Professional Documents
Culture Documents
a r t i c l e i n f o a b s t r a c t
Article history: The earth-to-air heat exchanger (EAHE) is a low-energy device used to improve the thermal condition of
Received 30 July 2015 buildings, which is filled with the air directed from the outside and surrounded by the soil. The temper-
Accepted 24 November 2015 atures of both the air and soil are periodically fluctuating, leading to the EAHEs working in a harmonic
Available online 17 December 2015
thermal environment. However, most of the previous theoretical studies investigated the performance
of EAHEs by ways of static and steady-state models, paying insufficient attention to the temperature
Keywords: phase shifting and fluctuation attenuation effects. The main purpose of this work is to develop an
EAHE
approach to predict the performance of EAHE subjected to harmonic thermal environments. The har-
Harmonic thermal environment
Phase shifting
monic temperature signals transmitted from both the pipe inlet and the ground surface are incorporated
Cooling/heating potential in the model by means of the ‘excess fluctuating temperature’. The amplitude dampening and phase-
Excess fluctuating temperature shifting of the EAHE air temperature for both annually and daily fluctuating cycles are derived as explicit
Analytical solution expressions. The analytical results are validated against numerical simulations. The model is applied in a
hot-summer/cold-winter region. Results indicate that a deep-buried EAHE pipe can reduce the air tem-
perature by 7 °C on a summer day. The maximum cooling or heating capacities occur in spring/summer
or autumn/winter transitional seasons. The use of an EAHE pipe can create a 3000-W cooling or heating
capacity.
Ó 2015 Elsevier Ltd. All rights reserved.
1. Introduction acts as a large reservoir for solar energy. Because of the thermal
inertia of the soil, the fluctuation amplitude of the soil tempera-
Mankind constantly pursues a comfortable building environ- ture, with respect to the ambient air temperature, decreases expo-
ment. However, energy is essential in the process of maintaining nentially as the depth increases. However, the phase shift between
comfortable indoor building environments. Currently, energy the soil temperature and ambient air temperature increases with
consumption of buildings accounts for 25–40% of the total energy depth. For this reason, at a sufficient depth, the soil is not as cold
consumption, of which, most of the energy is used for heating or as the ambient environment during cold periods and is not as
air-conditioning and comes from non-renewable fossil fuels such hot during hot periods [9,10]. These features provide a promising
as coal, oil and natural gas [1–3]. The requirement for sustainable opportunity for the use of geothermal energy for passive regulation
development drives people to find alternative, renewable energy to of building thermal environments. There are two prevalent types of
regulate the indoor thermal environments. Scientists and engi- techniques. One type is the ground source heat pump (GSHP),
neers have undertaken many studies in this area, and in most which typically includes a heat pump and a ground heat exchanger
cases, solar energy is directly or indirectly used [4–7]. sub-system [11,12]. In the heating mode, the GSHP absorbs heat
The use of ground as a heat source or sink for passive heating or from the ground and uses it to heat buildings. In the cooling mode,
cooling of buildings has been used in ancient times [4,8], and this the thermodynamic process is reversed and the heat is absorbed
passive measure has attracted more and more attention in recent from the interior spaces of a building and released to the ground.
years. The ground receives solar radiation through its surface and GSHP systems have better energy efficiency compared to tradi-
tional air-conditioning and heating systems, leading to continued
⇑ Corresponding author at: Faculty of Urban Construction and Environmental
growth in applications. Earth-to-air heat exchangers (EAHEs) are
Engineering, Chongqing University, Chongqing 400045, China. Tel.: +86 23 simpler and typically cheaper devices, as also called ground air
65120750. tubes or earth-air-tube ventilation systems [4,13–15]. It is
E-mail address: yangdong@cqu.edu.cn (D. Yang). unnecessary to use thermodynamic cycles for the conversion of
http://dx.doi.org/10.1016/j.enconman.2015.11.050
0196-8904/Ó 2015 Elsevier Ltd. All rights reserved.
