You are on page 1of 6

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/3695264

Surge protection of a large medium voltage motor - A case study

Conference Paper · June 1997


DOI: 10.1109/ICPS.1997.595985 · Source: IEEE Xplore

CITATIONS READS

6 1,972

1 author:

P.E. Sutherland
ABB
67 PUBLICATIONS   455 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Power System Protection View project

Harmonics View project

All content following this page was uploaded by P.E. Sutherland on 03 January 2018.

The user has requested enhancement of the downloaded file.


SURGE PROTECTION OF A LARGE MEDIUM VOLTAGE
MOTOR - A CASE STUDY

Peter E. Sutherland
Power Systems Energy Consulting
GE Power Systems
Schenectady, NY 12345 USA

Abstract - The raw mill motor in a cement mill had been damaged Withstand level, may be calculated. This level is based upon
by repeated switching surges and subsequently rewound. New the motor’s nameplate voltage.
arresters were placed on the motor at that time. The surges coming in This paper does not intend to present any new concepts or
to the motor were measured, and the surge protection was reviewed. terminology, but to present an example of the application of
It was found that the original gapped silicon carbide surge arresters
on the motor had insufficient protective margin, while the new zinc existing knowledge to solve an interesting problem in the
oxide arresters provided an adequate margin. The operation of the industry.
surge capacitors in protecting the motor was analyzed. Surge This paper is intended not only to discuss motor protection,
protection and insulation coordination should be reviewed in but to provide an example of insulation coordination for an
comprehensive power system studies. industrial plant. Inadequate surge protection can result in
damage to equipment just as surely as inadequate overcurrent
INTRODUCTION
protection.
This case study illustrates the importance of evaluating the TRANSIENT ANALYSIS
surge protection of a large, medium-voltage motor. The motor
that was analyzes had been damaged and rewound, with new A transient analysis was performed to determine the
surge arresters installed. The purpose of the study was to magnitude and origin of transient overvoltages, which are
investigate the protection of the motor and determine whether entering the power system under evaluation. Transient
the new arresters would protect the motor in the future. voltages had caused the destruction of the mill motors.
When Zinc Oxide surge arresters were introduced, the To perform the analysis, disturbance analyzers were placed
advantages of the new arresters and the improved protection on the incoming 4160V lines. The recorders were connected
which they provide, as compared to the old gapped silicon to monitor the phase-to-phase voltages on the voltmeter
carbide arresters, was widely discussed. [ 11 However, in many switches, and line and neutral currents on the phase and
cases, old arresters were not re-evaluated, but were left in ground overcurrent relays. The results were recorded for a
place until replaced in the normal course of events, if ever. time of approximately one month.
This is in contrast to the situation with circuit breakers, where
short-circuit studies are performed on a periodic basis in many
plants as levels of available fault current change and improved 69 kV Transmission Line
circuit breaker technology becomes available. When surge I I
arresters are inadequate, the damage can result in expensive 1
repairs or replacement of equipment. To prevent cases such as
the one described here, industrial plants should have adequate
surge protection, which is re-evaluated occasionally.
Unlike other apparatus, a motor does not have a defined
Basic Insulating Level, which is used to determine surge
protection. However, a similar quantity, a Voltage Surge N.C.,T ~ f,N.C.

4160V Bus
,
T
Switched
Capacitors

20 Surge Capacitors

4000 HP
Fig. 1 . Simplified One-Line Diagram

-1-

36
The voltage transformer ratio in the switchgear is 4200/120, HQSE 2 3 IMPULSE
so that the 41 60V nominal voltage becomes 118.8V in the 181 U peak
69 phase post tion
recordings. The typical system voltage is slightly higher than 1.7 usec rise time
350 Joules (estimated), a t 50 ohms
that, 70.5 kV in the 69 kV system, or 4250V in the 4160V
PHRSE 2 3 IMPULSE
system. The peak voltage is 1.414 times this or 601 1V. The
typical system voltage as seen through the voltage transformers 200u
is thus 121Vrms,172V peak. ;_. - _- - - - - - - - - - - - -
Ou
The frequency response of a typical voltage transformer
loaded by a digital transient recorder has been tested [2], and
__-_- __--
the ratio correction factor found to be within +3% of unity for
a frequency range of 60 Hz to 10 kHz.
-200u L ' '
'V
I ' ' ' ' ' ' '
162.4 MICROSEWNDS/DIUISION HORIZONTRL
'
Transient Overvoltages 500R

