You are on page 1of 9

Energy and Buildings 35 (2003) 389±397

Thermo-hydraulic design of earth-air heat exchangers


M. De Paepea,*, A. Janssensb
a
Department of Flow, Heat and Combustion Mechanics, Ghent University, Sint-Pietersnieuwstraat 41, B9000 Ghent, Belgium
b
Department of Architecture and Urbanism, Ghent University, Jozef Plateaustraat 22, B9000 Ghent, Belgium
Received 29 April 2002; received in revised form 2 July 2002; accepted 17 July 2002

Abstract

Earth-air heat exchangers, also called ground tube heat exchangers, are an interesting technique to reduce energy consumption in a building.
They can cool or heat the ventilation air, using cold or heat accumulated in the soil. Several papers have been published in which a design
method is described. Most of them are based on a discretisation of the one-dimensional heat transfer problem in the tube. Three-dimensional
complex models, solving conduction and moisture transport in the soil are also found. These methods are of high complexity and often not
ready for use by designers. In this paper, a one-dimensional analytical method is used to analyse the in¯uence of the design parameters of the
heat exchanger on the thermo-hydraulic performance. A relation is derived for the speci®c pressure drop, linking thermal effectiveness with
pressure drop of the air inside the tube. The relation is used to formulate a design method which can be used to determine the characteristic
dimensions of the earth-air heat exchanger in such a way that optimal thermal effectiveness is reached with acceptable pressure loss. The
choice of the characteristic dimensions, becomes thus independent of the soil and climatological conditions. This allows designers to choose
the earth-air heat exchanger con®guration with the best performance.
# 2002 Elsevier Science B.V. All rights reserved.

Keywords: Thermo-hydraulic; Heat exchangers; Earth-air; Ventilation

1. Introduction An interesting and promising technology are earth-air


heat exchangers, sometimes called ground tubes, or
The Kyoto-protocol stimulates the world to reduce CO2 ground-coupled air heat exchangers. Tubes are put into
production. This resulted in two important measures. First of the ground, through which air is drawn (see Fig. 1). Because
all efforts are focused on producing electricity with higher of the high thermal inertia of the soil, the temperature
ef®ciency. Old power plants are more rapidly phased out and ¯uctuations at the ground surface exposed to the exterior
replaced by new, more ef®cient plants. Secondly, the atten- climate, are damped deeper in the ground. Further a time lag
tion was drown on energy use. More ef®cient use of energy occurs between the temperature ¯uctuations in the ground
in production processes, buildings, etc. not only reduces the and at the surface. Therefore at a suf®cient depth the ground
consumption of electricity, but also lowers the spending of temperature is lower than the outside air temperature in
primary energy sources. summer and higher in winter. When fresh ventilation air is
Buildings, residential or of®ces, mainly use energy to drawn through the earth-air heat exchangers the air is thus
obtain comfort for it's inhabitants. This comfort is visual, cooled in summer and heated in winter. In combination with
ergonomic, but mainly thermal. In order to reduce energy other passive systems and good thermal design of the
consumption of buildings, several passive techniques are building, the earth-air heat exchanger can be used to avoid
nowadays introduced in HVAC-installations. In most cases air-conditioning units in buildings, which results in a major
solar energy is directly or indirectly used to supply heat or reduction in electricity consumption of a building.
electrical energy. Sometimes solar gains inside the building In several European countries this technique is imple-
are avoided to keep down the size of the air-conditioning mented in private houses and of®ce buildings. Recent
unit. Other techniques are based on recovering heat or even examples are found in Germany [1] and Switzerland [2].
`cold'. In most cases several passive measures are combined. Architects and building installation designers are often
interested in installing earth-air heat exchangers, but due
*
Corresponding author. Tel.: ‡32-9-264-3294; fax: ‡32-9-264-3586. to lack of knowledge or design criteria, the introduction
E-mail address: michel.depaepe@rug.ac.be (M. De Paepe). of the heat exchanger in the building design is omitted.

