PCS-931S Line Differential Relay will ensure fast clearance of internal fault and non-operation
of external fault.
25
www.nrec.com/en
Mho or quadrilateral characteristic, directional, load • Four stages overvoltage protection (59P)
encroachment, power swing blocking releasing and unique Time characteristics is selectable between definite-time and
low-voltage elements are provided for phase-to-phase inverse-time. Phase voltage or phase-to-phase voltage can be
distance protection. selected for protection calculation. “1-out-of-3” or “3-out-of-3”
• Six zone phase-to-ground distance protection (21Q/21M) logic can be selected for protection criterion.
Mho or quadrilateral characteristic, reactance characteristic, • Four stages negative-sequence overvoltage protection (59Q)
directional, load encroachment, power swing blocking • Four stages zero-sequence overvoltage protection (59G)
releasing and unique low-voltage elements are provided for
• Switch-onto-fault (SOTF) logic
phase-to-ground distance protection.
Switch-onto-fault logic is used to acceleratedly clear the faults
• Pilot distance protection (85)
during manual closing and auto-reclosing based on distance
one of selectable six zone for pilot scheme, such as PUTT, element or overcurrent element (phase current and residual
POTT, Blocking, Unblocking, DTT & Zone Extension. The current).
scheme integrates current reversal logic, weak-infeed echo
• Unique power swing blocking releasing logic (PSBR)
and open breaker echo.
The power swing blocking releasing logic prevents
• Pilot directional earth-fault protection (85)
mal-operations during external faults in power swing
Directional zero-sequence comparison element for pilot situations. It quickly clears the internal faults in power swing
scheme, such as PTT, Blocking and Unblocking. The scheme scenarios.
integrates current reversal logic, weak-infeed echo and open
• Auto-reclosing (79)
breaker echo.
Single-/Three-pole reclosing mode is provided. Up to four-shot
26
PCS S Series
breaker auto-reclosing with synchronism and voltage check logic. • IEC 61850, DNP3.0 or IEC 60870-5-103 over TCP/IP
sources used for synchronism. • One front RJ-45 port for debugging
• Self diagnostic
Communication
27