Common\REPORT\A24R 

INCOMER- 2

AS PER RDSO Specs: TI/SPC/PSI/PROTCT/6071


TYPE: A24R (HV)
TSS: GARHI HASARU
Sr. No.: 18AA24R0014 Date: 05/12/2018

Aux. Voltage: 110V D.C. CT: 5 Amps


* Functional Test: -
Operating Value Test for I1>1 IDMT:
I1>1 Pickup Operating Value in Tolerance value in Amp
setting Amp
50% = 2.5A 2.57 A 2.375 – 2.625
160% = 8.0A 8.23 A 7.60 – 8 .40
240% = 12.0A 12.36 A 11.40 – 12.60
Observation: The pickup value of relay observed within ± 5%.

Operating Value Test for I1>2 Inst. Element:


I1>2 Setting Operating Value in Tolerance value in Amp
Amp
200% = 10A 10.26 A 9.5 – 10.5
400% = 20A 20.49 A 19.0 – 21.0
Observation: The error in relay operating value was observed within ± 5%.

Operating Value Test for Restricted Earth Fault (REF):


IN> Pick-up Operating Value in Tolerance Value in Amp
setting Amp
10% = 0.5A 0.51 A 0.475 – 0.525
50% = 2.5A 2.57 A 2.375 – 2.625
Observation: The pick-up value of relay observed within ± 5%.

Operating Value for Over Load Element:


Pick-up Operating Value in Amp
Tolerance Value in Amp
setting OL 1 OL 2 OL 3
80% = 4.0A 4.09 A 4.09 A 4.09 A 3.80 – 4.20
160% = 8.0A 8.19 A 8.19 A 8.19 A 7.60 – 8.40
Observation: The pickup value of relay observed within ± 5%.

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


OLP Pick up test:3
When relay is operated in any ‘Overload operation’ relay start post timer
During post timer OLP setting is activated.
Operating Value in
Setting Tolerance Value in Amp
Amp
100% = 5A 5.12 A 4.75 – 5.25
Observation: The pick-up value of relay observed within ± 5%

* Operating Time Measuring Test:


Time Testing for IDMT:
Setting: I1>1 = 80%, TMS = 1.0
I(I/ I1>1) Expected Time Observed Tolerance in
from curve Time in sec sec
8A(2N) 10.03s 10.17 9.528 – 10.531
20A(5N) 4.28s 4.32 4.066 – 4.494

Setting: I1>1 = 80%, TMS = 0.1


I(I/ I1>1) Expected Time Observed Tolerance in sec
from curve Time in sec
8A(2N) 1.00s 1.02 0.950 – 1.050
20A(5N) 0.43s 0.439 0.408 – 0.451

Over Load Operating Time Test:


OL1 - Setting: = 80%=4A
Set Injected Observed Time Tolerance(Sec)
Time(Sec) current (Sec)
1 8A 1.04 0.95 – 1.05
Observation: The Relay operating time found within +/-5%.

OL2 - Setting: = 80%, =4A


Set Injected Observed Time Tolerance(Sec)
Time(Sec) current (Sec)
1 8A 1.04 0.95 – 1.05
Observation: The Relay operating time found within +/-5%.

OL3 - Setting: = 80%, = 4A


Set Injected Observed Time Tolerance(Sec)
Time(Sec) current (Sec)
1 8A 1.03 0.95 – 1.05
Observation: The Relay operating time found within +/-5%

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


OLP - Setting: = 80%, = 4A
Set Injected Observed Time Tolerance(Sec)
Time(Sec) current (Sec)
10 8A 10.14 9.50 – 10.50
Observation: The Relay operating time found within +/-5%.
.
* I1>2 Inst. Operating Time Test for phase:
Setting Injected Current Time (ms)
400% =20A 40A 28.57
Observation: Inst. Element operating time is found within 30ms.

* REF Operating Time Test:


IN> Setting: 20% = 1.0A
Injected Current Time (ms)
5A 28.40
Observation: operating time was found within 30ms.

