You are on page 1of 4

VAJRA 322P

PORTABLE MONITOR

TECHNICAL DATA :
MODEL VAJRA – 322P

SIZE 3 INCH (75mm)

MAXIMUM SERVICE 12 Bar (175 PSI)


PRESSURE in deck mode.
7 Kg/Sqcm.(100 PSI) in
portable mode.

FLOW Up to 3000 LPM in


Portable mode and 4500
LPM in Deck fixed mode

MATERIAL OF Hard anodized aluminium.


CONSTRUCTION Support legs with carbide
tips

FACTORY HYDRO TEST 25kg/cm.sq.(355 PSI)


PRESSURE

NOZZLE THRUST Flow in LPM X Pressure


REACTION IN KG. in Kg./cm. sq. x 0.0228

INLET CONNECTION - Flanged 80 NB for deck


mode VAJRA – 322P is a durable Manual Control Portable
- Two nos 63 NB instanious or Deck Mounted Water/ Water Foam Monitor. The
male coupling with NRV monitors have rugged construction with the corrosion
connection for portable resistant Aluminium material. It possesses several
mode. design features for easy operation, minimum
maintenance and resistant to the corrosive
MONITOR OUTLET SIZE 3” BSP (M)
environment. It has high flow capability up to 3000
MONITOR MOVEMENT Manual Gear operated,
LPM (800 GPM) when used as a Portable Monitor and
hand wheel driven for 4500 LPM (1200 GPM) when used as Deck type
vertical movement. Handle Monitor or in a fixed installation.
operated with manual lock
for horizontal movement. The horizontal and vertical rotation is through swiveling
joint, with double rows of stainless steel ball bearings.
SWIVEL JOINT Stainless Steel Ball Bearing The hand wheel is for easy vertical rotation control
type through worm wheel and worm shaft. The horizontal
movement is through handle and with manual lock.
WORM SHAFT Stainless Steel 304
When used as a Portable Monitor, the safety lock is to
WORM WHEEL Hard anodized aluminium
be used for maximum vertical elevation operation at
35º.
MONITOR ROTATION 360º continuous in deck
mode.Portable mode - 150º The Monitor has the provision to mount various nozzles
such as straight stream nozzle, aspirating and non-
MONITOR ELEVATION 90º above horizontal aspirating jet and fog nozzles, foam barrel and self
65º below horizontal for inducting foam nozzle.
Deck mode.
90º to 35º above horizontal The internally cast water vanes reduces the turbulence
in portable mode Use safety and the friction loss, thus increasing the nozzle
lock for elevation when used as performance. The design ensures to prevent jet
Portable mode. reaction force from affecting the horizontal and vertical
position of the monitor.
WEIGHT 24.5 Kg
To ensure desired performance, the friction loss
FINISH Red Polyurethane
through Monitor must be considered while selecting
ORDERING INFORMATION Please specify Monitor Model, the nozzle and the flow through the monitor, with
Flange connection, Nozzle reference to available base pressure at the inlet of
model & flow rate. the monitor.

NOVEMBER, 2007 PAGE 1 OF 4 HD170


THE MONITOR CAN BE USED AS WATER OR WATER- WARNING: A trained personnel for fire fighting must
FOAM MONITOR DEPENDING ON THE NOZZOLE. FOR use the monitor. Appropriate guidance and training
SELECTION OF FLOW, JET REACH, AND FOR must be given to reduce the risk of enjury.
APPLICATION AS WATER OR WATER FOAM REFER
MONITOR NOZZLE DATA SHEET. WARNING: READ OPERATING INSTRUCTIONS BEFORE
USE AND FOLLOW THE INSTRUCTIONS.
INSTALLATION,TESTING & MAINTENANCE
The monitor must be installed and operated carefully WARNING:Monitor in portable mode must be anchored
by a trained person. properly to prevent unwanted sliding along the ground

After few initial successful test, an authorized person WARNING:Low nozzle elevation angle can cause por-
must be trained to perform the inspection and testing table monitor to slide or lift off the ground, which may
of the monitor. result in injury or death.DO NOT OPERATE THE MONI-
TOR ON THE PORTABLE BASE BELOW THE ELEVATED
The monitor should be always ready for use. To achieve
SAFETY STOP..
this condition, scheduled inspection and maintenance
operation should be performed and recorded in the
WARNING:The monitor when used on the portable
maintenance register book indicating the requirement
base, the nozzle stream must be kept as close to inline
or recommendation. The recommended maintenance
with the anchor strop to maintain the reaction force
procedure must be followed as given in the manual
of the nozzle on the strop. It is possible to slide the
and also as per the local authority having jurisdiction.
Monitor in an arc around the anchor point, but greater
It is recommended to carry out weekly physical the horizontal angle between the strap & the nozzle
inspection of the monitor. The inspection should verify stream, the greater the danger of sliding. ‘Keep the
that no damage has taken place to any component rotation lock locked, when not rotating the Monitor.
and the monitor is ready for use.
WARNING:Incorrect hose layout may cause instabil-
Carry out functional test every month for the flow, ity. Use two hoses and bring both hoses straight back
regular rotation in horizontal and vertical plane for paralleled to each other. Loosely tie the hoses to-
the entire operating angle to observe any leakage. gether 3 meters from the monitor with a hose and
ladder strap, rope etc. as shown in figure 1.
At least once in three months proper greasing through
grease nipple provided on bearing, worm wheel and WARNING:When unit is operating in the portable mode,
worm shaft must be ensured. Each monitor must be do not attempt to move or pick up any part of the
operated with the full flow in accordance to the base or supply hoses.
guidelines of the organisation having local jurisdiction.

