Professional Documents
Culture Documents
1993 EPE About Higher Harmonic Currents in DC Grid Caused by 3 Level
1993 EPE About Higher Harmonic Currents in DC Grid Caused by 3 Level
1 University of Bath, UK
2 Universita' degli Studi di Genova, Italy
A railway traction system simulator intended for the study of electrical interference produced by
converter-fed W o n drives is described. The simulationmodel comprises a neutral-pont-clamped inverter
drive, a 3 kV DC 12-pulserectifier substationand a section of traction line. Time and frequency domain
simulation r a ~ l tds c m ~ ~ t rthe
a tinfluence
~ of the system DC cumnt and nonlinear traction line impedance
on the production ofhigher frequency harmonics in the catenary power supply circuit.
Authorized licensed use limited to: Glyndwr University. Downloaded on September 13,2020 at 12:43:40 UTC from IEEE Xplore. Restrictions apply.
25
RECTIFIER SUBSTATION
1- 3 k V D C . .p
Rated primary voltage 150 kV
Rated secondmy voltage 2.71 kV
Rated AC side power 5.75 M W
Rated DC side power 5.4 M w
Figurr 2: Neutral point clamped inverter strucI~re Ratcdm-hdDc voltage 3.65 kV
Transformer d c voltage 11%
Rtsdanocratio: 0.13
intermediate capacitors, the capacitor divider will become unbalanced
in the absence of a special control strategy. One possible
arrangement is to modulate the switches to obtain zero average
capacitor current. This exploits the fact that the correct
phase-to-phase inverter voltages may be synthesised by several The ESS model WO developed from a dynamic representation
different switch configurations, 80 the optimum configuration will intended for short circuit transient analysis of DC traction systems
maintain the appropriate voltage divider balance. An alternative 181. For the present simulation, a linear network model was
strategy is to incorporate a discharging resistor, controlled by a sufliaent, as the most important feature required was the overlap
fuaher switch, in parallel with each capacitor. behaviour on cumnt commutation. The rectifier diodes were
modelled as perfeet switches and all phases were assumed to be in
The NPC inverter shown in Figure 2 has been modelled using the balance.
circuit simulation program EMTP [I]. The simulation objective was
to study the effect of source cumnt harmonics, so it was sufficient to Figure 4 shows the time and frequency domain waveforms for a
represent the induction motor by a fimt-order load with time constant mean substation DC output level of 415 A. A resistive load W M
e& to that of the machine. Figure 3 shows typical rcsults for the applied in order to produce the worst-case DC-side harmonic
source " n t in the time and frequency domains. with the invelter performance. The IZ-pulscwaveform shows the expected 600 Hz
operatingat a modulation frequency of 50 Hz and a carrier fresuenfy fuadamenlal with the full m n p of harmonica It should be noted that
of 750 Hz,and supplied by M ideal voltage source delivering 4 I5 A. the amplitude of each of these harmonics is in most c a m greater than
Even though the harmonics me attenuated by the NPC inverter filter the NPC inverter harmonics at the same frequencies as shown in
of 6 mH and 10 mF, the spectrum clearly demonstrates the enhanced Figure 3.
performance of the NPC invettcr comparedwith a conventionalVSI.
lml
... ..
-t i
Figure 3: Supply c u m " and harmonic spcclrwn of NPC F w r e 4: Supply currcnt and harmonic specmm of
inverter fed from idcal voltage sourcc rectifier substation with ideal resistive load
Authorized licensed use limited to: Glyndwr University. Downloaded on September 13,2020 at 12:43:40 UTC from IEEE Xplore. Restrictions apply.
26
RAIL TRACK MODEL frequency range of interest is significant, with the line mistance
increasing by a factor of seven and the inductance decreasing by a
quarter over the frequency range 30 Hz to 6 kHz. The line time
A railway traction line may be modelled as a number of mutually constant thus reduces from 10 ms at 50 Hz to 1 ms at 6 kHz.
coupled parallel conductors. The lines correspond to each running
rail, power cables such ascatenary, auxiliary feeders & earth wires,
and parallel signalling & communications wires. A model for a SYSTEM SIMULATION
single catenary electrified ttackwith no additional feeders is shown in
Figure 5a Deriving the impedancesand admittances for an e-
multi-wire line is difiicult because of the proximity of the conducting The simulationobjectives were to study the production of harmonics
earth and the frequency and current depmdency of the equivalent along the traction line. The NPC inverter, ESS rectifier and traaion
distributed line components. Methods for defining the line phase line models were implemented using the package EMTP. Line
impedance and admittance matrices may be found in reference 191. lengths of 1 , 2 , 5 and 10 km were eonsidered, with the NPC invnter
The resulting coupled line model may be utilised either in terms of operating with constant modulation. The DC supply current,
phaw vatiables for time domain simulation [IO] or as modal variables dependingon the ESS rectifier load, varied between 300 and 700 A.
for frequency domain simulation.
