Professional Documents
Culture Documents
H O S T E D BY
Gulf Organisation for Research and Development
Original Article/Research
Abstract
Thermal comfort is an imperative factor that determines the health and productivity of the occupants living in residential buildings.
The growing health related symptoms and demand for the electrical energy encourage the occupants to switch over to natural ventilation.
Thermal comfort for naturally ventilated buildings mainly depends on the size and orientation of window openings. Even though most
research works include the study on indoor thermal comfort for various positions of window opening it was limited to single sided and
cross ventilated buildings. In real situation most of the rooms attached to the residential buildings are having window openings at their
adjacent wall and hence this paper was focused to study the occupants’ thermal comfort and indoor air flow characteristics for a room
with adjacent window openings under generalized approach. Computational fluid dynamics (CFD) technique is employed to study the
indoor air flow for a three-dimensional room model. The CFD simulation is checked for grid independence and having good validation
with experimental measurements on the reduced scale model at wind tunnel and with the network model with the k–e turbulence model.
Air temperatures along various midlines, planes, areas occupied by low temperature zone and predicted mean vote (PMV) contours are
presented in this paper. From this study a new set of strategies are identified to locate the window openings and the best location
improves percentage of low temperature by 50%, reduces the PMV and PPD by 0.12% and 3.51%, respectively with reference to the worst
window opening position.
Ó 2015 The Gulf Organisation for Research and Development. Production and hosting by Elsevier B.V. All rights reserved.
1. Introduction
http://dx.doi.org/10.1016/j.ijsbe.2015.02.003
2212-6090/Ó 2015 The Gulf Organisation for Research and Development. Production and hosting by Elsevier B.V. All rights reserved.
D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57 43
to keep their indoor environment under good thermal com- tions based on the CFD simulation and full scale
fort. Thermal comfort is the state of mind that expresses experiments. These correlations have been set up to
the satisfaction with the thermal environment. Thermal assess the airflow rate due to the combination of stack
comfort can be maintained by dissipating the heat generat- and wind effects. Kato et al. (1992) investigated the
ed by the body due to metabolic activity to the environ- mechanism of cross ventilation by the LES model in a
ment and thereby the thermal equilibrium was room with opening at their opposite walls. Karava
maintained with the surrounding. The indoor thermal com- et al. (2011) made an experimental study of basic cross
fort can be maintained by providing proper ventilation ventilation flow characteristics that are essential for accu-
which in turn depends on many factors like wind force, rate natural ventilation modeling and design. The
outdoor temperature, surrounding building topography, authors also mentioned that the airflow pattern in room
height, shape, orientation, window opening type, size and with cross ventilation is complex and cannot be predicted
its position. Among the above factors, window opening by simplified macroscopic models such as orifice equa-
can be designed easily by the engineer for good ventilation tion. Liang ji et al. (2011) investigated the influence of
and thermal comfort and rest of the factors could not be fluctuating wind direction on cross ventilation using wind
easily controlled. tunnel experiments with the aim of improving the evalua-
In this context, Gao and Lee (2011) evaluated the tion accuracy for natural ventilation. Similarly, the recent
influence of opening configuration on natural ventilation research works are also pertained to study the air flow in
performance of residential unit at Honk Kong and stated a room with single sided ventilation (Zhen and Kato,
that relative position of the two window opening groups 2011; Caciolo et al., 2011) and cross ventilation (win-
(bed room windows and living room windows) was the dows at the opposite walls) (Hu et al., 2008; Lo and
most affecting parameter. Also better natural ventilation Novoselac, 2013; Nikolopoulos et al., 2012; Lo and
performance can be achieved when the two openings Novoselac, 2012; Lo et al., 2013).
