You are on page 1of 14

Types KBCH 120, 130, 140

Differential Protection for


Transformers and Generators

T&D
Energy Automation & Information
Types KBCH 120, 130, 140
Differential Protection for Transformers and Generators

Introduction
The KBCH relay provides a package of functions primarily for the protection
of transformers and generator transformers but may also be applied to
protect reactors and generators. As a part of the K-range of relays, the
KBCH can be integrated into an overall protection and control system by
utilising its integral serial communications facility.

Features Models Available


• Fully numerical design • KBCH120
offers 2 bias inputs per phase
• Biased differential protection
for the protection of a two- Figure 1 KBCH relay withdrawn from case
• Restricted earth fault protection winding power transformer.
• Overfluxing protection • KBCH130
offers 3 bias inputs per phase
• Integral CT ratio and vector All models are three phase units
for the protection of a three-
group compensation with internal vector group
winding power transformer or a
• Remote transformer tap control two-winding power transformer compensation and line current
with 2 sets of CTs on one transformer ratio correction, thus
• Measurement of phase, eliminating the need for interposing
winding.
differential and bias currents transformers in most cases.
• KBCH140
• Record of fault current Up to four biased current inputs per
offers 4 bias inputs per phase
magnitudes for the last fault phase can be provided to cater for
for all applications requiring up
• Relay flag details for the to 4 bias circuits. power transformers with more than
previous 5 faults two windings and/or more than
All models are available with either one circuit breaker controlling each
• 8 programmable optically 1A or 5A inputs on the primary winding, as in mesh or one-and-a-
isolated inputs to monitor the and secondary side. Alternatively half circuit-breaker busbar
status of external plant the KBCH 120 and 140 can be arrangements. Versions are
provided with 1A CTs on the high available that can accommodate a
• IEC870-5 compatible
voltage windings and 5A CTs on mixture of 1A (HV) and 5A (LV)
communications via K-Bus
the low voltage windings. CTs.
• Integral disturbance recorder
Models are available with menus Typical applications are shown in
accessible from a remote PC
written in English, French, German Figures 7, 8 and 9.
• Integral event recorder or Spanish.
accessible from a remote PC In addition to the biased differential
Application protection, restricted earth fault
• Comprehensive self-checking and protection has been included to
alarms Type KBCH relays offer biased cover a larger percentage of the
differential current, restricted earth transformer windings. Figure 10
fault and overfluxing protections shows some typical restricted earth
primarily for the protection of two fault applications. The differential
or three winding power protection has been designed to
transformers, auto transformers or restrain when the transformer is
generator-transformer units. overfluxed so that an instantaneous
trip is not issued for transient
The KBCH is also suitable for other
overfluxing. Since a transformer
applications where biased
cannot withstand a severe
differential protection is
overfluxing condition indefinitely,
appropriate
time delayed overfluxing protection
(eg. generators, reactors and
and an alarm stage has been
motors).
incorporated.

2
Contacts that monitor the status of 3
external plant, such as Buchholz
protection and temperature
measuring devices, can be Figure 2 2
connected to any of the eight Operate
Differential current (xIn) = pe
control inputs that are available. Biased slo Restrain
I1 + I2 + I 3 + I 4 0%
differential 8
Each input can be routed to any
characteristic
number of the output relays via a 1
able
Allow o error
variable time delay if required. 20% r
ati

The functions of each of the slope


Setting range 20%
auxiliary inputs can be recorded on 0.1 - 0.5In
0 1 2 3 4
the table situated on the relay
frontplate. Effective Bias (xIn) = |I1| + |I2| + |I3| + |I4|

