POWER PLANT OPERATION

BOILER & AUXILIARIES

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 1


Presentation outline
OPERATING PROCEDURE
APH
ID, FD AND PA FAN

FURNACE PURGE

BOILER LIGHT UP
MILLING SYSTEM

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 2


Before starting any equipment…..

 ENSURE

 No PTW is pending on the equipment which is to be


normalized .

 Equipment is properly boxed up and no maintenance staff


working.

 Local operator is informed before the equipment is started.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 3


Pre start checks before light up

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 4


Before Light up……
Equipment cooling water is charged in boiler side and proper
venting is done.

Service water /filter water for sealing in the boiler bottom is


charged .Get the clearance from AHP for sealing of bottom
hopper.

Service and instrument air is charged and air for SADC and
burner tilt are charged .

Fire water/ sprinkler water is available in boiler area.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 5


Before Light up……
 DM water is available .

 Ensure the availability of aux. steam .

 Ensure 6.6 kv, 415 volt , 220 volt DC,110 V AC, 24 V DC SUPPLIES
are normal . Ensure that all MCC s are charged. Both buses are
charged independently and Bus coupler is in OFF position
.ensure all chargers are in charged condition and all the batteries
are in healthy condition .

 All unit protections/interlocks ( boiler ,turbine & generator ) are


checked and recorded in the protection register .

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 6


Before Light up……
Start LDO PUMP or charge LDO line upto firing floor if other
units are running.

Start HFO pump or charge charge HFO line upto firing floor on
long recirculation if other unit is running. also inform other units .

 charge atomising air and atomising steam lines.

Keep boiler drum vents,SH vents , SH drains ,CRH drains, HRH


drains open.

Ensure all low point drains are closed .

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 7


Before Light up……
 Inform shift chemist to take water sample before water filling in
the boiler and take clearance from shift chemist. Inform him to
prepare hydrazine , ammonia and phosphate solution for
dosing . Check availability of all LP and HP dozing pumps .

 Fill water in the boiler upto normal level by running one BFP .

 Ensure at least two ESP passes are clear and their inlet / outlet
gates are open. Elect. Supply of fields are kept off .

 Inspect the boiler up to drum floor . Ensure that all manholes


/peepholes are closed.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 8


Before Light up……

 Ensure start up vent and ECO recirculation valve are open.

 Charge the SCAPH LINE .

 Keep the burner tilt at 0 deg ( horizontal )

 Ensure boiler and auxiliaries areas are clean , safe and


properly illuminated .

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 9


FLUE GAS & AIR PATH
PA-A FD-A
MILL

A
ECO I/L 493ºC CHIMNEY

134ºC

129ºC
351ºC
B ESP
PASS A
APH PA
1165ºC

126ºC
ESP O/L X – OVER DUCT
WIND BOX 136ºC
SA FG
SA –X-OVER DUCT

ESP
C ID-A

ESP I/L X – OVER DUCT


PASS B

SCAPH
FURNACE
SCAPH
ESP
324ºC D PASS C
ID-B
WIND BOX SA FG
APH
PA ESP
PASS D
E
320ºC

F COLD SA
HOT SA
27ºC COLD PA
HOT PA
PA-B FD-B FLUE GAS

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 10


AIR PRE-HEATER OPERATION
PRE START CHECKS

• Support bearing/ guide bearing lub oil pumps RUNNING and lub
oil coolers are CHARGED.
• Bearing temperature NOT HIGH (less than 60oC)
• Electrical supply to APH motor is AVAILABLE.
• Local operation - Isolating valves of air motors are 'OPEN' and
bypass valves of air motor solenoids are 'CLOSED'.
• 'Air motors' lub oil level ADEQUATE
• Service air pressure is ADEQUATE (> 5 Kg/cm2)

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 11


AIR PRE-HEATER OPERATION
APH STARTING PROCEDURE

• WHEN BOTH APHS ARE OFF


• START air motor of APH.
• Air motors ON indications come on
• Isolating dampers of APHs start opening.
• INSTRUCT local operator to check, locally for any abnormal
sounds from bearings/seals.
• START air heater electrical motor.
• Breaker CLOSED & its indication comes on UCB
• Associated air motor stops.
• Starting current shoots up and comes down to normal load
current.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 12


AIR PRE-HEATER OPERATION
•Isolating dampers of the air heater remain open.
•Isolating dampers of the other air heater, not in service, start
closing if its air motor is not ON.
•INSTRUCT local operator to check, locally for any abnormal
sounds from bearings/seals.
•There should be no abnormal hunting in air heater amperes
meter readings.
•There should be no abnormal sounds from air pre-heater seals or
bearings.
•Bearing temperatures must be within the normal range (65 0C -75
0
C)