D. Yang et al. / Energy Conversion and Management 109 (2016) 184–194 185
Nomenclature
A temperature fluctuation amplitude (K) jn normalized fluctuation amplitude of pipe air tempera-
A0 temperature fluctuation amplitude combined with ture with respect to outdoor air
phase shift (K) ks thermal conductivity of soil (W/m K)
Ca specific heat of air (J/kg K) qa air density (kg/m3)
F a combination of modified Bessel functions ug phase shift of ground surface temperature with respect
h1 heat transfer coefficient at the pipe inner wall (W/m2 K) to the outdoor air temperature (rad)
In first kind of modified Bessel functions of order n un phase shift of pipe air temperature with respect to out-
Kn second kind of modified Bessel functions of order n door air (rad)
Nu Nusselt number x fluctuating frequency (s1)
P fluctuation period (s)
q volume flow rate of ventilation air (m3/s) Superscripts
Q heating or cooling capacity (W) — time-averaged value
QL reduction in heating or cooling load (W) time-dependent value
r radial coordinate (m) _ Laplace transformation
R radius of an EAHE pipe (m)
Re Reynolds number Subscripts
T temperature (K) ini initial condition
t time (s)
g ground surface
Va velocity of pipe air (m/s) n earth-tube air
x pipe length (m) o outdoor air
z burial depth of pipe (m) r radius coordinate
s soil
Greek symbols y; d values of annual or daily fluctuation period
as thermal diffusivity of the soil (m2/s) z depth
~
h excess fluctuating temperature (K)
jg normalized fluctuation amplitude of ground surface
temperature with respect to the outdoor air temperature
geothermal energy in an EAHE, and thus the associated sub-system heat transfer enhancement effects and pressure drop penalty for
is omitted. The ventilation air is drawn through the pipes that are the tube heat exchangers embedded with porous media. However,
buried in the soil and exchanges heat with the soil directly. Thus, most of the previous studies treated the EAHEs by ways of static
the air is pre-cooled in summer and pre-heated in winter before and steady-state models, which cannot account for the phase-
entering the interior building spaces, which could reduce both shifting effects induced by the transient heat transfer process.
cooling and heating loads of buildings and in turn reduce electric- However, the ambient air temperature, as the inlet air temperature
ity consumption. EAHEs have been applied in various climates. of an open-loop EAHE, periodically fluctuates throughout both
They are also applicable for several types of buildings, such as annual and daily cycles. Meanwhile, the temperatures of the soil
office buildings [16], commercial buildings [17], residential build- surrounding a pipe could also periodically fluctuate with damp-
ings [18] and agricultural greenhouses [15,19]. The combined sys- ened amplitudes and amplified phase shifts. The EAHE perfor-
tems that integrate EAHEs with other passive techniques, e.g., wind mance is thus strongly influenced by both the fluctuating
towers and solar chimneys [2,20], could provide both cooling or characteristics of the ambient temperature and that of the soil
heating capacity and fresh air for the conditioned buildings with temperatures. To quantify the contribution of EHAEs to the load
negligible fan energy consumption. reduction of buildings over the whole annual or daily cycles, it is
The growth in the applications of EAHEs requires tools for eval- necessary to obtain the transient air temperature profiles of the
uating the thermal performance of EAHEs. The performance of EAHE outlet. To date, very few studies provided explicit expres-
EAHEs depends on various factors such as climate conditions, the sions for the phase shift and fluctuation amplitude of the outlet
configuration parameters of the pipes (e.g., length and radius), air temperature of an EAHE pipe. Although the Computational
the buried depth of the pipes, the thermal physical parameters of Fluid Dynamics (CFD) codes combined with numerical heat trans-
the soil, etc. Various papers presented simplified models for pre- fer simulations, such as Fluent, can be used for assisting the design
dicting the thermal performance of EAHEs [21–24]. Sulaiman of EAHEs, the numerical solutions are implicit. In addition, the
[22] studied the cooling effect of underground heat pipes theoret- computational cost of CFD even becomes unaffordable for simulat-
ically. Malaysia and Kreider [23] calculated the energy perfor- ing an annual fluctuation cycle. Hollmuller [29] derived analytical
mance of an underground air tunnel in a steady, periodic state solutions for the heat diffusion of a cylindrical earth-air tube,
using an analytical model. A detailed numerical model considering which accounts for the periodic fluctuation of ambient air temper-
the effect of the thermal stratification in soil was presented by ature, but his study does not account for the periodic fluctuation of
Mihalakakou, which was developed inside the TRNSYS simulation soil. In Hollmuller’s study, the penetration radius of heat diffusion
program [24]. Wu et al. [25] developed an implicit model based inside the soil is specified as a constant. In a recent study, Yang
on numerical heat transfer and computational fluid dynamics et al. [30] proposed a method for determining the penetration
(CFD) to predict the thermal performance and cooling capacity of radius of soil heat diffusion based on fluctuation frequency [30].
earth-air pipe systems. Al-Ajmi et al. [26] developed a theoretical In the study of Yang et al., the effects of pipe air temperature fluc-
model for the outlet air temperature of an EAHE in a hot climate. tuation are considered, but the soil temperature fluctuation is
Dehghan et al. [27] and Rashidi et al. [28] developed mathematical excluded, reducing the accuracy for evaluating shallow-buried
models for analyzing the local thermal non-equilibrium condition, pipes.
