LITAFLEX uPVC Conduit Pipes and uPVC Conduit Fittings are produced from a specially formulated
compound, Polyvinyl Chloride. They are manufactured to comply with the British Standard BS EN 50086-2-1:
1996 and BS 4607 Part 5 respectively.

LITAFLEX uPVC Conduit Pipes are widely used for surface installation, and also particularly for wiring system
buried in concrete slab.

uPVC CONDUIT PIPE


British Standard BS EN 50086-2-1:1996
uPVC CONDUIT PIPE

Norminal Size Wall Thickness Packing


Outer Medium Heavy
Product No. Local Export
Dimension Gauge Gauge

CP 20 20mm 1.6 1.8 20 50


CP 25 25mm 1.7 1.9 20 40
CP 32 32mm 2.0 2.2 10 10
CP 40 40mm 2.2 2.5 10 10
CP 50 50mm 2.5 2.8 5 5

CLASSIFICATION : MEDIUM GAUGE CLASS 332112


: HEAVY GAUGE CLASS 442112
STANDARD LENGTH : 2.9 METERS
WALL THICKNESS TOLERANCE : ± 0.1mm
COLOUR : WHITE / BLACK

ADVANTAGE OF LITAFLEX uPVC CONDUIT SYSTEM


Lightweight - uPVC is approximately 1/6 the weight of equivalent galvanized steel

system, making it easier to transport, install and handle.

It is easy to cut and push fit to accessories. No treading and special tools
Time Saving Installation - are required to cut and joint. The conduit cuts easily with a sharp
handsaw or PVC cutter and is securely joined by solvent cement.

Cold bending - Form a 90° angle with just the aid of a bending spring.

Safety - u PVC is a non-conductive material, producing a fully insulated system.

Corrosion resistant - Rigid, non-conducting PVC conduit is immune to almost all types of

corrosive such as chemical, inorganic acids biological, or electrochemical

encountered in either underground or aboveground systems.


Cost effectiveness - uPVC Conduit is less expensive compared to steel. Further savings on
labour cost can also be generated due to a faster installation time.

Physical Properties of LITAFLEX Conduit Material


Unit PVC
Specific Gravity g/ cm3 1.35
Water Absorption - negligible
Module of Elasticity kg/ cm2 30,000
Softening Temperature °C 75-85
Forming Temperature °C 120
Insulating Temperature Megohm 2.8 X 105
Elongation at Tear % 30
CIRCULAR BOX FITTING
SPECIFICATION
BS 4607 Part 5 where applicable
Available in Black and White
M4 Brass Threads

End Box Thru Box (2 Way)

Product No. Size Packing Product No. Size Packing


CPC 201 20mm 100pc CPC 202 20mm 100pc
CPC 251 25mm 100pc CPC 252 25mm 100pc
CPC 321 32mm 100pc CPC 322 32mm 100pc

Angle Box (2 Way) Tee Box (3 Way)

Product No. Size Packing


Product No. Size Packing
CPC 203 20mm 100pc
CPC 20A 20mm 100pc
CPC 253 25mm 100pc
CPC 25A 25mm 100pc
CPC 323 32mm 100pc
CPC 32A 32mm 100pc

Cross Box (4 Way) Extension Ring

Product No. Size Packing Product No. Size Packing


CPC 204 20mm 100pc CPC ERL 25mm 100pc
CPC 254 25mm 100pc CPC ERH 37mm 100pc
CPC 324 32mm 100pc
CIRCULAR BOX FITTING
Circular Lid Bar Saddle

Product No. Size Packing Product No. Size Packing


CPC CL 20/25/32 1000 CPC 20BS 20mm 100pc
CPC 25BS 25mm 100pc
CPC 32BS 32mm 100pc

Socket Female Adaptor

Product No. Size Packing Product No. Size Packing


CPC 20SK 20mm 1000pc CPC 20FA 20mm 1000pc
CPC 25SK 25mm 100pc CPC 25FA 25mm 100pc
CPC 32SK 32mm 100pc CPC 32FA 32mm 100pc

Inspection Bend Inspection Tee

Product No. Size Packing Product No. Size Packing


CPC 20IB 20mm 1000pc CPC 20IT 20mm 1000pc
CPC 25IB 25mm 100pc CPC 25IT 25mm 100pc
CPC 32IB 32mm 100pc CPC 32IT 32mm 100pc
SQUARE JUNCTION BOX

Product No. 40mm Entry Packing


CPS 401 End Box (1 Way) 10
CPS 402 Thru Box (2 Way) 10
CPS 40A Angle Box (2 Way) 10
CPS 403 Tee Box (3 Way) 10
CPS 404 Cross Box (4 Way) 10
CPS 40S Socket 20
AVAILABLE IN BLACK ONLY

Dimension

L W H D C
81 81 55.5 67 67
BOX COMPLETE WITH COVER LID AND SCREW
SWITCH AND SOCKET BOX

Knock Out Box

Product No. Type Depth Packing


CPS K01 1 Gang 38mm 100
CPS K02 2 Gang 38mm 100
AVAILABLE IN BLACK AND WHITE
HAVE 20mm / 25mm KNOCKOUT ON ALL SIDES

Surface And Socket Box

Product No. Type Depth Packing


CPS SM1 1 Gang 28mm 100
CPS SM2 2 Gang 28mm 100
AVAILABLE IN WHITE ONLY
Corrugated Flexible Conduit & Fitting | Dimension | Fitting

LITAFLEX is the first manufacturer to introduce Corrugated Flexible Conduit in Singapore.

The unique design of corrugated construction provides and offers considerable flexibility for laying long runs of cables buried under the concrete without excessive joints.
It is extremely suitable for surface installation, especially running cables from concrete ceiling down to false ceiling, generally for lighting fixtures.