0378-7788/02/$ ± see front matter # 2002 Elsevier Science B.V. All rights reserved.
PII: S 0 3 7 8 - 7 7 8 8 ( 0 2 ) 0 0 1 1 3 - 5
390 M. De Paepe, A. Janssens / Energy and Buildings 35 (2003) 389±397

of the earth-air heat exchanger based on the de®nition of the


Nomenclature
heat exchanger effectiveness. With this, the important design
parameters are studied: tube diameter, tube length and
A heat transfer area (m2 )
number of tubes. As a result the relative in¯uence of these
cp thermal capacity (J/kg K)
parameters can be analysed. This results in a design-map on
D tube diameter (m)
which a proper selection of the design parameters can be
h convection coefficient (W/mK)
made.
L tube length (m)
m_ mass flow rate (kg/s)
n number of tubes
2. Literature review
NTU number of transfer units
Nu Nusselt number
In the literature several calculation models for ground-
Pr Prandtl number
coupled heat exchangers are found. Tzaferis et al. studied
Dp pressure drop (Pa)
eight models [3]. The authors classi®ed the algorithms in
Q_ transferred heat (W)
two groups:
Re Reynolds number
T temperature (K) 1. The algorithms that first calculate the convective heat
DTlm logarithmic temperature difference (K) transfer from the circulating air to the pipe and then
v velocity (m/s) calculate the conductive heat transfer from the pipe to
V_ volume flow rate (m3 /s) the ground inside the ground mass. The necessary input
data are:
Greek symbols  the geometrical characteristics of the system,
E heat exchanger effectiveness  the thermal characteristics of the ground,
l thermal conductivity (W/m2 K)  the thermal characteristics of the pipe,
n kinematic viscosity (m2 /s)  the undisturbed ground temperature during the opera-
r density (kg/m3 ) tion of the system.
2. Those algorithms that only calculate the convective heat
Subscripts transfer form the circulating air to the pipe. In this case
air of the air the necessary input data are:
in the inlet of the heat exchanger  the geometrical characteristics of the system,
out the outlet of the heat exchanger  the thermal characteristics of the ground,
ground of the ground  the temperature of the pipe surface.
wall of the tube wall
Six of the models use a steady-state one-dimensional
description of the pipe. A relation between inlet and outlet
temperature of the tube is derived. For all of these models no
In literature, several design strategies and calculation meth-
in¯uence of thermal capacity of the earth can be taken into
ods are discussed. Most of them are based on experiments or
account. Secondly the in¯uence of different pipes on each
on one-, two- or three-dimensional calculation models. They
other cannot be studied. In one algorithm the ground is
are proven to be accurate, but mostly they are highly
divided into co-axial cylindrical elements. The thermal
complex. Recent experience shows that these methods do
resistance of the ground is considered to be time-dependent.
not ®nd their way from an academic level to the every day
The pipe is divided in segments. In each segment the exit
practice. Therefore this paper presents an analytical analysis
temperature is determined. In an other algorithm the steady-
state heat balance is solved between a point in the ground
and the tube. The authors conclude that the different models
give comparable results. This is mainly caused by the fact
that the models offer different solution methods and dicre-
tisations of the same equations. The compliance with mea-
surements done by Tzaferis et al. is quite good. This shows
that a steady-state one-dimensional model may characterize
the behaviour of the earth-air heat exchangers. This
approach will be followed in this paper.
Mihalakakou et al. [4], Bojic et al. [5], Ghautier et al. [6]
and Hollmuller et al. [7] have reported on more complete
and dynamic models for earth-air heat exchangers. The
models differ in the way the geometry is described (2D,
Fig. 1. Ground-coupled heat exchanger. 3D, polar coordinates) and in the way the effects of moisture
M. De Paepe, A. Janssens / Energy and Buildings 35 (2003) 389±397 391

