PCS-978S Transformer Relay Reliable differential CT circuit failure supervision. The relay
can detect multi-phase CT wire-break, multi-side CT
wire-break, short-circuit, and other complex situation. The
corresponding logic setting can be used to select blocking
differential protection or not, in case of CT circuit failure.
Functions
Protection and Control
• Transformer differential protection (87T)
• The relay supports at most 6 branches differential protection. The The 2nd and 3rd harmonics are both employed to detect both
transformer angle can be adjusted flexibly, and any transformer steady-state CT saturation and transient CT saturation. In
angle compensation mode is supported and any side can be addition, the time intervals between difference current and
chosen as the reference side of differential protection. restraint current are utilized to distinguish internal faults and
59
www.nrec.com/en
Specifications
Electrical Specifications
AC Current Input
Linear to 0.01A~200A
Thermal withstand
-continuously 20A
-for 10s 150A
-for 1s 500A
-for half a cycle 1250A
AC Voltage Input
Linear to 1V~300V
Power Supply
Burden
Quiescent condition <30W
Operating condition <35W
Transducer Input
68
PCS S Series
0.5A@48Vdc
0.35A@110Vdc
Breaking capacity (L/R=40ms) 0.30A@125Vdc
0.20A@220Vdc
0.15A@250Vdc
0.5A@48Vdc
0.35A@110Vdc
Cyclic Capacity
0.30A@125Vdc
(2.5 cycle/second, L/R=40ms)
0.20A@220Vdc
0.15A@250Vdc
30A@3s
Short duration current
50A@1s
69
www.nrec.com/en
10A@48V
10A@110V
Breaking capacity (L/R=40ms)
10A@125V
10A@250V
10A@48V L/R=40ms
Cyclic Capacity (4cycles in 1 second,
10A@110V L/R=40ms
followed by 2 minutes idle for
10A@125V L/R=40ms
thermal dissipation)
10A@250V L/R=20ms
30A@3s
Short duration current
50A@1s
Mechanical Specifications
Device structure Plug-in modular type @ rear side, integrated front plate
Protection Class
Standard IEC 60529-2013
Operating temperature -40°C to +80°C (Readability of display may be impaired below -20°C and above 70°C)
Pollution degree II
Altitude <3000m
70
PCS S Series
Communication Port
EIA-485 Port
Max. capacity 32
Connector type LC
Connector type LC
71
www.nrec.com/en
Connector type ST
Print Port
Type RS-232
Type Tests
Environmental Tests
Mechanical Tests
Electrical Tests
72
PCS S Series
Electromagnetic Compatibility
IEC 60255-26:2013
IEC 61000-4-2-2008
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
IEC 60255-26:2013
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 5kHz, 5/50ns
IEC 60255-26:2013
Surge immunity test Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV
IEC 60255-26:2013
Conducted RF electromagnetic disturbance Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Spot frequency
10V/m (rms), f=27MHz/68MHz
IEC 61000-4-8:2009
Power frequency magnetic field immunity
Class V, 100A/m for 1min, 1000A/m for 3s
IEC 61000-4-9:2016
Pulse magnetic field immunity
Class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2016
Damped oscillatory magnetic field immunity
Class V, 100kHz & 1MHz–100A/m
IEC 60255-26:2013
Conducted emission 0.15MHz ~ 0.50MHz: 79dB(μV) quasi peak, 66dB(μV) average
0.50MHz ~ 30MHz: 73dB(μV) quasi peak, 60dB(μV) average
IEC 60255-26:2013
Below 30MHz ~ 230MHz: 40dB(μV/m) quasi peak @10m, 50dB(μV/m) quasi peak @3m
Radiated emission 1GHz 230MHz ~ 1000MHz: 47dB(μV/m) quasi peak @10m, 57dB(μV/m) quasi peak @3m
Voltage dips Up to 200ms for dips to 40% of rated voltage without reset
Auxiliary power supply performance 50ms for interruption without rebooting without energy
storage board (Typical configuration)
Voltage short interruptions
500ms for interruption without rebooting with energy
storage board (Typical configuration)
73
www.nrec.com/en
Terminals
Management Function
Control Performance
Clock Performance
Duration & Recording position Settable pre-disturbance, post-disturbance and maximum recorded duration