This allows the indication on the 2

relay, which flags the operation of


the timers associated with these
inputs (AUX0, AUX1 etc.) to be
readily interpreted.
Figure 3
A
Functions Typical
magnetising
Biased differential element inrush
B
waveforms
Each relay, contains a biased
differential element per phase with C
a characteristic as shown in Figure
2. The minimum differential current
required for operation is adjustable
between 10% and 50% of rated
current. The KBCH has a dual slope
bias characteristic (Figure 2).
The current waveform associated In applications where heavy internal
The initial slope of 20%, from zero
with magnetising inrush is earth fault levels can occur and
to rated current, ensures sensitivity
characterised by a period of each where a high stabilising resistor
to faults whilst allowing for up to
cycle where its magnitude is very setting is used, a voltage limiting,
15% mismatch when the power
small, as shown in Figure 3. By non-linear resistor may be required.
transformer is at the limit of its tap
measuring the time of this period of
range, Overfluxing alarm and
low current, an inrush condition can
in addition to current transformer tripping protection
be identified.
ratio errors. At currents above
rated, extra errors may be Overfluxing restraint is conditioned A single phase-phase connected
gradually introduced as a result of by the percentage of fifth harmonic voltage input is provided to enable
CT saturation. The bias slope is current present. overfluxing detection. Alarm and
therefore increased to 80% to tripping characteristics, which are
compensate for this. High set differential element based on a measurement of the
voltage/frequency ratio, are
A magnetising inrush element and a An additional high set
provided.
selectable overfluxing element are instantaneous differential element is
included. These are used to inhibit provided to ensure rapid clearance The alarm is definite time delayed
the relay and prevent unwanted of heavy faults. This element is whilst the trip characteristic may be
tripping under these conditions. essentially peak measuring to selected as either definite time or an
ensure fast operation for internal inverse time curve, as shown in
The use of the traditional second faults with saturated CTs. Figure 4.
harmonic restraint technique, to
block the relay during inrush Restricted earth fault
conditions, may result in a protection
significant slowing of the relay
during heavy internal faults. This is Greater sensitivity for earth faults is
due to the presence of second obtained by including restricted
harmonics as a result of saturation earth fault protection. A separate
of the line current transformers. element per winding is provided.
To overcome this, the KBCH uses a An externally mounted stabilising
waveform recognition technique. resistor will be necessary for
optimum performance.

3
Configuration Operating time as a function of the actual excitation and the set
starting value for different time multiplier settings (K)
time (s)
Logic 1000 Figure 4

The configuration of the relay is Inverse time


accomplished in software. characteristic for
The setting of logic function links, 100
overfluxing
together with the input and output K = 63
protection
masks, define the way the relay will K = 40
operate. This allows: 10 K = 20

• Selection of features K=5


• Implementation of user defined
K=1
logic using auxiliary timers 1
1 1.1 1.2 1.3 1.4 1.5 1.6
• Control of the integral
M= (V/f)
disturbance recorder. (V/f) setting
These may be user defined via the
relay front panel function keys, or
remotely by a PC (personal Ancillary functions Event records
computer) via the communications
system. Fifty events can be stored in a
Measurements
buffer. Software is available to
The logic also allows the local or The relay can display the allow the events to be accessed
remote control of the transfomer tap magnitude of phase currents for remotely by a PC via the
changer. communications system.
each input, differential current and
Inputs and outputs average bias current. Any change of state of a control
input or output relay, local setting
KBCH has 8 optically isolated Primary display quantities are
change or operation of a control
inputs which may be reassigned by based on the ratios of the line
function, is logged by the relay with
the user with any of the available current transformers which may be
a resolution of 1ms. Fault records
functions from the setting menu. programmed into the relay as a
and alarms are also stored as
setting.
There are 8 programmable outputs, events.
The power system frequency is also
each comprising a relay with displayed.
1 normally open contact, which Disturbance records
may also be reassigned by the user. Fault records The internal disturbance recorder
A dedicated watchdog contact with has sixteen analogue channels and
The fault flags for the last five faults
1 normally open and 1 normally sixteen digital channels.
are recorded by the relay.
closed contact is also available. The analogue channels record up to
Additional records of the magnitude
nine phase currents (three per
Typical applications diagrams of the fault currents are also stored
transformer winding) three
(Figures 7, 8 and 9) show the for the last fault.
differential currents, three average
default settings of functions as they
are assigned in the factory. All of the records are stored in a bias currents and the voltage.
non-volatile memory for local or The digital channels record the
Alternative setting group remote retrieval. status of the output relays and
control inputs.
Two setting groups are provided.
This allows the user to set one The disturbance records can be
group to normal operating accessed and displayed remotely by
conditions while a second group a PC, via the communications system.
may be set to cover alternative
operating conditions.
Test features
A number of features are provided
to enable the relay to be thoroughly
1