transport in the ground and in the air are accounted for. 3.1.2. Dimensions of the heat exchanger
However, these four calculation methods are quite complex. The geometric sizing parameters of an earth-air heat
They are mainly used to show that the heat exchanger is a exchanger are:
promising and effective technology. Therefore the applic-
 D: the diameter of the tube
ability for design is limited to people who are able to use the
 L: the length of the tube
calculation codes. In most cases the earth-air heat exchan-
 n: the number of tubes in parallel in the heat exchanger
gers are just one component in a whole buildings system.
Designers do not have much freedom of choice to determine Once the number of tubes is known, the problem is reduced
the size and lay-out of the heat exchanger. They are limited to determining the size of the tube. The thermo-hydraulic
by space-constraints and economic boundary conditions. problem is then limited to one tube, with an air ¯ow rate
They need a simpli®ed way to predict the general perfor- given by:
mance of the heat exchanger. Their main concern is to be m_ air;tot
able to select a reasonable size of the tube diameter, tube m_ air;tube ˆ (1)
n
length and number of tubes. The most important question
is whether adding another tube or another meter to the For the designer, these parameters have to be determined in
tubes, will result in an economic performance amelioration. such a way that the boundary conditions and the heat
These in¯uences can be derived by the method discussed in exchanger performance are met. This means that the location,
this paper. the available space, the building design and economics
induce restrictions to the choice of tube length and number
of tubes. It is important to be able to evaluate the in¯uence of
3. Design parameter analysis the parameters on the performance. Different combination of
these parameters will lead to the same thermal performance.
3.1. Design parameters of the earth-air heat exchanger So a second design criterion has to be introduced. Pressure
loss of the ¯ow through the tube is of main importance for the
3.1.1. Specified parameters quanti®cation of the fans in the ventilation system.
The earth-air heat exchanger should be sized in order
to meet certain design requirements. For instance, during 3.2. Heat exchanger effectiveness and NTU
cold weather the ventilation air at the outlet of the earth-air
heat exchanger should be heated above the freezing point In the earth-air heat exchanger air is the only heat
to prevent icing of other heat recovery components in the transporting ¯uid. The heat released or absorbed by the
ventilation system. Alternatively, the air leaving the earth- air is ¯owing through the tube walls to the surrounding soil.
air heat exchanger should deliver total or part of the If the contact of the tube wall with the earth is considered
building cooling load during a design summer day. These to be perfect and the conductivity of the soil is taken to be
design requirements are achieved by heating or cooling very high compared to the surface resistance, then the wall
the ventilation air in the ground tube from the external temperature at the inside of the tube can be assumed to be
air temperature towards the ground temperature in the constant.
vicinity of the tube. Hence, by the nature of the design The total heat transferred to the air when ¯owing through
problem the following parameters of the sizing problem a buried pipe can be written as:
are speci®ed: Q_ ˆ m_ air cp;air …Tair;out Tair;in † (2)
 m_ air : the air mass flow rate Due to convection between the wall and the air, the trans-
 Tair;in : the inlet air temperature ferred heat can be also be written as:
 Tair;out : the desired outlet air temperature after the heat
exchanger Q_ ˆ hADTlm (3)
 Tground : the ground temperature The logarithmic average temperature difference is given by
The air mass ¯ow rate and the outlet air temperature are set …Tground ˆ Twall †:
by the design requirement. The inlet air temperature and the …Tair;in Twall †…Tair;out Twall †
ground temperature follow from the design climate condi- DTlm ˆ
ln ‰…Tair;in Twall †=…Tair;out Twall †Š
tions for the problem.
The ground temperature is de®ned by the external climate Tair;in Tair;out
ˆ (4)
and by the soil composition, its thermal properties and water ln ‰…Tair;in Twall †=…Tair;out Twall †Š
content. The ground temperature ¯uctuates in time, but Eliminating Q_ from (2) and (3) gives the exponential relation
the amplitude of the ¯uctuation diminishes with increasing for the outlet temperature of the tube as function of the wall
depth of the tubes, and deeper in the ground the temperature temperature and inlet temperature:
converges to a practically constant value throughout the
…hA=m_ air cp;air †
year. Optimal depths are in the range of 2±4 m [8]. Tair;out ˆ Twall ‡ …Tair;in Twall †e (5)
392 M. De Paepe, A. Janssens / Energy and Buildings 35 (2003) 389±397

If a tube of in®nite length …A ˆ 1† is used the air will be The heat transfer area is a function of both D and L:
heated or cooled to the wall temperature. The effectiveness
of earth-air heat exchanger can thus be de®ned as: A ˆ pDL (10)