Although the complete coupled line model is necessary for a Harmonic amplitudes at ESS rectifier and NPC inverter
thorough study of interference mupling between electric traction terminals
power and signalling systems, a simplified modcl is suficient for the
present study of the factors affecting harmonic generation. A
two-wire transmission line representing the catenary system with Figure 6 shows a simulation record of the DC supply current along a
curent return through the parallel mbination of the running rails 10 km track section, calculated at the ESS rectifier and NPC inverter
shown in Figure 5b has thus been modelled. The equivalent loop terminals. The traction line impedance is linear and is equal to the 50
feeding impedance may be calculatedknowingthe self impedances of Hz values in Figure 5c. Although the differences in the time domain
the catenary and each running rail and the earth-return mutual traces appear insignificant, the frequency spectrum docs show
impedance between the catenary and each tunning rail. The feeding variationsin harmonic amplitude between the two locations at higher
inductance and resistance have been evaluated using models from frequencies, with a larger amplitude at the NPC inverter terminal.
reference [ 9 ] and are shown in Figure 5c. The feeding admittance These higher frequency harmonics contain contributions from both
hasaconstant capacitanceof 11.4nFhandzero~~d~~tanee1111. the ESS rectifier and the NPC invertcr. The greater amplitude of the
higher frcqucncy harmonics at the NPC inverter terminals may be the
If transmission line effects are insignificant, any length of tfaction result of a local traction line monant d i t i o n [SI.
line may be simulated by a single T-section model based on the per
unit length equivalent circuit of Figure 5b. The worst CBM is at the
highest frequency of interest (6 kHz), where the wavelength was Effect of track length on harmonic amplitudes
evaluated at 42.1 km. The average substation separation distance on
a 3 kV DC line for doublcend feeding on FS is 20 km,so simulation
of the full single-end feeding length of 10 km was indeed acccptable Simulations were performed with the track length equal to 1,2,5 and
with a single T-section equivalent circuit. 10 km. The frequency spectra, shown in F w r e 7 using reference
(50 Hz) traction line impedance data, indicates there is more
Figure 5c shows that the variation of line impedance over the attenuation for longer f e c d i i distances. As shown later, this is due
to the reduced system load owing to the increased traction line
impedance and the change in ESS rectifier load time eonstant due to
the relative imporlance of the traction line and NPC inverter loads.
-
554
I
2-WIRE MODEL
0.005 0.01 0.015 0.02
Time [I]
-VSI Dc current, .-FSS Dc current
1 II- /
Frequency [Hz]
Authorized licensed use limited to: Glyndwr University. Downloaded on September 13,2020 at 12:43:40 UTC from IEEE Xplore. Restrictions apply.
27
Figure 7: Simulated harmonic spcctra at NPC inveacr terminals for track lengths of 1 , 2 , 5 and IO Ian
Effect o f DC current on harmonic amplitudes increasing frcqucncy, the amplitude of high order harmonics will also
inaease.
Fwre 8 shows simulation results made to BYKSS the effect of the DC The curvc8 at 50 Hz and 300 Hz reflect the influence of the NPC
current on the harmonic amplitudes. Results for selected harmonics inverter harmonics. With a large load current, the magnitude of the
arc shown on a 2 km track section, again using reference (50 Hz) NF’C inverter filter capacitor chargddischarge cycle voltage
traction line impcdanoc data. excursions will increase. The harmonic amplitudes will thus also
increase, which will make them more sensitive to DC current
The 600 Hz and 3kHz harmonic amplitudes are insensitive to magnibldevariation compared with variatiws in the h&er frequency
changes in DC current magnitude. These particular harmonics ESS-generated harmonics.
originate mainly from the ESS rectifier. This indicates that the
harmonic amplitude variations shown in Figure 7 at thosc frequencies
arc determined largely by the nature of the traction line impedance, Effect of nonlinear traction line impedance
rather than hy the magnitude of the converter I d DC current. This
is consistent with the fact that a rectifier substation produces higher
peak-to-peak oscillations and hence higher harmonic amplitudes The results in Figure 8 were obtained using reference (50 Hz)
when the time constant of its equivalent load is raised. This occurs tlaaion line impedance data The practical impedancedata of Figure
when the load current has low ripple, which is INC at high frequency 5c shows that the traction line time constant decreases from about 10
due to the incrcaud reactance. In the prexnt situation, the rectifier ms at low frequencics to I ms at high frequencies. If the DC am”
load is the combination of the traction line impedance and NPC is maintained constant, simulations using the frequency-dependent
inverter input impedance and as the total reactance rises with traction line impedance data should produce higher harmonic
amplitudes than those with the reference tradionline impedance data.
The differences in harmonic amplitude between the two sets of
impedance data would thus be due only to the derreasc in the traction
10‘ , lie time c0-t with inerrase of frequency.
600 Hz To test this hypothesis, successive simulations were performed with
9 the traction line impedance set at the high frequency values. The
track length wan limited to I km to restrict the variation in DC current
to less than about 10%.
The results are presented in Table 2. It is confirmed that the
harmonics obtained with frequency-dependent traction line
impedance data are generally greater in magnitude than thoseobrained
with the reference data. Care, however, must be taken in comparing
the two sets of simulation results, since the circuit simulation model
does not allow the DC current to circulate independently of the
harmonics. Because the production of harmonics is linked to a
VSI DC current [A] number of interrelated factors such an the value of the DC current, it
is dimcult to pmvide a cpntitative comparison between the harmonic
amplitudes. However, it does appear that the tractaion line time
Figure 8: Effect of cmvettm DC load NtEllt constant is an important additional factor in determining the harmonic
on selected NPC inVMer harmonics:
amplitudes in the system.
Authorized licensed use limited to: Glyndwr University. Downloaded on September 13,2020 at 12:43:40 UTC from IEEE Xplore. Restrictions apply.
28
Authorized licensed use limited to: Glyndwr University. Downloaded on September 13,2020 at 12:43:40 UTC from IEEE Xplore. Restrictions apply.