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


AS PER RDSO Specs: TI/SPC/PSI/PROTCT/6071


TYPE: A24R (LV)
Sr. No.:18AA24R00013. Date: 05/12/2018

Aux. Voltage: 110V D.C. CT: 5 Amps


* Functional Test: -
Operating Value Test for I1>1 IDMT:

I1>1 Pickup Operating Value in Tolerance value in


setting Amp Amp
50% = 2.5A 2.57 A 2.375 – 2.625
160% = 8.0A 8.24 A 7.60 – 8 .40
240% = 12.0A 12.36 A 11.40 – 12.60
Observation: The pickup value of relay observed within ± 5%.
Operating Value Test for Restricted Earth Fault (REF):
IN> Pickup Operating Value in Tolerance Value in
setting Amp Amp
10% = 0.5A 0.51 A 0.475 – 0.525
50% = 2.5A 2.55 A 2.375 – 2.625
Observation: The pickup value of relay observed within ± 5%.
Operating Value for Over Load Element:
Pickup Operating Value in Amp Tolerance Value in
setting OL 1 OL 2 OL 3 Amp
80% = 4.0A 4.09 A 4.10 A 4.10 A 3.80 – 4.20
160% = 8.0A 8.19 A 8.19 A 8.19 A 7.60 – 8.40
Observation: The pickup value of relay observed within ± 5%.

OLP Pick up test:


When relay is operated in any ‘Overload operation’ relay start post timer
During post timer OLP setting is activated.
Setting Operating Value in Amp Tolerance Value in Amp
100% = 5A 5.12 A 4.75 – 5.25
Observation: The pickup value of relay observed within ± 5%

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


* Operating Time Measuring Test:
Time Testing for IDMT:
Setting: I1>1 = 80%, TMS = 1.0
I(I/ I1>1) Expected Time Observed
Tolerance in sec
from curve Time in sec
8A(2N) 10.03s 10.11 9.528 – 10.531
20A(5N) 4.28s 4.31 4.066 – 4.494
Setting: I1>1 = 80%, TMS = 0.1
I(I/ I1>1) Expected Time Observed Tolerance in sec
from curve Time in sec
8A(2N) 1.00s 1.01 0.950 – 1.050
20A(5N) 0.43s 0.434 0.408 – 0.451

Over Load Operating Time Test:


OL1 - Setting: = 80%=4A
Set Injected Observed Time Tolerance(Sec)
Time(Sec) current (Sec)
1 8A 1.03 0.95 – 1.05
Observation: The Relay operating time found within +/-5%.
OL2 - Setting: = 80%, =4A
Set Injected Observed Time Tolerance(Sec)
Time(Sec) current (Sec)
1 8A 1.03 0.95 – 1.05
Observation: The Relay operating time found within +/-5%.
OL3 - Setting: = 80%, = 4A
Set Injected Observed Time Tolerance(Sec)
Time(Sec) current (Sec)
1 8A 1.03 0.95 – 1.05
Observation: The Relay operating time found within +/-5%.
OLP - Setting: = 80%, = 4A
Set Injected Observed Time Tolerance(Sec)
Time(Sec) current (Sec)
10 8A 10.13 9.50 – 10.50
Observation: The Relay operating time found within +/-5%.
* REF Operating Time Test:
IN> Setting: 20% = 1.0A
Injected Current Time (ms)
5A 29.9
Observation: operating time was found within 30ms.

