Professional Documents
Culture Documents
Abstract: This paper deals with single phase isolated neutral, a single-phase ferroresonance occurs
ferroresonance in high voltage substations with in high voltage networks with a solidly earthed neutral
inductive voltage transformers (VT) and provides an system. In this case the electrical circuit can be
overview of uncritical and critical network described by a simple single-phase system. There are
configurations, parameters influencing the two situations in which a single phase ferroresonance
ferroresonance behaviour and measures to avoid can occur. The first situation may exists by the
ferroresonance occurrence. A special measure to avoid coupling between double circuit lines when the line of
ferroresonance, which is applied by Trench Germany lower voltage is disconnected at both ends while the
(TG), is discussed. This measure is to de-tune the non- line of higher voltage keeps energised and the voltage
linear resonant circuit by a VT iron-core with an transformer is connected to the de-energised line [6,7].
integrated air-gap. By means of TG’s VT-design it is The more important and more often reported
possible to avoid ferroresonance occurrence for nearly ferroresonance situation may occur when a VT,
all substation arrangements. A comparison of connected to an open busbar section, is de-energised
theoretically and experimentally obtained by tripping a circuit breaker (CB) equipped with
ferroresonance studies is discussed. grading capacitors [6,8,9].
Again, it must be pronounced that ferroresonance
1. Introduction occurs only for specific network configurations, that
means a critical combination of the circuit breaker
Although the first papers on ferroresonance were grading capacitance, phase to ground capacitance and
published in the beginning of the last century [1,2] magnetizing characteristic of the VT.
ferroresonance, which can occur exceptionally for As already mentioned above this paper will now focus
specific power network configurations, is still a not on triggering a single-phase ferroresonance by
fully understood phenomenon. This paper focus on so opening of a circuit breaker with grading capacitors.
called single-phase ferroresonance in networks with Figure 1 shows the typical substation arrangement for
inductive voltage transformers (VT), fed by the circuit this case. For a qualitative understanding of the
breaker grading capacitance. In principle ferroresonance phenomenon this arrangement can be
ferroresonance is a forced oscillation in a non linear reduced to a series resonant circuit (s. figure 2).
series resonance circuit including a capacitance and a
non linear inductance, which shows significantly
distorted voltage and current waveforms. The non
linear behaviour of the saturable inductance can cause
oscillations at network frequency so called
fundamental ferroresonance, simple fractions of it
described as sub-harmonic ferroresonance and even
chaotic oscillations. Ferroresonance can result in high
overvoltages, especially at system frequency, and high
overcurrents, which can finally result in insulation Figure 1: Substation arrangement with CB and VT according to [3].
failures of the high voltage equipment or in
destruction of the inductive voltage transformer due to
overheating [3,4,5]. However, there are measures to
avoid ferroresonance with respect to substation and
VT design as will be discussed below. Even if there is
the risk of ferroresonance for specific substation
configurations, inductive VTs, rather than capacitive
ones, are used because of their reliability, cable
discharge capability, higher accuracy and stable
transformation ratio during the entire lifetime [4].
2. Single-phase ferroresonance
In contrast to the well known three-phase
Figure 2: Series resonant circuit for describing the single phase
ferroresonance, which can occur in systems with ferroresonance phenomenon according to [10].
1
With Thevenin’s theorem the voltage divider, built by a stable ferroresonance. Therefore loading the VT
the grading capacitance and the phase to ground with maximum burden is recommended in case of
capacitance of the busbar, can be substituted by the critical substation configurations. When designing a
equivalent Thevenin voltage and capacitance. A new substation circuit breakers with low or even no
detailed description is found e.g. in [11]. grading capacitance will reduce or even prevent the
The intersections of the straight capacitance line with risk of ferroresonance generation. For a given CB
the magnetizing curve of the non-linear inductance grading capacitance there is no risk of ferroresonance
shows three possible operating points. It can be if the phase to ground capacitance value exceeds a
shown, that point B is unstable whereas A and C are certain limit. Therefore an adequate high phase to
stable ones. Point C is correlated to high voltages and ground capacitance connected to the inductive VT will
higher currents which may destroy the high voltage also lower this risk of ferroresonance appearance.
equipment and must therefore be avoided. However, even for phase to ground capacitance values
below this limit there may exist several distinct ranges
Uncritical network configurations wherein only damped transient ferroresonances occur.
