Professional Documents
Culture Documents
1 Introduction system of two innovative concepts [6]. The EAHE and the
Fossil fuel have long been used as a significant source of chimney solar will be used as a system that cooling the
energy for human consumption, but as the population room and perceived significantly in its application [7]. The
growth, the need for fossil fuel will also increase. Many room to be cooled is the main target of using both
energy source than fossils to replace energy needs, which conceptual passive cooling systems; the benefits gained can
are the primary of human needs. Solar energy is an option be applied in human life as the supportive innovation in a
that can be maximized to replace existing energy [1]. The renewable energy for the future [8].
use of solar radiation that produces heat can be used to heat Heat transfer is the transfer of heat energy due to the
water in the solar energy heating system and to heat the air temperature differences [9]. There are three known forms
in the Solar Chimney system [2]. Its enormous potential of heat transfer mechanisms, namely conduction,
can support the conversion of used energy into renewable convection, and radiation. Conduction is the transfer of
energy for the future. heat from a place of high temperature to the low
Furthermore, we can also recognize the earth as a temperature in a medium in direct contact. Meanwhile,
natural cooling agent that has long been used by humans to convection is the heat transfer that occurs by two
innovate energy [3]. A constant soil temperature every year mechanisms [10]. In addition, to energy transfer due to
at a depth of 1.5 - 2 m is an idea to use the cold soil as an molecular movement, energy transfer is also transferred
earth-air heat exchanger (EAHE) converter [4]. The due to the large molecular movement of fluid. Meanwhile,
concept of using this soil temperature is to plant one or radiation is the release of energy from a material that is not
more pipes in the ground to obtain a constant cold at zero temperature through electromagnetic waves [11].
temperature along the outer surface of the pipe as a cooling An underground heat exchanger or referred to an Air
media that flows through the pipe. Earth Air Exchanger is a heat exchanger with the use of
This concept continues to be developed by researches one or more pipes buried in the soil to a certain depth [12].
as an innovation in the manufacture of air conditioning, The pipes are made of PVC (polyvinyl chloride), HDPE
depending on the type and condition of the challenge in its (high density polyethylene), or galvanized. The EAHE
application [5]. The concept of EAHE and chimney solar as concept is to utilize the soil as a cooling medium to drain
a unified system rise to the idea of creating a pairing air into the pipe.
In the summer, the hot air releases its contents into the QEAHE,l = hvap Vair ρair (woa,hr –wah,hr) (10)
pipe wall through the convection and then disappears to the
2 Materials and research methods
ground through conduction. The air that comes out will
2.1 Experimental scheme
have a cooler temperature than the surrounding air using
The testing process began at 11:00 am to circulate air into
the cold air as a media of air conditioning. The low
the air heat exchanger from solar chimney. The Cole-
temperature air will undoubtedly depend on the length of
Parmer acquisition data recorded temperatures in the inlet,
the pipe used as a conveying media as well as the depth of
outlet, and solar chimney, and along the heat exchanger
the soil.
pipe. Soil temperatures were also recorded using Cole-
The heat transfer between the airs flowing in the
Parmer acquisition data. Data is connected with the
pipe depends on the surface area of the pipe obtained from
thermocouples. Data acquisition recorded the temperature
the calculation of the diameter and length of the pipe. The
in every minute. The test ended at 4 pm. Then the test was
maller pipe with longer diameters have better thermal
performed in the next day with the same procedure. The
performance, but reduces pressure. The larger the diameter
tests carried out for two consecutive days in July 2020 in
of the pipe cross section, the decrease in speed will occur
the city of Medan. Table 1 shows the specifications of the
with the rate of heat transfer, vice versa.
EAHE system, assembled rooms, and solar chimney.
Equations used in heat transfer and performance
The purpose of this research is to determine how much
analysis in air-ground heat exchangers are as follows:
the temperature reduction resulted from the effect of the
Mass flow rate
performance of the solar chimney and the EAHE as well as
π 2
D ρVa to find out the appropriate of the passive cooling system
ṁ= = 4 (1)
applied. The humidity of the room determine whether the
Np room is suitable to occupied after the cooling effect of the
Pipe thermal resistance EAHE.
1 Table 1. The specification of the eahe
Rpipe = ln (re/ri) (2)
K pipe 2 πL No Data Description
1 Diameter of EAHE pipe d = 0,1016 m
Thermal soil resistance 2 Length of EAHE pipe l =26,5 m3
1 3 Room size mxlxp : 2m x 2m x 2m
Rsoil = ln (R (z,x) | re) 4 Chimney Height t=5m
K soil 2 πL 5 Solar Chimney Diameter d : 0,30 m
(3)
Thermal convection resistance
1
Rconv = (4)
h Ai
Substitute thermal conductivity
1
U=
(Rconv+ Rpipe+ Rsoil)
(5)
Effectiveness of earth air heat exchanger
T ∈−T out
ε= = 1 – e -(hA/ṁCp)
Tin−Twall
(6)
NTU numbers
UA
NTU=
ṁCp Fig 1. Scheme of the study
(7)
3 Result and discussion
Earth air heat exchanger
3.1 Chart of an EAHE inlet versus outlet temperature
QEAHE,t = ṁ ρa (hin-EAHE – hout-EAHE) (8)
Sensible Work
QEAHE,s = ṁ ρa Cp (Tin-EAHE – Tout-EAHE) (9)
Laten
Fig 3. Chart of QEAHE, on July 18, 2020
Figure 3 above shows the working size (W) of the heat
exchanger. The maximum of QEAHE,t is 49.55 W, and the the
lowest of QEAHE, is 11.35 W. Then QEAHE,t is obtained based
on the tests performed is small, because it is a passive
working system with no assistance in distributing air
inside.