tested during commissioning,


routine maintenance and fault
Figure 5 finding operations:
• The measurement functions allow
Communication terminal
arrangement
each analogue input and its
associated wiring to be checked.
• The on/off states of the digital
54
56

inputs and relay outputs can be


K-Bus
displayed.
Screened 2 core cable
• Trip test facility

4
Power-on diagnostics and The front plate contains a 2 x 16 The K-Bus is connected through a
self monitoring character, alphanumeric liquid protocol converter known as KITZ,
crystal display (LCD) and 4 either directly or via a modem, to
Power-on diagnostic tests are pushbuttons to provide local access the RS-232 port of the PC. The K-
carried out by the relay when it is Bus is RS-485 based and runs at
to the relay’s menu. There are also
energised. These tests include 64kbits/s. The K-Bus connection is
3 light emitting diodes (LED) for
checks on the timer, microprocessor, shown in Figure 5.
memory and the analogue input visual indication of the relay’s
circuitry. Continuous self-monitoring, status. This system allows up to 32 relays
in the form of watchdog circuitry Standard Midos terminal blocks are to be accessed through one RS-232
and memory checks are also located at the rear of the relay communications port (Figure 6).
performed. In the event of a failure, providing connections for all input Software is available with each
the relay will either lock out or and output circuits. KITZ to provide access to the relays
attempt a recovery, depending on to read and change settings.
the type of failure detected.
User Interface Additional software entitled
Hardware Description ‘Protection Access Software &
Front panel user interface Toolkit’ is also available. This
The relay is housed in a Midos size 8 The features of the relay can be provides access to the disturbance
case, suitable for either rack or panel accessed through a menu-driven recorder and the event recorder
mounting as shown in Figure 11. system. The menu is arranged in the together with other additional
form of a table, into each column of functions.
The relay uses a highly integrated
which related items (menu cells) are Each relay is directly addressable
16-bit micro-controller, which
grouped. over the bus to allow
performs most of the major software
functions such as input signal The user can move around the communication with the PC.
processing, scheme logic, output menu by means of the keys on the It should be noted that protection
relay control and handling of the relay frontplate. This can be done tripping and blocking signals are
operator interface. with the cover in place, but any not routed via the K-Bus. Separate
change to the settings requires the conventional wiring is used for
An additional digital signal cover to be removed. these functions. Where appropriate,
processor is provided to carry out the isolated 48V dc supply
the protection algorithm. Remote access user interface available on each relay is used to
The number of analogue inputs The menu table can also be energize its optically isolated inputs
depends upon the version of the accessed via the remote via external contacts.
relay. There are 6, 9 or 12 bias communications facility. This allows
all of the menu cells in a column to Communications protocol
current inputs, 2 or 3 zero
sequence current inputs for the be displayed simultaneously on the The communications protocol used
restricted earth fault protection and screen of a PC. Changes to the with K Series relays is designated
a voltage input for the overfluxing menu cell can be made from the PC Courier. The Courier language has
protection. keyboard. been developed specifically for the
purpose of developing generic PC
The internal transducers are used to Relay interconnection programs that will, without
isolate, step down and condition The relays can be interconnected modification, communicate with any
the inputs from the VT and CTs. via a shielded, twisted wire pair device using the Courier language.
Their output signals are then known as K-Bus. Up to 32 relays
converted into digital data for In the Courier system, all
may be connected in parallel across information resides in the relay.
further processing. the bus. Each time communication is
established with the relay, the
Relay 32 Relay 4 Relay 3 Relay 2 Relay 1 requested information is loaded to
the PC. The protocol includes
extensive error checking routines to
ensure that the system remains
reliable and secure.

Password protection
Figure 6 Password protection is provided on
Protocol
converter settings which alter the configuration of
Basic communication the relay, any accidental change to which
KITZ system could seriously affect the ability of the
IEC870-5 relay to perform its intended function.
RS232 K-Bus These include: enable/disable settings,
RS485
protection function characteristic selection,
Desktop
computer scheme logic settings and system CT and
VT ratios.