The owner is responsible for maintaining the equipment


in proper operating condition.

CAUTION:
A trained personnel for fire fighting must use the
monitor. Appropriate guidance and training must be
given to reduce the risk of injure. The nozzle must be
fixed to the monitor carefully, mismatched or damaged
threads may cause leakage or uncouple the nozzle
during operation.

Do not operate the Portable Monitor below the


elevation level safety lock. Monitor must be anchored
properly to prevent sliding. Operation of Portable
Monitor at a low nozzle elevation or below the safety
lock may cause slide or seriously injury the operator.

Read and follow the warning tag instructions on the


Monitor.

The water supply valve must be opened and closed


slowly. Quick operation of the same may damage the
Monitor and result in injury.

Application of water or foam on an electric appliance


can cause injury by way of electrocution, as water is a
conductor of electricity.

NOVEMBER, 2007 PAGE 2 OF 4 HD170


4 5 3 10 11

6 2
7
13 1

ELEVATION 8 12 9
SIDE VIEW

PART LIST
ITEM NO. DESCRIPTION MATERIAL SPECIFICATION
1 BASE ALUMINIUM *
2 SWIVEL JOINT ALUMINIUM *
3 ELBOW ALUMINIUM *
4 NOZZLE ELBOW ALUMINIUM*
5 WORM SHAFT STAINLESS STEEL
6 HAND WHEEL ALUMINIUM *
7 KNOB BAKELITE
8 COUPLING BRASS
9 LEGS ALUMINIUM *
10 PRESSURE GAUGE 0-16 KG/SQ CM
11 HANDLE GRIP RUBBER
12 SPIKES CARBIDE TIPS
13 LOCK PIN STAINLESS STEEL/BRASS

* Heat treated to T6 condition and hard anodized

NOVEMBER, 2007 PAGE 3 OF 4 HD170


LIMITED WARRANTY
Products manufactured by HD FIRE PROTECT PVT.LTD.. are warranted against defects in material and workmanship for a period of Two (2) years from the date of
shipment.
HD's obligation under this warranty is limited to replace or repair the products or its parts, which are shown to HD's examination to be in a defective condition
attributable to HD. No warranty is given for products or components which have been subject, to misuse, improper installation, corrosion, wear and tear,
improper storage, modification or repaired. If the defect attributable to HD cannot be rectified by repair or replacement, then HD may elect to refund the
purchase price of the equipment in complete discharge of its obligation under this Limited Warranty.
IN NO EVENT SHALL HD FIRE PROTECT PVT. LTD. BE LIABLE IN CONTRACT, STRICT LIABILITY OR ANY OTHER LEGAL THEORY, FOR INCIDENTAL, IN-DIRECT, SPECIAL OR
CONSEQUENTIAL DAMAGES, INCLUDING DAMAGES. FOR INJURY TO PERSON OR DEATH OR DAMAGE TO PROPERTY AND OR PENALTIES RESULTING FROM ANY
PRODUCTS OR COMPONENT MANUFACTURED OR ASSEMBLED BY HD. THIS IS LIMITED WARRANTY ONLY. HD DISCLAIMS WITH RESPECT TO THE PRODUCTS ALL IMPLIED
WARRANTIES OF MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE. THERE IS NO WARRANTY OF ANY NATURE MADE BY
HD BEYOND AS STATED ABOVE.
NOTICE :
The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also
with the provision of government codes or ordinances wherever applicable.
The information provided by us are to the best of our knowledge and belief, and are general guidelines only. Site handling and installation control is beyond our
reach. Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information,
recommendation or damages due to our product.
Product development is a continuous programme of HD FIRE PROTECT PVT. LTD. and hence the right to modify any specification without prior notice is reserved
with the company.

C-3/6, THE NANDANVAN IND. ESTATE, L.B.S. MARG, THANE 400 604., INDIA.
PHONES : +(91) 22 2583 5434 2582 6958 2582 6793
FAX : +(91) 22 2581 2524 6796 9049
EMAIL : info@hdfire.com WEBSITE : www.hdfire.com

NOVEMBER, 2007 PAGE 4 OF 4 HD170