Tair;out Tair;in The convection coef®cient inside the tube is de®ned by:
Eˆ (6)
Twall Tair;in
Nul
hˆ (11)
Using (5) the effectiveness becomes D
…hA=m_ air cp;air †
The Nusselt number for ¯ow inside a tube is given by [9]:
Eˆ1 e (7)
The non-dimensional group is called the number of transfer Nu ˆ 3:66 if Re < 2300
units (NTU). x=8…Re 1000†Pr
Nu ˆ p
hA 1 ‡ 12:7 …x=8†…Pr 2=3 1†
NTU ˆ (8) 2
m_ air cp;air with x ˆ …1:82 log Re 1:64†
6
which gives if 2300  Re < 5  10 and 0:5 < Pr < 106

NTU
The ®rst equation applies to fully developed laminar ¯ow,
Eˆ1 e (9) the second equation applies to turbulent ¯ow in tubes with
The effectiveness of the heat exchanger is determined by the smooth internal surfaces. The Reynolds number is related to
dimensionless group NTU. Fig. 2 shows the change of the average air velocity and diameter:
effectiveness as function of NTU. Increasing the NTU vair D
increases the effectiveness, though the curve rapidly ¯attens. Re ˆ (12)
nair
After NTU > 3, the relative gain is small. There are several
ways to construct an earth-air heat exchanger to obtain a The mass ¯ow rate is given by:
given NTU and thus a desired effectiveness. The in¯uence of pD2
the design parameters on NTU will now be studied. m_ air ˆ rair vair (13)
4

3.3. Influence on the heat transfer The length L is an independent parameter in¯uencing the
NTU. There is a linear variation of NTU with length.
The NTU consists of three parameters which can vary: Changing the diameter D or the mass ¯ow rate m_ both
change the air velocity inside the tube. This results in a
 h: the convection coefficient of the air inside the tube changing Reynolds number Re. D and m_ have thus no
 A: the heat transfer surface of the tube independent in¯uence on the NTU. As NTU varies linearly
 _ the air mass flow rate
m: _
with L, the parameter NTU=L is only depending on D and m.

Fig. 2. Effectiveness as function of NTU.


M. De Paepe, A. Janssens / Energy and Buildings 35 (2003) 389±397 393

Fig. 3. Contour plot of NTU=L as a function of diameter and volume flow rate.

This gives: with [9]:


64
NTU hA Nu lair pDL lair 1 xˆ if Re < 2300
ˆ ˆ ˆ Nup Re
L _
Lmair cp;air _
D rair Vcp;air L cp;air rair V_ 2
x ˆ …1:82 log Re 1:64† if Re  2300
(14)
The tube length L is again an independent parameter in¯u-
For laminar ¯ows Nu is constant, so NTU=L is independent
encing pressure drop. The in¯uence is linear.
of the diameter D. In Fig. 3 the contour lines for NTU=L are
Diameter and ¯ow rate have a combined in¯uence. In
given for small ¯ow rates and large tube diameters. When
Fig. 5 the contour plots of pressure drop per unit of length
the ¯ow is laminar the contour lines become vertical lines.
Dp=L for varying diameter and ¯ow rate are shown. Having a
In Fig. 4 the contour plots for NTU=L with changing range
small ¯ow rate per tube and a large diameter gives the least
of D and volume ¯ow rate V_ for the turbulent ¯ow case are
pressure loss. This would mean using many tubes, with a
shown.
large diameter. This is in con¯ict with the thermal demand of
In general, lowering D raises the effectiveness, higher
a small diameter. In both cases a large number of tubes is
¯ow rates reduce the effectiveness. So it is better to have
bene®cial. The tube length and diameter combination have
several tubes of small diameter over which the ¯ow rate is
to be optimized.
divided.
Long tubes with a small diameter are pro®table for the
heat transfer. They, however, raise the pressure drop in the 4. Heat exchanger design calculations
tubes, resulting in high fan energy.
4.1. Specific pressure drop
3.4. Influence on pressure drop
As both NTU and pressure drop are linear with the tube
The pressure drop in a smooth tube is given by: length, the parameters NTU=L and Dp=L are only dependent
of diameter and volume air ¯ow rate. These two parameters
L v2air are, respectively, a measure for the thermal and hydraulic
Dp ˆ x r (15)
D 2 performance per unit of length.
394 M. De Paepe, A. Janssens / Energy and Buildings 35 (2003) 389±397

Fig. 4. Contour plot of NTU=L as function of diameter and volume flow rate.