are positioned in opposite direction or perpendicular to But, in real case, the rooms attached with residential
each other. Hassana et al. (2007) investigates the effect buildings have their openings at the adjacent walls and
of window combinations on ventilation characteristics not at their opposite walls. The air flow for the room with
for thermal comfort in buildings. The author also stated window openings at their adjacent walls is entirely different
that for single sided ventilation with two non adjacent from single sided and cross ventilated buildings. The air
openings gives better ventilation than adjacent openings. enters through the window openings at the windward side
Seifert et al. (2006) studied the airflow for the building wall and turns 90°, travels along the wall and leaves
envelop having window opening nearer to the roof and through the window opening at the adjacent wall. The path
floor level, windward opening nearer to the roof and lee- of air travel depends upon the relative position of window
ward opening starts from the mid height of the building opening at the adjacent walls. Ravikumar and Prakash
and both the window openings nearer to the roof level. (2009) studied the effect of window opening size and its
Stavrakakis et al. (2012) optimized the window opening aspect ratio on indoor airflow characteristics for the room
design for thermal comfort in naturally ventilated build- with window openings at adjacent walls and the impor-
ing by the artificial neural network method. Ramponi tance of investigating such a type of window orientation
and Bloken (2012) studied the physical diffusion of is also pointed out. The air flow pattern inside a room is
indoor air for the building envelope with both openings complex and is characterized by multi-flow features such
near to the floor and at the mid height of the building as laminar boundary layers, highly turbulent diffuser jets
under 5% and 10% of wall porosity. Favarolo and and low turbulence flow.
Manz (2005) also analyzed the influence of opening con- Air flow analysis can be performed by methods like the-
figuration on natural ventilation performance by flow oretical models, experimental testing and Computation
visualization and CFD technique and identified that ven- Fluid Dynamics (CFD) technique. In order to obtain reli-
tilation performance is mainly affected by its vertical able information concerning the air flow and the pressure
position and width of the opening. However, all the distribution around and inside a naturally ventilated build-
above studies are focused to investigate the effect of win- ing, full-scale measurements can be performed (Straw et al.,
dow opening orientation and its size for the building 2000; Koinakis, 2005). However, wind tunnel tests on
envelope with single sided ventilation or cross ventila- small-scale models are usually preferred, as they allow
tion. Similarly other studies on building ventilation per- the control of wind speed and direction, as well as the study
formance are also made on sided ventilation or cross on different configurations (Eftekhari et al., 2003; Wong
ventilation. Allocca et al. (2003) analysed the single sided and Heryanto, 2004). Walker and White (1992), Nielsen
natural ventilation to study the effect of buoyancy on the and Olsen (1993), Dascalaki et al. (1995), Zeidler and
ventilation rate. Straw et al. (2000) presented the results Fitzner (1997) used the tracer gas measurement technique
of experimental, theoretical and computational investiga- for their air flow studies. The study of complex flow pat-
tions of the wind driven ventilation with openings on the terns by experimental approach is highly infeasible and it
opposite walls of the room. Caciolo et al. (2012) devel- provides the flow pattern details only at the specified loca-
oped a new set of empirical relations in leeward condi- tions. An alternative approach is to rely on CFD, based on
44 D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57
@qmz @ðqmx mz Þ @ðqmy mz Þ @ðqmz mz Þ from CFD simulation and hence a grid independence check
þ þ þ
@t @x @y @z is required to conduct. For this grid independence check,
grid sizes of 0.9, 0.8, 0.7, 0.6 and 0.5 m are used in meshing
@P @ @mz @ @mz
¼ qgy þ Rz þ le þ le and solved with the above mentioned boundary conditions.
@y @x @x @y @y
The air temperature and velocity at the midline Y1Y2 are
@ @mz determined for different mesh sizes and shown in Fig. 2.
þ l þ sz ð4Þ
@z e @z Three-dimensional, double-precision, segregated solver is
where mx, my and mz are the components of velocity in x, y used to solve the governing equations sequentially.
and z directions, q is the density, t is the time, g is the grav- Standard k–e turbulence model is employed with standard
ity, le is the effective viscosity, P is the pressure, Ri is the wall function (Launder and Spalding, 1974). It is a two
source term for distributed resistance (suffix i is x, y and equation model in which the solutions of two separate
z) and s the viscous stress. transport equations allowing the turbulence velocity and
Energy equation length scale are to be independently determined. This mod-
el was widely used in industrial flow and heat transfer
@ @ @ @ simulation with reasonable accuracy and robustness. For
qC p T o þ qmx C p T o þ qmy C p T o þ qmz C p T o
@t @x @y @z this k–e, the values of turbulent kinetic energy, K and tur-
@ @T o @ @T o @ @T o bulent kinetic energy dissipation rate, e at the inlet region
¼ K þ K þ K are calculated from Eqs. (7) and (8), respectively
@x @x @y @y @z @z
@P (Versteeg and Malalasekera, 1995).
