature should be. If suction temperature is high, add refriger-
manently lubricated. No further lubrication of condenser- or
evaporator-fan motors is required. ant. If suction temperature is low, carefully recover some of the
charge. Recheck the suction pressure as charge is adjusted.
Condenser Fan Adjustment (Fig. 52) EXAMPLE: (Fig. 53)
1. Shut off unit power supply and tag disconnect. Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . .29 C (85 F)
2. Remove condenser-fan assembly (grille, motor, motor Suction Pressure . . . . . . . . . . . . . . . . . . . . . . .483 kPa (70 psig)
cover, and fan) and loosen fan hub setscrews. Suction Temperature should be . . . . . . . . . . . . . . . . .8 C (46 F)
3. Adjust fan height as shown in Fig. 52. (Suction Temperature may vary ± 2.5 C [5 F].)
4. Tighten setscrews and replace condenser-fan assembly.

39
FAN HEIGHT
UNIT “A”
VOLTAGE
in. mm
220 v 2.75 70
440 v 3.50 89
Fig. 52 — Condenser Fan Adjustment

Fig. 53 — Cooling Charging Chart, 50HJ006 Fig. 54 — Cooling Charging Chart, 50HJ007

40
Fig. 55 — Cooling Charging Charts, 50HJ008

Fig. 56 — Cooling Charging Charts, 50HJ009

41
Fig. 57 — Cooling Charging Charts, 50HJ012

Fig. 58 — Cooling Charging Charts, 50HJ014

42
TROUBLESHOOTING
Tables 31-33 are provided for troubleshooting the unit and economizer.
Table 31 — Cooling Troubleshooting
PROBLEM CAUSE REMEDY
Compressor and Power failure. Call power company.
condenser fan Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker.
will not start.
Defective thermostat, contactor, transformer, or control Replace component.
relay.
Insufficient line voltage. Determine cause and correct.
Incorrect or faulty wiring. Check wiring diagram and rewire correctly.
Thermostat setting too high. Lower thermostat setting below room temperature.
High-pressure switch tripped. See problem ‘‘Excessive head pressure.’’
Low-pressure switch tripped. Check for leaks, repair, and recharge.
Freeze-up protection thermostat tripped. See problem ‘‘Suction pressure too low.’’
Compressor will not start Faulty wiring or loose connections in compressor circuit. Check wiring and repair or replace.
but outdoor fan runs. Compressor motor burned out, seized, or internal Determine cause. Replace compressor.
overload open.
One leg of 3-phase power dead. Replace fuse or reset circuit breaker.
Determine cause.
Compressor cycles (other than Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and
normally satisfying thermostat). recharge to nameplate.
Defective compressor. Replace and determine cause.
Insufficient line voltage. Determine cause and correct.
Blocked condenser. Determine cause and correct.
Defective thermostat. Replace thermostat.
Faulty condenser-fan motor or capacitor. Replace.
Restriction in refrigerant system. Locate restriction and remove.
Compressor operates Dirty air filter. Replace filter.
continuously. Unit undersized for load. Decrease load or increase unit size.
Thermostat set too low. Reset thermostat.
Low refrigerant charge. Locate leak, repair, and recharge.
Leaking valves in compressor. Replace compressor.
Air in system. Recover refrigerant, evacuate system, and
recharge.
Condenser coil dirty or restricted. Clean coil or remove restriction.
Scroll compressor makes Compressor rotating in the wrong direction. Reverse the 3-phase power leads as described in
excessive noise Start-Up, page 35.
Excessive head pressure. Dirty air filter. Replace filter.
Dirty condenser coil. Clean coil.
Refrigerant overcharged. Remove excess refrigerant.
Air in system. Recover refrigerant, evacuate system, and
recharge.
Condensing air restricted or air short-cycling. Determine cause and correct.
Head pressure too low. Low refrigerant charge. Check for leaks, repair, and recharge.
Compressor valves leaking. Replace compressor.
Compressor rotation incorrect. Ensure compressor rotation is correct per start-up
procedure.
Restriction in liquid tube. Remove restriction.
Excessive suction pressure. High heat load. Check for source and eliminate.
Compressor valves leaking. Replace compressor.
Compressor rotation incorrect. Ensure compressor rotation is correct per start-up
procedure.
Refrigerant overcharged. Recover excess refrigerant.
Suction pressure too low. Dirty air filter. Replace filter.
Low refrigerant charge. Check for leaks, repair, and recharge.
Metering device or low side restricted Remove source of restriction.
Insufficient evaporator airflow. Increase air quantity. Check filter and replace if
necessary.
Temperature too low in conditioned area. Reset thermostat.
Field-installed filter drier restricted. Replace.
Outdoor ambient temperature below –4 C (25 F). Install low-ambient kit.
Compressor no. 2 Unit in economizer mode. Proper operation; no remedy necessary.
(sizes 008-014)
will not run.