5
P1 P2 P2 P1
A A
S1 S2 S2 S1
B HV LV B
C C

63 69

64 70
65 71

66 72
67 73

68 74
75
KBCH 120
76
21 77

22 78
23 79

24 80
25 81

26 82
27 83
HV lo> (see Figure 10) LV1 lo> (see Figure 10)
28 84
A
4
A B WD 6 Relay healthy
13
AC/DC
C 3
supply
A B C 14
Vx WD 5 Relay failed
C B
Phase rotation 30
N Id > A,B,C Id >> A,B,C
RL0 32 Trip
Io > HV,LV1,LV2 V/f trip
34
n Id > A,B,C Id >> A,B,C
RL1 36 Trip
Io > HV,LV1,LV2 V/f trip
38
a b c Id > A,B,C Id >> A,B,C
RL2 40 Trip
Io > HV,LV1,LV2 V/f trip
42
17 Id > A,B,C Id >> A,B,C
RL3 44 Trip
57 1 Io > HV,LV1,LV2 V/f trip
18
3 4 29 30 29
63 64
5 6 31 32 RL4 31 Tap up
65 66
7 8 33 34 33
Initiate aux. timer 0 L0
67 68 9 10 35 36 46 RL5 35 Tap down
69 70 37 38 48
Initiate aux. timer 1 L1 37
13 14 39 40 Alarm = V/f alarm
71 72 RL6 39
41 42 50
Initiate aux. timer 2 L2 41
73 74 43 44
17 18 Id > A,B,C Id >> A,B,C
52 RL7 43 Trip
75 76 45 46 Logic input common (1) Io > HV,LV1,LV2 V/f trip
19 20
47 48 Initiate aux. timer 3 L3 57
77 78 21 22
49 50 45 1
79 80 23 24 47
51 52 Initiate aux. timer 4 L4
Case earth connection
81 82 25 26 53 54
49
55 56 Initiate aux. timer 5 L5 54
83 84 27 28
SCN See Note 4
51
Initiate aux. timer 6 L6 56 K-Bus communications port
Module terminal blocks SCN
See Note 4
viewed from rear 53
Initiate aux. timer 7 L7 7
+48V field voltage
55 8
Logic input common (2)

Notes:
1. (a) CT shorting links make 2. VT input must be supplied with phase - phase voltage.
before (b) and (c) disconnect. Connections are typical only.
(b) Short terminals break before (c). 3. Earth connections are typical only.
(c) Long terminals. 4. SCN = Screen connection for K-Bus.
(d) Pin terminal (PCB type)

Figure 7 Typical application diagram KBCH120

6
P1 P2 P2 P1
A A
S1 S2 S2 S1
B HV LV1 B

C C
LV2

P2 P1
A
S2 S1
B

63 69

64 70
65 71

66 72
67 73

68 74
75
KBCH 130 LV2 lo> (see Figure 10)
76
21 77

22 78
23 79

24 80
25 81

26 82
27 83
HV lo> (see Figure 10) LV1 lo> (see Figure 10)
28 84
A
4
A B
13 WD 6 Relay healthy
AC/DC
C 3
supply
A B C 14
Vx WD 5 Relay failed
C B
Phase rotation 30
N
RL0 32 Trip Id > A,B,C Id >> A,B,C
Io > HV,LV1,LV2 V/f trip
n 34
Id > A,B,C Id >> A,B,C
RL1 36 Trip
Io > HV,LV1,LV2 V/f trip
a b c 38
Id > A,B,C Id >> A,B,C
RL2 40 Trip
Io > HV,LV1,LV2 V/f trip
17 42
Id > A,B,C Id >> A,B,C
57 1 RL3 44 Trip
18 Io > HV,LV1,LV2 V/f trip
63 64 3 4 29 30 29
5 6 31 32 RL4 31 Tap up
65 66
7 8 33 34 33
Initiate aux. timer 0 L0
67 68 9 10 35 36 46
RL5 35 Tap down
69 70 37 38 48
Initiate aux. timer 1 L1 37
13 14 39 40
71 72 RL6 39 Alarm = V/f alarm
41 42 50
Initiate aux. timer 2 L2
73 74 43 44 41
17 18 Id > A,B,C Id >> A,B,C
45 46 52 RL7 43 Trip
75 76 Logic input common (1) Io > HV,LV1,LV2 V/f trip
19 20
47 48 Initiate aux. timer 3 L3
77 78 21 22 57
49 50 45
47 1
79 80 23 24 51 52 Initiate aux. timer 4 L4
53 54
Case earth connection
81 82 25 26
49
55 56 Initiate aux. timer 5 L5
83 84 27 28 54
SCN See Note 4
51
Initiate aux. timer 6 L6 56 K-Bus communications port
Module terminal blocks SCN
See Note 4
viewed from rear 53
Initiate aux. timer 7 L7 7
55 +48V field voltage
8
Logic input common (2)

