Vendor Document / Drawing Front Sheet

Document Title : DATA SHEET FOR ULTRASONIC FLOW METER

Contractor / Client Doc No. : PGDD-KPE-1472-00-EIC-DS-V41-001 Rev : 0


Vendor Doc No. : YIN-PGDD-IS-003 Rev : C
Area : 1472-00

Location : Dumai Station

System : General

Document Type : Instrument

Discipline : Instrument Sub Discipline : -


 

Submitted For: Proyek Pembangunan Pipa Gas Duri – Dumai


( PGDD )
□ Review □ Certified □ Info
Review does not constitute acceptance of design details, Vendor / Supplier Name:
calculation, test methods or materials developed or selected
by supplier nor does it relieve supplier from full compliance
with contractual or other obligations. PT Yokogawa Indonesia
1. Approved to Proceed (Submit final Package No.: 41
documents in MDR/OM only).
Manufacture may proceed Package Description / Brand :

2. Approved with comments (Revised & Gas Metering Package


resubmit document).
Manufacture may proceed once comment PO No.:
actioned
4110071335
3. Rejected (Revised & Resubmit Work Tag No.:
may not proceed)
02-M-01
4. For Information only (submit Final
Document in MDR/OM only).
Manufacture may proceed

Name :
Date :

Signature :

PT PDC – PT ELNUSA
DATA SHEET FOR ULTRASONIC FLOW METER
Document No. Rev.
Page 2 of 5
PGDD-KPE-1472-00-EIC-DS-V41-001 0

CLIENT : PT Pertamina Gas

CONTRACTOR : Konsorsium PT Patra Drilling Contractor – PT ELNUSA

PROJECT TITLE : Pembangunan Pipa Gas Duri – Dumai ( PGDD )

0 Issued for Information 18/04/2018 MLF LIE HRL


PRPD CHKD APVD CHKD APVD
REV DESCRIPTION DATE
PT PDC – PT ELNUSA PT PTG PT PTG
DATA SHEET FOR ULTRASONIC FLOW METER
Document No. Rev.
Page 3 of 5
PGDD-KPE-1472-00-EIC-DS-V41-001 0

REVISION HISTORICAL SHEET

REV DATE DESCRIPTION


C 18/04/2018 Add local indication

Add indiaction Upstream/Downstream

Update I/O configuration for USM

Change minimum flowrate as per minimum velosity


DATA SHEET FOR ULTRASONIC FLOW METER
Document No. Rev.
Page 4 of 5
PGDD-KPE-1472-00-EIC-DS-V41-001 0

TABLE OF CONTENTS

1. Cover Vendor Document ................................................................................... 1


2. Cover Contractor Document ............................................................................. 2
3. Revision Historical Sheet .................................................................................. 3
4. Table of Contents ............................................................................................... 4
5. Data Sheet Ultrasonic Flowmeter ..................................................................... 5
6. Attachment-1 General Specification Ultrasonic Flowmeter