þ W v þ Ek þ Qv þ / þ ð5Þ
@t 3 2
K ¼ ðV avg T i Þ ð7Þ
where Cp is the specific heat, To is the total temperature, K 2
is the thermal conductivity of air, Wv is the viscous work 3
3
k2
term, Qv is the volumetric heat source, / is the viscous heat ¼ C 4l ð8Þ
lt
generation term and Ek is the kinetic energy.
where Vavg is the average flow velocity, Ti the turbulence
3. Boundary conditions and validation of the CFD simulation intensity and lt is the turbulence scale length. Ti and lt are tak-
en as 4% (Posner et al., 2003) and 0.4 m (AIRPAK, 2001)
In general, velocity of air flow varies with respect to respectively and Cl = 0.09. The K and e values at the velocity
building height. This variation is specified either by inlet boundary condition are calculated as 0.0024 and
logarithmic profile (Evalo and Papov, 2006) or by dividing
the velocity inlet into a number of sub inlet zones (Asfour
and Gadi, 2007). In this paper, the wind entering zone is
divided into 4 sub zones. The wind velocity at these sub
zones are predicted from the following Eq. (6) (Asfour
and Gadi, 2007).
V ¼ V r cH a ð6Þ
where, V is the wind speed at ground level (m/s), Vr is
the reference wind speed measured experimentally, H is
the height of the building, c is the parameter relating wind
speed to terrain nature (0.68 in the open country terrain),
and a is the exponent relating wind speed to the height
above the ground (0.17 in the open county terrain). Ambi-
ent temperature is specified as 306 K. Free slip boundary
conditions are employed to the wall surfaces. The tem-
perature value at the side walls, floor and roof is specified
as 312, 303 and 325 K, respectively. These values are based
on midday measurements conducted in an actual building
during the summer. Since the room analyzed in this paper
is an office room some electrical appliances used by the
occupants are considered and their heat generation value
is assumed to be 25 W/m2. This generated heat is uniformly
applied to the floor as a boundary condition. T grid scheme
of meshing is employed and this scheme uses tetrahedral
shaped element for meshing the flow domain. The grid size
in meshing must be independent to the results obtained Figure 2. Grid independence check.
46 D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57
Table 1
Test case details for generalized window opening position.
Case No. Test case details Equations Values
1 Changing the position of window in y direction h* = DH/H 0.1, 0.2, 0.3, 0.4, 0.5, 0.6 and 0.7
2 Changing the position of window in x and z directions at same height x* = DW/W 0.1, 0.2, 0.3, 0.4, 0.5, 0.6 and 0.7
z* = DL/L
s* = x*=z*
D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57 47
Table 2
Discrepancy of CFD simulation with network model for generalized window opening positions.
h* 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Predicted mass flow rate form CFD code (kg/s) 0.698 0.704 0.706 0.713 0.724 0.732 0.739
Discrepancy with network model (%) 7.12 6.3 6.17 5.35 4.055 3.11 2.28
s* = x* = z* 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Predicted mass flow rate form CFD code (kg/s) 0.715 0.712 0.7007 0.713 0.700 0.710 0.711
Discrepancy with network model (%) 5.06 5.43 6.8 5.35 6.8 5.68 5.58
Figure 5. Indoor temperature variation along the midline for various h* values.
variations along X1X2. The velocity magnitude raises negli- In the Y1Y2 midline, all the h* values yield different types
gibly from the cases h* = 0.2–0.5. For h* = 0.1 and 0.6, the of trend. For h* = 0.1, the indoor air velocity is maximum
air velocity between X = 1 and 4 m has low magnitude and up to Y = 1 m, and above 1 m, the velocity gradually
it is almost constant as 0.125 m/s. However, this low mag- reduced to 0.15 m/s at Y = 4.5 m. For h* = 0.2, the maxi-
nitude velocity is 0.25 m/s lesser than other h*cases except mum velocity is obtained between 1 and 1.75 m as
for h* = 0.7. For h* = 0.7, the velocity variation follows a 0.35 m/s and above 1.75 m, the velocity gradually reduced
unique trend and it is having a least magnitude of air velo- to 0.5 m/s at Y = 4.5 m. Also for the cases h* = 0.3 and 0.4,
city along X1X2. a similar trend in velocity variation is identified along Y1Y2
D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57 49
Figure 6. Indoor velocity variation along the midline for various h* values.
and for these cases the maximum velocity of 0.4 m/s is from 0.2 to 0.5 along Z1Z2 midline. For rest of the h* val-
obtained at Y = 2 and 3 m, respectively. For h* = 0.5 and ues (0.1, 0.6, 0.7), the velocity reduces significantly from
0.6, the velocity was reduced gradually from Y = 0.5 to Z = 1 to 3 m and this change in velocity is about
2 m and increased suddenly to a maximum magnitude of 0.125 m/s.