Notes:
1. (a) CT shorting links make 2. VT input must be supplied with phase - phase voltage.
before (b) and (c) disconnect. Connections are typical only.
(b) Short terminals break before (c). 3. Earth connections are typical only.
(c) Long terminals. 4. SCN = Screen connection for K-Bus.
(d) Pin terminal (PCB type)

Figure 8 Typical application diagram KBCH130

7
P2 P1
A
S2 S1
HV LV1 B

C
LV2
P1 P2 P2 P1
A
S1 S2 S2 S1
B
P2 P1
C A
S2 S1
B

63 69

64 70
65 71

66 72
67 73

68 74
75
KBCH 140 LV2 lo> (see Figure 10)
76
21 77

22 78
23 79

24 80
25 81

26 82
27 83
HV lo> (see Figure 10) LV1 lo> (see Figure 10)
28 84
A
4
A B WD 6 Relay healthy
13
AC/DC
C 3
supply
A B C 14
Vx WD 5 Relay failed
C B
Phase rotation 30
N Trip Id > A,B,C Id >> A,B,C
RL0 32
Io > HV,LV1,LV2 V/f trip
n 34
Trip Id > A,B,C Id >> A,B,C
RL1 36
Io > HV,LV1,LV2 V/f trip
38
a b c
Id > A,B,C Id >> A,B,C
RL2 40 Trip
Io > HV,LV1,LV2 V/f trip
42
17
57 1 RL3 44 Trip Id > A,B,C Id >> A,B,C
18 Io > HV,LV1,LV2 V/f trip
63 64 3 4 29 30 29
5 6 31 32 RL4 31 Tap up
65 66
7 8 33 34 33
Initiate aux. timer 0 L0
67 68 9 10 35 36 46 RL5 35 Tap down
69 70 37 38 48
Initiate aux. timer 1 L1 37
13 14 39 40
71 72 RL6 39 Alarm = V/f alarm
41 42 50
Initiate aux. timer 2 L2 41
73 74 43 44
17 18 Id > A,B,C Id >> A,B,C
45 46 52 RL7 43 Trip
75 76
19 20 Logic input common (1) Io > HV,LV1,LV2 V/f trip
47 48 Initiate aux. timer 3 L3 57
77 78 21 22
49 50 45
1
79 80 23 24 47
51 52 Initiate aux. timer 4 L4
Case earth connection
81 82 25 26 53 54
49
55 56 Initiate aux. timer 5 L5 54
83 84 27 28
SCN See Note 4
51 56
Initiate aux. timer 6 L6 K-Bus communications port
Module terminal blocks See Note 4 SCN
viewed from rear 53
Initiate aux. timer 7 L7 7

55 8 +48V field voltage


Logic input common (2)

Notes:
1. (a) CT shorting links make 2. VT input must be supplied with phase - phase voltage.
before (b) and (c) disconnect. Connections are typical only.
(b) Short terminals break before (c). 3. Earth connections are typical only.
(c) Long terminals. 4. SCN = Screen connection for K-Bus.
(d) Pin terminal (PCB type)

Figure 9 Typical application diagram KBCH140

8
P1 P2 P2 P1
A A
S1 S2 S2 S1
B B
C C
P2 S2

P1 S1
See
Note 2 Figure 10
63 69 Typical restricted
See Note 1 RS
64 70
earth fault connections
RS
65 71
See
See Note 1
Note 2 66 72
67 73

68 74
75
KBCH 120
76
21 77

22 78
23 79

24 80
25 81

Notes:
26 82 1. See Service Manual R8530 for the setting of
27 83
the external stabilising resistor.
2. Optional voltage limiting non-linear resistor
28 84
(see Service Manual R8530).