Total NTU and total pressure drop of the heat exchanger 4.2. NTU±J design method
are given by multiplying these unit parameters with the total
length of the tubes: Given the desired temperature programme the effective-
  ness E can be calculated with Eq. (6). With the inverse of
NTU Eq. (9) the desired NTU can be determined with equation:
NTUtot ˆ L (16)
L
  NTU ˆ ln …1 E† (20)
Dp
Dptot ˆ L (17) This NTU is the minimal desired NTU the heat exchanger
L
has to reach: NTUmin .
The speci®c pressure drop J can be de®ned as: Given the maximal allowable pressure drop DpMAX , the
maximal allowable J of the heat exchanger can be deter-
Dp mined as:
Jˆ (18)
NTU
DpMAX
J is a measure for the pressure drop necessary to realize one JMAX ˆ (21)
NTUmin
unit of NTU.
In Fig. 6 J is given as function of V_ and D, as calculated This JMAX de®nes a zone in Fig. 6 which is not allowed for V_
with Eqs. (18), (15), (13) and (8). J grows with growing V_ and D. The choice of D and V_ per tube is thus limited.
and smaller D. Combining this with Figs. 3 and 4, the choice for the most
The NTU per unit of length can be expressed as function effective heat exchanger is the one with the smallest tube
of J and pressure drop per unit of length as: diameter and the smallest ¯ow rate per tube. This allows for
the choice of D and the maximum number of parallel tubes.
NTU 1 Dp After the number of tubes in parallel is chosen and the
ˆ (19)
L J L tube diameter is accordingly determined the NTU per unit of
M. De Paepe, A. Janssens / Energy and Buildings 35 (2003) 389±397 395

Fig. 5. Pressure drop Dp=L as function of diameter and air volume flow rate.

Fig. 6. Specific pressure drop J as function of diameter and air volume flow rate.
396 M. De Paepe, A. Janssens / Energy and Buildings 35 (2003) 389±397

Fig. 7. Design graph for the sizing of earth-air heatexchangers with a heat exchanger effectiveness of 80%.

length can be determined by (14). Given the desired NTU, of 80% is considered to be an optimum for an earth-air heat
this gives the length. exchanger [8]. A higher effectiveness is only achievable at
the cost of an important increase of the tube length or of the
4.3. Graphical design method number of tubes. Eq. (23) is represented in the upper half of
Fig. 7, for different values of the tube diameter and a heat
The NTU J design method is used to derive a graphical exchanger effectiveness of 80%.
sizing tool which allows to de®ne the tube length and The use of the design graph is now illustrated with an
diameter from the air ¯ow rate per tube and the desired example. The boundary conditions for the sizing of an earth-
ground tube performance J. The relationship between the air heat exchanger for a small of®ce building are the
speci®c pressure drop J and the air volume ¯ow rate follows following:
from Eqs. (14), (15) and (18):
 The design air flow rate is 750 m3 /h.
 The geometry of the building site limits the length of the
cp;air r2air x _ 3
J ˆ 0:258 V (22) earth-air heat exchanger to a maximum of 25 m.
lair NuD5
 The pressure drop across the heat exchanger should not
This relation is represented in the lower half of Fig. 6 on a exceed 100 Pa.
log±log scale, for different values of the tube diameter. The pressure loss requirement de®nes the maximum allow-
The relationship between the tube length and the speci®c able speci®c pressure drop J. Assuming a heat exchanger
pressure drop J follows from Eqs. (15), (19), (20) and (22): effectiveness of 80%, Eq. (21) gives: J < 62 Pa/m. This
value, together with the requirement for the maximum
" #1=3 individual tube length, delimits a zone of allowable L and
JNTU c2p;air rair D5
Lˆ ˆ ln …1 E† J 1=3 (23) J in the upper half of Fig. 7. The maximum tube length
Dp=L 8l2air xNu2 depends on the lay-out of the tubes on the available strip of
land (Fig. 8). The maximum tube length in the example is
This expression may be solved when a value for the effec- 25 m for a bundle of parallel tubes, but may be a multiple of
tiveness E of the earth-air heat exchanger is chosen. The 25 m for a serpentine shape. To prevent interference between
desired effectiveness follows from the design requirements the individual tubes, the distance between them should be at
and climate conditions (Eq. (7)), but often an effectiveness least 1 m [8].
M. De Paepe, A. Janssens / Energy and Buildings 35 (2003) 389±397 397

