Reclosers

Electrical Apparatus
NOVA 15i, NOVA 27i, and NOVA 38i
280-43
®

Three-Phase, Microprocessor-Controlled Reclosers

DESCRIPTION
The NOVA®i three-phase,
microprocessor controlled,
vacuum-interrupting automatic
circuit reclosers provide advanced
system protection, metering,
and data acquisition with full
integration and automation
functionality for distribution
circuits rated through 38.0 kV.
The NOVA i recloser combines
solid cycloaliphatic-epoxy polymer-
encapsulated vacuum interrupters
with a reliable, lightweight operating
mechanism that utilizes a magnetic
actuator to provide a lifetime of
trouble-free operation. The solid
polymer system does not rely on a
gaseous, liquid, or foam dielectric.
The NOVA i recloser is highly
resistant to ozone, oxygen, moisture,
contamination, and ultraviolet light.
Designed and tested to be
compatible with the Cooper Figure 1.
Power Systems Form 6 recloser NOVA i vacuum-interrupting, three-phase, microprocessor-controlled
control, these automatic automatic circuit recloser. (Shown with 4-hole flat-pad terminal accessory.)
circuit reclosers offer superior
coordination, protection, and
application capabilities.
Cooper Power Systems is When needed, application expertise,
Recloser operations are programmed strongly committed to improving backed by world-wide systems
in an electronic control with accurate the reliability of the electric engineering knowledge and
characteristics and a host of power industry. Technological experience, is available. Customer-
advanced features. Precise operating advances, including the newest focused design capability, based
tolerances enable close coordination microprocessor-based controls and on more than 65 years of recloser
with other protective devices on the solid insulation NOVA i distribution experience, has made Cooper
system. When system requirements switchgear products, represent Power Systems an industry leader.
change, program settings are our investment in the future.
easily altered with no sacrifice NOVA i reclosers are designed
of accuracy or consistency. The NOVA i recloser is not only a and manufactured in accordance
technological breakthrough, but with IEC 62271-111 2005 and
Compact and lightweight, NOVA i a valuable component that brings IEEE Standard C37.60-2003™.
reclosers are easily installed on significant operational savings to
poles or in substations. Mounting the utility business unit, lowering ISO 9001:2000 Certified Quality
equipment is available for both the installation, operation, training, Management System
pole and substation applications. and maintenance costs on your
Recloser and control accessories power distribution system.
enable further tailoring of the
protective program to achieve
maximum system operating flexibility.

May 2007 • New Issue 1


Printed in USA
NOVA® 15i, NOVA 27i, and NOVA 38i Three-Phase, Microprocessor-Controlled Reclosers

RATINGS AND coordination includes a wide array ORDERING


CHARACTERISTIC of minimum trip values, reclosing INFORMATION
FEATURES and resetting time settings, and
a selection of accessories. All NOVA i reclosers include a
Three-phase protection on systems Form 6 microprocessor-based
rated 2.4 through 15.5 kV is Vacuum Interruption recloser control. The Form 6 control
provided by NOVA 15i reclosers. A single break on each phase includes full protection, TCC
NOVA 27i reclosers can be applied is accomplished by separating Editor™, metering, and diagnostics
on systems rated through 27 kV. contacts inside the vacuum for your application needs.
Higher-voltage system protection interrupter. All arcing is contained To order a NOVA i recloser,
at 38 kV is provided by NOVA 38i within the vacuum envelope. The electronic control, and control cable:
reclosers. A ratings summary for axial-magnetic vacuum interrupters
Type NOVA i reclosers is shown in used in NOVA i reclosers offer 1. See the Constructing a
Tables 1–3. For ratings and basic extended and increased duty cycles Catalog Number section to
application information on other compared with oil or radial-magnetic construct a catalog number that
Cooper Power Systems reclosers, interrupters. The axial-magnetic field describes the required recloser.
see Catalog Section 280-05. keeps the arc in a diffused mode, 2. From Tables 5–9, specify the
Operation resulting in less arc power to be catalog numbers that describe
dissipated, resulting in low thermal the required recloser accessories.
Each recloser includes integrated stress, suitable for encapsulation.
Cooper Power Systems designed
current transformers for accurate Surge Protection
secondary current input to the Best operating results are achieved
Cooper Form 6 recloser control. if reclosers are protected with surge
Due to a single CT ratio for all arresters. For line applications,
ratings, minimum-trip values of the arrester protection is recommended
electronic control are independent on both sides of the recloser. (If
of the continuous-current and protection is on one side only, it
interrupting ratings of the recloser. should be on the source side. In
Tripping and closing signals substations, arresters should be
from the control energize the on the load side.) Cooper Power
operating circuits in the recloser. Systems distribution-class arresters
Exceptional flexibility in coordination provide excellent protection and
with other protective devices are available with mounting
is provided by 35 resident brackets to fit Cooper reclosers
time–current curves that can be (see Catalog Section 235).
customized by the user for precise
system coordination. System

Figure 2.
NOVA i recloser.