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


As Per RDSO Specs: TI/SPC/PSI/PROTCT/6071


TYPE: A23R

Sr. No.: 17LA23R0014. Date: 05/12/2018


Aux. Voltage: 110V D.C. CT: 5 Amps.
* Functional Test: -
Operating Value Test
Operating Value in Amp
Set Value (Is1) Tolerance
HV CT LV CT
20% = 1.0A 1.00 0.99 0.950 – 1.050
30% = 1.5A 1.51 1.49 1.425 – 1.575
40% = 2.0A 2.00 1.99 1.900 – 2.100
50% = 2.5A 2.49 2.49 2.375 – 2.625
Observation: The measured operating value is within +/-5% of set value.
* Relay characteristics:
SLOPE 1 (S1)
I bias = Through Current
I diff = Difference Current
S1 = I diff / I bias
Is1 =20%, K1 = 20%, K2 = 80%, Is2 = 200%; Apply current between HVCT & LVCT
Initially Set Applied current Calculate Values
current HVCT LVCT I bias (Ib) I diff (Id) Slop S1 in %
across both
(IH1) (IL1) (IH1 + IL1) (IH1 - IL1) Id/Ib*100
CT
/2
5.0 4.01 5.0 4.505 -0.99 21.97%
Is1 =30%, K1 = 30%, K2 = 80%, Is2 = 200%; Apply current between HVCT & LVCT
Initially Set Applied current Calculate Values
current HVCT LVCT I bias (Ib) I diff (Id) Slop S1 in %
across both
(IH1) (IL1) (IH1 + IL1) (IH1 - IL1) Id/Ib*100
CT
/2
5.0 3.49 5.0 4.24 -1.51 35.06%

* Operating Time Measuring Test:


Set pickup Injected current Operating Time
20%=1A 2A 35.90 MS
40%=2A 4A 30.00 MS
Observation: The Relay operating time found less than 40ms.

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


As Per RDSO Specs: TI /SPC/PSI/PROTCT/6071


TYPE: A27R

Sr. No.:17LA27R0003. Date:06/12/2018


* Operating Value Test:
DC Under Voltage Alarm Element Test:
Sr.
Setting (V) Observed Pickup (V) Tolerance (V)
No.
1. 40V 40.31 V 38.00 – 42.00
2. 110V 109.33 V 104.5 – 115.5
Observation: The error in relay operating value was observed within ± 5%.
DC Under Voltage Trip Element Test:
Sr.
Setting (V) Observed Pickup (V) Tolerance (V)
No.
1. 40V 40.25 V 38.00 – 42.00
2. 110V 109.33 V 104.5 – 115.5
Observation: The error in relay operating value was observed within ± 5%.
DC Over Voltage Element Test:
Sr.
Setting (V) Observed Pickup (V) Tolerance (V)
No.
1. 120V 121.12 V 114.0 – 126.0
2. 170V 171.34 V 161.5 – 178.5
Observation: The error in relay operating value was observed within ± 5%.

AC Low Alarm Element Test:


Sr.
Setting (V) Observed Pickup (V) Tolerance (V)
No.
1. 150V 149.85 V 142.50 – 157.50
2. 200V 199.43 V 190.00 – 210.00
Observation: The error in relay operating value was observed within ± 5%.
AC High Alarm Element Test:
Sr.
Setting (V) Observed Pickup (V) Tolerance (V)
No.
1. 240V 241.06 V 228.00 – 258.00
2. 270V 271.46 V 256.50 – 283.50
Observation: The error in relay operating value was observed within ± 5%.

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


* Operating Time Measuring Test:
Under voltage Alarm Operating Time Test:
Sr. Set Time Applied Observe Tolerance
Setting (V)
No. (Sec) Voltage Time (Sec) (Sec)
1. 1.00 88V 95V To 70V 1.03 0.95 – 1.05
2. 10.00 88V 95V To 70V 10.12 9.50 – 10.50
Observation: The Relay operating time found within +/-5%.

Under voltage Trip Operating Time Test:


Sr. Set Time Applied Observe Tolerance
Setting (V)
No. (Sec) Voltage Time (Sec) (Sec)
1. 0.20 77V 85V To 70V 0.21 0.19 – 0.22
Observation: The Relay operating time found within +/-5%.

Over voltage Operating Time Test:


Sr. Set Time Applied Observe Tolerance
Setting (V)
No. (Sec) Voltage Time (Sec) (Sec)
1. 1.00 121V 110V To 145V 1.01 0.95 – 1.05
2. 10.00 121V 110V To145V 10.11 9.50 – 10.50
Observation: The Relay operating time found within +/-5%.

AC Low Alarm Operating Time Test:


Sr. Set Time Applied Observe Tolerance
Setting (V)
No. (Sec) Voltage Time (Sec) (Sec)
1. 1.00 160V 176V To 144V 1.03 0.95 – 1.05
2. 10.00 160V 176V To 144V 10.13 9.50 – 10.50
Observation: The Relay operating time found within +/-5%.