186 D. Yang et al. / Energy Conversion and Management 109 (2016) 184–194
In this paper, an analytical model for the evaluation of the ther- 2.2. The concept of ‘‘excess fluctuating temperature”
mal performance of an EAHE in a periodically fluctuating thermal
environment is proposed. Unlike the previous studies, we do not When an EAHE pipe intervenes in the soil, the soil tempera-
use a ‘‘penetration radius” to confine the distance of heat diffusion ture is not only a function of depth and time, but is also affected
in soil. Alternatively, the heat diffusion distance in the soil is by the temperature wave transmitted from the EAHE pipe. The
assumed to be semi-infinite. Furthermore, we propose using the fluctuating temperature wave originated from the EAHE pipe pen-
‘‘excess fluctuating temperature” to account for the interaction etrates into the soil and then changes the temperatures of the soil
between the thermal waver originated from the pipe and that pos- around the pipes (as shown in Fig. 1). This phenomenon is rela-
sessed in the soil, making the analysis procedure more straightfor- tively obvious in an annually cycle because of the long penetra-
ward and efficient. With this procedure, the heating and cooling tion time. The effect of the fluctuating temperature wave
capacities of the EAHE system in a fluctuating environment can originated from an EAHE pipe decays with increasing propagation
be quantified. The model results are compared to a three- distance. At an infinitely large radius, the disturbance effects
dimensional numerical simulation. The influence of the important induced by the intervention of the EAHE pipes are negligible
design parameters, such as diameter, pipe length, buried depth and and thus the soil temperature approaches the original undis-
air flow rate, are then investigated. turbed soil temperature. Therefore, in the present model, the
boundary condition (i.e., the undisturbed soil temperature) is
imposed at an infinitely large radius rather than at a specified
2. Mathematical model
finite radius. The excess fluctuating temperatures are introduced
here to represent the difference between a certain prescribed
2.1. The representation of soil and ambient air temperatures
fluctuating temperature and the undisturbed fluctuating soil
temperature:
The fluctuating components of ambient air temperature, pipe
air temperature and the undisturbed soil temperature at the depth ~hs;r ¼ Te s;r Te s;z ð7Þ
of z are represented as
~hn ¼ Te n Te s;z ð8Þ
Te o ¼ Ao eixt ð1Þ
~ho ¼ Te o Te s;z ð9Þ
Te n ¼ A0n eixt ¼ An eiðxtun Þ ; A0n ¼ An eiun ð2Þ
where un and us;z are the phase shift of the pipe air temperature
Te s;z ¼ A0s;z eixt ¼ As;z eiðxtus;z Þ ; A0s;z ¼ As;z eius;z ð3Þ and the undisturbed soil temperature at the depth z with respect
to the ambient air temperature, respectively.
respectively. Although there remain differences in the undisturbed soil tem-
The temporal profile of the ambient air temperature is repre- perature between different radial directions, the undisturbed fluc-
sented as the sum of the time-averaged and harmonic tuating soil temperature at the buried depth of the pipe is used
components: here. At an infinitely large radius surrounding the EAHE pipe,
X T e s;z and h
e s;1 ! T ~s;1 ! 0. For the deeply buried EAHE pipes,
T o;d ¼ T o;d þ Ao;d eixd td ¼ T o;y þ Ao;m eixm tm ð4Þ e s;z ¼ 0, and thus ~ e n and ~ e s;r .
m¼y;d
T hn ¼ T hs;r ¼ T
where m ¼ d corresponds to a daily fluctuation period 2.3. The thermal interaction between EAHE and soil with respect to
(xd ¼ 2p=24h) and t d is the number of hours since the start of a periodically fluctuating thermal environments
daily fluctuation period. The term m ¼ y corresponds to a yearly
fluctuation period (xy ¼ 2p=365d) and t y is the number of days The present model takes both the annual and daily fluctuation
since the start of a yearly fluctuating period. cycles into account. The EAHE pipes are assumed to be cylindrical
The annual and daily profiles of undisturbed soil temperatures (see Fig. 1), and the soil heat conduction equation is represented in
(i.e., those that are not disturbed by the intervention of EAHE a cylindrical coordinate system. The fluctuating component of the
pipes) are equation and the corresponding boundary and initial conditions
are represented by the excess fluctuating temperature as proposed
T s;y ðt y ; zÞ ¼ T s;z;y þ Te s;z;y in Section 2.2:
!