The recorded transient overvoltages appear to be caused by


BR
capacitor switching, based on their magnitudes and their high
resonant frequencies, in the order of 5-20 kHz. These
frequencies could be caused by resonance with an inductance -250u -5000
in the capacitor connections and busbars in the order of
-PHFISE 2 3 UOLTRGE -PHRSE 2 CURRENT
5.0 MILL I SECOND9DIUISION HOR I ZONTRL
25 pWphase. The magnitude of the transient overvoltages are
Fig. 2: Transient Recording of Voltage Surge. Current values on the chart
in the range to 110-200 secondary Volts. With a nominal should be multiplied by 10 to get system Amperes.
115V signal having a peak of 163V, a 181V surge (as shown
in Fig. 2), is 11 1% of the peak value. These values are typical INSULATIONCOORDINATION
of capacitor switching. The maximum peak voltage is
approximately twice the peak value of the incoming voltage The purpose of the insulation coordination study is to
wave. For a 4.16 kV system, the peak voltage is 5.88 kV, and compare the protection provided by the surge arresters in the
thus the maximum peak voltage is twice this or 1 1.77 kV. system with the insulation withstand of the equipment. This
A typical event is illustrated in Fig. 2. study was conducted because of the failure of the insulatiim in
Note that in the upper waveform, the time scale is the large synchronous motors. After that incident, the motors
magnified, and the period of the surge waveform is were rewound and new surge arresters installed on the motors
approximately 200 p. The frequency of 5 kHz is thus within and on the two 10 MVA transformers. This study will analyze
the range anticipated. the protection of the system and make recommendations for
changes as needed.

TABLE 1
CHARACTERISTICSOF STATION CLASS METAL OXIDE SURGE ARRESTERS

Location MCOV* 1 Second Front of Switching


Temp- Wave Surge
orary Protec-tive Protec-tive
Over- Level Level KV
Voltage kV Crest Crest
kV RMS @ 500A
SA1 I 57 I 85 ** I 191.8 1 136.6 147.3 I 154.9 I 162.0 I 174.4 I 193.1 I 219.2
SA3 I 3.7 I 5.3 I 13.0 I 9.0 9.9 I 10.3 I 10.8 I 11.5 I 12.9 I 14.8

Maximum 8/20 Discharge Voltage - kV at


Location Arrester Max.USA Max Max 1.5 kA 3.0 kA 5kA 10 kA 20 kA 4okA
Max. kV Std. FOW 1.2~50 Switching
Line- Spark-over Spark-over Surge
Ground kV Crest kV Crest Spark-over
kV Crest