2
280-43

FEATURES AND Construction HYDROPHOBICITY


DETAILED DESCRIPTION RECLOSER The module maintains excellent
NOVA i microprocessor-controlled, hydrophobicity, a property
Designed for long service life and no characterized by water beading
three-phase reclosers protect
maintenance, the NOVA i recloser into isolated drops, and is highly
systems operating through 38 kV
has three solid-polymer interrupter resistant to moisture absorption.
(see Ratings and Specifications
modules, current transformers, and Hydrophobicity prevents continuous
section of this catalog). These
a magnetic actuator mechanism; sheets of water from forming leakage
ratings and the wide range of
light gray is the standard color. current paths that deteriorate
programmable settings provided
by the Cooper Power Systems Cycloaliphatic-epoxy polymer the creepage withstand level.
Form 6 control meet a variety encapsulation provides solid ULTRAVIOLET RESISTANCE
of application requirements. insulation and maintenance-free,
environmentally safe operation. The cycloaliphatic epoxy resists
Recloser Operation There is no monitoring or ultraviolet radiation damage even
Fault currents are sensed by maintaining of gas pressure or in harsh climates, maintaining
three 1000:1 ratio sensing current oil levels; there are no toxic or a smooth, unblemished, self-
transformers. These CTs provide environmentally unfriendly materials. cleansing surface with low-
a continuous measurement There are no foam fillers or adhesion to contaminants.
of line current, monitored by insulation seals, eliminating potential TENSILE STRENGTH
the microprocessor control. moisture ingress areas. The NOVA i
When current level exceeds the recloser module exhibits excellent Outstanding tensile and flexural
programmed minimum trip level, absorption of elastic energy and strength characteristics mean the
the magnitude of the overcurrent resistance to cracking and crack NOVA i recloser modules are tough
is integrated with time, using propagation. Additionally, durable and non-fragmenting, reducing
a programmed time–current environmental properties make the shipment and handling charges.
curve characteristic. The solid polymer suitable for outdoor SHED DESIGN
control then signals the trip in applications, including seacoasts,
the recloser, opening the main deserts, and areas of high pollution. The shed design utilizes alternate-
contacts of all three phases. sized skirts. The major sheds
SURFACE TRACKING shield and protect the minor sheds
The control signals tripping The cycloaliphatic epoxy is highly to enhance the hydrophobicity
and closing. The recloser resistant to contaminants and and ultraviolet resistance of the
always maintains energy for resists tracking and flashovers module, eliminate formation of
a tripping operation following under extreme pollution levels microcracks, and ensure extra-
a closing operation. to reduce both flashovers and protected creepage. Additionally,
The electronic recloser control the associated cost of repairs. sharp edges direct water away
provides determination of phase- from the unit. Water paths and ice
and ground-trip sequences formations are effectively eliminated.
and operations to lockout and
reclosing and resetting timing,
adjustable with the control, without
de-energizing the recloser.

Magnetic Actuator Mechanical


Trip-and-Close Manual OPEN Handle Operations Counter Heater
Capacitors
Heater

OPEN/CLOSE
Aluminum Mechanism Contact Position Control Cable Ground Connector
Housing (Standard) Indicator Actuator Board CT Protection Board Receptacle #10 - #2 Stranded

Figure 3.
NOVA i recloser mechanism with control-powered interface (view from bottom of recloser with bottom cover removed).