Technical Data • AC voltage • Vector group and ratio correction


Vn = 110V <0.002VA
• DC auxiliary voltage HV VectorCor (primary)
Ratings 4.8W to 12.0W* LV1 VectorCor (secondary)
• Inputs • AC auxiliary voltage LV2 VectorCor (tertiary)
AC current (In) 6.7VA to 21.0VA*
1A or 5A or HV 1A/LV 5A Yy0 (0deg), Yd1 (–30deg), Yd2 (–60deg),
*Note: depending on the power supply Yd3 (–90deg), Yd4 (–120deg),
(KBCH 120 and 140 only) rating, the applied voltage and the Yd5 (–150deg), Yy6 (+180deg),
number of inputs and outputs energised. Yd7 (+150deg), Yd8 (+120deg),
AC Voltage (Vn) Yd9 (+90deg), Yd10 (+60deg), Yd11 (+30deg),
110V • Thermal withstand
Ydy0 (0deg), Ydy6 (+180deg),
Current inputs (In)
3In continuous
• Auxiliary voltage (Vx) HV Ratio Cor (primary)
100In for 1s
Nominal Operative Absolute with a maximum of 400A 0.05 to 2 in steps of 0.01
(Vx) range (V) maximum (V)

24–125V dc 20–150V dc Voltage input (Vn) LV1 Ratio Cor(secondary)


or 190V crest
180V continuous 0.05 to 2 in steps of 0.01
110V
50/60Hz ac 50–133V ac 230V for 30s
LV2 Ratio Cor(tertiary)
48–250V dc 33–300V dc Operating time 0.05 to 2 in steps of 0.01
or 380V crest • low set typically30 – 35ms
220V
50/60Hz ac 87–265V ac • high set typically15ms
• REF typically20 – 40ms
• Frequency (Fn) 50/60Hz Accuracy 7.5% of setting (at
reference conditions)
• Output field voltage 48V dc
• Reference conditions
(current limit: 60mA)
• Temperature 20°C
• Auxiliary voltage
Burdens
Nominal dc voltage range
• AC current • Frequency 50Hz or 60Hz
Bias differential
In = 1A <0.045VA Transformer ratios
In = 5A <0.22VA
• Current transformers
Restricted earth fault (REF) HV 1:1 to 9999:1
In = 1A <0.085VA LV1 1:1 to 9999:1
In = 5A <0.24VA LV2 1:1 to 9999:1
Note: Figures for the REF
exclude the stabilising resistor.

9
CT requirements Stabilising resistance
Note: Values to be as given below with minima of 60/In for star-connected To assure stability for through faults
CTs and 100/In for delta connected CTs a stabilising resistor will be
Application Knee point voltage Through fault required;
Vk stability the appropriate value of series
X/R If resistance is calculated as follows:
Rs = Vs
Transformers Vk≥24In[Rct + 2RL]* 40 15In Is
Generators Vk
where: Vs = 4
Generator transformers Vk≥24In[Rct + 2RL]* 40 15In
Vs = setting voltage
Overall generator-
transformer units Vk≥48In[Rct + 2RL]* 120 15In Rs = value of stabilising
resistor
Motors
Is = current setting of
Shunt reactors restricted earth
fault element
Series reactors also Vk≥24In[Rct + 2RL]* 40 15In
The effective setting of the REF is
transformers connected
given by:
to a mesh corner
having two sets of Vk≥48In[Rct + 2RL]* 40 40In Ie = Is + Ir +∑Ιm
CTs each supplying
where:
separate relay inputs. 120 15In
Ie = effective fault
*Note: an explanation of the KBCH CT requirements is given in the current setting
Applications section of the Service Manual (R8530).
Ir = current taken by
Note: CTs should be of equal ratio and magnetisation characteristic Metrosil
where:
Im = magnetising
In = Rated line CT secondary current (1A or 5A) current of current
transformers at Vs
Rct = Resistance of line CT secondary winding
Non linear voltage limiting devices
RL = Resistance of a single lead from line CT to relay
‘METROSILS’ are available where
X/R = Maximum value of primary system required.
reactance/resistance ratio Further information on the
If = Maximum value of through fault current application of restricted earth fault
elements is available in the KBCH
The CT knee point should also satisfy the requirements for operation of the service manual.
REF element.
For general applications the following applies:
Vk = 2If’ (Rct + 2RL)
where:
If’ = maximum secondary fault current for which stability
is required
Rct = resistance of current transformer secondary winding
RL = resistance of a single lead from current transformer
to relay