 
GENERAL 1 Tag Number FIT-001A & FIT-001B
2 Service Gas Metering Package Dumai
3 P&ID No. DUDM-02-PRO-PID-006 / YIN-PGDD-DR-001
4 Design Pressure Min. Max. 690 Psig
5 Design Temperature Min. Max. 0 0F 150 0F
PROCESS 6 Fluid Name State Hydrocarbon / Gas Gas/Vapor
CONDITIONS 7 Min. Nor. Max.
8 Flow MMCFD 57 120 157
9 Pressure @ Flow Psig 363 363 363
10 Temperature @ Flow °F 86 100 100
11 Viscosity @ Flow cP 0.012 0.014
12 Density @ Flow (Liq. / Steam) (lbs/ft3) 1.2479(Note1) 1.2480(Note1) 1.2481(Note1)
TRANSDUCER / 13 Type Direct Path
METER 14 Path Number of Reflexion 4 Path N/A
15 Meter Connection In Rating Sch Type 16" 300 40 RF
16 Meter Connection out Rating Sch Type 16" 300 40 RF
17 Upstream/Downstream Req 10D-10D / 5D
18 Retractable Yes
19 Transducer Cable Length Integrated
20 Pressure Tapping Connection ½” NPT F
21 Meter Body Material A350 LF2
22 Transducer Material Titanium
23 Painting Colour Factory Standard
24 Standard Compliance to Meter AGA 9 standard
25 Velocity @ max flowrate 59.087 ft/s (Note 2)
TRANSMITTER 26 Type Multipath Ultrasonic Flow Meter
27 Local Indication LCD
28 Totalizer Single Flow Computer per Stream
29 Meter Range Min. Max. 13.8 MMSCFD 157 MMSCFD
30 Accuracy 0.2% After flow calibration and adjustment with constant factor
31 Repeatability < 0.1 % of the measured value
32 Elec. Haz. Protection STD Method Gr. Temp. Class 1 Div 2 Gr D T4
33 Weather Protection IP67
34 Power Supply / Power consumption 12 ... 28.8 V DC / ≤ 1 W
35 Local Display Yes
36 3 outputs (2 pulse & 1 Digital) , 30 V, 10 mA Passive, electrically isolated, Open
Digital Collector or according to NAMUR (EN 50227)
37 Serial Communication 2 x RS 485
38 Electrical Connection M20 x 1,5 (3x)
39 Remote Output Gauge Tag No. NA NA
40 Press. / Temp. Compensation Function NA
41 Press. Tag No. Elec. Conn. NA NA
42 Temp. Tag No. Elec. Conn. Sig. Type NA NA NA
PURCHASE 43 Manufacturer SICK
44 Model Flowsick600
Notes:
1. Density value as per document PGDD-KPE-14000-00-EPS-DG-001
2. Max Velocity as per sizing USM with flowrate 157 MMSCFD

INSTRUMENT DATA SHEET

C IH 18-Apr-18 RE-ISSUED FOR APPROVAL Data Sheet For Ultrasonic Flow Meter
B IH 06-Apr-18 ISSUED FOR APPROVAL
A IH 23-Mar-18 ISSUED FOR REVIEW
No By Date Revision Dwg. No.: Sheet 5 of 5 Rev.:C
ATTACHMENT-1
GENERAL SPECIFICATION ULTRASONIC FLOW
METER
P R O D U C T I N FO R M AT I O N
FLOWSIC600
CUSTODY TRANSFER GAS FLOW MEASUREMENT
AND PROCESS MONITORING

Gas flow meters


INVESTING IN A HIGH-QUALITY METER SAVES MONEY
Every day natural gas flows in great quantities through pipelines or into storage facilities, thus changing
owners. Precise gas quantity measurement is of the utmost importance, as even very small measurement
errors could result in substantial economic loss. In addition, challenging ambient measurement conditions
often play a decisive role. Moisture, ice, cold, heat and desert sand place great demands on the instru-
ments in the field. This is why a gas flow meter is needed that is both accurate and reliable.
The FLOWSIC600 gas flow meter from SICK achieves both of these goals. It is ideal for both natural gas
custody transfer and the highly precise measurement of process gases in the chemical industry.

Natural gas pipeline in Bawu-Changnan using FLOWSIC600

2 F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 8009840/2014-09
Subject to change without notice
Highly Durable High Measurement Accuracy Maximum Reliability
The FLOWSIC600 compact gas flow The FLOWSIC600 measures gas flow The FLOWSIC600 uses ultrasonic
meter hermetically shields all of its using ultrasonic technology. The ar- measurement and operates without me-
measurement equipment from the rangement of the ultrasonic sensors in chanically moving parts making it largely
environment. The use of internal cable the measurement device (path layout) resistant to contamination and wear.
routing prevents harsh climate condi- matches its performance parameters The result is maximum measurement
tions and contamination from harming perfectly. With the FLOWSIC600, SICK reliability even under adverse measure-
the device. The FLOWSIC600 is virtually developed ultrasonic sensors designed ment conditions.
maintenance-free. for maximum immunity to noise.

