You are on page 1of 6

2KVA UPS SPECFICAITON

Rack Mount with -48V for Telecom Systems


2KVA UPS SPECFICAITON
Rack Mount with -48V for Telecom Systems

.1 Working theory block diagram


2KVA UPS SPECFICAITON | INDUSTRIAL PRODUCTS, WORLD CLASS QUALITY

1.1Theory of operation

This series of dedicated UPS (INV) power supply is designed for communication systems, railway systems,
power system requirements and it is a new generation of intelligent dedicated UPS (INV) power supply to meet
the communications, railways, power applications in various application environments on the power supply high
quality and high reliability requirements, and suitable for all power interference sensitivity, A stable, reliable,
purified, uninterrupted sine wave AC output system is required.

2 .Product Features

 Using advanced PWM+SPWM pulse width modulation technology, the output is stable frequency
stabilizer, filter noise, low distortion of pure sine wave.

 Advanced DC-AC Electrical Isolation technology, unlike other pseudo-isolation modes, truly enables
DC to be completely electrically isolated from AC in all circuits, meets the isolation requirements of all
applications, and eliminates all possible interactive interference.

 With post function, strong carrying capacity, good load compatibility, built-in bypass switch, improve
the UPS (INV) power supply continuity, reliability.

 With the direct power-on function of the city, allowing the user in the non-DC input, bypass electricity
output to the load supply, allowing to cut off DC in the boot state, automatic switching to the power
bypass, does not affect the load of electricity supply, easy to maintain and replace the battery.

1
 With the Power input 50HZ/60HZ adaptive function, can track and memorize the power input
frequency and UPS (INV) output the same frequency mode, so that the UPS (INV) input frequency
range of 44Hz~66Hz, output 50Hz or 60Hz, widely adapted to different power grid and equipment
requirements.

 Intelligent unattended function, in the presence of DC voltage is too high or too low, power power off,
such as shutdown output, DC voltage or electricity back to normal, automatic recovery output,
especially suitable for unattended communication base station.

 With perfect security protection function, DC input anti-reverse and DC input buffer protection, with overvoltage,
overload, short circuit, over-temperature, UPS (INV) failure and other comprehensive protection measures. The use of
advanced anti-irrigation noise suppression technology, and other common DC screen communication equipment do not
interfere with each other, the AC input end using multiple filtering, eliminate the interference of the power grid, to meet
the needs of the application system for the main AC power supply.

2KVA UPS SPECFICAITON | INDUSTRIAL PRODUCTS, WORLD CLASS QUALITY

2
2KVA UPS SPECFICAITON | INDUSTRIAL PRODUCTS, WORLD CLASS QUALITY

3
3.1 Outline
3. Products Picture
3.2 Picture

4
2KVA UPS SPECFICAITON | INDUSTRIAL PRODUCTS, WORLD CLASS QUALITY
4. Specification
Capacity: 2000VA/1400W

Nominal DC Input(Vdc): 48V

DC Input Range(Vdc)/48V -18% ~48V +25%

AC Input Range:120Vac-25% ~ 120V+20%

Input Frequency: 60Hz±10%

Output(Vac)120V±3%

Frequency(INV) (Hz):50Hz±0.1%

Output Current(A): 5.8 A

Input Power Factor(PF): 0.8

THD ≤3%

Transient(ms) : Load change 0-100%,response time≤30ms

Output power factor(PF): 0.8

Transfer Time(ms) <4ms

Overload

Under AC:125% work 10 minutes, 150% 10 second


2KVA UPS SPECFICAITON | INDUSTRIAL PRODUCTS, WORLD CLASS QUALITY

Under DC:125% 1 minutes, 150% 10 second

Efficiency(80% linear load)>88%

Protection: DC Anti-connection, buffer, excessive pressure, electricity input over undervoltage,


output overload, short circuit; Over temperature, etc.

Interface: LCD

Communication Port: RS32 and SNMP Slot

Dry Contact(Optional)

Noise(1 m) ≤40dB

Temperature(℃) -10℃ ~ 45℃

Humidity 0-95% Non-condensing

Height(m) <1500

Dimension(W*D*H): 440×88×350

Weight(Kg): 18