10
Transformer configuration • Definite timer
tV/f (Trip) 0.1 to 60s
tV/f (Alarm) 0.1 to 60s
Setting No. of bias inputs Configuration Applicable to: tof 5th harmonic detector
HV
0.1s to 14.4ks (4Hrs)
HV + LV 2 KBCH120/130/140
LV
Digital inputs
HV Optically isolated inputs
HV + LV1 + LV2 3 KBCH130/140
8 energised from the
LV1 LV2 48V field voltage
HV
Contacts
HV (x2) + LV 3 KBCH130/140** • Output relays 8 single make
LV
• Contact ratings
HV

Make:
HV + LV (x2) 3 KBCH130/140
30A and carry for 0.2s
LV

HV Carry:
HV (x2) + LV1 + LV2 4 Only KBCH140 5A continuous
LV1 LV2

HV Break:
DC 50W resistive
HV + LV1 (x2) + LV2 4 LV1 LV2 Only KBCH140** 25W inductive
(L/R = 0.04s)
HV AC 1250VA
(5A maximum)
HV (x2) + LV (x2) 4 Only KBCH140

LV
Subject to maxima of 5A and 300V

• Watchdog relays
Current settings Time settings 1 make and 1 break
• Differential protection Auxiliary timers
Id> 0.1 to 0.5pu Make:
Id>> 5 to 20pu tAUX0 0 to 14.4ks (4Hrs) 10A and carry for 0.2s
• REF protection tAUX1 0 to 14.4ks (4Hrs)
Io>HV (primary) tAUX2 0 to 14.4ks (4Hrs) Carry:
0.05 to 1.0pu tAUX3 0 to 14.4ks (4Hrs) 5A continuous
tAUX4 0 to 14.4ks (4Hrs)
Io>LV1 (secondary) tAUX5 0 to 14.4ks (4Hrs) Break:
0.05 to 1.0pu tAUX6 0 to 14.4ks (4Hrs) DC 30W resistive
tAUX7 0 to 14.4ks (4Hrs) 15W inductive
Io> LV2 (tertiary) tTEST 0.5 to 10s (L/R = 0.04s)
0.05 to 1.0pu tTapUp 0.5 to 10s AC 1250VA
tTapDown 0.5 to 10s (5A maximum)
Overfluxing settings
Overfluxing element timers Subject to maxima of 5A and 300V
• Inverse timer
• Iof 5th harmonic
tV/f (Trip)= 0.8 + 0.18 x K • Durability
0.1 to 0.5pu (M – 1)2 Loaded contact
• V/f Trip 1.5 to 3V/Hz Where 10,000 operations minimum
• V/f Alarm 1.5 to 3V/Hz tV/f (Trip)= operating time
K = time multiplier Unloaded contact
setting (1 to 63) 100,000 operations minimum

M = (V/f)
(V/f)setting

11
Communications port (K-Bus) • Fast transient disturbance • IEEE Radiated Immunity
• Language Courier IEC 60255-22-4: 1992 Class IV ANSI C37.90.2
• Transmission mode: 25 – 1000MHz, zero and 100%
Synchronous 4kV, 2.5kHz applied directly to square wave modulated.
• Signal levels RS485 all inputs. Field strength 35V/m.
• Message format HDLC
• Data rate 64 kbits/s 4kV, 2.5kHz applied via a • EMC compliance
• Connection Multidrop (32 units) capacitive clamp to the K-Bus port. 89/336/EECCompliance with
the European Commission
• Cable type Screened twisted
• Electrostatic discharge Directive on EMC is claimed via
pair of wires
IEC 60255-22-2: 1996 Class II the Technical Construction File
• Cable length 1000m (maximum)
4kV air discharge. route.
• Connector Screw terminals (M4)
• Isolation 2kV rms for 1 minute 4kV contact discharge.
• EN 50081-2: 1994
• DC supply interruptions Generic Standards were
IEC 60255-11: 1979 EN 50082-2: 1995
High voltage withstand
The unit will withstand a 10ms used to establish conformity.
• Dielectric withstand interruption in the auxiliary
IEC 60255-5: 1977 supply, under normal operating • Product safety
conditions, without de-energising. 72/23/EEC
2kV rms for one minute between Compliance with the European
all case terminals (except • AC ripple on dc supply Commission Low Voltage Directive.
terminals 1 and 57) connected IEC 60255-11: 1979 • EN 61010-1: 1993/A2 : 1995
together and the case earth/ The unit will withstand 12% ac Compliance is demonstrated by
terminals 1 and 57. ripple on the dc supply EN 60950: 1992/A11: 1997
reference to generic safety
2kV rms for one minute between standards.
• IEEE Surge Withstand Capacity (SWC)
terminals of independent circuits
ANSI C37.90.1 (1990)
including contact circuits.1.5kV rms
4 – 5kV fast transient and
for 1 minute across open contacts
2.5kV (Reaff 1994) oscillatory.
of output relays 0 to 7.
Applied directly to each input and
earth.
1kV rms for one minute across
open contacts of the watchdog Applied directly across the auxiliary
relay. power supply, opto isolated input
and each output contact.