Excellent System Integration Worldwide Approvals Low Power Consumption


The FLOWSIC600 is available for nomi- The FLOWSIC600 conforms to all rele- SICK ultrasonic sensors combine high
nal pipe sizes from DN80 to DN1200 for vant natural gas guidelines and has performance with low power consump-
custody transfer applications, and as worldwide approval. tion. Due to low power consumption, it
small as DN50 for process applications. is possible to use a stand-alone power
Easy connection to flow computers supply, such as a solar module.
allows straightforward integration into
any measurement station. SICK also
provides inlet and outlet sections, flow
computers, and pressure and tempera-
ture transmitters.

The FLOWSIC600 is available in four types

Ideal for custody transfer appli- Ideal for applications having Ideal for fully redundant Ideal for process gas measure-
cations additional monitoring measurements ment and internal billing

FLOWSIC600, 4-path FLOWSIC600 2plex FLOWSIC600 Quatro FLOWSIC600, 2-path

•• The standard design is •• The 2plex design provi- •• The FLOWSIC600 Quatro •• A reliable two-path de-
equipped with a fourpath des enhanced diagnos- provides a redundant sign provides adequate
system in which the tics, combining a custody solution, integrating two measurement accuracy
measured values of the transfer meter with a meters into one meter in both custody and non-
individual sensor pairs check meter. body while retaining the custody applications.
are averaged. same overall length.

8009840/2014-09 F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 3
Subject to change without notice
EXCELLENT MEASUREMENT TECHNOLOGY IN AN OUTSTANDING
MEASUREMENT DEVICE
The FLOWSIC600 is a top-quality measurement device. It features a robust meter body incorporating
measurement equipment, performs measurement with high noise immunity and long-term stability, and is
nearly maintenance-free.

Ultrasonic Sensors from SICK


The FLOWSIC600 is equipped with high-performance ultraso-
nic sensors developed by SICK. A hermetically sealed titanium
housing contains ultrasonic transducers that operate at a
selectable ultrasonic frequency of 80 kHz, 135 kHz, 200 kHz,
or 300 kHz to match the operating conditions.
The sensors can also be deployed at very high or very low
temperatures (from –194 °C to +280 °C), at high pressures
(up to 450 barg), under corrosive conditions, and with heavy
background noise. They exhibit unrivaled reliability in sound-
absorbing gases that are high in carbon dioxide.
The FLOWSIC600 features an efficient transducer for perfor-
ming measurements at atmospheric pressure, allowing calibra-
tion using air.
Sensor

Direct Path Layout


The transit time difference principle is used for performing ultrasonic gas flow measurement. This measurement principle uses
ultrasonic transit time to determine the gas flow rate. The direct path layout minimizes the influence of turbulence, contamination,
moisture, and background noise.
Two ultrasonic sensors are installed opposite each other at a specific angle to the gas flow and operate alternately as a transmit-
ter and receiver.

Direct path layout

4 F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 8009840/2014-09
Subject to change without notice
Automatic Self-Diagnostics
The FLOWSIC600 is equipped with a warning signal that informs the user of a malfunction before the measured value is affected.
To do this, current diagnostic indicators are compared to indicators that were learned by the device under normal measurement
conditions. The results of the self-diagnostics are permanently logged by an internal electronic data log to allow a retroactive
check of the measurement process. Important measured variables such as gas flow and gas velocity (VOG) or diagnostic parame-
ters such as signal-to-noise ratio (SNR) or speed can be read directly.

Operating Software
MEPAFLOW600 CBM operating software allows efficient and effective meter and data management and provides extensive
diagnostics options. The software provides simple, user-friendly access to FLOWSIC600 data. MEPAFLOW600 CBM provides
permanent online and offline access to the FLOWSIC600. In addition to easy-to-understand visualization, the software supports
the user with logs and assistance functions when operating the gas flow meter.

