TSS: GARHI HASARU

(CAPACITAR BANK) 

AS Per RDSO Specs: TI/SPC/PSI/PROTCT/6071


TYPE: A25R

Sr. No.: 18AA25R0015. Date: 05/12/2018


Aux. Voltage: 110 VDC CT-1: 5Amp. CT-2: 1Amp
* Operating Value Test
Operating Value Test for I1> IDMT:
I1>1 Pickup Operating Value in Tolerance value in
setting Amp Amp
20% = 1.0A 1.05 A 0.95-1.05
80% = 4.0A 4.16 A 3.80-4.20
100% = 5.0A 5.20 A 4.75-5.25
Observation: The error in relay operating value was observed within ± 5%.

Operating Value Test for Current Unbalance:


ICU1> Setting Operating Value in Tolerance value in
Amp Amp
5% = 0.05A 0.051 A 0.0475-0.0525
50% = 0.50A 0.515 A 0.475 – 0.525
100% = 1.00A 1.029 A 0.90 – 1.050
Observation: The error in relay operating value was observed within ± 5%.
* Operating Time Measuring Test:
Time Testing for IDMT:
Setting: I1> = 50%, TMS = 1.0
I(I/ I1>1) Expected Time Observed Tolerance in
from curve Time in sec sec
5A(2N) 10.03s 10.09 9.528 – 10.531
12.5A(5N) 4.28s 4.31 4.066 – 4.494
25.0(10N) 2.97s 3.00 2.820 – 3.110
Observation: The Relay operating time found within +/-5%

Time Test for Current Unbalance:


ICU1> Setting: = 20%=0.40A
Set Injected Observed Time Tolerance(Sec)
Time(Sec) current (Sec)
0.100 0.40A 0.103 0.095 – 0.105
0.500 0.40A 0.514 0.475 – 0.525
1.000 0.40A 1.02 0.950 – 1.050
Observation: The Relay operating time found within +/-5%.
SSE/RC/NDLS SSE/RE/JP M/S L&T M/S ASHIDA
(CAPACITAR BANK) 

As Per RDSO Specs: TI/SPC/PSI/PROTCT/6071


TYPE: A26R

Sr. No.: 17LA26R0013. Date: 05/12/2018


Aux. Voltage: 110VDC PT: 27.5/110VAC

* Operating Value Test


Under Voltage Operating Value Test for (UV):
UV Pickup Operating Value in Tolerance value in
setting Volt Volt
20% = 22.0V 22.39 V 20.90 – 23.10
55% = 60.5V 59.64 V 57.48 – 63.35
90% = 99.0V 96.79 V 94.05 – 103.95
Observation: The error in relay operating value was observed within ± 5%.

* Over Voltage Operating Value Test for (OV):


OV Pickup Operating Value in Tolerance value in
setting Volt Volt
100% = 110.0V 112.32 V 104.50 – 115.50
150% = 165.0V 169.52 V 156.75 – 173.25
200% = 220.0V 229.25 V 209.00 – 231.00
Observation: The error in relay operating value was observed within ± 5%.

* Operating Time Measuring Test:


UV Operating Time Testing for IDMT: AT TMS 1
Initially keep voltage 105 Volts
SET UV Applied Expected Observed Tolerance in
TRIP (%) voltage Time (Sec) Time (Sec) Sec
20% 80%=17.60V 14.10 14.19 13.40 – 14.81
55% 40%= 24.20V 6.810 6.91 6.47 – 7.15
90% 0%= 0.00V 5.000 5.06 4.75 – 5.25
Observation: The Relay operating time found within +/-5%.

SSE/RC/NDLS SSE/RE/JP M/S L&T M/S ASHIDA


* UV Operating Time Testing for DT:
SET UV TRIP=90%; initially keep voltage 105 Volts
Set Observed Time Tolerance(Sec)
Applied voltage
Time(Sec) (Sec)
0.10 0%= 0.00V 0.104 0.095 – 0.105
1.00 0%= 0.00V 1.01 0.950 – 1.050
10.0 0%= 0.00V 10.11 9.50 – 10.50
Observation: The Relay operating time found within +/-5%.
OV Operating Time Testing for IDMT: AT TMS 1
Initially keep voltage 0 Volts
SET OV TRIP Applied Expected Observed Tolerance in
(%) voltage Time (Sec) Time (Sec) Sec
100% 200%=220.0V 3.500 3.51 3.33 – 3.68
150% 160%= 264.0V 5.833 5.85 5.54 – 6.12
200% 120%= 264.0V 17.500 17.33 16.63 – 18.38
Observation: The Relay operating time found within +/-5%.

OV Operating Time Testing for DT:


SET OV TRIP=100%; initially keep voltage 105 Volts
Set Observed Time Tolerance(Sec)
Applied voltage
Time(Sec) (Sec)
0.10 165.0V 0.102 0.095 – 0.105
1.00 165.0V 1.01 0.950 – 1.050
10.0 165.0V 10.11 9.50 – 10.50
Observation: The Relay operating time found within +/-5%.

* Master Trip Relay (CAPACITOR)

Type: AVAJS13 (86) Sr.NO. 18AJS130047.

Time Test : 12.25 msec(Operational Time)

Permissible Value: 12 +/- 2 msecs, / Contact Combination: Coil A: 5NO (SR)

SSE/RC/NDLS SSE/RE/JP M/S L&T M/S ASHIDA


SSE/RC/NDLS SSE/RE/JP M/S L&T M/S ASHIDA