43
Table 32 — Durablade Economizer Troubleshooting
PROBLEM CAUSE REMEDY
Damper does not Indoor (evaporator) fan is 1. Check to ensure that 24 vac is present at terminal C1 on the IFC or that 24 vac is
open. off. present at the IFO terminal. Check whether 24 vac is present at PL6-1 (red wire)
and/or PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label
diagram).
2. Check proper thermostat connection to G on the connection board.
No power to economizer 1. Check that SW3 is properly making contact with the damper blade. Check that
motor. SW1 is in the NC (normally closed) position.
2. Check diode D18. If diode is not functioning properly, replace economizer control board.
3. Confirm that the economizer control board is grounded properly at PL6-4 (brown
wire) and at brown terminal of the economizer control board (brown wire). The
economizer motor must also be grounded properly at the negative motor terminal
(brown wire).
4. Verify SW1 and SW3 are working and wired properly (see unit label diagram).
5. Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black wire). If 24 vac
not present, check unit wiring (see unit label diagram). If 24 vac is found in both
places, check for 24 vac at the yellow terminal of the economizer control board
(yellow wire). If 24 vac power is not present, replace the economizer control board.
Economizer motor failure. If the indoor (evaporator) fan and economizer motor are energized, verify that there is a
minimum of 18 vdc at the positive motor terminal. If the motor is not operating,
replace the motor.
Economizer operation OAT or EC set too high. 1. Set at correct temperature (3 F below indoor space temperature).
limited to minimum 2. Check OAT or EC by setting above outdoor temperature or humidity level. If the
position. OAT or EC switches do not close, replace OAT or EC.
Economizer control board 1. Perform the following tests when OAT or EC is closed. Y1 is called for, and damper
incorrectly wired or not is at minimum position. Confirm 24 vac on gray terminal of the economizer control
functioning. board (gray wire). If 24 vac is not present, check wiring (see unit label diagram).
2. Verify that SW1 and SW3 are wired correctly and working properly (see unit label
diagram).
3. Check to ensure that 24 vac exists at PL6-2 (blue wire). If 24 vac is not present,
check wiring (see unit wiring label diagram).
4. Check 24 vac output at PL6-10 (white wire). If 24 vac is not present, replace
economizer control board.
Incorrect SAT wiring or 1. After verifying that the OAT and EC settings and the economizer control board wir-
inoperative SAT. ing are correct, check to ensure that the 24 vac terminal of the SAT has 24 vac
(white wire). If OAT, EC, and control board are functioning and wired properly and
no 24 vac exists, check wiring (see unit label diagram).
2. If supply-air temperature is greater than 57 F, 24 vac should be found at terminal
T2 on the SAT (pink wire). If 24 vac is not present, replace SAT.
Damper does not Incorrect economizer 1. Verify that SW2 and SW4 are wired and working properly (see unit label diagram).
close. wiring. 2. Check diode D19. If diode is not functioning properly, replace economizer control board.
Incorrect damper actuator 1. After verifying that the wiring is correct, modulate the damper to the minimum posi-
wiring or inoperative tion. Remove the calls for G.
economizer circuit board. 2. If the damper does not move, check for 24 vac at PL6-1 (red wire). If 24 vac is not
present, check wiring (see unit label diagram).
3. If damper still does not move, check for 24 vac at blue terminal of economizer con-
trol board (blue wire). If 24 vac is not present, replace the economizer control board.
Incorrect SAT wiring or 1. After verifying that the wiring is correct and the economizer control board is func-
inoperative SAT. tioning properly, place the OAT or EC switch in the closed position. Place a call for
Y1 and open the damper to the fully open position. Confirm that the 24 vac terminal
of the SAT has 24 vac (white wire). If 24 vac is not present, check wiring (see unit
label diagram).
2. If supply-air temperature is less than 52 F, 24 vac should be found at terminal T1
on the SAT (violet wire). If 24 vac not found, replace SAT.
Economizer motor failure. If economizer control board and SAT are functioning properly, verify that there is a
minimum of 18 vdc at the positive motor terminal. If a minimum of 18 vdc is present
and the motor is still not operating, replace the motor.
Economizer damper Insufficient battery power, 1. Check voltage potential across batteries. If lower than 14 vdc, replace close-on-
does not close on inoperative economizer power-loss power supply (9-v alkaline batteries). Check this emergency power sup-
power loss. control board. ply on a regular basis or whenever the filters are changed.
2. If the close-on-power-loss and economizer control board are functioning properly,
check for 14 vdc or higher at the blue terminal of the economizer control board
(blue wire) when power is disconnected from unit. If 14 vdc is not present, replace
the control board.
LEGEND
C1 — Common Power
EC — Enthalpy Control
IFC — Indoor (Evaporator) Fan Contactor
IFO — Indoor (Evaporator) Fan On
OAT — Outdoor-Air Thermostat
PL — Plug
SAT — Supply-Air Thermostat
SW — Economizer Position Switch