MEPAFLOW CBM

8009840/2014-09 F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 5
Subject to change without notice
FLOWSIC600 Gas flow meters

A
GAS FLOW METERS FOR CUSTODY TRANSFER
B TRAFFIC AND PROCESS APPLICATIONS
C Product description

D The FLOWSIC600 measurement device


is an ultrasonic gas flow meter and sets
the standard in its market segment. The
stability. The FLOWSIC600 features
extensive diagnostics options to allow
detection of malfunctions even before

E visually technical design demonstrates


that it is geared to the tough industry
conditions. The compact design with
the measurement is affected. Types
having 2, 4, 4 + 1, or 4 + 4 measur-
ing paths enable a variety of process

F
integrated cable routing means that the applications, including custody transfer
measuring system is durable, failsafe, measurements.
low-maintenance, and has long-term

At a glance
• High efficient ultrasonic transducers • Integrated log book and data logger

H • Direct path layout (Westinghouse


design)
• Large measuring range 1:120
• Bidirectional measurement
• Intelligent self-diagnostics • Low power consumption: <1 W

I • Compact, robust design

Your benefits
J • Long-term stability, reliable measure-
ment
• Virtually immune to pressure regula-
tor noise
• Low maintenance due to intelligent • Ultrasonic transducers can be ex-
K self-diagnostics changed under operating pressure
• Wide application range

L
M
N ®

C US

O
P Additional information
Fields of application ����������������������������7 

Q Detailed technical data������������������������7 


Measuring ranges��������������������������������8 

R
Ordering information����������������������������9
Dimensional drawings��������������������������9 
Dimensions ����������������������������������������10 
-- www.mysick.com/en/FLOWSIC600

S Instruction for installation ��������������� 14 For more information, just enter the link and get direct access to technical data, CAD design models, operating
instructions, software, application examples and much more.

T 6 F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 8009840/2014-09
Subject to change without notice
Gas flow meters FLOWSIC600

Fields of application
• Custody transfer applications (natural gas, N2, O2, air, • Cryogenic gas applications down to –194 °C
A
ethylene) • Also for process gases
• Onshore and offshore applications
• Underground gas storage facilities (bidirectional measur-
• For gases with high H2S component such as sour gas or
biogas
B
ment possible)

Detailed technical data


C
D
The exact device specifications and performance data of the product may deviate from the information provided here, and depend on the appli-
cation in which the product is being used and the relevant customer specifications.

System
Measured values
Number of measuring paths
Volumetric flow, a. c., volume a. c., gas velocity, sound velocity
2, 4, 4+1, 4+4
E
Measurement principle
Measuring medium
Ultrasonic transit time difference measurement
Natural gas, air, C2H4, steam, process gases (e. g. CO2 up to 100%, N2, O2, Cl2 etc.), gases like F
sour gas or bio gas with high H2S content
Measuring ranges
Volumetric flow, a. c. 4 ... 400 m³/h / 1,600 ... 100,000 m³/h
Measuring ranges depend on nominal pipe size
Repeatability
Accuracy
< 0.1 % of the measured value
H
I
Error limits
2-path version 1: ≤ ± 1 %
4-path version :2
≤ ± 0.5 %

4-path version 2:
Dry calibrated
≤ ± 0.2 %
After flow calibration and adjustment with constant factor
J
K
4-path version 2: ≤ ± 0.1 %
After flow calibration and adjustment with polynomial or piecewise correction
1
In the range Q t ... Qmax with straight 20D/3D inlet/outlet section or with 10D/3D flow condi-
tioner
2
In the range Q t ... Qmax with undisturbed 10D/3D inlet/outlet section or with 5D/3D flow
Conditioner L
Diagnostics functions Integrated device diagnosis and extended diagnosis via MEPAFLOW600 CBM software
Gas temperature
–40 °C ... +180 °C
M
N
On request: –194 °C ... +280 °C
Operating pressure 0 bar (g) ... 250 bar (g)
On request: Up to 450 bar (g)

O
Nominal pipe size
2 " ... 48 "
(DN 50 ... DN 1200)

P
Ambient temperature
ATEX, CSA: –40 °C ... +60 °C
IECEx: –40 °C ... +70 °C

IECEx:
Optional
–50 °C ... +70 °C Q
Storage temperature –40 °C ... +70 °C
Ambient humidity ≤ 95 %
Relative humidity R
S
8009840/2014-09
Subject to change without notice
F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 7
T
FLOWSIC600 Gas flow meters

A Conformities AGA-Report No. 9


API 21.1
OIML D11

B OIML R137-1
ISO 17089-1
BS 7965

C
Pattern approval: MID, PTB, NMi, Measurement Canada, GOST ...
Ex-approvals
IECEx Gb/Ga Ex d e ib [ia Ga] IIA T4