demands are known, the thermo-hydraulic design of the


heat exchanger only depends on the constructional con-
straints and economics.
Three dimensions have to be determined: tube length,
tube diameter and number of parallel tubes. Thermal per-
formance and pressure drop both grow with length. Smaller
tube diameters give better thermal performance, but also
larger pressure drop. More tubes in parallel both lower
pressure drop and rise thermal performance.
To be able to reduce the in¯uencing parameters the
speci®c pressure drop is introduced. The speci®c pressure
drop is a measure for the pressure drop needed to realize a
given thermal performance. This way a maximal speci®c
pressure drop can be calculated.
Fig. 8. Lay-out of ground tubes on a strip of land. The speci®c pressure drop is used to derive a straight
forward design method.
Table 1
Heat exchanger configurations for design air flow rate 750 m3/h, E ˆ 80%,
Dp < 100 Pa References
D (mm) Number L per v (m/s) Dp (Pa) Lay-out
of tubes tube (m) [1] M. Schuler, Design for daylighting and energy in Ingolstadt,
Advanced Building Newsletter 23/24 (1999) 18±23.
100 4 14 6.6 77 Parallel [2] M. Zimmermann, The Schwerzenbacherhof office and industrial
150 2 22 5.9 61 Parallel building Swerzenbach, Switzerland, ground cooling (air), IEA Low
200 3 25 2.2 8 Parallel Energy Cooling Demonstration 15/1±15/8, 1998.
250 1 38 4.2 32 Serpentine [3] A. Tzaferis, D. Liparakis, M. Santamouris, A. Argiriou, Analysis of
the accuracy and sensitivity of eight models to predict the performance
of earth-to-air heat exchangers, Energy and Buildings 18 (1992)
35±43.
From the zone of allowable L and J in Fig. 7 a suitable
[4] G. Mihalakakou, M. Santamouris, D. Asimakopoulos, Modelling the
tube diameter may be chosen, closest to the value of max- thermal performance of earth-to-air heat exchangers, Solar Energy 53
imum speci®c pressure drop. Following the lines of equal (3) (1994) 301±305.
speci®c pressure drop J to the line for the chosen diameter in [5] M. Bojic, N. Trifunovic, G. Papadakis, S. Kyritsis, Numerical
the lower half of the graph, the air volume ¯ow rate per tube simulation, technical and economic evaluation of air-to-earth
heat exchanger coupled to a building, Energy 22 (12) (1997) 1151±
is de®ned. The ratio between the design air ¯ow rate and the
1158.
¯ow rate per tube thus de®nes the number of tubes of a [6] C. Gauthier, M. Lacroix, H. Bernier, Numerical simulation of soil heat
speci®c diameter and length to be installed. Table 1 shows all exchanger-storage systems for greenhouses, Solar energy 60 (6) (1997)
possible combinations which are a solution to the design 333±346.
problem of the example. [7] P. Hollmuller, B. Lachal, Cooling and preheating with buried pipe
systems: monitoring, simulation and economic aspects, Energy and
Buildings 33 (5) (2001) 509±518.
[8] IEA Annex 28, Early design guidance for low energy cooling
5. Conclusion technologies, International Energy Agency, Energy Conservation in
Buildings and Community Systems Programme, Annex 28 Low
The design of an earth-air heat exchanger is a separate Energy Cooling, Subtask 2, Report 2, 1999.
[9] VDI, WaÈrmeatlas, Springer, Verlag, 1994.
problem of the building design. Once the ventilation

You might also like