¼ T s;z;y þ Ao;y jg;y @ ~hs ðt; rÞ as @ @ ~hs ðt; rÞ
rffiffiffiffiffiffiffiffiffiffi rffiffiffiffiffiffiffiffiffiffi ¼ r ð10Þ
p 2pt y p @t r @r @r
exp z exp i ug;y z
as Py Py as Py
ð5Þ @ ~hs
ks j ¼ h1 ð~hn ~hs ðt; RÞÞ; r ¼ R ð11Þ
@r r¼R
T s;d ðt d ; zÞ ¼ T s;z;d þ Te s;z;d ¼ T s;y ðty ; zÞ þ Te s;z;d
X ~hs ¼ 0; r ¼ 1 ð12Þ
¼ T s;z;y þ Ao;m jg;m
m¼y;d
rffiffiffiffiffiffiffiffiffiffiffi rffiffiffiffiffiffiffiffiffiffiffi ~hs ð0; rÞ ¼ 0; t ¼ 0; R < r < 1 ð13Þ
p 2pt m p
exp z exp i ug;m z The convective heat transfer coefficient at the inner surface of
as Pm Pm as Pm
the EAHE pipe, h1 , is obtained from Appendix A.
ð6Þ
The details for the solution of Eqs. (10)–(13) are shown in
The term z is the depth below ground surface. The terms ug and Appendix B. The complex form for the excess fluctuating tempera-
jg are the phase shift and the normalized fluctuation amplitude of ture of the pipe wall of the EAHE is given as
the ground surface temperature with respect to the outdoor air
~hs ðt; RÞ ¼ ~hn Fðix; RÞ ð14Þ
temperature, respectively.
D. Yang et al. / Energy Conversion and Management 109 (2016) 184–194 187
Ts , z Tn
Ts , z
θs , r = 0
Tn r →∞
R R r
(a) The cross-sectional view of the EAHE pipe and the variation
of the soil temperature surrounding the pipe
Ground Surface
TR
To z
Tn
Fig. 1. Schematic of the heat transfer between an EAHE pipe and the surrounding soil.
where F 0 ðix; RÞ is a combination of modified Bessel functions, as jn ¼ An =Ao ¼ absðA0n Þ=Ao ð18Þ
shown in Appendix B.
Thus, Eq. (14) describes the thermal interaction between the un ¼ ð1Þ angleðA0n Þ ð19Þ
EAHE pipe and the surrounding soil. In Section 2.3, the analytical
expressions for quantifying the performance of an EAHE system where abs and angle of Eqs. (18) and (19) denote the complex mod-
will be presented. ulus and phase angle, respectively.
The above equations and solutions are applicable to both annual
2.4. Thermal performance of an EAHE and daily cycles. Eq. (17) shows that,
The original form of the heat balance equation of air flow inside The buried depth, z, has significant effects on both jn and un ;
an EAHE pipe is however, both jn and un are nearly independent of Ao .
@T n @T n For a deep-buried pipe, A0s;z ! 0, and thus, the outlet air temper-
qa C a pR2 dx ¼ qa C a V a pR2 dx h1 ðT n T R Þ2pRdx ð15Þ ature of a deep-buried pipe is
@t @x
The fluctuating component of Eq. (15) is 0
ix þ2d ð1FÞ
A0n ðxÞ ¼ Ao e Va R
x
ð20Þ
R @ Te n @ Te n
¼ R 2d0 ð Te n Te R Þ ð16Þ
V a @t @x In a year cycle, thermal balance could be achieved between the
where V a is the averaged air velocity over the cross section of the ambient environment and the soil. Therefore, both the yearly aver-
pipe and d0 ¼ h1 =qa C a V a . aged soil temperature, T s;z;y , and the yearly averaged pipe air tem-
The details for the solution of Eq. (16) are shown in Appendix C. perature are approximately equal to the yearly averaged outdoor
The complex form of the fluctuating component of the outlet air air temperature:
temperature is given as T s;z;y T o;y ð21Þ
0
½Vix þ2dR ð1FÞx
A0n ¼ Ao e a
" ix 2d0
# T n;y T o;y ð22Þ
V a 2d0 ðF 1Þe½V a þ R ð1FÞx þ V a 2d0 ð1 FÞ 0
þ As;z ð17Þ Then, the annual profile of air temperature at the pipe outlet of
Rix þ V a 2d0 ð1 FÞ
an EAHE is
where F ¼ Fðix; RÞ.