D ATEX
Gb/Ga Ex d e ib [ia Ga] IIC T4
Ultrasonic transducers intrinsically safe
II 1/2G Ex de ib [ia] IIA T4

E
II 1/2G Ex de ib [ia] IIC T4
Ultrasonic transducers intrinsically safe
NEC/CEC (US/CA) Class I, Division 1, Groups B, C, D T4
Class I, Division 2, Groups A, B, C, D T4

F Class I, Division 1, Group D T4


Class I, Division 2, Group D T4
Ultrasonic transducers intrinsically safe
Electrical safety CE
Enclosure rating
IP 65 / IP 66 / IP 67

H Analog outputs 1 output:


4 ... 20 mA, 200 Ω
Active/passive, electrically isolated

I Digital outputs 3 outputs:


30 V, 10 mA
Passive, electrically isolated, Open Collector or according to NAMUR (EN 50227), fmax = 6 kHz
(scalable)

J Interfaces
Bus protocol
RS-485 (2x, for configuration, output of measured values and diagnosis)
Modbus ASCII

K
Modbus RTU
HART
Operation Via meter display and software MEPAFLOW600

L
Dimensions (W x H x D) See dimensional drawings
Weight Depending on device version
Material in contact with media Low temperature carbon steel, stainless steel, duplex steel

M Electrical connection
Voltage 12 ... 28.8 V DC
With active current output: 15 ... 28.8 V DC

N Power consumption ≤ 1 W

O
Measuring ranges
Measuring ranges

P
Flow rate Max. velocity *
m³/h ft³/h m/s ft/s
Nominal size Min. Max. Min Max.

Q DN 50
DN 80
2"
3"
4
8
400
1,000
140
280
14,000
35,000
65
65
213
213

R
DN 100 4" 13 1,600 460 56,000 60 197
DN 150 6" 20 3,000 710 106,000 50 164
DN 200 8" 32 4,500 1,130 159,000 45 148

S DN 250 10" 50 7,000 1,770 247,000 40 131

T 8 F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 8009840/2014-09
Subject to change without notice
Gas flow meters FLOWSIC600

m³/h
Flow rate
ft³/h m/s
Max. velocity *
ft/s
A
B
Nominal size Min. Max. Min Max.
DN 300 12" 65 8,000 2,300 282,000 33 108
DN 350 14" 80 10,000 2,830 353,000 33 108
DN 400
DN 450
16"
18"
120
130
14,000
17,000
4,240
4,600
494,000
600,000
33
33
108
108
C
D
DN 500 20" 200 20,000 7,070 707,000 33 108
DN 550 22" 260 26,000 9,185 919,000 33 108
DN 600 24" 320 32,000 11,300 1,131,000 33 108
DN 650
DN 700
26"
28"
360
400
36,000
40,000
12,700
14,100
1,272,500
1,414,000
32
30
103
98 E
DN 750 30" 400 45,000 14,100 1,590,000 30 98
DN 800
DN 850
32"
34"
400
525
50,000
58,000
14,100
18,550
1,767,000
2,050,000
30
30
98
98
F
DN 900 36" 650 66,000 23,000 2,333,000 30 98
DN 950 38" 650 73,000 23,000 2,580,500 30 98
DN 1000 40" 650 80,000 23,000 2,828,000 30 98
DN 1050
DN 1100
42"
44"
1,300
1,400
85,000
90,000
46,000
49,500
3,004,000
3,181,000
30
28
98
92
H
I
DN 1150 46" 1,500 95,000 53,050 3,358,000 28 91
DN 1200 48" 1,600 100,000 56,600 3,535,000 27 89
* When using installation configuration 2 (with flow conditioner) the maximum allowed gas velocity in the pipe is limited to 40 m/s (131 ft/s).

Ordering information
J
K
Our regional sales organization will help you to select the optimum device configuration.