In today’s worldwide advance telecommunication industries, LITAFLEX Corrugated Flexible can be extended with a Pre-installed pulling tape made of Nylon meant for
the drawing of Cables. It is widely used as a Sub-Duct for the protection of Optical-fiber Cable.

PRODUCT FEATURES

Flame Retardant - Self-extinguishing in event of fire


Temperature Resistance - From -5°C to 60°C
Excellent resistance to most acids and chemicals
Compression - Has compression strength
Available in long length, thus reducing the number of connections
Lightweight, flexible and easy to install
Can be simply cut by knife or cutter
Do not kink

Home | About | uPVC Cable Truncking | uPVC Air-Con Truncking | uPVC Drain Pipe & Fitting | Corrugated Flexible Conduit & Fitting
uPVC Conduit Pipe | Circular Box Fitting | Square Junction Box | Switch and Socket Box | uPVC Cable Cover Plate | Contact
Copyright Litaflex 2004 - 2009. All Rights Reserved.
This page is best viewed with 1024 X 800 resolution.

Corrugated Flexible Conduit & Fitting | Dimension | Fitting

CONDUIT
IEC 61386 - 22 : 2002
PVC CORRUGATED CONDUITS

Diameter
Product No. Standard Coil Packing Export
Outer Inner
FC 16 PVC 16mm 11.0mm 50M 5
FC 20 PVC 20mm 14.6mm 50M 5
FC 25 PVC 25mm 19.0mm 50M 5
FC 32 PVC 32mm 24.8mm 25M 5
FC 40 PVC 40mm 32.0mm 25M 3
FC 50 PVC 50mm 41.2mm 25M 3
COLOUR : BLACK, WHITE, GREY, ORANGE

CORRUGATED SUB-DUCT
(Complete with pre-installed Nylon Pulling Cord)
Diameter
Product No. Standard Coil Packing Export
Outer Inner
FC 32SD 32mm 25mm 500M 2
FC 40SD 40mm 32mm 500M 2
TEST SPECIFICATION
British Standard BS EN 50086-2-1 : 1996
Test Specification for Conduit Systems made of insulating material
Properties/Tests Test Methods Passing Criteria

Classification Clause 6 of BS EN 50086-2-1:1996 442112 332112

Classification – Resistance to Clause 6.1.1 of BS EN 50086-2-1:1996 4 - Heavy 3-Medium


compression

Classification – Resistance to impact Clause 6.1.2 of BS EN 50086-2-1:1996 4 - Heavy 3-Medium

Classification – Resistance to bending Clause 6.1.3 of BS EN 50086-2-1:1996 1 - Rigid

According to temperature – Lower Clause 6.2.1 of BS EN 50086-2-1:1996 Transport, permanent


temperature range application & installation
>= -5 °C

According to temperature – Upper Clause 6.2.2 of BS EN 50086-2-1:1996 Transport, permanent


temperature range application & installation <=
60 °C

According to electrical characteristics – Clause 6.3.2 of BS EN 50086-2-1:1996 With electrical insulating


with electrical insulating characteristics characteristics

Marking and Documentation Clause 7.1 of BS EN 50086-2-1:1996 The conduit shall be marked on
the product with:
a) the name of the
manufacturer
b) a product identification mark

Dimensions Clause 8.1 of BS EN 50086-2-1:1996 Threads & outside diameter


shall comply with EN 60423

Construction Clause 9.1 of BS EN 50086-2-1:1996 There shall be no sharp edges,


burrs or surface projections
which are likely to damage
insulated conductors or cables
or inflict injury to the installer or
user

Mechanical Properties – Compression Clause 10.2 of BS EN 50086-2-1:1996 After the test, the specimens
test shall show no cracks visible to
normal or corrected vision
without additional
magnification.

Mechanical Properties – Impact test Clause 10.3 of BS EN 50086-2-1:1996 After the test, at least in 9 of
the samples there shall be no
sign of disintegration, nor shall
there be any crack visible to
normal or corrected vision
without magnification & there
shall be no deformation
impairing its normal use.

Mechanical Properties – Bending test Clause 10.4 of BS EN 50086-2-1:1996 After the test, the samples shall
show no cracks visible to
normal or corrected vision
without magnification & it shall
be possible to pass the
appropriate gauge through the
sample under its own weight
and without any initial speed.

Electrical Properties – Electrical Clause 11.6.1 of BS EN 50086-2-1:1996 The samples shall be


insulating strength and resistance considered to have adequate
(conduits) electrical insulating strength if a
100 mA trip device does not
trip during the 15 min test

Electrical Properties – Electrical Clause 11.6.1 of BS EN 50086-2-1:1996 Insulation resistance > 100 M
insulating strength and resistance ohm
(conduits)

Thermal Properties – Resistance to Clause 12.1 of BS EN 50086-2-1:1996 The sample is not ignited by
flame propagation the test flame

Thermal Properties – Resistance to Clause 12.1 of BS EN 50086-2-1:1996 There is no evidence of


flame propagation burning or charring within
50mm of the lower extremity of
the upper clamp & also within
50 mm of the upper extremity
of the lower clamp

Thermal Properties – Resistance to Clause 12.1 of BS EN 50086-2-1:1996 If the sample burns it shall be
flame propagation deemed to have failed the test
if the combustion is still in
progress 30 s after removal of
the flame

Thermal Properties – Resistance to Clause 12.1 of BS EN 50086-2-1:1996 If the tissue paper ignites the
flame propagation sample shall be deemed to
have failed the test

Thermal Properties – Resistance to Clause 12.2 of BS EN 50086-2-1:1996 It shall be possible to pass the
heat appropriate gauge through the
sample under its own weight
and without any initial speed.

You might also like