3
NOVA® 15i, NOVA 27i, and NOVA 38i Three-Phase, Microprocessor-Controlled Reclosers

FLASHOVER RECOVERY Electronic Control Manual Operation


Flashovers occur when an object, NOVA 15i, NOVA 27i, and The recloser can be opened
usually wildlife, contacts energized NOVA 38i reclosers are integrated manually with a hotstick to pull down
parts of the equipment. The NOVA i with Cooper Power Systems’ the yellow manual OPEN handle
recloser minimizes the effect of Form 6 electronic recloser control under the sleet hood. With the
flashovers with remarkable physical as a total system to provide handle in the OPEN position, the
resilience, arc-quenching properties, a complete reliability solution control cannot close the recloser.
and a self-healing ability. The NOVA i for distribution systems. The yellow handle, when pulled in
recloser can withstand the enormous a downward motion, will remain in
forces experienced during faults Control-Powered the down position, providing visible
without wholesale damage and Interface indication that the unit is open
allows re-energizing after external and disabled from any closing.
The NOVA i recloser and (see
flashover without cleaning. Cooper
Figure 4) Form 6 microprocessor- The recloser is closed, following a
Power Systems also offers wildlife
based control provides complete manual open, by pushing the yellow
guards to minimize flashovers.
open-close sequences without handle back under the sleet hood
Vacuum Interrupters ac power. The control-powered and then using the microprocessor
interface includes a 19-pin control to close the recloser.
NOVA i reclosers use vacuum receptacle on the recloser and
as the interrupting medium. an internal heater (for humidity Similarly, the recloser can be closed
Vacuum interrupters provide control) powered from the control from the close button on the Form 6
fast, low-energy arc interruption input power supply (ac or dc). control panel, provided the manual
with long contact and interrupter The dc-to-dc converter board operating handle is up. A red contact
life, low mechanical stress, and converts the control’s 24 V dc position indicator flag, adjacent to
maximum operating safety. With battery supply to 53 V dc to charge the manual operating handle, shows
arc interruption taking place in a the trip/close capacitors in the the recloser’s contact position.
vacuum, contact and interrupter NOVA i recloser mechanism.
life are several times greater than
with interruption in oil, virtually The dc-to-dc converter board also
eliminating interrupter maintenance. houses voltage monitoring and
conditioning circuits that protect the
Vacuum interrupters are designed battery from failure and provide trip/
with a metal and ceramic housing close operations without ac power.
for maximum strength and
long-term vacuum integrity.
Enclosed in the interrupter
are a stationary and a moving
contact assembly.

Figure 4.
Control-powered NOVA i recloser configuration with potential transformer input power.

4
280-43

Internal Voltage TERMINALS POLE-MOUNTING HANGER


Sensor Option The standard is a 2-hole, flat-pad A pole-mounting hanger, which
The NOVA i recloser is available with (630 A) terminal. An eyebolt bolts directly to the recloser
internal voltage sensors at time of 1/0-500 mcm (630 A), eyebolt frame, is available for pole-
order. Using a high-voltage resistor 4/0-1000 mcm (800 A), and mounting installation.
within each interrupter module 4-hole (800 A), flat-pad terminals
are available as an accessory. ARRESTER-MOUNTING
with source-side connections, the BRACKETS
sensing option, cable, and control The eyebolt and flat-pad
support a magnitude accuracy of terminals are made of copper The arrester-mounting bracket
2% or better and a phase degree alloys. Cooper Power Systems accessory can be bolted to
accuracy of ±1.5° throughout the recommends terminal connection the recloser frame and pole-
temperature range of -40°C to to copper wires to optimize the mounting hanger for the addition
+65°C. The internal voltage electrical connection. Aluminum of inboard and outboard
sensing option is compatible cables may produce aluminum arresters. The arresters are not
with a control-powered Form 6 oxide sufficient to compromise included with the brackets.
Pole-Mount control. the electrical connections. SUBSTATION-MOUNTING FRAME
Accessories Anti-oxide coatings for temporary A substation-mounting frame
protection of wire-brushed aluminum accessory is available for
AUXILIARY SWITCH
cable connections to flat-pad substation-mounting applications.
A three-stage auxiliary switch can terminals must be maintained at
be provided as an accessory. Each intervals determined by the customer
stage has two independent contacts based on load current, climate,
that permit any desired combination and other installation conditions.
of “a” (follow state of recloser
contacts) and “b” (opposite recloser Eyebolt terminals are recommended
contacts) positions. The switch for copper conductors only.
contacts are insulated for 600 V
and have a continuous current
rating of 10 A. Their interrupting
ratings are shown in Table 4.

5
NOVA® 15i, NOVA 27i, and NOVA 38i Three-Phase, Microprocessor-Controlled Reclosers

RATINGS AND SPECIFICATIONS


Check Recloser Ratings
Prior To Installation
The recloser must be applied
within its specified ratings. Check
nameplate ratings and compare
with the system characteristics
at the point of application prior to
installation. Tables 1, 2, 3, and 4
list the ratings and specifications
for the NOVA i recloser.