The highest performance of QEAHE,t occurs around 2:30
and 3:00 pm. This is due to the high ambient temperature
Fig 2. Inlet-Outlet Temperature Chart on July 18, 2020 enters the EAHE. The lowest performance conditions
From figure 2 above, a significant decrease in occurs around 12:30 - 1:00 pm. The result of Q EAHE,t
temperature occurred during the test on July 18, 2020. The relatively low due to the ambient temperature of the
inlet maximum temperature into the heat exchanger (Tin- environment to circulate into the EAHE.
EAHE) was 32.29 oC, and the lowest was 29.48 oC . The
outlet maximum temperature (Tout-EAHE) was 28.21 oC,
and the lowest was 27.32 oC. The average temperature
reduction that can be carried out by the heat exchanger was
3 to 4 oC.
3.2 Chart of QEAHE,t – QEAHE,s - QEAHE,l Fig 5. Chart of QEAHE,l on July 18, 2020
Acknowledgment
The author would like to thank DRPM DIKTI for the
financial assistance provided through the university's
applied research project in 2020.
Fig 11. Chart of NTU - ε EAHE on July 18, 2020 References
[1] Incropera F.P. “Fundamentals of Heat and Mass Transfer”, Sixth
Edition. New York : John Wiley & Sons, 2011
[2] Cengel, Yunus A. “Heat Transfer : A Practical Approach”, Second
Edition. New York: McGraw-Hill, 2002
[3] Kumar A, Baredar P. “Experimental and Analytical Studies of
Earth–Air Heat Exchanger (EAHE)”, India: Renewable and
Sustainable Energy Review, 2013
[4] Ozgener, Leyla. “A review on the Experimental and Analytical
Analysis of Earth to Air Heat Exchanger (EAHE) System in
Turkey”, Renewable and Sustainable Energy Review, 2011
[5] Kumar A, Baredar P. “Review Article Study on Calculation Models
of Earth-Air Heat Exchanger System”, India: Energy and Buildings,
2014
[6] Bisoniya, TS. “Design of Earth-Air Heat Exchanger”, India:
Fig 12. Chart of NTU – ε on July 20, 2020 Geothermal Energy, 2015
[7] Zhang J. “Investigation of Airflow and Heat Transfer in Earth-to-
Air Heat Exchangers”, Canada: Ph.D. thesis. Concordia University,
Figures 4.11 and 4.12 show the relationship between 2009
[8] Menhoudj, Sayeh. “Study of The Energy Performance of An Earth-
NTU and ε. The higher the NTU value, then the greater the Air Heat Exchanger For Refreshing Buildings In Algeria”, Algeria :
ε value. The EAHE affects the circulation of the mass flow Energy and Buildings, 2017
[9] Yusof, T. M. “Thermal Analysis of Earth-to-Air Heat Exchanger
rate (kg/s). Using Laboratory Simulator”, Malaysia: University Malaysia
Pahang, 2017
[10] Li Haorong, Yu Yuebin. “Performance of A Couple Cooling
4 Conclusion System With Earth-to-Air Heat Exchanger and Solar Chimney”,
The EAHE and Solar Chimney as a passive cooling can USA : Renewable Energy, 2013
[11] Duffie, John A, and A William Beckman. “ Solar Engineering of
provide proper performance. The temperature in the test Thermal Processes”, New Jersey : John Wiley & Sons, Inc, 2013
room is around 3 - 5oC. The air circulating in the EAHE [12] Richart. “Pengujian Pemanas Air Tenaga Surya Sistem Pipa Panas
Menggunakan Fluida Kerja Refrigeran R-718 pada Tekanan
has decreased to an average of 27.74 oC on July 18, 2020, Vakum 45 cmHg, 40 cmHg, dan 35 cmHg dengan Variasi Sudut
and 28.59 oC on July 20, 2020 The lowest NTU (Number Kolektor 20o dan 30o”, Medan : Departemen Teknik Mesin FT
USU.
of Transfer Units) at 0.7120 and the highest at 0.7260 on
July 18, 2020, with an airspeed of 0.3 m/s. Meanwhile, on
July 20, the highest NTU value was 0.1735, and the lowest
was 0.1714, with an air velocity of 0.6 m/s.
The higher the air velocity to circulate in the EAHE, the
smaller NTU value obtained. The value of effectiveness (ε)