You are on page 1of 1

O242 MV Protection Relay Applications / Earth-fault protection

Exercise
(Resistance earthed, 1 gen)

1. Calculate E/F current neglecting earth capacitances, when Rf = 0

11kV
E  6350V
3

6350V
I  10 A
635

2. Calculate E/F current neglecting earth capacitances, when Rf = 500

6350V
I  5.6 A =5.6% (CT = 100/1A)
635  500