TABLE 1
Voltage Ratings (kV)
Description 15 kV 27 kV 38 kV

Maximum Voltage 15.5 kV 27 kV 38.0 kV


Rated Basic Impulse Level (BIL) 110.0 kV 150.0 kV 170.0 kV*
Radio Noise Limit (µv) 100 @ 9.4 kV 100 @ 16.4 kV 100 @ 23.0 kV
Power Frequency Withstand, Dry 50 kV 60 kV 70 kV
Power Frequency Withstand, Wet 45 kV 50 kV 60 kV
* 150 kV BIL open contacts.

TABLE 2
Current Ratings (A)
Description 15 kV 27 kV 38 kV

Rated Continuous Current 630 A* 630 A* 630 A*


Short Circuit Current, Symmetrical 12.5 kA** 12.5 kA** 12.5 kA
Making Current, Asymmetrical Peak 31.0 kA 31.0 kA 31.0 kA
Making Current, Asymmetrical RMS 20.0 kA 20.0 kA 20.0 kA
*800 A option available.
** 16.0 kA option available.

TABLE 3
Mechanical Ratings
Description 15 kV 27 kV 38 kV

Min. Mechanical/Electrical Operations


Without Maintenance (C-O) 10,000 10,000 10,000
Mass (Weight) - kg (lbs.) 110 (242) 115 (253) 125 (275)

TABLE 4
Duty Cycle*

Type Percentage of Number of Minimum


Interrupting Rating Unit Operations Circuit X/R Value
NOVA i 15-20 44 4
45-55 56 8
90-100 16 17
Total 116
*Compliant with IEC 62271-111 2005
*Compliant with IEEE Standard C37.60-2003™

6
280-43

E
394 394
Terminal
Connectors
A A

Terminal C
Connectors

298

1000
285

D NOTE: All dimensions are mm. Dimensions shown are approximate.

Figure 5.
NOVA i three-phase recloser dimensions.

Terminal Options A B C D E
Eyebolt, 1/0-500mcm
89
Cable Range (630 A Max.) NOVA 15i 809 528 400.5 285
Eyebolt, 4/0 - 1000 mcm
111
Cable Range (800 A Max.) NOVA 27i 908 627 400.5 285
Flat Pad, 2-hole
119
(630 A Max.) NOVA 38i 1007 676 441.1 298.6
Flat Pad, 4-hole
121
(800 A Max.)

Creepage Distances

Description Creepage Distance (mm) Creep (mm/kV)

Terminal to terminal 1180 79


NOVA 15i
Lower Terminal to Ground/Earth 671 45
Terminal to terminal 1473 55
NOVA 27i
Lower Terminal to Ground/Earth 951 35
Terminal to terminal 1763 46
NOVA 38i
Lower Terminal to Ground/Earth 1215 32

7
NOVA® 15i, NOVA 27i, and NOVA 38i Three-Phase, Microprocessor-Controlled Reclosers

POLE

1085
637

617 A
Min.

290

POLE 779

POLE

NOTE: All dimensions are mm.


Dimensions shown are approximate.

Figure 6.
Dimensions of NOVA i recloser with pole-mounting hanger accessory (NOVA 15i shown).

Terminal Options A Dimension B

Eyebolt, 1/0 - 500 mcm 89 NOVA 15i


809
Cable Range (630 A maximum) 110 kV BIL
Eyebolt, 4/0 - 1000 mcm NOVA 27i
111 908
Cable Range (800 A maximum) 150 kV BIL
Flat Pad, 2-hole NOVA 38i
119 1007
(630 A maximum) 170 kV BIL
Flat Pad, 4-hole 121
(800 A maximum)

8
280-43

NOTE: All dimensions are mm. Dimensions shown are approximate.

Figure 7.
Dimensions of NOVA i recloser with substation-mounting frame accessory.

Terminal Options A B C

Eyebolt, 1/0 - 500 mcm NOVA 15i


89 809 528
Cable Range (630 A maximum) 110 kV BIL
Eyebolt, 4/0 - 1000 mcm NOVA 27i
111 908 627
Cable Range (800 A maximum) 150 kV BIL
Flat Pad, 2-hole NOVA 38i
119 1007 676
(630 A maximum) 170 kV BIL
Flat Pad, 4-hole
121
(800 A maximum)

9
NOVA® 15i, NOVA 27i, and NOVA 38i Three-Phase, Microprocessor-Controlled Reclosers

CONSTRUCTING A CATALOG NUMBER


To order a type NOVA i recloser with 15 kV, 12.5 kA interrupting, 630 A two-hole pad terminals, 120 V ac heater,
no internal voltage sensors, and aluminum housing, the catalog number would be constructed like this:

