Professional Documents
Culture Documents
NODE No. FX FY FZ MX MY MZ
FX EXCEEDING
IN ALL PUMPS,
VENDOR TO
CONFIRM HVAC PUMP
CHWP-004
SUCTION NODE : 3690
DISCHARGE NODE :3660
HVAC PUMP
CHWP-003
SUCTION NODE : 2690
DISCHARGE NODE : 2660
HVAC PUMP
CHWP-002
SUCTION NODE : 1690
DISCHARGE NODE : 1660
HVAC PUMP
CHWP-001
SUCTION NODE : 690
DISCHARGE NODE :660
60-PU-0493 GLYCOL CHILLER
NOZZLE LOADS
PUMP DISCHARGE AND GLYCOL CHILLER QUALIFIED AS PER
NOZZLE LOADS QUALIFIED AS PER VENDOR
ALLOWABLES. ALLOWABLES
TANK NOZZLE
NODE : 780
560 TYPE=Rigid ANC;
4(OPE) -97 -172 -1221 0 -391 11
6(SUS) -308 195 -80 18 -8 -61
780 TYPE=Flex X; Rigid RX; Rigid Y; Flex RY; Rigid Z; Flex RZ; GLYCOL PUMP DISCHARGE
4(OPE) -266 -2260 923 -1131 13 501 60-PU-0493 NODE : 10
6(SUS) -157 -1732 -12 -38 -6 390
MAX -266/L4 -2260/L4 923/L4 -1131/L4 13/L4 501/L4
TANK ALLOWABLES AWAITED
60-PU-0495
PUMP DISCHARGE NOZZLE LOADS QUALIFIED
AS PER ALLOWABLES.
GLYCOL PUMP
60-PU-0495
10010 TYPE=Flex Y; Flex RY; Flex RX; Flex RZ; Rigid X; Rigid Z;
SUCTION
5(OPE) 454 -1751 4333 -563 -2076 -335 NODE : 400
6(SUS) 121 -965 -49 -31 82 -124
MAX 454/L5 -1751/L5 4333/L5 -563/L5 -2076/L5 -335/L5
ALLOWABLE NOZZLE LOADS AWAITED
ALTERNATE SUCTION ROUTING FOR PUMP 60-
PU-0495 (REF PROPOSED MODIFICATION
INDICATED ON SNAPSHOT HERE)
10010 TYPE=Flex Y; Flex RY; Flex RX; Flex RZ; Rigid X; Rigid Z;Tag=60-VS-0492/N14
5(OPE) 434 -1283 721 -217 -596 -269
6(SUS) 194 -1161 -62 -131 155 -225
MAX 434/L5 -1283/L5 721/L5 -217/L5 -596/L5 -269/L5
ALLOWABLE NOZZLE LOADS AWAITED