0.3 m/s at a height of Y = 3.25 and 3.75 m, respectively. Furthermore, the temperature prevailed in the room is
For h* = 0.7, the indoor air velocity is reduced gradually discussed from the temperature plots predicted at the
up to 2.75 m and an increase in velocity is noticed up to planes P1, P2, P3 and P4 as shown in Fig. 7. For
3.75 m from the ground surface and above which, a slight h* = 0.1, at the plane P1, the least temperature is identi-
fall is identified. fied nearer to the corner C3 as 307 K and increasing
In the Z1Z2 midline, all the h* values show a rise in diagonally toward the corner C1. For the plane P2, except
indoor air velocity up to Z = 1 m and beyond 1 m, the the portions nearer to the corner C1 experience low tem-
velocity is reduced gradually up to a distance of Z = 3 m. perature and is less than 307 K. Planes P3 and P4 are
The velocity variation for the cases h* = 0.2, 0.3, 0.4 and having almost similar pattern of temperature contours
0.5 shows similar pattern of trend. For these h* values, with the lowest temperature of 307 K that is nearer to
the velocity reduces from Z = 1 to 4 m however, the varia- the corner C3 and increase diagonally toward the corner
tion in velocity among the h* cases is 0.05 m/s. The velocity C1. For h* = 0.2, all the planes experience low tem-
magnitude increased slightly by changing the h* values perature at about 307 K and some portions near the
50 D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57
Figure 7. Indoor temperature plot at planes P1, P2, P3 and P4 for various h* values.
windward side opening are having comparatively very low 307 K and portions nearer to wall W2 are having elevated
temperature of about 306 K. For h* = 0.3, the central temperatures. Similarly for h* = 0.6 and 0.7, the low tem-
region of the plane P1 is having low temperature of about perature zone is identified only at the plane P4 and rest of
307 K and for the plane P2 the zone along the path of air the planes are having uniform high temperature. From
travel through the windward window opening is having these plots, it is inferred that window opening position
low temperature. Also in planes P3 and P4 some portions in the range of h* = 0.1–0.3 offers more low temperature
nearer to walls W3 and W4 are having low temperature at zone at all the planes whereas if it is in the range of
about 307 K and portions nearer to wall W1 are having h* = 0.5–0.7 only the plane P4 is offering low temperature.
high temperature as above 309 K. For h* = 0.4, plane Hence positioning the window opening in the range of
P3 is having comparatively low temperature and the por- h* = 0.1–0.3 provides good comfort at the floor level
tions except the corner C1 are experiencing low tem- and also up to a height of 3 m from the floor.
perature in the range of 306–307 K. In the plane P4, the For h* = 0.1, plane P1 has some low temperature zones
portion nearer to wall W3 is having low temperature whereas P2, P3 and P4 planes are affected by high tem-
and the corner C3 is having a temperature of 308.75 K. peratures. For h* = 0.2, P1 and P2 have some downs in
Plane P1 is having almost uniform temperature at about the temperature level and also the average peak tem-
307 K except the corner C1. For the plane P2, half of perature value is 308.325 K which is 0.3 K less than
the plane nearer to wall W4 is having comparatively h* = 0.1. For h* = 0.3, P1 and P2 will have the peak tem-
low temperature at about 307 K. For h* = 0.5, 0.6 and perature value as 307.7 and 308 K, respectively. These val-
0.7 the temperature pattern at the planes P1 and P2 is ues are 0.1 K less than the peak temperature value obtained
almost similar. In these planes some comparatively low for the case h* = 0.2. For h* = 0.3, planes P1 and P2 have
temperature zones are noticed nearer to the wall W4 elevated temperatures in comparison with the case h* = 0.2.
and rest of the portions are having higher temperatures. For h* = 0.4–0.7, temperature pattern shows some downs
However for h* = 0.5, some portions along the path of at the level of window position and rest of the planes are
air travel at plane P3 are having low temperature at about affected by elevated temperatures.