SA2 4.5 16 15 15 7.4 8.7 9.5 10.8 12.3 15.1

-2-

37
PROTECTION
OF SUBSTATION
TRANSFORMERS Lightning Protective Level (LPL) and is equal to 162.0 kV.
This is compared to the BIL of the transformer:
The incoming 69 kV line is unshielded until it reaches the
metering point, about one mile from the plant entrance. The BIL 350
PR(2) = -= -= 2.1 6
metering point is protected by station class arresters. The line LPL 162
past the metering point is shielded. The 69 kV substation is PM(2) = (2.16 - 1.0) x 100% = 116%.
protected by lightning rods on the towers, and by station class
arresters where the lines enter. At the primary terminals of the This is much larger than the recommended minimum value of
10 MVA transformers new MOV station class surge arresters 20%.
are mounted (Table 1, SA 1). The purpose of placing arresters The switching surge protective ratio measures the ability of
directly on the transformer terminals is to limit the voltage the arrester to protect the transformer against switching surges,
doubling effect when a traveling wave reaches the end of a which are much slower than lightning surges. The Switching
line. For the purposes of this study, only the transformer Surge Protective Level (SPL) of the arrester with a
primary arresters will be evaluated. 500 Ampere discharge current is 136.6 kV. This is compared
The transformer primary windings have a Basic Impulse with the Basic Switching Level (BSL) of the insulation IEEE
Level (BIL) of 350 kV. A transformer with a 350 kV BIL has, Std. C57.12.00-1993, [2, Table 51. For the transformer, this is
according to IEEE Std. C57.12.00-1993 [3, Table 41, a 280 kV. The protective ratio and protective margin are thus:
chopped wave impulse level of 400 kV crest.
BSL 280
The Maximum Continuous Operating level (MCOV) of the PR(S) = -= -- - 2.05
arrester should be higher than the maximum possible line- SPL 136.6
neutral voltage in the system. In a 69kV system with 5% PM(S) = 105%.
overvoltage, the line-to-neutral voltage is 42 kV, which is well
within the arrester MCOV rating. This is much larger than the recommended minimum value of
The maximum temporary overvoltage (TOV) that the 15%.
arrester may experience is dependent upon the system w, Note that these values are optimistic, and do not include the
effect of lead length, which may reduce the calculated
ratio (2.27), Rl/X1 ratio (0.692) and Rdxl ratio (0.976), protective margins.
provided by the utility. These are used to calculate the
maximum voltage that may be experienced during a ground PROTECTION OF 4160V SWITCHGEAR, CABLES AND
fault. Other possible causes of temporary overvoltages include DISTRBUTION TRANSFORMERS
ferroresonance, loss of ground, resonance, and open
conductors. These are less likely to occur in this system. This equipment is protected by arresters installed in the
Using information provided in IEEE Standard C62.22- 1991 switchgear. The BIL levels are as follows:
[4, Appendix B, Fig. B3], the overvoltage during a ground Switchgear 60kV
fault was estimated to be 70% of the system voltage or 48 kV. 5 kV Cables 75 kV
This is 114% of the normal line to neutral voltage. The Transformers 60 kV
arrester has a TOV rating of 85 kV for Is, or 219% of the line
to neutral voltage. Equipment BIL may be taken from nameplates (where
The protective ratios and protective margins for lightning available) and ANSVIEEE standards. Much of this data is
and switching surges are determined as follows: tabulated in [SI. A 60 kV BEL will be used in this analysis.
The arresters are silicon carbide units with a maximum
Protective Ratio #1 measures the ability to protect against a
continuous voltage rating of 4.5 kV. The transformer
chopped wave, which is a lightning surge tfuncated due to
secondaries are low resistance grounded, resulting in a
insulator flashover. The chopped wave withstand (CWW)
temporary overvoltage equal to the line-to-line voltage of
capability of the transformer insulation is 400 kV. The Front
4.16 kV in the event of a single-line-to-ground fault. There is
of Wave (FOW) protective level for the arrester is 191.8 kV.
thus no need to further analyze the temporary or continuous
Thus, the PR( 1) ratio is:
overvoltage ratings of the arrester.
CWW
-- The FOW protective level is 16 kV, so:
- 2.09.
FOW

The Protective Margin #1 is: )


PM(1) = -- 1 x 1 0 0 % = 275%

PM(1) = (2.09 - 1.0) x 100% = 109%. The LPL for this type of arrester (ANSI C62.2-1987) [6] is
the greater of the let-through sparkover (LT) for a 1 . 2 ~ 5 0ps
This is much larger than the recommended minimum value of wave, which is 15 kV for this arrester (Table 2, SA 2), or the
20%. lightning discharge voltage level for an 8x20 ps wave at a
Protective Ratio #2 measures the ability to protect against a selected discharge current. A conservative value of 10 kA was
typical lightning surge characterized by a 5 kA, 8x20 ps wave. selected, which is much larger than is likely to be encountered
in a shielded installation such as this. The discharge voltage at
The arrester discharge voltage at this current is called the

-3-
38
10 kA is 10.8 kV. Thus the LPL is 15 kV and the Protective where VL is the motor line-to-line voltage, which is 4 kV.
Margin #2 may be calculated: This steady-state capability is the horizontal line on the top of
the curve, V, in Fig. 3. The withstand envelope is used instead
(;:
PM(2) = -- 1 x 100%= 300% of a BIL for motors. Motors do not have a defined switching
surge impulse level. The slope of an incoming surve voltage
should be plotted on the graph as well, to see whether it
The switching surge sparkover for this arrester is 15 kV.
Thus the switching protective margin is: exceeds the withstand envelope, but the recording equipment
used did not produce detailed enough oscillograms in order to
do this. The dotted line, Vc, on the graph is a surge whose
slope is decreased by the surge capacitors. This is calculated
[5] based upon the assumption that a step front wave of
All of these are well above the recommended values. Voltage E, on a line of surge impedance Z, meets a capacitive
Note that these values are ideal, and do not include the termination, C:
effect of lead length, which may reduce the calculated
protective margins.