There are some substation configurations which are In general these ranges strongly depend on the burden
uncritical regarding ferroresonance generation. For connected to the secondary. This phenomenon is
instance the large inductance of a power transformer related to a non matching phase angle between the
or the large capacitance of a transmission line directly network voltage and the natural oscillation of the
attached to the VT will prevent ferroresonance ferroresonance circuit. Another important aspect
occurrence. According to figure 2 the high capacitive affecting ferroresonance generation is the circuit
or inductive reactance will not allow to match the breaker switching event itself, since ferroresonance
ferroresonance conditions. Of course if circuit appearance is completely determined by the electrical
breakers without grading capacitors are installed in the circuit and the initial conditions. In most of the cases
substation, which are nowadays available for system voltage maximum is assumed to be the most critical
voltages up to 500 kV, there is also no risk of time for circuit breaker opening.
ferroresonance.
The measures to avoid a single-phase ferroresonance
Critical network configurations can be divided in two classes: damping of the
More attention should be given to critical network ferroresonance oscillation and de-tuning of the
configurations. The three most important substation resonance circuit. Damping of the ferroresonance can
configurations which may produce ferroresonance are either be done on the primary or the secondary side. In
listed below. A critical situations may occur when a air insulated substations the resistance attributed to
busbar section, connected to the VT, is de-energised corona losses and leakage current on outdoor
by tripping one or several circuit breakers insulators is sometimes sufficient to provide an
simultaneously. The second situation is more critical effective damping on the primary side. This resistance
because of the greater equivalent grading capacitance is in parallel to the phase to ground capacitance. In
caused by circuit breakers arranged in parallel. Critical GIS, however, theses kind of power losses do not
situations can also occur during opening of the circuit exist. Damping on the VT secondary, in addition to
breaker in line bays or in bus coupling bays with open the connected burden, can consist of an active or
feeder disconnector. In general a critical network passive damping circuit. For active damping an
configuration exists if the ratio of the phase to ground appropriate damping circuit is switched in the VT
capacitance to the grading capacitance of the circuit secondary circuit in case of ferroresonance
breaker is low. occurrence. A passive damping device consists of a
saturable reactor with an extreme knee of the
3. Mitigation and measures to avoid saturation characteristics in combination with a
ferroresonance resistor in parallel to the VT burden. The reactor can
then be considered as a magnetic switch. The resistor
The possibility of ferroresonance occurrence in critical on the secondary only works as an additional burden
network arrangements is affected by several as long as the reactor is saturated. Sometimes this
parameters like the actual system voltage, power happens for a short time only which is not sufficient to
losses, grading and phase to ground capacitance damp the oscillation. Moreover if the VT core is
values, the moment of circuit breaker switching and saturated the coupling between the primary and
finally the VT design. secondary side is not ideal due to an increased leakage
Power losses and therefore damping is always present flux of the VT’s primary coil. Therefore the damping
in the form of corona losses, leakage current on of the oscillation is lower than theoretically expected.
insulators, iron and eddy current losses in the VT and Another possibility is to de-tune the resonant circuit.
the burden on the VT secondary. Damping reduces the De-tuning of the resonant circuit can be obtained by
ferroresonance current and can sometimes even avoid changing the ratio of the CB grading capacitance to
0
-0.025
[12]. Especially the effect of power losses has a great
-0.05 influence on the ferroresonance behaviour, as shown
b) by the experiment.
0 0.5 1 1.5 2 2.5 3
t [s]
Figure 4: Calculated secondary voltage (a) and corresponding 7. References
primary current (b) waveform of a transient ferroresonance (worst
case scenario). [1] J. Bethenod,”sur le transformateur et resonance”, L’Eclairae
Electrique, pp. 289-296, Nov. 30, 1907.
150
100
[2] P. Boucherot, “Existence de deux regimes en ferro-
50 resonance”, R.G.E., pp. 827-828, Dec. 10, 1920.
U [V]
0
-50
[3] Z. Emin, B.A.T. Al Zahawi, Y.K. Tong., “Voltage
-100 transformer ferroresonance in 275 kV substation”, Proc. ISH,
-150 1999.
0 0.5 1 1.5
t [s] [4] R. Mareachen, A. Christesen, G. Poletto, “Ferroresonance on
Figure 5: Measured secondary voltage waveform of a highly 345-kV bus kills PT”, pp. 69-70, Electrical World, April
damped transient ferroresonance. 1986.
[5] D.A.N. Jacobson, D. Swatek, R. Mazur, “Mitigating potential
150
100 transformer ferroresonance in a 230 kV converter station”,
50 Computer Analysis of Electric Power System Transients:
U [V]