• UL 1449 Third Edition Listed
• 100kA – 200kA per phase ratings
• Type 1 SPD
–– Included internal overcurrent protection coordinated with
thermal protection avoids safety blind spots
• 20kA Inominal (In) (most models)
• 200kA Short Circuit Current Rating (SCCR, most models)
• Models for Types TN-C, TN-S, TN-C-S, IT and option
for Type TT system
• UL 96A Lightning Protection Master Label (@20kA In)
• Voltage Specific Design – highly configurable
• All MOV suppression elements monitored
SPS 02 HDS 20 4x A
Voltage Code for Electrical System Surge Current Rating Enclosure Rating Options
Common Power Systems: 10 = 100kA/Phase 4X = IP56 (NEMA 4X) Non- A = Audible Alarm & Dry
All Systems Type TN-C, TN-S, TN-C-S unless noted: 15 = 150kA/Phase Metallic (size: 152mm Contacts, Form C, 240V, 5A
(All Type TT systems Must have ‘G’ option at right) x 152mm x 102mm 2 = Type 2 SPD Bearing cUL
20 = 200kA/Phase
12 = 240V Single Phase (Fig 5) (6” x 6” x 4”)) Mark
02 = 208Y/120V Wye - 3Ø 4W+Grnd (Fig 2) Delete Options
42 = 415Y/240V Wye - 3Ø 4W+Grnd (Fig 2) Consult Factory for Order Code
43 = 400Y/230V Wye - 3Ø 4W+Grnd (Fig 2) L = Delete L-N Protection
44 = 440Y/250V Wye - 3Ø 4W+Grnd (Fig 2) (reduces kA rating)
07 = 380Y/220V Wye - 3Ø 4W+Grnd (Fig 2) G = Delete L-G Protection
(reduces kA rating)
Other Available SystemsConfirmation encouraged: N = Delete N-G Protection
01 = 240/120V Split Phase - 1Ø, 3W+Grnd, (Fig 1) (reduces kA rating)
15 = 254/127V Split Phase - 1Ø 3W+Grnd (Fig 1) J = Delete Noise Filtering
18 = 480/240V Split Phase, or Two legs of Wye (Call)
21 = 220Y/127V Wye - 3Ø 4W+Grnd (Fig 2) Available Accessory
03 = 240/120V High Leg Delta (B High) (Fig 3) (order separately)
04 = 480Y/277V Wye - 3Ø 4W+Grnd (Fig 2) KITFMXF = Flush Mount Kit
41 = 520Y/300V Wye - 3Ø 4W+Grnd (Fig 2) RM = Remote Monitor
05 = 480V Delta (Type IT) - 3Ø 3W+Grnd (Fig 4) & HRG Wye
51 = 480V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
06 = 240V Delta (Type IT) - 3Ø 3W+Grnd (Fig 4)
61 = 240V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6)
08 = 600Y/347V Wye - 3Ø 4W+Grnd (Fig 2)
09 = 600V Delta (Type IT) - 3Ø 3W+Grnd (Fig 4) & HRG Wye (Available: 100kA)
91 = 600V B Corner Grnd Delta, 3Ø 3W+Grnd (Fig 6) (Available: 100kA)
11 = 120V Single Phase (Fig 5)
13 = 127V Single Phase (Fig 5)
14 = 300V Single Phase (Fig 5)
16 = 277V Single Phase (Fig 5)
17 = 480V Single Phase (1 Hot, 1 Neu, 1 Grnd) (Fig 5)
}
Phase A (BLK) Hot (BLK)
}
Hot (BLK) Phase A (BLK) Phase A (BLK)
}V A B Phase B (BLK) Phase B (ORNG)
V
V }V Phase A (BLK)
}V Neutral (WHT)
N
Neutral (WHT) }V Phase B (BLK)
Neutral (WHT) Phase C (BLK)
}
Hot (BLK) Phase C (BLK)
V Phase C (BLK) Ground (GRN)
Neutral (WHT) Ground (GRN)
Phase C (BLK)
Ground (GRN) Ground (GRN) Ground (GRN)
C Ground (GRN)
Power Systems: Type TN-C, Power Systems: Type TN-C, Power Systems: Type TN-C, Power System: Type IT Power Systems: Type TN-C, Power Systems: Type TN-C,
Type TN-S, Type TN-C-S, Type TN-S, Type TN-C-S, Type TN-S, Type TN-C-S, Type TN-S, Type TN-C-S, Type TN-S, Type TN-C-S,
Type TT must use G option Type TT must use G option Type TT must use G option Type TT must use G option Type TT must use G option
Performance Data
UL 1449 Third Edition (Sept. 2009) Test Data - Voltage Protection Ratings (VPR - 3kA)
Common Power Systems
L-N L-G N-G L-L Type In SCCR MCOV
12 = 240V Single Phase 1200 1200 1200 N/A Type 1 20kA 100kA 320
02 = 208Y/120V 3Ø Wye 700 700 600 1000 Type 1 20kA 200kA 150
42 = 415Y/240V Wye 1200 1200 1200 2000 Type 1 20kA 200kA 320
43 = 400Y/230V Wye 1200 1200 1200 2000 Type 1 20kA 200kA 320
44 = 440Y/250V Wye 1200 1200 1200 2000 Type 1 20kA 200kA 320
07 = 380Y/220V Wye 1200 1200 1200 2000 Type 1 20kA 200kA 320
Contact us for other available systems 5.1.13.lh