Protection of Synchronous Motors

The synchronous motors are protected by surge capacitors


Vc=2.E
i -'j
1-e z-c

for this example, the applied voltage, E was the protective


and arresters located in junction boxes immediately below level of the arresters on the bus, 15 kV, the capacitance OSpF,
each motor. The capacitors are the 0.5 pF recommended for and the surge impedance of the cable assumed to be 30Q
this application. Their purpose is to slow down the rate of rise based on typical values given in the reference [5, Table 11.
of incoming surges. The original surge arresters used did not The arresters in the switchgear may be similar to the original
protect the motors, which were damaged by incoming surges. silicon carbide arresters used on the motor, which have a let-
After the motors were rewound, new arresters were installed. through sparkover of 15 kV, a 10 kA lightning discharge level
The motor has a voltage-time profile which graphically of 10.8 kV, and a switching surge sparkover of 15 kV. Thus,
illustrates its ability to withstand surge impulses. A machine these arresters have a protective margin of:
impulse withstand envelope may be plotted, as shown in
Fig. 3. This curve is presented in the IEEE Red Book [7]. P E ( ~LTSO
- l ) x l o o %

*O
= (z - 1) x 100% = 6%,

for lightning surges. This is less than the recommended 20%.


The PM(1) front of wave protective margin is not applicable
because of the presence of surge capacitors.
The new arresters used on the motor terminals (SA 3, Table
1 ) are a 4.5 kV metal oxide arrester with an MCOV of 3.7 kV,
one second TOV rating of 5.3 kV, 500 A switching surge
protective level of 9.0 kV, 10 kA discharge voltage of 1 1.5 kV
and Front of Wave protective level at 10 kA crest of 13.0 kV.
The PM(2) lightning protective margin is 38%, calculated as
0 5 10 follows:

[ &- 1) x 100%
I

Time, ps PM(2) =
Fig. 3. Machine Impulse Withstand Envelope for 4 kV Motors where V is
the Machine Impulse Withstand Envelope and V, is the result of a
IS kV steep front surge being limited by a surge capacitor. [7]
=(%- 1) x 100% = 38%

The surge capacitors act to slow down the front of the surge, The switching surge protective levels of the arresters may
so that the sloping front of the withstand curve will be also be compared to the maximum expected capacitive
protected. The arresters will then protect the impulse switching surge of 6.8 kV line-neutral. When this surge
withstand envelope of the motor: reaches the motor, its magnitude doubles to 13.6 kV. The
expected surge magnitude is smaller than the 15 kV protective
w = 1.25 0 4 5 . (2 v, 0 +I) level of the original arresters and larger than the 9 kV level of
= 15.9kV the new. While there is no protective margin defined in this
case, the newer arresters provide a far better level of
protection.