D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57 51
To identify the best position of window opening from However, for s* = 0.4, the temperature decreases from
the ground surface, another factor - area occupied by low X = 0.5 to 2 m and maintains almost constant up to 3 m
temperature zone is predicted at the planes P1, P2, P3 and increases again up to 4.5 m. For s* = 0.5, the tem-
and P4 and shown in Fig. 8. perature is nearly constant up to 2 m and between X = 2
For h* = 0.1, 0.2 and 0.3 the maximum area of low tem- and 4.5 m an increase in temperature is noticed. For
perature zone is obtained at the plane P1 as 15, 19 and s* = 0.6 and 0.7, the temperature steadily raises from
15.5 m2, respectively. Rest of the h* cases are not having X = 1 to 4.5 m. In the Y1Y2 midline, the temperature varia-
maximum area of low temperature zone at plane P1 and tion for the cases s* = 0.3, 0.4 and 0.5 shows almost con-
for h* = 0.7 it is completely zero. For the plane P2, the area stant up to a height of 3 m from the ground surface and
of low temperature zone starts to increase drastically from above which a drastic raise in temperature is identified.
the cases h* = 0.1 to 0.2 and almost constant for the Rest of the s* cases, have a steady raise in temperature
h* = 0.3, 0.4 and 0.5 and falls drastically for h* = 0.7. from the ground surface to the roof. In comparison,
For the plane P3, the area occupied by low temperature s* = 0.3, 0.4 and 0.5 cases have indoor air under low tem-
zone is less than 10 m2 for the cases h* = 0.1, 0.2 and 0.3 perature in between the height of 1.75 and 4.5 m. In the
and increased gradually as 11.93–15.32 m2 for the cases Z1Z2 midline, s* = 0.3, 0.4 and 0.5 yield almost constant
h* = 0.4–0.6, respectively. In the plane P4, the area occu- temperature along the Z direction. Among the analyzed
pied by the low temperature zone is negligible as 2 m2 for s* cases, s* = 0.4 yields the lowest temperature along all
the cases h* = 0.1–0.4 and rest of the h* cases have a slight the midlines. The velocity variation along the same midli-
increase in low temperature zone area as about 5 m2. From nes for various s* values is shown in Fig. 10.
this figure, it is noticed that, locating the window openings In X1X2 midline, for s* = 0.1, 0.2 and 0.3, the air velocity
at h* = 0.2 will maintain the low temperature zone at all the is comparatively very low from X = 0 to 3.5 m and have a
planes and at an average area of low temperature zone is high velocity between X = 3.5 and 4.5 m. This shows that
predicted as 11.18 m2 which is the maximum among the the air circulation in X1X2 midline is predominant only
analyzed h* cases. between X = 3.5 and 4.5 m for s* = 0.1, 0.2 and 0.3. For
s* = 0.4 and 0.5, the highest air velocity is obtained as 0.2
5. Effect of window position in lateral and longitudinal and 0.3 m/s, respectively and it is noticed at X = 2.25 m.
direction on indoor air flow characteristics For s* = 0.6 and 0.7, the maximum velocity of 0.25 m/s is
obtained between X = 1 m and beyond 1 m. The velocity
The effect of window opening position in lateral and lon- is drastically reduced to 0.05 m/s at X = 4.5 m. This shows
gitudinal direction on their respective windward and lee- that the air circulation is predominant only in between
ward side walls is studied by varying the corresponding X = 0.5 and 1 m for s* = 0.6 and 0.7. In Y1Y2 midline,
non dimensional numbers x* and z*. In this case, the posi- the velocity decreases up to 1 m and maintains constant
tion of both windows is changed uniformly (x* = z* = s*) up to 4 m for all the s* cases except for s* = 0.3, 0.4 and 0.5.
and the h* value is kept constant at 0.4. The s* is varied The variations of air velocity for these s* cases are less
from 0.1 to 0.7 with an increment of 0.1. The temperature than 0.25 m/s. For s* = 0. 3, 0.4 and 0.5, the velocity
along the line X1X2, Y1Y2 and Z1Z2 is shown in Fig. 9. gradually reduces up to a height of 1.5 m and increases
The temperature trend along X1X2 for various s* values drastically to a value of 0.2 m/s at y = 3.5 m and above
reveals three types of trends. For s* = 0.1, 0.2 and 0.3, the 3.5 m a significant fall in velocity is noticed. However,
temperature decreases gradually along the X1X2 midline. for s* = 0.3, 0.4 and 0.5, the indoor air velocity is
Figure 8. Area of low temperature zone at planes P1, P2, P3 and P4 for various h* values.