T n;y ¼ T n;y þ Te n;y ¼ T o;y þ jn;y Ao;y cosðxy t y hn;y Þ ð23Þ
Then, the normalized fluctuation amplitude and phase shift of
the tube air temperature with respect to the outdoor air tempera- For a daily fluctuation cycle, the hourly variation in air temper-
ture are given by ature at the pipe outlet of an EAHE is
188 D. Yang et al. / Energy Conversion and Management 109 (2016) 184–194
Table 1
Thermo-physical properties of the soil (artificial) and air used for simulations.
295
290
285
280
(a) Case #1
100 150 200 250 300 350 400 450 500
Time (s)
Fig. 3. Simulation results for pipe air temperatures under different grid cell
densities.
28 24.8
27
Daily-averaged temperature
24.7
Daily-averaged temperature
0.4
Phase shift An/Ao
1.5 Phase shift
0.3
1.0 0.2
0.1
0.5
0.0
0.0 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 R
Buried depth (m) (b) Daily phase shift and normalized fluctuation
(b) Daily phase shift and normalized fluctuation amplitude of outlet air temperature
amplitude of outlet air temperature
0.76 0.11
1.0 An/Ao Phase shift
0.75 0.10
0.9
0.74 0.09
0.8 An/Ao 0.73 0.08
An/Ao & Phase shift
Phase shift
An/Ao
0.72 0.07
0.6
0.71 0.06
0.5
0.70 0.05
0.4
0.3 0.69 0.04
4.3. The effects of pipe length 4.4. The effects of ventilation flow rate
The radius of the tube is 0.5 m, and the ventilation flow rate is The radius of the tube is set to 0.3 m, and the length is 200 m.
0.5 m3/s. Fig. 7(a) shows that the daily-averaged outlet air temper- Fig. 8(a) shows that the daily-averaged outlet air temperature gen-
ature in a typical summer day decreases with the tube length, erally increases with the ventilation flow rate in a typical summer
D. Yang et al. / Energy Conversion and Management 109 (2016) 184–194 191
27 26
Daily-averaged temperature 25
Daily-averaged temperature
Daily-averaged temperature
26
24
25 23
22
24
21
23 20
19 Daily-averaged temperature
22
18
21 17
0 20 40 60 80 100 120 140 160 180 200 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Length q
(a) Daily-averagedoutlet air temperature (a) Daily-averaged outlet air temperature
1.0
0.9 0.6
An/Ao
0.8
An/Ao & Phase shift
Phase shift
0.7 0.5
0.6
0.4
0.5
0.4 0.3
0.3
0.2
0.2
0.1 0.1
0.0 0.0
0 50 100 150 200 250 300 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Length q
(c) Annual phase shift and normalized fluctuation (c) Annual phase shift and normalized fluctuation
amplitude of outlet air temperature amplitude of outlet air temperature
Fig. 7. The effects of the pipe length. Fig. 8. The effects of the flow rate.
day. The phenomena shown in Fig. 8(a) do not mean that the
increase in ventilation flow rate is unfavorable because the cooling 4.5. Heating and cooling capacities provided by an EAHE
or heating capacity provided by an EAHE is proportional to the pro-
duct of the ventilation flow rate and the air temperature difference The heating and cooling capacities provided by an EAHE system
between the pipe inlet and outlet. This occurrence will be further in an annual cycle, as defined in Eq. (26), depend on the engineer-
explained in Section 4.5. Fig. 8(b) shows that the phase shift of ing parameters referred in Sections 4.1–4.4. However, the effects of
the outlet air temperature in a daily cycle varies non- the ventilation flow rate are not straightforward. The heating and
monotonically with ventilation flow rate; however, the daily fluc- cooling capacities are functions of both the outlet air temperature
tuation amplitude generally increases with increasing ventilation and the ventilation flow rate, where the former variable is also
flow rate. Fig. 8(c) shows that, in an annual cycle, the phase shift affected by the latter. Therefore, the effects of the ventilation flow
of the outlet air temperature initially increases and then decreases rate on the heating and cooling capacities provided by an EAHE
with ventilation flow rate; however, the annual fluctuation ampli- system are investigated in this section. The pipe length is 100 m,
tude generally increases with increasing ventilation flow rate, indi- and the radius is 0.5 m.