-4-
39
CAPACITORS
SURGE Where large motors or other apparatus are protected by
surge arresters, it is well to consider: (a) if any changes have
The effect of the capacitors on an incoming surge is to occurred which result in increased voltage surges, such as the
increase the rise time by adding a time constant equal to the installation of capacitor banks? (b) If there are there still
capacitance times the surge impedance of the cable. If the silicon carbide arresters in the system and are they adequate?
cable has a typical 30Q surge impedance and the capacitors (c) If an insulation coordination study would possibly prevent
are 0.5 pF,then the time constant is 15 ps. The equation for future problems?
this calculation [ 5 ] is that of an exponential rise:
ACKNOWLEDGMENTS
The author would like to thank Mr. John Skliutas of the
GE’s Power Systems Energy Consulting, who assisted in the
preparation of the study which formed the basis for this paper.
where V is the voltage seen by the motor, E is the magnitude
of the incoming surge, t is time in micro-seconds (p),Z is the REFERENCES
surge impedance of the cable and C is the surge capacitor G.W. Walsh, A New-Technology Station Class Arreester
capacitance in J.I.F. The effect of a vertical front surge of for Industrial and Commercial Power systems,
15 kV magnitude as limited by the arresters in the switchgear Conference Record of the IEEE Industrial and
is shown in Fig. 3. The voltage will eventually rise to 30 kV Commercial Power Systems Conference, May 9- 12,
unless limited by the surge arresters. However, the initial 1997, Pittsburgh, PA. Catalogue No. 77CH1198-I 1A.
slope is gradual enough to stay within the motor withstand D.A. Douglas, Potential Transformer Accuracy at
envelope. 6 0 H z Voltages Above and Below Rating and at
The protective margins above are best case conditions, Frequencies Above 60 Hz.,IEEE Transactions on Power
ignoring the effects of lead length. It is recommended practice Apparatus and Systems, Vol. PAS-100, No. 3, March
that the lead length to the capacitors from the incoming cable 1981, pp. 1370-1375.
be as short as possible. If the cable between the motor and the IEEE Standard General requirements f o r Liquid-
surge arrester is taken into account, the protective margins will Immersed Distribution, Power and Regulating
be reduced. The amount of reduction depends upon the rise Transformers, ANSI/IEEE Std. C57.12.00- 1993
time of the incoming current surge. The additional voltage IEEE Guide f o r the Application of Metal-Oxide Surge
generated on the lead is calculated as follows: Arresters f o r Alternating Current Systems, ANSVIEEE
di Standard C62.22-1991.
V=L-
dt G.W. Walsh, A Review of Lightning Protection and
Where V is the generated voltage in kV,L is the inductance of Grounding Practices, IEEE Transactions on Industry
the lead in pH, and di/dt is the rise time of the current in Applications, Vol. IA-9, No. 2, MarchIApril 1973.
kA/p. With a cable surge impedance of 3052, the current IEEE Guide for the Application of Gapped Silicon-
surge will have a slope of 0.03 Wp. If the cable to the Carbide Surge Arresters f o r Alternating Current
motor from the arresters is 3’ long and has an inductance of Systems, ANSMEEE Standard C62.2- 1987.
1.5 pH, a current surge with an assumed rise time of lEEE Recommended Practice for Electric Power
0.1 W p s will generate a voltage of 0.15 kV. This must be Distribution in Industrial Plants (IEEE Red Book), IEEE
added to the protective level of the breakers. For a lightning Standard 141-1993, Chapter 6, pp. 31 1-361.
protective level of 11.5 kV, the voltage seen at the motor
Peter E. Sutherland (M ‘83) received the A.S. Degree in Electrical
would be 11.65 kV, and the protective margin would be 36% Engineering Technology (‘79) and the B.S. degree in Electrical Engineering
instead of 38% with the cable not considered. Thus added (‘83) from the University of Maine at Orono. In 1986 he received the M.Sc.E
cable length reduces the protective margin. Degree in Electrical Engineering from the University of New Brunswick
(Canada).
CONCLUSIONS He has worked as a Test Engineer and a Design Engineer for Accutest
Corp. of Chelmsford, Mass.,a manufacturer of automatic test equipment for
This paper has presented an example of surge protection in the semiconductor industry. For a short time he worked as a Planning
an industrial plant, where an earlier generation of arresters was Engineer for an Electric Utility Company. In 1987 he joined General Electric
not providing protection for a large motor. Voltage surges, Company, and has been employed as an Engineer in the Industrial Power
caused by the daily switching of a nearby capacitor bank in the Systems Engineering Operation in Schenectady, NY, as an Instructor in the
Training and Development Center, and as a Power Systems Engineer in
utility system, were believed to have caused the motor Albany, NY. His current position is Senior Engineer in the Power Systems
insulation to fail. The motor was rewound, and new arresters Energy Consulting, where he performs a variety of power system studies for
installed. The analysis was performed after the fact to industrial clients.
determine whether the motor was now protected. The analysis Mr.Sutherland is currently enrolled as a part-time student in the Ph.D.
showed that application of zinc oxide arresters provided the program in Electric Power Engineering at Rensselaer Polytechnic Institute,
Troy, NY. Mr. Sutherland is a member of Eta Kappa Nu and Tau Beta Pi.
protective margin necessary to be assured that such damage
He is a Registered Profession& Engineer in Maine and in New York.
would not occur again.

-5-
40

View publication stats

You might also like