44
Table 33 — Troubleshooting
PROBLEM POTENTIAL CAUSE REMEDY
Damper Does Not Indoor (Evaporator) Fan is Check to ensure that 24 vac is present at Terminal C1 (Common Power)
Open Off on the IFC (Indoor Evaporator Fan Contactor) or that 24 vac is present at
the IFO (Indoor Evaporator Fan On) terminal. Check whether 24 vac is
present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is
not present, check wiring (see unit label diagram).
Check proper thermostat connection to G on the connection board.
No Power to EconoMi$er Check to ensure that 24 vac is present across Terminals 24 VAC and
Controller 24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring
(see unit label diagram). If 24 vac is present, STATUS light should be on
constantly.
No Power to G Terminal If IFM is on, check to ensure 24 vac is present on G Terminal of the
EconoMi$er controller. If 24 vac is not present, check wiring (see unit
label diagram).
Controller Fault If STATUS light is flashing one flash, the EconoMi$er controller is
experiencing a fault condition. Cycle power to the controller. If condition
continues, replace the EconoMi$er controller.
Thermostat Fault If STATUS light is flashing two flashes, the EconoMi$er controller believes
the thermostat is wired incorrectly. Check wiring between the thermostat
and the connection board in the electrical panel. The fault condition is
caused by Y2 being energized before Y1.
Actuator Fault Check the wiring between the EconoMi$er controller and the actuator.
Hold CONFIG button between 3 and 10 seconds to verify the
actuator’s operation. (This process takes 3 minutes to complete.)
EconoMi$er Minimum Position Set Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%)
Operation Limited to Incorrectly to 100% to verify operation, and then set to correct setting.
Minimum Position EconoMi$er Changeover Set at correct value. See Table 5.
Set Point Set Too High or
Too Low
Supply Air Temperature If STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is
Sensor Faulty faulty. Check wiring or replace sensor.
Outdoor Air Temperature If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is
Sensor Faulty faulty. Check wiring or replace sensor.
Damper Position Supply Air Low Limit The supply-air temperature is less than 45 F, causing the minimum
Less than Minimum Strategy Controlling position to be decreased. Refer to the Start-Up instructions. Verify correct
Position Set Point setting of MIN POS (%). If correct, EconoMi$er is operating correctly.
Damper Does Not CO2 Ventilation Strategy If a CO2 sensor is being used, and the damper position is greater than
Return to Minimum Controlling minimum position, the ventilation control strategy is controlling. Refer to
Position the Start-Up instructions. EconoMi$er is operating correctly.
Damper Does Not Damper Travel is Check to ensure the damper is not blocked.
Close on Power Loss Restricted
LEGEND
IFM — Indoor Fan Motor
PL — Plug

45
Fig. 59 — Typical Wiring Diagram and Component Arrangement (50HJ007)

46
Fig. 59 — Typical Wiring Diagram and Component Arrangement (50HJ007) (cont)

47
Fig. 60 — Typical Wiring Diagram and Component Arrangement (50HJ008-014)

48
Fig. 60 — Typical Wiring Diagram and Component Arrangement (50HJ008-014) (cont)

49
LEGEND FOR FIG. 58 AND 59 — TYPICAL WIRING SCHEMATIC AND
COMPONENT ARRANGEMENT
IMPORTANT: Refer to unit wiring label for actual
unit wiring information.

