You are on page 1of 4

Document number Date Pages

SupportLine ID 3363 August 9, 2012 1 (4)

Quick Guide to set IP address for Relion® 615 Series


and PC

Checking IP address of Relion® 615 series


Using Front port

IP address and subnet mask are fixed in Relion® 615 series:


IP address is 192.168.0.254
Subnet mask is 255.255.255.0

Using Rear port

Go to HMI -> Configuration -> Communication -> Rear port(s) and check IP address field numbers.
Default IP address is 192.168.2.10, remember that IP address has to be unique in network. Check also
the subnet mask in the same place, usually it is 255.255.255.0.
Do not use IP addresses which end with 255 or 0, those are reserved for special usage in network.
Use private IP addresses in LAN network, ranges described below.
- 10.0.0.0 – 10.255.255.255
- 172.16.0.0 – 172.31.255.255
- 192.168.0.0 – 192.168.255.255

Setting IP address of computer


Windows XP:

Right click My Network Places on your desktop and choose Properties. Right click Local Area
Connection and select Properties. Double click Internet Protocol (TCP/IP).

Windows 7:

Start -> Control Panel -> View network status and tasks -> Change adapter settings -> Local Area
Connection -> Right click Local Area Connection and select Properties. Double click Internet
Protocol (TCP/IP).

ABB Oy
Medium Voltage Products Visiting address Address Telephone Internet
Domicile: Helsinki Strömberg Park, P.O.Box 699 +358 10 22 11 www.abb.com/fi
Muottitie 2 A FI-65101 Vaasa www.abb.com/substationautomation
Business ID: FI07634030
Vaasa, Finland Finland
2 (4)

Using Front port

Select box Obtain an IP address automatically.

Press OK and close all the windows.

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document. In no event shall ABB be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising
from the use of this document.

Copyright © ABB, 2012. All rights reserved


3 (4)

Using Rear port

Define an IP address for your computer. Enter IP address: it has to be same as in IED, except the last
number which has to be unique. It is assumed that subnet mask is 255.255.255.0.
The Subnet mask is generated automatically when you select the empty field. If IED’s Subnet mask is
different than default, enter that value also here.

Press OK and close all the windows.

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document. In no event shall ABB be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising
from the use of this document.

Copyright © ABB, 2012. All rights reserved


4 (4)

Checking communication
Select Start and Run. Write cmd and press OK.

Write the command ping 192.168.2.10 which is the IP address of IED. Press enter in order to test if the
communication is working properly.
If you get text “Reply from ...” text, then communication is working.