52 D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57
Figure 9. Indoor temperature variation along the midline for various s* values.
comparatively very much high in between Y = 2.5 and P1, P2 and P3 are having low temperature at one half
4.5 m. For Z1Z2 midline, the air velocity is increased up of the plane nearer to the wall W4 where as the next half
to 1 m and later reduced gradually up to 3.5 m and again that is nearer to wall W2 is having elevated temperature
increases slightly up to Z = 4 m. This trend is common in the range of 308–309 K. For s* = 0.3 at plane P1, por-
for all the s* cases. However among the analyzed s* cases, tion nearer to the corner C2 is having comparatively low
the indoor velocity is high for s* = 0.3, 0.4 and 0.5 at all temperature and less than 307 K. In plane P2, wide
midlines. region away from the corner C1 is having low tem-
The indoor air temperature at the planes P1, P2, P3 perature in the range of 306–307 K and this portion is
and P4 is predicted for various s* cases and is shown having further reduction in temperature in plane P3.
in Fig. 11. For s* = 0.1, a smaller region nearer to the However for plane P4, the temperature is lower at the
corner C2 at plane P1 is having comparatively low tem- corner C3 and increases diagonally toward the other cor-
perature as 307 K; in plane P2 a narrow portion along ners. For s* = 0.4, one quadrant of the plane P1 nearer
the wall W4 is having low temperature and this portion to the corner C1 is having high temperature as 308 K
is having further reduction in temperature at the plane and rest of the portions are having relatively lower tem-
P3 and rest of the potions at the P3 is having elevated perature at about 307 K. In the same case, the planes P2
temperature. In plane P4 the temperature is increasing and P3 are having almost similar pattern of temperature
diagonally from corner C3 to C1. For s* = 0.2, planes contour however the temperature at the plane P2 is com-
D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57 53
Figure 10. Indoor velocity variation along the midline for various s* values.
paratively lesser than P3. In both the planes the portions W2 and plane P4 shows most regions at elevated tem-
nearer to the corner C1 are having relatively higher tem- perature of above 309 K. Finally for s* = 0.7 at plane
perature. Also in the plane P4, the portions nearer to the P1, a marginal zone nearer to the walls W2 and W1
wall W3 are having low temperature and rest of the por- has high temperature, plane P2 is having uniform tem-
tions are having higher temperature, especially at the perature of about 307 K and planes P3 and P4 experi-
region nearer to wall W1 having temperature greater ence high temperature at above 309 K. With all these
than 308 K. For s* = 0.5, all the planes are having com- inferences, it is noticed that s* = 0.5 shows almost uni-
paratively lesser temperature than in the case s* = 0.4. form and lower temperature at all the planes in compar-
Also the high temperature region nearer to the corner ison with other s* cases.
C1 gets decreased for s* = 0.5 in comparison with 0.4. Area occupied by the low temperature zone is predicted
Specifically the plane P3 in s* = 0.5 is having a large at planes P1, P2, P3 and P4 for the analyzed s* cases and is
zone under the temperature of 307 K and however in shown in Fig. 12.
plane P4 certain portions nearer to the corner C1 and From Fig. 12, s* = 0.3, 0.4 and 0.5 yield an average
C3 show elevated temperature as above 308 K. For low temperature zone area of 12.4, 13.4 and 14.3 m2,
s* = 0.6 at plane P1, portion except the zone nearer to respectively. For these s* cases, around 64% of the room
wall W3 is having low temperature. But in planes P2 interiors are kept at low temperature. However, for
and P3, the low temperature zone moves toward the wall s* = 0.1, 0.2, 0.6 and 0.7, the average low temperature
54 D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57
Figure 11. Indoor temperature plot at planes P1, P2, P3 and P4 for various s* values.
