Professional Documents
Culture Documents
System and
Design
Part 1
THE BUILDING WATER
SUPPLY SYSTEM
Building Main
Water Meter
Water Service
General Water Distribution System Layout
Rigid-Pipe Distribution
Configuration
The hot and cold water distribution
pipes are installed parallel to one
another as they convey hot and
cold water to risers and branch
pipes.
Downfeed distribution
Downfeed distribution systems may be designed for
building more than six stories in height. Water is
pumped to the roof of the building to storage tanks.
The water from the storage tanks serves the floors
below due to the force of gravity.
Upfeed and Downfeed Distribution
1.Hydrostatic Pressure
Code specifies that the highest (most remote outlet) fixture have a
minimum pressure of 8 psi (55 kPa) for flush tanks and 15 psi (103
kPa) for fixtures with flushometer valves.
𝜟𝑷𝒔𝒕𝒂𝒕𝒊𝒄 = −0.433𝑍
𝜟𝑷𝒔𝒕𝒂𝒕𝒊𝒄 in KPa
SI Units
Z in meter
𝜟𝑷𝒔𝒕𝒂𝒕𝒊𝒄 = −9.8𝑍
𝜟𝑷𝒇𝒓𝒊𝒄𝒕𝒊𝒐𝒏 = 𝟐 𝑷𝒔𝒊
Pressure Losses from Friction
In addition to pipe length, friction loss from fittings and valves must be
taken into account. Analysis is usually founded on the equivalent length
based on type of valve or fitting. As a minimum, pressure drop analysis
should be performed to ensure that pressure available at the most remote
outlet (farthest and highest fixture) is adequate.
Pressure Losses from Friction
EXAMPLE
Determine the equivalent length of six 90° elbows, three straight-run tees
(all wrought), and two gate valves for 1 in diameter copper pipe:
Valves can develop cavitation when they are partially closed and
flow is restricted. The result is noise and possible damage from
erosion.
Cross-Connections
A cross-connection is an unsatisfactory
connection or arrangement of piping that can
cause nonpotable water to enter the potable
water system. A cross-connection can cause
used or contaminated water to mix with the
water supply.
Water Hammer
A large pressure develops when fluid
moving through a pipe is suddenly
stopped. The sudden closing of a valve
will cause fast-flowing water to stop
quickly, resulting in a large increase in
pressure
Thermal Expansion
Some expansion in the pipe will occur. This expansion must be
considered in the design of the system. The amount of expansion
will depend on the type of piping material and the range of
temperatures that the pipe will be subjected. Expansion of copper
tubing is slightly greater than one inch in a 100 ft length in a 100°F
temperature change.
Viscosity
As water flows through a pipe, its viscosity (thickness) decreases
with temperature decrease. Water at 40°F (4°C) is twice as viscous
as water at 90°F (32°C) and four times as much at 170°F (77°C). As a
result, pumping energy and cost are higher when water
temperatures are lower.
Volume Change with Temperature Change
Water is the only substance that can exist as a solid, liquid, and gas at
ordinary temperatures. Like most substances, water expands when it is
heated. Unlike most substances, the volume of water increases when it
freezes.
Aging
Pipes in a plumbing system are used, their
inner walls become increasingly rough. The
effects of aging in a plumbing system are
related to piping material, quality of water
(e.g., hard versus soft), and water
temperature. Buildup from calcium
deposits (especially in high-temperature
hard water) and corrosion (especially in
ferrous pipe materials) reduces the inside
opening in the pipe, which restricts flow.
Pipe Insulation
Pipe insulation is applied to the outer walls of
piping to reduce heat loss from the pipe or
prevent condensation on the outside pipe
walls.
Testing
The water supply system should be tested for leaks before it is
covered with finish materials to determine if it is watertight. Tests
commonly run on water systems require that it be watertight under
a hydrostatic water pressure of 125 psi for a minimum of 1 hr.
Leaks
Plumbing leaks contribute
significantly to water
consumption in operating
plumbing systems.