cating that the increase in ventilation flow rate could be As shown in Figs. 9 and 10, although the increase in ventilation
unfavorable to stabilizing the indoor air temperature. flow rate is unfavorable to both raising the outlet air temperature
192 D. Yang et al. / Energy Conversion and Management 109 (2016) 184–194
Temperature difference between outlet and inlet (K) improvement effects induced by an EAHE are attributed mainly
350 6 to the air temperature phase shifting in an annual cycle. The buried
300 4 depth and pipe length are crucial for the outlet air temperature of
Day number
250 2 an EAHE pipe. The improving effects of an EAHE on the air temper-
200 ature are enhanced by an increase of buried depth or pipe length.
0
150 For a typical hot-summer/cold-winter region, a temperature drop
-2
100 of over 5 °C on a summer day can be achieved by a deep-buried
-4
50 EAHE pipe with a length of 200 m. Ventilation flow rate is another
0 -6 important parameter. For a typical hot-summer/cold-winter
0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
region, the increase of pipe air flow rate results in remarkable
Ventilation flow rate (cubic meter per second)
increase in cooling or heating capacities for the spring/summer
Fig. 9. The variation of temperature difference between the outlet and inlet air with or autumn/winter transitional seasons.
ventilation flow rate in an annual fluctuation cycle.
Acknowledgements
Heating or cooling capacity (W) The authors gratefully acknowledge the support from the
350 3000
National Natural Science Foundation of China (NSFC) under Grant
300 2000
No. 51578087 and the 111 Project (No. B13041).
Day number
250 1000
200 0 Appendix A. Convective heat transfer coefficient at the inner
150 surface of a cylindrical pipe
-1000
100
-2000
50 The convective heat transfer coefficient at the inner surface of a
-3000
0 cylindrical pipe is given by
0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
Ventilation flow rate (cubic meter per second) h1 ¼ Nu ka =d ðA1Þ
Fig. 10. The variation of heating or cooling capacity with ventilation flow rate in an where ka is the thermal conductivity of air, d is the diameter of the
annual fluctuation cycle (positive: heating capacity; negative: cooling capacity).
air-tube, and the Reynolds number of the pipe flow is
Re ¼ V a d=ma ðA2Þ
of an EAHE pipe in cold days and lowering it in hot days, it gener-
where ma is the kinematic viscosity of air.
ally increases both the heating capacity in cold days and the cool-
The Nusselt number of a pipe flow is given by Incropera et al.
ing capacity in hot days. For Chongqing, the beneficial effects
[33] as
induced by the increase of ventilation flow rate are notable during
the transitions from springs to summers or from autumns to win- Nu ¼ 4:36 if Re < 2300 ðA3Þ
ters. For example, on the 160th and 350th days, an EAHE pipe com-
bined with a ventilation flow rate of 2 m3/s could decrease the ðf =8ÞðRe 1000ÞPr
Nu ¼ if Re > 2300 ðA4Þ
cooling or heating loads by over 3000 Watts. However, during 1 þ 12:7ðf =8Þ
1=2
ðPr2=3 1Þ
the transitions from winters to springs or from summers to
autumns (e.g., on the 75th and 260th days), the beneficial effects where f is the friction coefficient of the pipe, which is determined
induced by the increase of ventilation flow rate are very small. from Petukhov’s formula [33], expressed as
2
f ¼ ð0:79 ln Re 1:64Þ ðA5Þ
5. Conclusions
This paper provides an analytical approach for evaluating the Appendix B. Solution of the fluctuating component of the heat