KNOVA i Basic letters for a NOVA i recloser with base Form 6 recloser control*
1 Recloser Type:
1 NOVA 15i for 15 kV, 630 A continuous, 12.5 kA interrupting, 110 kV BIL
2 NOVA 15i for 15 kV, 630 A continuous, 16.0 kA interrupting, 110 kV BIL
3 NOVA 27i for 27 kV, 630 A continuous, 12.5 kA interrupting, 150 kV BIL
4 NOVA 27i for 27 kV, 630 A continuous, 16.0 kA interrupting, 150 kV BIL
5 NOVA 38i for 38 kV, 630 A continuous, 12.5 kA interrupting, 170 kV BIL
1 Bushing Terminals:
1 2-hole flat-pad terminal, 630 A max**
2 4-hole flat-pad terminal, 800 A max
3 Eyebolt terminal, 800 A 4/0 1000 MCM
4 Eyebolt terminal, 1/0 to 500 MCM, 630 A max
1 Heater Voltage:
1 120 V ac Heater
2 240 V ac Heater
1 Internal Voltage Sensor:
1 No voltage sensor per recloser
2 Three voltage sensors per recloser
1 Housing
1 Aluminum housing
2 Stainless steel housing

KNOVA i 1 1 1 1 1
KNOVA i –11111 is the catalog number for the required basic NOVA i recloser.
* Include the base catalog number of the selected control when ordering a type NOVA i recloser.

** Two-hole flat-pad terminal provided when not specified.

TABLE 5
Internal Voltage Sensing Cable

Catalog
Description Number

Internal Voltage Sensing Cable,


with plugs on both ends
maximum 15 m (50 ft).
Replace X with number of meters. KA97ME-X

10
280-43

TABLE 6
Mounting Equipment
Catalog
Description Number
Single pole-mounting hanger with stainless steel hardware KNOVAi54-3
Single concrete-pole-mounting hanger with stainless steel hardware KNOVAi54-4
Surge-arrester-mounting brackets with stainless steel hardware
Inboard mounting brackets KNOVAi61-2
Outboard mounting brackets KNOVAi61-1
Alley-pole-mounting hanger with stainless steel hardware KNOVAi352-1
Arrester brackets (set of 3) KNOVAi353-1
Arrester brackets (set of 6) KNOVAi353-2
Substation-mounting frame with stainless steel hardware
includes control-mounting bracket for Form 6 Pole Mount Control KNOVAi59-1
Field kit to mount NOVA i recloser on substation-mounting frame KA89WV1* KNOVAi457-1
Field kit to mount NOVA i recloser on substation-mounting frame KA584R1* KNOVAi457-2

* Does not include substation frame.

TABLE 7
Factory Assembly*
Catalog
Description Number

Recloser in single pole-mounting hanger KNOVAi54-3 or KNOVAi54-4 KNOVAi354-1


Recloser in single pole-mounting hanger, KNOVAi54-3
or KNOVAi54-4, with arrester brackets KNOVAi354-2
Recloser on alley-pole-mounting hanger KNOVAi352-1 KNOVAi456-1
Recloser on alley-pole-mounting hanger KNOVAi352-1 with arrester brackets KNOVAi456-2

*Covers factory assembly only: recloser, control, and mounting equipment must be ordered separately.

TABLE 8
Auxiliary Switch

Description Catalog
Number
Three-stage auxiliary switch with six independent contacts
and receptacle for KNOVAi82 cable KNOVAi66-2
Auxiliary switch cable with plugs on each end, maximum 30 meters (100 ft)
Replace X with number of meters. KNOVAi82-X

TABLE 9
Miscellaneous Accessories

Description Catalog
Number

Source and load wildlife guards, 630 A recloser (set of 6) KNOVAi56-6


Source and load wildlife guards, 800 A recloser (set of 6) KGS560-6

11
NOVA® 15i, NOVA 27i, and NOVA 38i Three-Phase, Microprocessor-Controlled Reclosers

© 2007 Cooper Power Systems, Inc., or its affiliates.


NOVA® is a registered trademark of Cooper Power
Systems, Inc., or its affiliates.
TCC Editor™ is a trademark of Cooper Power Systems,
Inc., or its affiliates. 1045 Hickory Street
IEEE Standard C37.60-2003™ is a trademark of the Pewaukee, WI 53072 USA
Institute of Electrical and Electronics Engineers, Inc. www.cooperpower.com
12 MI
05/07

You might also like