Dimensional drawings (Dimensions in mm (inch))


Versions with nominal sizes from 3" up to and including 14" (cast)
206 (8.11)
L
M
N
B

O
D

A
C P
Q
R
S
8009840/2014-09
Subject to change without notice
F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 9
T
FLOWSIC600 Gas flow meters

A Versions for nominal sizes from 16" (forged)

C
C
D A

E
Longitudinal section for nominal widths up to 48"

F F*
E
°
10

H
I Dimensions

J Weight Length (A) Height (B)


Flange diame-
ter (C)
Width of mea-
suring section Internal diame-
(D) ter (E)
Nominal Connection

K pipe size
3"
flange
Cl. 150
Standard
ANSI B16.5
[kg]
37
[mm]
240
[mm]
344
[mm]
190
[mm]
180
[mm]
73
Cl. 300 38 354 210

L Cl. 600
Cl. 900
42
84 400
354
395
210
240

M DN 80 PN 16
PN 63
DIN 2633
DIN 2636
37
40
240 349
356
200
215
PN 100 DIN 2637 43 364 230

N 4" Cl. 150


Cl. 300
ANSI B16.5 44
55
300 375
388
230
255
240 95

O
Cl. 600 66 398 275
Cl. 900 99 500 408 290
DN 100 PN 16 DIN 2633 40 300 372 220

P PN 63
PN 100
DIN 2636
DIN 2637
52
61
405
410
250
265
6" Cl. 150 ANSI B16.5 100 450 445 280 300 142

Q Cl. 300
Cl. 600
110
140
465
483
320
355

R DN 150
Cl. 900
PN 16 DIN 2633
220
90
750
450
496
448
380
285
PN 63 DIN 2636 110 478 345

S PN 100 DIN 2637 130 483 355

T 10 F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 8009840/2014-09
Subject to change without notice
Gas flow meters FLOWSIC600

Weight Length (A) Height (B)


Flange diame-
ter (C)
Width of mea-
suring section Internal diame-
(D) ter (E)
A
Nominal Connection
pipe size
8”
flange
Cl. 150
Standard
ANSI B16.5
[kg]
150
[mm]
600
[mm]
498
[mm]
345
[mm]
350
[mm]
190
B
Cl. 300 180 516 380
Cl. 600
Cl. 900
210
300
536
562
420
470
C
DN 200 PN 16
PN 63
DIN 2633
DIN 2636
140
190
498
535
340
415 D
PN 100 DIN 2637 210 543 430
10” Cl. 150
Cl. 300
ANSI B16.5 240
250
750 548
568
405
445
410 235
E
F
Cl. 600 330 600 510
Cl. 900 470 625 545
DN 250 PN 16 DIN 2633 220 547 405
PN 63 DIN 2636 270 580 470
PN 100 DIN 2637 320 597 505
12” Cl. 150 ANSI B16.5 350 900 586 485 470 270
Cl. 300
Cl. 600
400
490
605
625
520
560
H
DN 300
Cl. 900
PN 16 DIN 2633
720
325
685
575
610
460 I
PN 63 DIN 2636 425 610 530

14”
PN 100
Cl. 150
DIN 2637
ANSI B16.5
525
475 1,050
638
642
585
535 540 315
J
K
Cl. 300 600 667 585
Cl. 600 675 677 605
Cl. 900 850 700 640
DN 350 PN 16
PN 63
DIN 2633
DIN 2636
475
625
635
675
520
600
L
M
PN 100 DIN 2637 750 705 655
For all meter ≥ 16" an installation length of 3D is optionally available
16” Cl. 150 ANSI B16.5 475 762 700 595 570 360
Cl. 300
Cl. 600
550
640
728
745
650
685 N
Cl. 900 1,025 800 755 705
DN 400 PN 16
PN 63
DIN 2633
DIN 2636
370
600
762 693
738
580
670
O
P
18” Cl. 150 ANSI B16.5 660 820 754 635 620 405
Cl. 300 760 792 710
Cl. 600 960 820 745

DN 450
Cl. 900
PN 16
1,300 900 830
Data on request
785
Q
R
S
8009840/2014-09
Subject to change without notice
F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 11
T
FLOWSIC600 Gas flow meters

A Weight Length (A) Height (B)


Flange diame-
ter (C)
Width of mea-
suring section Internal diame-
(D) ter (E)
Nominal Connection