performance of the earth-to-air heat exchangers subjected to peri- transfer equation for the soil surrounding a cylindrical pipe
odically fluctuating thermal environments. The present model
incorporates the fluctuation effects of both soil temperature and We apply the Laplace transformation in Eqs. (10)–(13) to obtain
ambient air temperature; consequently, it is favorable to the eval- _ _
rffiffiffiffiffi
_ s Combining the boundary condition ~
hn jx¼0 ¼ ~ eo T
ho ¼ T e s;z , the
h s;r ¼ BK 0 r ðA10Þ
as solution of Eq. (A20) is
Combining the other boundary condition, (A7), gives 0
~hn ¼ Te o e½Vixa þ2dR ð1FÞx
rffiffiffiffiffi rffiffiffiffiffi
_ rffiffiffiffiffi
s s s " ix 2d0
#
ks B K1 R ¼ h1 h n BK 0 R ðA11Þ V a 2d0 ðF 1Þe½V a þ R ð1FÞx Rix e
as as as þ T s;z ðA21Þ
Rix þ V a 2d0 ð1 FÞ
Then, B is given as
The expression for the air temperature at the outlet of the EAHE
_ h1
B ¼ hn qffiffiffiffi qffiffiffiffi qffiffiffiffi ðA12Þ pipe is then given by
as R þ ks as K 1
s s s
h1 K 0 as R 0
Te n ¼ Te o e½V a þ R ð1FÞx
ix 2d
Inserting Eq. (A12) into Eq. (A10), the excess fluctuating tem- " ix 2d0
#
perature of the soil surrounding the EAHE pipe is given as V a 2d0 ðF 1Þe½V a þ R ð1FÞx þ V a 2d0 ð1 FÞ e
þ T s;z ðA22Þ
qffiffiffiffi Rix þ V a 2d0 ð1 FÞ
s
_ _ h1 K 0 as r _
h s;r ¼ h n qffiffiffiffi qffiffiffiffi qffiffiffiffi ¼ h n Fðs; rÞ ðA13Þ Eq. (A22) can also be expressed as
as R þ ks as K 1
s s s
h1 K 0 as R 0
A0n ¼ Ao e½V a þ R ð1FÞx
ix 2d
f ð1; rÞ~hn ðt 1Þ d1
buildings in arid and hot climate. Energy Convers Manage 2015;91:1–11.
¼ [3] Yang D, Li P. Natural ventilation of lower-level floors assisted by the
Z0 1 h i ðA15Þ mechanical ventilation of upper-level floors via a stack. Energy Build
f ð1; rÞ~hn ðt 1Þ d1 ðwhen t is very longÞ 2015;92(1):296–305.
[4] Santamouris M, Kolokotsa D. Passive cooling dissipation techniques for
0
buildings and other structures: the state of the art. Energy Build
2013;57:74–94.
[5] Suárez-López MJ, Blanco-Marigorta AM, Gutiérrez-Trashorras AJ, et al.
Because ~ hn ¼ A0n eixt A0s;z eixt (as shown in Eqs. (7)–(9)), the Numerical simulation and exergetic analysis of building ventilation solar
chimneys. Energy Convers Manage 2015;96:1–11.
excess fluctuating soil temperature is derived as [6] Matrawy KK, Mahrous AF, Youssef MS. Energy management and parametric
Z 1 optimization of an integrated PV solar house. Energy Convers Manage
~hs ðt; rÞ ¼ f ð1; rÞ ðA0n A0s;z Þ exp½ixðt 1Þd1 2015;96:377–83.
0 [7] Acred A, Hunt GR. Stack ventilation in multi-storey atrium buildings: a
Z 1
¼ ðA0n A0s;z Þ expðixtÞ f ð1; rÞ expðix1Þd1 ðA16Þ dimensionless design approach. Build Environ 2014;72:44–52.
[8] Santamouris M, Assimakopoulos D, editors. Passive cooling of
0 buildings. London (UK): James & James (Science Publishers) Ltd.; 1997.
¼ ~hn Fðix; rÞ [9] Labs K. Earth coupling. In: Cook J, editor. Passive cooling. Cambridge,
Massachusetts, London, England: MIT Press; 1989. p. 197–346.
Then, the complex form of the excess fluctuating temperature of [10] Bharadwaj SS, Bansal NK. Temperature distribution inside ground for various
surface conditions. Build Environ 1981;16:183–92.
the pipe wall of the EAHE is [11] Soni SK, Pandey M, Bartaria VN. Ground coupled heat exchangers: a review
and applications. Renew Sust Energy Rev 2015;47:83–92.
~hs ðt; RÞ ¼ ~hn Fðix; RÞ ðA17Þ [12] Morrone B, Coppola G, Raucci V. Energy and economic savings using
geothermal heat pumps in different climates. Energy Convers Manage
with 2014;88:189–98.
qffiffiffiffi [13] Vaz J, Sattler MA, Brum RS, et al. An experimental study on the use of earth-air
ix
h1 K 0 as R
heat exchangers (EAHE). Energy Build 2014;72:122–31.
