MV1 AHU1 MV4 AHU2 MV7 AHU3 MV10 AHU4 MV13 AHU5
Egg Setter Hatcher Chick Pull
32ø 50ø 40ø 40ø 25ø
Room Rooms Rooms Rooms Rooms
MV17 0.72l/s 1.59l/s 1.17l/s 1.35l/s 0.25l/s
100ø
T12 P23
10.78l/s
100ø
T13
10.78l/s
Chick Master Hatchers VF96 EmTech Hatchers VT204‐165‐17
T14
25ø
25ø
80ø
6.38l/s Hatcher
25ø
NOTES
Setter
All drawings supplied are for guidance only. Local installer to co‐ordinate new services with building infrastructure.
Pump
Any change in design to be notified to EmTech to ensure that the system will meet the required performance criteria.
All pipework to be insulated to minimise heat loss/gain.
Pipework installation to follow TR20.
Strainer
All pipework to be thoroughly flushed before system commissioning and an inhibiter added to stop corrosion and bacterial
growth.
Non‐return Valve
Where the ambient temperature drops below freezing (0 deg C) a glycol solution should be added to meet the minimum
temperature to stop the system freezing.
Double Regulating Valve
Suitable mains water connection to meet local regulations to be connected to the system either through a pressurised top
up unit (closed system) or a ball valve arrangement within the buffer tank (open system).
Isolating Valve Please referee to individual equipment specifications for connection details and clearance recommendations.
All materials for the pipework to be supplied by local installer.
Two Port Motorised Control Valve
It is recommended that black mild steel is used for both the Chilled Water System and LTHW systems.
Three Port Motorised Control Valve Drain valves, automatic air‐vents, temperature and pressure gauges to be installed to ensure system functionality.
All pumps supplied are single‐stage, low‐pressure, gladded, in‐line centrifugal pumps with flange connections.
INCUBATION CHILLED WATER SCHEMATIC T‐‐ Temperature Transmitter All dimensions are in mm and indicate internal diameter.
ROSE CHICKS – PAKISTAN CO50220 P‐‐ Pressure Transmitter
DRG. No. CO50220-M-001 SHEET 1 of 1 REV.