LEGEND
AHA — Adjustable Heat Anticipator QT — Quadruple Terminal
AWG — American Wire Gage R — Relay
C — Contactor, Compressor SAT — Supply-Air Thermostat
CAP — Capacitor SW1 — Switch Fully Open
CB — Circuit Breaker SW2 — Switch Fully Closed
CC — Cooling Compensator SW3 — Switch Minimum Vent Position
CLO — Compressor Lockout SW4 — Switch Maximum Vent Position
COMP — Compressor Motor TB — Terminal Block
EC — Enthalpy Control TC — Thermostat-Cooling
ECON — Economizer TH — Thermostat-Heating
EPS — Emergency Power Supply TRAN — Transformer
EQUIP — Equipment Field Splice
ER — Economizer Relay
FPT — Freeze-Up Protection Thermostat Marked Wire
FSS — Filter Status Switch
FU — Fuse Terminal (Marked)
GND — Ground Terminal (Unmarked)
HC — Heater Contactor
HPS — High-Pressure Switch Terminal Block
IFC — Indoor-Fan Contactor
IFM — Indoor-Fan Motor Terminal Econ 2 Position Board
IFMOVL — Indoor-Fan Motor Overload Splice
IFR — Indoor-Fan Relay
LPS — Low-Pressure Switch Splice (Marked)
LSM — Limit Switch (Manual Reset) Factory Wiring
MTR — Motor
OAT — Outdoor-Air Thermostat —— Field Control Wiring
OFC — Outdoor Fan Contactor Field Power Wiring
OFM — Outdoor Fan Motor
OLR — Overload Relay Accessory or Optional Wiring
P — Plug To indicate common potential only.
PL — Plug Assembly Not to represent wiring.

NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90° C wire
or its equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostat: HH07AT170,172
Subbase: HH93AZ176,177,178, and 179
4. Set heat anticipator at .8 amp for first stage and .3 amp for second stage.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum, or aluminum conductors.

Copyright 2000 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Catalog No. 005-006 Printed in U.S.A. Form 50HJ-C7SI Pg 50 10-00 Replaces: 50HJ-C5SI
Tab 1b 6b
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.: __________________________________ SERIAL NO.: ______________________________________
DATE: ________________________________________ TECHNICIAN: _____________________________________
BUILDING LOCATION: _____________________________

II. PRE-START-UP (insert checkmark in box as each item is completed)


 VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
 CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
 CHECK THAT INDOOR AIR FILTERS ARE CLEAN AND IN PLACE
 VERIFY THAT UNIT INSTALLATION IS LEVEL
 CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS
 CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS

CUT ALONG DOTTED LINE


III. START-UP
ELECTRICAL
SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1
CIRCUIT 1 COMPRESSOR AMPS L1 L2 L3
CIRCUIT 2 COMPRESSOR AMPS L1 L2 L3
INDOOR FAN AMPS L1 L2 L3

TEMPERATURES
OUTDOOR-AIR TEMPERATURE DB
RETURN-AIR TEMPERATURE DB WB
COOLING SUPPLY AIR DB WB

PRESSURES
REFRIGERANT SUCTION, CIRCUIT 1 °F/C

CUT ALONG DOTTED LINE


REFRIGERANT SUCTION, CIRCUIT 2
(SIZES 008-014 ONLY) °F/C
REFRIGERANT DISCHARGE, CIRCUIT 1 °F/C
REFRIGERANT DISCHARGE, CIRCUIT 2
(SIZES 008-014 ONLY) °F/C

 VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION


 VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGES 40-42.

Copyright 2000 Carrier Corporation