VOLTAGE MONITORING RELAYS

GKR / DGRC / MCC Series (Under / Over Voltage)


General
GKRC type over and under / over voltage monitoring relays are
designed to protect single phase or three phase systems from
voltage variations and phase sequence failure.

Note: These relays include the feature of switching OFF


immediately if any of the phases exceeds (or reduces from)
the nominal voltage by 50%.
DGRC type under voltage monitoring relays are designed to
protect single phase or three phase systems from lasting
under voltage variations.
Non-flammable enclosure
Rail-mounted or surface mounted with clips
Protection Degree: IP20
Ambient Operating Temperature : -5 oC, +50 oC
MCC-1D
IEC 60255-3, IEC 60255-6, IEC 60870-5, IEC 60529
GKRC-02FA

DIN 1 Rail Mount


DIN 2 Rail Mount
Without Neutral

Auxiliary Supply
Under Voltage
Single-phase

Over Voltage

Phase Seq.

pcs / carton
Delay-On

Delay-Off
3-Phase

Failure
GKRC-20F
Product Code
DGRC-01 10
GKRC-01 10
GKRC-02 10

GKRC-02F 10

GKRC-02FA 10

GKRC-03 10

GKRC-03F 10

GKRC-M2 10

MCC-1D 5-15 min. Delay-Off 24

MCC-3D 5-15 min. Delay-Off 24

GKRC-20F 10

Operating Principle
The relay is directly connected to the from instantaneous voltage peaks are delay (within less than 500msec.). If any
network and the required under / over prevented with the adjustable delayed of the phase voltages falls below 0,5xUn,
voltage limit is adjustable by knobs. tripping between 0,1 and 10 seconds. the relay switches OFF without delay
If any of the monitored phase voltage (within less than 500 msec.)
When the monitored voltages of all exceeds the set value, delay time If the voltage value returns within preset
3-phase are within the preset limits, starts to count. limits before the end of counting time,
then the output relay switches ON. If any of the phase voltages exceed the delay time ends and relay continues
Faulty tripping operations effected 1,5xUn, the relay switches OFF without to its normal operation.

MODELS
GKRC-02FA
GKRC-02F

GKRC-20F

GKRC-03F

GKRC-M2

DGRC-01
GKRC-02

GKRC-03

MCC-1D

MCC-3D
(new)

SPECIFICATIONS
Electrical Parameters
Operating Voltage (Un) 230 V AC, ±30%
230 V AC, ±10% 400 V AC, ±10% 230 V AC, ±10%
400 V AC, ±30%
Operating Frequency 50/60 Hz
3-phase / 4 wire 1-phase / 2 wire 3-phase / 3 wire 1 phase / 3-phase / 4 wire 1 phase / 3-phase / 4 wire
Network Type
(Star) 3-phase / 4 wire (Star) (Delta) 2 wire (Star) 2 wire (Star)
Under Voltage Adj. Interval (0,70-0,95)xUn (0,80-1,30)xUn (0,70-0,95)xUn (0,70-0,95)xUn -
Over Voltage Adj. Interval (1,05-1,30)xUn (0,70-1,20)xUn (1,05-1,30)xUn

Instant Tripping
£ 0,5xUn £ 0,5xUn 168 V AC
³ 1,5xUn
Instant Tripping Time < 500 msec
Hysteresis 3% -
Output Contact 1 C/O, 8 A, 2000 VA (cosj =1) 1 N/O, 8 A, 2000 VA (cosj =1)
Mechanical Parameters
Dimensions PK25 PK22 (DIN1) PK25 PK22 (DIN I)
Weight / each 0,25 kg 0,1 kg 0,25 kg 0,1 kg
Quantity in 1 package 24 pcs

40

www.entes.com.tr
VOLTAGE MONITORING RELAYS
GKR / DGRC / MCC Series (Under / Over Voltage)

Connection Diagram Dimensions


GKRC-01 GKR-03 / GKRC-03F GKRC-02 / GKRC-02F

1 2 3 1 2 3 1 2 3
58
1.25 1.30 GKRC 1.25 1.30 GKRC 1.25 1.30 GKRC
1.20 3 1.20 3
1.20 3 2
2 xU n xU n 2
xU n 1 1
1 1.15 1.15
1.15
1.10 1.05 1.10 1.05
1.10 1.05
U> U< On Out U> On Out
U> U< On Out

0.90 0.95 8 10 8 10
0.90 0.95 8 10
0.85
0.85 t (sn.)
xU n 4 4 t (sn.)
xU n 4 t (sn.)

90

62
35

45
0.80
0.80
2 0.1 2
2 0.75 0.70 0.1
0.75 0.70 0.1

N L1 L2 L3 L1 L2 L3 N L1 L2 L3
N N N
L1 L1 L1

L2 L2 L2 32 35
L3 L3 L3 48
System System System
N N
TYPE PK25

DGRC-01 GKRC-M2 GKRC-02FA

1 2 3
1 2 3
A1 1 2 3

1.25 1.30 DGRC GKRC-02FA


1.20 3

1.15
xU n 2
1 1.25 1.30 GKRC 480 500
1.20 3 460 2
1.10 1.05
xU n 2 (V)
U< On Out 1.15 1
440 1 3
1.10 1.05 420 400
8 10 ON OUT
U> U< On Out
U> U<
4 t (sn.)

2
0.90 0.95 8 10 380 400 8 10
0.1
0.85 360 6
xU n 4 t (sn.) (V) t(s)
0.80 340 4
2 0.1 320 300 2 0.1
0.75

61

90
0.70

45
N L1 L2 L3
N A2 L1 L2 L3
L1
N L
L2 A1
N
L Un A2
L3 N
N
System N
System L1
Vin (L-L) 28
L2 19
L3 System
48
MCC-1D MCC-3D 58
GKRC-20F TYPE PK 22
2 1 L1 2 1
L1
MCC-1D MCC-3D L2
On On
L3
N
Out Out

7 7
N L3
5 5
t (m.)
9
t (m.)
9
L1 L2
11 11
15 13 15 13

2
1
2
1 A1 15
R

N L L2 N L3 A2 16 18

15
N N 87
45

16 18
System System
L L1
N L2 GKRC-20F
L3 L
5 44
N 17,5
N 60
N L3
L1 L2 TYPE PK 27
Auxiliary Supply Connection Diagram (For only GKRC-02FA) A1 15
R

A1 A2 L1 L2 L3 A2 16 18
A1
A2 15
L1
L2 16 18
L3

Utilization with Single-Phase and Two-Phase Systems


(For only GKR-01/02, GKRC-01/02, DGR-01, DGRC-01)
See following connection diagrams for both cases:
N L1 L2 L3 N L1 L2 L3
L1 L1
L2 N
N
Two Phase Connection Diagram Single Phase Connection Diagram

Connection diagrams are given for reference. Please always check the latest user manual given with product or download from www.entes.com.tr.