AC High Alarm Operating Time Test:


Sr. Set Time Applied Observe Tolerance
Setting (V)
No. (Sec) Voltage Time (Sec) (Sec)
1.00 250V 230V To 275V 1.03 0.95 – 1.05
10.00 250V 230V To 275V 10.13 9.50 – 10.50
Observation: The Relay operating time found within +/-5%.

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


As Per RDSO Specs: TI/SPC/PSI/PROTCT/6071 

TYPE: A21R

Sr. No.: 17KA21R0017. Date: 06/12/2018


Aux. Voltage: 110V D.C. C.T.: 5 Amps P.T: 110 VAC

* Operating Value Test: -


Distance Element Test:
Minimum Operating current Test:
Setting (Ohms): RF = 5, RB = 5, XF = 5, XB = 5, RCA = 70°

Applied
Set Imin Observed Current Tolerance
Voltage
1.0A 0 1.01 A 0.95 – 1.05

Fundamental Wave Front & Back Operating Test:


Setting (Ohms): RF = 5, RB = 5, XF = 1, XB = 1, RCA = 70°

Value of Impedance from


Measured
Measured Value Parallelogram drawn from
Impedance
settings
Amp Nominal
PA Volt Z Min. (-5%) Max (+5%)
s Z
10 27.10 5 5.42 5.149 5.42 5.691
70 5.00 5 1.00 1.007 1.06 1.113
Observation: Impedance value found within ±5%.
Directional Front & Back operating Test
The value of voltage and current are adjusted such that impedance will fall
with parallelogram setting. The phase angle varies from 0 – 360 measure
the operating and non-operating.
Setting: RF=5, RB=5, XF=25, XB=10, RCA=70°
Observed
Set Applied value
Phase Relay Status
PA
V I φ
46 Non Operated
-45
44 Operated
40 10
135 Non Operated
135
134 Operated
Observation: The operating region is found with in +/-2Deg.

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


* Wrong Phase Coupling Element:
Wrong Phase Coupling – Phase angle Operating Value test
Setting: Z min = 2.0Ω Z max = 60.0Ω A1 = 90° & A2 = 150°

Voltage Current Phase (observed)


Relay Status
(V) (A) (Deg.)
80 10 89.90 Not operated
80 10 90.10 Operated
80 10 150.30 Operated
80 10 150.40 Not operated
Observation: The operating regions found within +/-2Deg.
Wrong Phase Coupling – Impedance Operating Value test
Voltage Current Phase angle Z
Setting Tolerance
(V) (A) (Deg.) (Ohm)
60.0Ω 80 1.34 120 59.70 57Ω - 63Ω
Observation: The WPC operation found within ± 5% of set impedance limit
* Over Current Element (OCR)
Over Current Element - Operating Value Test
Set Value Pickup Value Tolerance (A)
5A 5.04 A 4.75 – 5.25
10A 10.09 A 9.50 – 10.50
Observation: Relay operating value found within ± 5%
* PT Fuse Failure Element
Voltage Threshold Test
Setting: VPTFF = 20V, TPTFF = 0.10S, IPTFF = 1Amp.

Voltage level at
Set Threshold Injected Tolerance
which alarm
Voltage Current (V)
observed
20V 1.5A 20.00 V 19 – 21
Observation: The PT fuse failure alarm voltage threshold value found
within ±5%
* Current Threshold Test
Current level at
Set Threshold Applied Tolerance
which Trip
Current Voltage (A)
observed (A)
1A 15V 1.02 A 0.95 – 1.05
Observation: The PT fuse failure alarm current threshold found within ±5%.