Fðix; RÞ ¼ qffiffiffiffi qffiffiffiffi qffiffiffiffi ðA18Þ [14] Bisoniya TS, Kumar A, Baredar P. Experimental and analytical studies of earth-
h1 K 0 ix
as R þ k s
ix
as K 1
ix
as R
air heat exchanger (EAHE) systems in India: a review. Renew Sust Energy Rev
2013;19:238–46.
[15] Mongkon S, Thepa S, Namprakai P, Pratinthong N. Cooling performance
assessment of horizontal earth tube system and effect on planting in tropical
Appendix C. Solution of the fluctuating component of pipe air greenhouse. Energy Convers Manage 2014;78:225–36.
[16] Pfafferott J. Evaluation of earth-to-air heat exchangers with a standardized
temperature method to calculate energy efficiency. Energy Build 2003;35(10):971–83.
[17] Aschehoug O, Perino M. IEA ECBCS Annex 44 integrating environmentally
Inserting Eq. (14) and Eq. (8) into Eq. (16) gives responsive elements in buildings, expert guide part 2 – responsive building
elements; 2009.
ix ~ @ ~hn 2d0 [18] Thiers S, Peuportier B. Thermal and environmental assessment of a passive
ðhn þ Te s;z Þ ¼ ð1 FÞ~hn ðA19Þ building equipped with an earth-to-air heat exchanger in France. Solar Energy
Va @x R 2008;82(9):820–31.
[19] Ghosal MK, Tiwari GN. Modeling and parametric studies for thermal
Eq. (A19) is rearranged as performance of an earth to air heat exchanger integrated with a greenhouse.
Energy Convers Manage 2006;47:1779–98.
@ ~hn ix 2d0 ix Te s;z
þ þ ð1 FÞ ~hn þ ¼0 ðA20Þ [20] Li H, Yu Y, Niu F, et al. Performance of a coupled cooling system with earth-to-
@x Va R Va air heat exchanger and solar chimney. Renew Energy 2014;62:468–77.
194 D. Yang et al. / Energy Conversion and Management 109 (2016) 184–194
[21] Sodha MS, Buddhi D, Sawhney RL. Thermal performance of underground air [28] Rashidi S, Bovand M, Esfahani JA. Heat transfer enhancement and pressure
pipe: different earth surface treatments. Energy Convers Manage 1991;31 drop penalty in porous solar heat exchangers: a sensitivity analysis. Energy
(1):95–104. Convers Manage 2015;103:726–38.
[22] Sulaiman F. A numerical analysis of heat transfer process in an underground [29] Hollmuller P. Analytical characterisation of amplitude-dampening and phase-
heat tube. J Phys Sci 1995;6:57–67. shifting in air/soil heat-exchangers. Int J Heat Mass Transfer 2003;46:4303–17.
[23] Krarti M, Kreider JF. Analytical model for heat transfer in an underground air [30] Yang D, Zhang J. Analysis and experiments on the periodically fluctuating air
tunnel. Energy Convers Manage 1996;37(10):1561–74. temperature in a building with earth-air tube ventilation. Build Environ
[24] Mihalakakou G, Santamouris M, Asimakopoulos D. Modeling the thermal 2015;85:29–39.
performance of the earth to air heat exchangers. Solar Energy 1994;53: [31] Rodrigues MK, Brum RS, Vaz J, et al. Numerical investigation about the
301–5. improvement of the thermal potential of an earth-air heat exchanger (EAHE)
[25] Wu H, Wang S, Zhu D. Modelling and evaluation of cooling capacity of earth- employing the Constructal Design method. Renew Energy 2015;80:538–51.
air-pipe systems. Energy Convers Manage 2007;48:1462–71. [32] Bansal V, Misra R, Agrawal GD, Mathur J. Performance analysis of earth-pipe
[26] Al-Ajmi F, Loveday DL, Hanby VI. The cooling potential of earth-air heat air heat exchanger for summer cooling. Energy Build 2010;42:645–8.
exchangers for domestic buildings in a desert climate. Build Environ [33] Incropera FP, DeWitt DP. Introduction to heat transfer. 2nd ed. New
2006;41:235–44. York: Wiley; 1996.
[27] Dehghan M, Jamal-Abad MT, Rashidi S. Analytical interpretation of the local [34] Lu X, Tervola P, Viljanen M. An efficient analytical solution to transient heat
thermal non-equilibrium condition of porous media imbedded in tube heat conduction in a one-dimensional hollow composite cylinder. J Phys A: Math
exchangers. Energy Convers Manage 2014;85:264–71. Gen 2005;38:10145–55.