• High voltage impulse Figure 11 Case outline size 8


IEC 60255-5: 1977
155.4
4 holes Ø 4.4
200
Three positive and three negative 24
impulses of 5kV peak, 1.2/50µs,
0.5J between all terminals
(except output contacts);
independent circuits; all terminals 168 159

connected together (except


terminals 1 and 57) and case
earth/terminals 1 and 57 Push button
203
projection 10 max.
• Insulation resistance Panel cut-out:
Flush mounting fixing details.
IEC 60255-5: 1977
>100MW 32 212
25 min.

Electrical environment
• High frequency disturbance
IEC 60255-22-1: 1988 Class III 177 157 max.

2.5kV peak applied between all


circuits and case earth.
Reset
1kV peak applied across 206 11
Flush mounting.
terminals of the same circuit All dimensions in mm.
(except metallic contacts).

12
Atmospheric environment Mechanical environment Case
• Temperature • Vibration
IEC 60255-21-1: 1988 The KBCH unit is housed in a size
IEC 60068-2-1: 1990 (cold) Response Class 2 8
Storage and transit –25°C to +70°C Endurance Class 2 Midos case as shown in Figure 11.

IEC 60068-2-2: 1974 (dry heat) • Shock and bump Additional Information
Operating –25°C to +55°C IEC 60255-21-2: 1988
KBCH service manual R8530
Shock response Class 2
• Humidity Shock withstand Class 1
IEC 60068-2-3: 1969 Bump Class 1
56 days at 93% RH and +40°C
• Seismic
• Enclosure protection IEC 60255-21-3: 1993
IEC 60529: 1989 Class 2
IP50 (dust protected)
Information Required with Order
Unit type KBCH1 0

2 bias inputs per phase 2


3 bias inputs per phase 3
4 bias inputs per phase 4

Configuration:
Standard 0 1

Case size:
Size 8 Midos flush mounting H 1

Auxiliary voltage:
24/125V (See page 10 Ratings for dc/ac Operative range) 2
48/250V (See page 10 Ratings for dc/ac Operative range) 5

Rating:
Vn = 100/120V In = 1A L
Vn = 100/120V In = 5A M
*Vn = 100/120V In = 1A/5A P

Language:
English E
French F
German G
Spanish S

*Not available for KBCH 130.


Number of stabilising resistors and Glossary
‘METROSILS’ required for the
• Courier A communications language developed to provide generic
restricted earth fault protection control, monitoring, data extraction and setting changes on remote devices
function. (primarily on protective relays) within the substation environment.
• K-Bus The 64 kbps twisted pair cable used to connect Courier
compatible devices and transfer Courier data.
• KITZ The interface unit which converts between K-Bus and
IEC870-5 FT1.2 format data which is used to transfer Courier data over
modems and RS232 connections.

13
© 2003 ALSTOM - Electronic file only
Publication: KBCH/EN BR/Kb

Transmission & Distribution Energy Automation & Information, Le Sextant, 3 avenue André Malraux, 92300 Levallois-Perret. France
Tel: +33 (0) 1 41 49 20 00 Fax: +33 (0) 1 41 49 24 85 energy-automation.information@tde.alstom.com www.tde.alstom.com
Contact Centre on line 24 hours a day : +44 (0) 1785 25 00 70

ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product
referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

You might also like