B pipe size
20"
flange
Cl. 150
Standard
ANSI B16.5
[kg]
750
[mm]
902
[mm]
815
[mm]
700
[mm]
670
[mm]
450
Cl. 300 930 853 775

C Cl. 600
Cl. 900
1,080
1,500 1,000
872
892
815
855

D DN 500
22"
PN 16
Cl. 150
DIN 2633 700 902 823
Data on request
715

Cl. 300

E Cl. 600
Cl. 900

F
DN 550 PN 16
24" Cl. 150 ANSI B16.5 1,090 991 927 815 760 540
Cl. 300 1,390 978 915
Cl. 600 1,615 990 940
Cl. 900 2,100 1,200 1,040 1,040
DN 600 PN 16 DIN 2633 1,015 991 940 840

H 26" Cl. 150


Cl. 300
ASME B16.47 1,475
1,825
1,050 965
1,016
870
972
828 585

I Cl. 600
Cl. 900
2,100
2,500 1,250
1,038
1,073
1,016
1,086
DN 650 PN16 Data on request

J 28" Cl. 150


Cl. 300
ASME B16.47 1,950
2,225
1,100 1,027
1,080
927
1,035
862 630

K
Cl. 600 2,450 1,100 1,073
Cl. 900 3,000 1,300 1,150 1,169
DN 700 PN16 Data on request

L 30" Cl. 150


Cl. 300
ASME B16.47 2,195
2,545
1,150 1,080
1,135
985
1,092
902 675

M
Cl. 600 2,820 1,154 1,130
Cl. 900 3,350 1,350 1,205 1,232
DN 750 PN16 Data on request

N 32" Cl. 150


Cl. 300
ASME B16.47 2,485
2,835
1,200 1,145
1,190
1,061
1,150
979 720

Cl. 600 3,110 1,212 1,194

O DN 800
Cl. 900
PN 16
3,800 1,400 1,272
Data on request
1,315

P
34" Cl. 150 Data on request
Cl. 300
Cl. 600

Q DN 850
Cl. 900
PN 16

R
36" Cl. 150 ASME B16.47 3,125 1,250 1,250 1,169 1,082 810
Cl. 300 3,525 1,300 1,270
Cl. 600 3,850 1,323 1,315

S Cl. 900 5,225 1,450 1,396 1,461

T 12 F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 8009840/2014-09
Subject to change without notice
Gas flow meters FLOWSIC600

Weight Length (A) Height (B)


Flange diame-
ter (C)
Width of mea-
suring section Internal diame-
(D) ter (E)
A
Nominal Connection
pipe size
DN 900
flange
PN 16
Standard [kg] [mm] [mm]
Data on request
[mm] [mm] [mm]
B
38" Cl. 150 ASME B16.47 3,800 1,300 1,310 1,238 1,160 855
Cl. 300
Cl. 600
3,725
4,300
1,275
1,325
1,169
1,270
C
DN 950
Cl. 900
PN 16
Data on request 1,421
Data on request
1,461
D
40" Cl. 150 ASME B16.47 3,825 1,350 1,359 1,289 1,213 900
Cl. 300
Cl. 600
4,125
4,675
1,334
1,375
1,239
1,321
E
F
Cl. 900 Data on request 1,470 1,512
DN 1000 PN 16 Data on request
42" Cl. 150 ASME B16.47 4,675 1,450 1,415 1,346 1,261 945
Cl. 300 4,650 1,386 1,289
Cl. 600 5,450 1,444 1,404
Cl. 900 Data on request 1,523 1,562
DN 1050
44"
PN 16
Cl. 150
Data on request
Data on request
H
Cl. 300
Cl. 600 I
Cl. 900
DN 1100
46"
PN 16
Cl. 150 Data on request
J
K
Cl. 300
Cl. 600
Cl. 900
DN 1150
48"
PN 16
Cl. 150 ASME B16.47 6,400 1,600 1,574 1,511 1,416 1,080
L
M
Cl. 300 6,475 1,552 1,467
Cl. 600 7,850 1,615 1,594
Cl. 900 12,100 1,900 1,711 1,785
DN 1200 PN 16 Data on request
N
O
P
Q
R
S
8009840/2014-09
Subject to change without notice
F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 13
T
FLOWSIC600 Gas flow meters