Figure 12. Area of low temperature zone at planes P1, P2, P3 and P4 for various s* values.
zone area is 3.6, 10.01, 10.15 and 9.29 m2, respectively. 6. Thermal comfort index – PMV contour for varying
These s* values keep only 40% of the room interior with window position
low temperature. All these discussions recommend to
position the windows in the range of s* = 0.3–0.5 for The thermal comfort index – predicted mean vote for the
reducing indoor air temperature. generalized position of window opening studies is deter-
D. Prakash, P. Ravikumar / International Journal of Sustainable Built Environment 4 (2015) 42–57 55
Caciolo, M., Stabat, P., Marchio, D., 2012. Numerical simulation of Lo, L.J., Banks, D., Novoselac, A., 2013. Combined wind tunnel and
single-sided ventilation using RANS and LES and comparison with CFD analysis for indoor airflow prediction of wind-driven cross
full-scale experiments. Build. Environ. 50, 202–213. ventilation. Build. Environ. 60, 12–23.
Chen, Q., 2004. Using computational tools to factor wind into architec- Montazeri, H., Blocken, B., 2013. CFD simulation of wind-induced
tural environmental design. Energy Build. 36, 1197–1209. pressure coefficients on buildings with and without balconies: valida-
Dascalaki, E., Santamouris, M., Argiriou, A., Helmis, C., Asi- tion and sensitivity analysis. Build. Environ. 60, 137–149.
makopoulos, D.N., Papadopoulos, K., Silemes, A., 1995. Predicting Nielsen, A., Olsen, E., 1993. Measurements of if air change and energy
single sided natural ventilation rates in buildings. Solar Energy 5, 327– loss with large open outer doors. Building physics’93, Lyngby,
341. Denmark, BjarneSaxhof.
Eftekhari, M.M., Marjanovic, L.D., Pinnock, D.J., 2003. Air flow Nikolopoulos, N., Nikolopoulos, A., Larsen, T.S., Nikas, K.S.P., 2012.
distribution in and around a single-sided naturally ventilated room. Experimental and numerical investigation of the tracer gas method-
Build. Environ. 38, 389–397. ology in the case of a naturally cross-ventilated building. Build.
Evalo, G., Popov, V., 2006. Computational analysis of wind driven Environ. 56, 379–388.
natural ventilation in buildings. Energy Build. 38, 491–501. Posner, J.D., Buchanan, C.R., Dunn-Rankin, D., 2003. Measurement and
Favarolo, P.A., Manz, H., 2005. Temperature-driven single-sided venti- prediction of indoor air flow in a model room. Energy Build. 35, 515–
lation through a large rectangular opening. Build. Environ. 40 (5), 526.
689–699. Ramponi, R., Blocken, B., 2012. CFD simulation of cross-ventilation flow
Gao, C.F., Lee, W.L., 2011. Evaluating the influence of openings for different isolated building configurations: validation with wind
configuration on natural ventilation performance of residential units tunnel measurements and analysis of physical and numerical diffusion
in Hong Kong. Build. Environ. 46 (4), 961–969. effects. J. Wind Eng. Ind. Aerodyn. 104–106, 408–418.
Hassana, M.A., Guirguisa, N.M., Shaalanb, M.R., El-Shazlyc, K.M., Ravikumar, P., Prakash, D., 2009. Analysis of thermal comfort in an
2007. Investigation of effects of window combinations on ventilation office room by varying the dimensions of the windows on adjacent
characteristics for thermal comfort in buildings. Desalination 209, walls using CFD: a case study based on numerical simulation. Build.
251–260. Simulation 2 (3), 187–196.
Hoang, M.L., Verboven, P., De Baerdemaeker, J., Nocolai, B.M., 2000. Rouaud, O., Havet, M., 2002. Computation of the airflow in a pilot scale
Analysis of the air flow in a cold store by means of computational fluid clean room using k–e turbulence models. Int. J. Refrig. 25, 351–361.
dynamics. Int J Refrig. 23, 127–140. Seifert, Joachim, Li, Yuguo, Axley, James, Rösler, Markus, 2006.
Hooff, T.V., Blocken, B., Aanen, L., Bronsema, B., 2012. Numerical Calculation of wind-driven cross ventilation in buildings with large
analysis of the performance of a venturi-shaped roof for natural openings. J. Wind Eng. Ind. Aerodyn. 94 (12), 925–947.
ventilation: influence of building width. J. Wind Eng. Ind. Aerodyn. Song, D., Kato, S., 2003. Radiational panel cooling system with
104–106, 419–427. continuous natural cross ventilation for hot and humid regions.
