USE CASES- IEC 61850-90-5

Allowable Maximum
Communication measurement timing
Minumim
Sno. Objects delay (latency) errror// Time
Rate/sec
time// or Transfer synchronization
Time Class accuracy class
1 Synchro-check 4 0.1 s 0.05 ms
2 Adaptive Relaying 4 TT3 0.1s T3 0.025 ms
Out-of-step (OOS)
3 10 TT2 0.5s T3 0.025 ms
protection
Inter-area oscillation
4 10 TT0>1s T3 0.025 ms
detection
Local oscillation detection
5 50 TT0>1s T3 0.025 ms
(<10Hz)
Rate>3x(max
Series resonance
6 frequency TT0>1s T3 0.025 ms
detection (f<f0)
observed)
7 System phase angle 1 TT0>1s T3 0.025 ms
8 Power flow 1 TT0>1s T3 0.025 ms
9 Voltage profiles 1 TT0>1s T3 0.025 ms
10 State estimation 1/5 min to 10/s TT0>1s T3 0.025 ms
11 Special Protection scheme 10 TT2 0.5s T3 0.025 ms
Predictive dynamic
12 stability maintaining 30 20ms 0.05ms
system
Under voltage load
13 30 100ms 10ms
shedding
PMU to PDC/CE:
Phenomenon assumption 5s 0.05ms
14 1/s to 10/s
type WAMPAC
PMU to IED: 60/s 20ms 0.05ms
APPLICATION VS FRAMES PER SECOND
60

30 30

10 10 10 10
4 4
1 1 1