A Instruction for installation


FLOWSIC600 integration into the pipeline for unidirectional use in configuration 1 (A) and configuration 2 (B)

B
≥ 3 DN
≥ 10 DN 1.5 ... 5 DN


C

DN
D A 

E
≥ 5 DN ≥ 3 DN
≥ 2 DN ≥ 3 DN 1.5 ... 5 DN


F
B 


H 1 FLOWSIC600
2 Temperature measuring point

I
3 Flow conditioner

FLOWSIC600 integration into the pipeline for bidirectional use in configuration 1 (A) and configuration 2 (B)
≥ 10 DN ≥ 10 DN

J 
5 ... 8 DN 5 ... 8 DN

K
DN

A

L ≥ 2 DN
≥ 5 DN
≥ 3 DN ≥ 3 DN
≥ 5 DN
≥ 2 DN
1 ... 5 DN 1 ... 5 DN

M  

N B




O 1 FLOWSIC600

P
2 Temperature measuring point
3 Flow conditioner

Q
R
S
T 14 F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 8009840/2014-09
Subject to change without notice
SERVICES

WWW.MYSICK.COM – SEARCH ONLINE AND ORDER


Search online quickly and safely – with the SICK “Finders” Efficiency – with the e-commerce tools from SICK

Product
Applications
Literature
Service
Accessories
Software

Product Finder: We can help you to quickly target the product Find out prices and availability: Determine the price and
that best matches your application. possible delivery date of your desired product simply and
quickly at any time.
Applications Finder: Select the application description on
the basis of the challenge posed, industrial sector, or product Request or view a quote: You can have a quote generated
group. online here. Every quote is confirmed to you via e-mail.

Literature Finder: Go directly to the operating instructions, Order online: You can go through the ordering process in just
technical information, and other literature on all aspects of a few steps.
products from SICK.

These and other “Finders” at - www.mysick.com

SERVICES FOR MACHINES AND SYSTEMS: SICK LifeTime Services


Our comprehensive and versatile LifeTime Services are the perfect addition to the comprehensive range of products from
SICK. The services range from product-independent consulting to traditional product services.

Consulting & Design


Safe and professional

Product & System Support


Reliable, fast and on-site

Verification & Optimization


Safe and regularly inspected

Upgrade & Retrofits


Easy, safe, economical

Training & Education


Practical, focused and professional

8009840/2014-09 F L O W S I C 6 0 0 G a s flow m e t e r s | S I C K 15
Subject to change without notice
SICK AT A GLANCE
8009840/2014-09 ∙ 4M_PS ∙ Pre USmod en43

SICK is a leading manufacturer of intelligent sensors and sensor solutions for industrial applications. With
more than 6,500 employees and over 50 subsidiaries and equity investments as well as numerous repre-
sentative offices worldwide, we are always close to our customers. A unique range of products and services
creates the perfect basis for controlling processes securely and efficiently, protecting individuals from
accidents and preventing damage to the environment.

We have extensive experience in various industries and understand their processes and requirements.
With intelligent sensors, we can deliver exactly what our customers need. In application centers in Europe,
Asia and North America, system solutions are tested and optimized in accordance with customer specifica-
tions. All this makes us a reliable supplier and development partner.

Comprehensive services round out our offering: SICK LifeTime Services provide support throughout the
machine life cycle and ensure safety and productivity.

For us, that is “Sensor Intelligence.”

Worldwide presence:
Australia, Austria, Belgium/Luxembourg, Brazil, Czech Republic, Canada, China, Denmark, Finland, France,
Germany, Great Britain, Hungary, India, Israel, Italy, Japan, Mexico, Netherlands, Norway, Poland, Romania,
Russia, Singapore, Slovenia, South Africa, South Korea, Spain, Sweden, Switzerland, Taiwan, Turkey, United
Arab Emirates, USA
Detailed addresses and additional representatives - www.sick.com

SICK AG | Waldkirch | Germany | www.sick.com