Hu, C.H., Ohba, M., Yoshie, R., 2008. CFD modelling of unsteady cross Energy Build. 36, 1273–1280.
ventilation flows using LES. J. Wind Eng. Ind. Aerodyn. 96, 1692– Stavrakakis, G.M., Koukou, M.K., Vrachopoulos, M.Gr., Markatos,
1706. N.C., 2008. Natural cross-ventilation in buildings: building-scale
Huo, Y., Haghighat, F., Zhang, J.S., Shaw, C.Y., 2000. A systematic experiments, numerical simulation and thermal comfort evaluation.
approach to describe the air terminal device in CFD simulation for Energy Build. 40, 1666–1681.
room air distribution analysis. Build. Environ. 35, 563–576. Stavrakakis, G.M., Zervas, P.L., Sarimveis, H., Markatos, N.C., 2012.
Ji, Liang, Tan, Hongwei, Kato, Shinsuke, Zhen, Bu, Takahashi, Takeo, Optimization of window-openings design for thermal comfort in
2011. Wind tunnel investigation on influence of fluctuating wind naturally ventilated buildings. Appl. Math. Model. 36, 193–211.
direction on cross natural ventilation. Build. Environ. 46, 2490–2499. Straw, M.P., Baker, C.J., Robertson, A.P., 2000. Experimental measure-
Karava, P., Stathopoulos, T., 2011. Wind-induced internal pressures in ments and computations of the wind-induced ventilation of a cubic
buildings with large facade openings. J. Eng. Mech. ASCE. structure. J. Wind Eng. Ind. Aerodyn. 88, 213–230.
Karava, P., Stathopoulos, T., Athienitis, A.K., 2011. Airflow assessment Versteeg, H.G., Malalasekera, W., 1995. An Introduction to Computa-
in cross-ventilated buildings with operable façade elements. Build. tional Fluid dynamics: The Finite Volume Method Approach. Wiley,
Environ. 46, 266–279. New York.
Kato, S., Murakami, S., Mochida, A., Akabayashi, S.I., Tominaga, Y., Visagavel, K., Srinivasan, P.S.S., 2009. Analysis of single side ventilated
1992. Velocity-pressure field of cross ventilation with open windows and cross ventilated rooms by varying the width of the window
analyzed by wind tunnel and numeric simulation. J. Wind Eng. Ind. opening using CFD. Solar Energy 83 (1), 2–5.
Aerodyn. 41–44, 2575–2586. Walker, R.R., White, M.K., 1992. Single sided natural ventilation-how
Koinakis, C.J., 2005. Combined thermal and natural ventilation modelling deep an office. Build. Serv. Eng. Res. Technol. 13, 231–236.
for long-term energy assessment: validation with experimental mea- Wong, N.H., Heryanto, S., 2004. The study of active stack effect to
surements. Energy Build. 37, 311–323. enhance natural ventilation using wind tunnel and computational fluid
Larsena, T.S., Nikolopoulos, N., Nikolopoulos, A., Strotos, G., Nikas, dynamics (CFD) simulations. Energy Build. 36, 668–678.
K.S., 2011. Characterization and prediction of the volume flow rate Yang, T., Wright, N.G., Etheridge, D.W., Quinn, A.D., 2006. A
aerating a cross ventilated building by means of experimental comparison of CFD and full-scale measurement for analysis of natural
techniques and numerical approaches. Energy Build. 43, 1371–1381. ventilation. Int. J. Ventil. 4 (4), 337–348.
Launder, B.E., Spalding, D.B., 1974. The numerical computation of Zeidler, O., Fitzner, K., 1997. Investigation of the impact of natural
turbulent flows. Comp. Methods Appl. Mech. Eng. 3, 269–289. ventilation through windows on the thermal comfort. Proc. Clima
Lo, L.J., Novoselac, A., 2012. Cross ventilation with small openings: 2000, Brussels.
measurements in a multi-zone test building. Build. Environ. 57, 377– Zhen, Bu., Kato, Shinsuke., 2011. Wind-induced ventilation performances
386. and airflow characteristics in an areaway-attached basement with a
Lo, L.J., Novoselac, A., 2013. Effect of indoor buoyancy flow on wind- single-sided opening. Build. Environ. 46, 911–921.
driven cross ventilation. Build. Simulation 6 (1), 69–79.