C Standard driver
communication Variation 1a:
Windpark
Park
communication Park
Windpark Park
Windpark Park server is connected
level level level
level level level to the turbine PLCs via
WinCC OA driver
communication.
No server on the turbine
T
Variation 1c:
Turbine
Turbine server is
Turbine
Turbine Turbine
Turbine Turbine
level level
level level
level
Driver
connected to the turbine
level
PLC via WinCC OA driver
communication
PLC
M u l t i l e v e l W i n d S C A D A C e n t e r
Control room
C C C
level
Park level C C C
Turbine level T T T T
PARK MODULE
C
MAPS MODULE CCTV MODULE
ALARM MODULE
DETAIL MODULE TREND MODULE
CCTV MODULE
PARK DETAIL
MODULE MODULE
MAPS TREND
MODULE MODULE
CCTV MODULE
T
Turbine library
Technical assumptions:
Based on our experience the following number of tags/IO´s seems to be sufficient:
Total: max. 3,500 tags per turbine
Performance assumptions:
• 15 turbines per park
• The analog values are read every second
PARK SERVER
• 1 WinCC OA server • Redundant park server
Park
Windpark
Standard driver
communication
53,000 I/O’ s configuration C
level • 6 WinCC OA UI client • Web Client(s)
level
• 1 Driver: (e.g.) • External database (Oracle)
• IEC61400 Control center library
• OPC
• S7
• Modbus
• …
Turbine
Turbine
level
level
Turbine
Turbine
level
level
Park
Windpark
level
level
Central
Control
SERVER
• 1 WinCC OA server • Redundant park server
room
control 16,000 I/O’s configuration
level
level • 6 WinCC OA UI client • Web Client(s) C
• Dist • External database (Oracle)
Control center library
WinCC OA TCP/IP
Park communication
Windpark
level
level
30% of the turbine information will be
forwarded / used (=157,500 I/O’s)
subject to vary depending on
project
• 1 WinCC OA server • Redundant park server
3,500 I/O’s configuration
• 1 WinCC OA UI client • Ultralight Client
Turbine
Turbine
level
level
Driver
• Dist
• 1 Driver: (e.g.)
• External database (Oracle)
T
• IEC61400
• OPC
PLC • S7 Turbine library
• Modbus
• …
© Siemens AG 2014 All rights reserved.
2014-07-01 Petar Anic / VMM Wind
Proposed WinCC OA configurations – Variation 2c
Central
Control
SERVER
• 1 WinCC OA server • Redundant park server C
room
control
level
16,000 I/O’s configuration
level • 6 WinCC OA UI client • Web Client(s) Control center library
• Dist • External database (Oracle) 30% of the turbine information will be
forwarded / used (=15,750 I/O’s)
PARK SERVER
WinCC OA TCP/IP • 1 WinCC OA server • Redundant park server subject to vary depending on project
communication
42,000 I/O’s configuration
Park
Windpark
• 6 WinCC OA UI client • Web Client(s)
level
level
• Dist • External database (Oracle)
C
Control center library
80% of the turbine information will be
• 1 WinCC OA server • Redundant park server forwarded/used (=42,000 I/O’s)
3,500 I/O’s configuration subject to vary depending on project
• 1 WinCC OA UI client • Ultralight Client
Turbine
Turbine • Dist • External database (Oracle)
level
level Driver • 1 Driver: (e.g.)
• IEC61400 T
• OPC
PLC • S7
• Modbus Turbine library
Control room server and park server do have
• … parallel communication to each turbine server.
© Siemens AG 2014 All rights reserved.
2014-07-01 Petar Anic / VMM Wind
Security information
Siemens provides products and solutions with industrial security functions that support the secure
operation of plants, solutions, machines, equipment and/or networks. They are important
components in a holistic industrial security concept. With this in mind, Siemens’ products and
solutions undergo continuous development. Siemens recommends strongly that you regularly
check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable
preventive action (e.g. cell protection concept) and integrate each component into a holistic,
state-of-the-art industrial security concept. Third-party products that may be in use should also
be considered. For more information about industrial security, visit
http://www.siemens.com/industrialsecurity.
To stay informed about product updates as they occur, sign up for a product-specific newsletter.
For more information, visit http://support.automation.siemens.com.