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


* Operating Time Test:
Operating Time Test for DPR
Setting: RF = 5, RB = 5, XF = 5, XB = 5 & RCA = 70°

Current Voltage Phase Angle Operating Time


5A 15V 30° 30.30 MS
Observation: Operating time found within 40 ms
Operating Time Test for Wrong Phase Coupling -
Setting: Z min = 2.0Ω Z max = 30.0Ω A1 = 90° & A2 = 150°

Voltage Current Phase Angle Operating Time


80V 10A 120° 37.70 MS
Observation: Operating time found within 40 ms
Operating Time Test for Over Current Element
Setting Applied Current Time
5A 25 A 19.60 MS
Observation: Operating time found within 30ms.
* Breaker Fail (BF)
Logic – After executing trip command relay start BF timer. If fault is not
clear with in this time relay operate another contact marked as BF.
Set BF delay Measured Delay % Error
200 ms 222.9-19.60=203.3 3%
Observation: BF operating time is found within ±5%

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


As Per RDSO Specs: TI /SPC/PSI/PROTCT/1982 with A&C slip No.1


TYPE: A22R

Sr. No.:17KA22R0014. C.T.: 5 A Date: 06/12/2018


Aux. Voltage:110V DC
* Functional Test: -
Operating Value Test for Delta I:
The fault is created by adding V.dI current in base current.
Setting: Delta I Prot. = Enable; Delta I = as per Table; ATD= 000; Set DS = 000;
Delta T = 060;
Applied
Set Base Current DI current Error
Voltage
DI
V PA I PA I PA %
1A 60 0 1 60 1.01 A 10 1%
3A 60 0 2 10 3.00 A 20 0%
6A 60 0 4 70 6.02 A 40 2%
Observation: Relay operating value found within ± 5%.

Operating Time Test for Delta I:


Setting: Delta I Prot. = Enable; Delta I = 1.00; Set DS = 000; Delta T = 060
Tolerance
Set ATD Obs. Delay (ms)
in ms
120 122.7 MS 114 – 126
800 811.2 MS 760 – 840
Observation: Operating time is within ±5%.

* Operating Value Test for BUDPR:


Setting: Backup Dist Prot= Enable; RF=5; RB=5; XF=5; XB=5; A1=37; A2=37; Z min=2;
Min operating Current = 0.10; RCA=90deg; Time Delay = 0.
Applied Current
Measured Z Exp. Z Observed
Current Phase
Voltage (V) (Ohm) (Ohm)
(A) Angle
5.0 -70 25.90 V 5.312 5.18
5.0 -15 9.98 V 2.00 1.99
5.0 -325 9.90 V 2.00 1.98
5.0 -140 32.80 V 6.527 6.56
5.0 -240 28.09 V 5.774 5.61
Observation: Relay operating value found within ±5%

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


* Operating Time Test for BUDPR:
Setting: Backup Dist Prot.= Enable; RF=5; RB=5; XF=5; XB=5; A1=37; A2=37;
Zmin=2; min operating Current = 0.10; RCA=90deg;Time Delay = 0.
Applied value: current = 5.0Amp, Voltage = 20Volts; set PA =70deg

Tolerance
Set ATD Obs. Delay (ms)
in ms
150 148.6 MS 142.5 – 157.5
1000 1009 MS 950 – 1050

Observation: Operating time is within ±5%.

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA


* 10.1. Master Trip Relay (FDR) DATE:06/12/2018

Type: AVAJS13 (86F) Sr.NO. 18AJS130054.


Time Test : 13.12 msec(Operational Time)

Permissible Value: 12 +/- 2 msecs, / Contact Combination: Coil A: 5NO (SR)

* 10.2. Master Trip Relay (LV)

Type: AVAJS13 (86L) Sr.NO. 18AJS130055.

Time Test : 12.40 msec(Operational Time)

Permissible Value: 12 +/- 2 msecs, / Contact Combination: Coil A: 5NO (SR)

• 10.3. Inter Trip Relay (HV)

Type: AVAJH13 (86H) Sr.NO. 18AJH130074.

Time Test : 13.50 msec(Operational Time)

Permissible Value: 12 +/- 2 msecs


Contact Combination: Coil A: 5NO+2NC (HR)

* 10.4. High Speed Master Trip Relay 4 Elements With HR Contacts.

Type: AVAJH43 : Sr.NO. 17KJH30014.

Operating time at rated voltage


Coil A 16.30 Coil C 15.60

Coil B 16.90 Coil D 15.20

SSE/RC/NDLS SSE/RE/GGN M/S L&T M/S ASHIDA