You are on page 1of 1

Product Data Sheet

INQUIRY NO. ITEM NO.


72-90608 001

1/C, 35kV Rated, 100% Insulation Level, Type MV-105 For CT Use
A. CONDUCTOR: 750 kcmil Compact Round Class B Strand Copper
B. CONDUCTOR SCREEN: Extruded Semiconducting (SC-EPR)
C. INSULATION: 345 Extruded Ethylene Propylene Rubber OKOGUARD®
D. INSULATION SCREEN: Extruded Semiconducting (SC-EPR)
E. METALLIC SHIELD: .005'' Bare Copper Tape Shield with 25% Minimum Overlap
F. JACKET: 110 Extruded RED LT/FR OKOSEAL PVC

A. Conductor D. Insulation Screen

B. Conductor
E. Metallic Shield
Screen

C. Insulation F. Outer Jacket

Dimensions Thickness (in.) Diameter (in.) Cable Description

Nominal Minimum Nominal 1/C 750 CLASS B COPPER C-RD


Point -SS- 345 OKOGUARD EPR - 024
SC EPR - 005 COPPER TAPE (25%
Conductor N/A 0.908 MIN LAP) - 110 RED LT/FR
OKOSEAL PVC - SEQ PRINT -
35KV FOR CT USE
Cond. Screen 0.025 0.020 0.957

Insulation 0.345 0.330 1.660

Insul. Screen 0.027 0.024 1.720 TEMPERATURE RATINGS


105°C - Continuous, 140°C - Emergency
Metallic Shield 0.005 1.734 250°C - Short Circuit

Outer Jacket 0.110 0.100 1.970

Cable Weight (lbs./M'): 3784

Customer Name: WHOLESALE ELECTRIC


Customer Spec: 103-16058-LTE01619-ESP-120-E- 0008
Industry Standards: AEIC CS8-13, ICEA S-93-639/S-97-682, UL 1072.

APPROVED BY: Date: 10/25/19


Okonite Product Code 115
PREP. BY SCALE INQUIRY NO. ITEM NO. SERIAL NO. DRAWING NO.
RWP 10/25/19 TDN None 72-90608 001 01580 T - 52008

www.okonite.com
Cable Dimensions are Subject to Normal Manufacturing Tolerances.