You are on page 1of 1

 

       

MV1 AHU1 MV4 AHU2 MV7 AHU3 MV10 AHU4 MV13 AHU5
Egg  Setter Hatcher Chick  Pull 
32ø 50ø 40ø 40ø 25ø
Room  Rooms Rooms Rooms Rooms
MV17 0.72l/s 1.59l/s 1.17l/s 1.35l/s 0.25l/s

100ø
T12 P23
10.78l/s

100ø
T13
10.78l/s

Chick Master Hatchers VF96 EmTech Hatchers VT204‐165‐17

25ø 65ø 100ø


4.41l/s 13.42l/s

T14
25ø
25ø

EmTech Setters PT24‐165‐17 100ø 150ø Chiller 282kW


Chick Master Setters C576 T11 P21
10.78/s PMP1 PMP3 T15
Chilled Water Warm Water
KEY Buffer Tank Buffer Tank
Min 10,000l Min 10,000l
Heat Recover Coil
PMP2 PMP4

80ø
6.38l/s Hatcher

25ø
NOTES
Setter
 All drawings supplied are for guidance only. Local installer to co‐ordinate new services with building infrastructure.

Pump
 Any change in design to be notified to EmTech to ensure that the system will meet the required performance criteria.
 All pipework to be insulated to minimise heat loss/gain.
 Pipework installation to follow TR20.
Strainer
 All pipework to be thoroughly flushed before system commissioning and an inhibiter added to stop corrosion and bacterial 
growth. 
Non‐return Valve
 Where the ambient temperature drops below freezing (0 deg C) a glycol solution should be added to meet the minimum 
temperature to stop the system freezing.
Double Regulating Valve
 Suitable mains water connection to meet local regulations to be connected to the system either through a pressurised top 
up unit (closed system) or a ball valve arrangement within the buffer tank (open system).
Isolating Valve  Please referee to individual equipment specifications for connection details and clearance recommendations.

   All materials for the pipework to be supplied by local installer.
Two Port Motorised Control Valve
 It is recommended that black mild steel is used for both the Chilled Water System and LTHW systems.

Three Port Motorised Control Valve  Drain valves, automatic air‐vents, temperature and pressure gauges to be installed to ensure system functionality.
 All pumps supplied are single‐stage, low‐pressure, gladded, in‐line centrifugal pumps with flange connections.
INCUBATION CHILLED WATER SCHEMATIC T‐‐ Temperature Transmitter  All dimensions are in mm and indicate internal diameter.
ROSE CHICKS – PAKISTAN CO50220 P‐‐ Pressure Transmitter
DRG. No. CO50220-M-001 SHEET 1 of 1 REV.