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 13


AIR PRE-HEATER OPERATION
• SHUT DOWN PROCEDURE
• CHECK Corresponding ID & FD Fans are running.
• UNLOAD associated ID/FD fans, gradually.
• The other pair of ID/FD fans (if running) starts loading up on auto.
• STOP the associated FD fan. Maintain desired oxygen percentage.
• Furnace total airflow indication drops slightly. Reduce firing if
required.
• STOP the associated ID fan.
• Furnace pressure increases slightly. Maintain furnace draft
between -5 to - 10 mm wcl.
• STOP air heater electrical motor.
• With a few seconds time delay, the isolating dampers of the air
heater are closed, if the other AIR HEATER is in service.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 14


FURNACE

CHIMNEY
MILLS
SECONDRY AIR HEATER

PRIMERY AIR HEATER

FD FAN A FD FAN B

ID FAN A Atmospheric air

ESP PA FAN A PA FAN B

ID FAN B Atmospheric air

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 15


ID FAN OPERATION

PRE START CHECKS

WHEN BOTH THE FANS ARE OFF

• Fan lub oil pressure is ADEQUATE (1.2 Kg/cm2).


• Fan bearing temperature is NOT HIGH (< 60 0C .)
• All permissive for the fan AVAILABLE. ''Inlet guide vanes min.'' &
Inlet/outlet dampers closed''
• Local operator is informed before the fan is started.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 16


ID FAN OPERATION

START fan.

• Inlet/outlet dampers start closing. Inlet vanes come to minimum.


• The fan breaker is CLOSED after inlet/outlet dampers close fully.
• Inlet/outlet dampers open up after a time delay.
• Inlet/outlet dampers of the other fan closes and regulating vanes
comes to minimum position.
• ADJUST inlet guide vanes to maintain furnace draught between - 5 mm. to -10
mm.
• INSTRUCT the local operator to check for abnormal bearing vibration and
temperature.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 17


ID FAN OPERATION
• WHEN ONE FAN IS RUNNING
• All pre-start checks are OVER.
• START fan motor
• Fan motor current settles down at no load current.
• Inlet/outlet dampers start opening.
• Maintain furnace draft -5 to - 10 mm wcl.
• Maintain desired airflow.
• ADJUST bias to 50% and furnace draught set point to 45%.
• Check furnace draught is maintained between 5 mm wcl to-10
mm wcl.
• TRANSFER vane controllers of both fans to ''AUTO''.
• Inlet vanes modulate to maintain set value of furnace draught.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 18


ID FAN OPERATION
• SHUT DOWN PROCEDURE
• Reduce the coal firing and air flow so as to sustain with one ID fan.
• SELECT IGV controls of fan to manual.
• IGVs control transfers to manual.
• REGULATE IGVs of the ID Fan to minimum.
• ID fan discharge pressure decreases.
• ID fan current come to minimum, other fan loading increases.
• STOP the ID fan.
• Total airflow drops slightly avoid Boiler trip.
• The inlet and outlet dampers close on interlock.
• REGULATE the inlet guide vanes of the running ID fan to desired loading.
• Maintain furnace draught at -5 mm wcl.
• Note : If associated FD fan is in service it will be necessary to unload FD fan
and stop it before stopping ID fan;

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 19


FD FAN OPERATION
• CHECK before starting the FD fan, all start permissive is satisfied.
• Fan control oil temp is NORMAL (<55 oC)
• Fan blade pitch is MINIMUM and Discharge damper is CLOSED
• Fan control / lub oil pressure is ADEQUATE.
• Fan bearing temperature is NOT HIGH (<60 0C.)
• CHECK if FD fan is lined up locally for starting.
• Fan lub oil system is LINED UP and oil coolers are charged.
• Lub oil tank level is ADEQUATE.
• Anyone LOP is ON and other one is on AUTO.
• Fan EPBs are in RELEASED position.
• FD fan blade pitch controller is OPERATIONAL and is REMOTE.
• Instrument air pressure is AVAILABLE.
• Any or both ID fans: APHs' secondary air isolating dampers are OPEN.
• SCAPH is available
• FD fan discharge dampers are OPERATIONAL and electrical supplies are
AVAILABLE.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 20


FD FAN OPERATION
• STARTING PROCEDURE.
• WHEN BOTH THE FANS ARE OFF
• All pre-start checks are OVER.
• START the FD fan motor.
• Discharge dampers start closing
• Blade pitch comes to minimum.
• As soon as discharge damper closes, "Blade pitch minimum“
permissive comes on.
• Fan takes starting current and comes down to no load current
after a while.
• Discharge damper starts opening (for the fan started).
• FD fan discharge pressure increases.
• Blade pitch for the other fan goes to minimum.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 21


FD FAN OPERATION
• Discharge damper for the other fan closes.
• Instruct local operator to check bearing vibration and
temperature.
• ADJUST the blade pitch controller to get desired airflow.
• Fan discharge pressure increases.
• Maintain furnace draught between-5 to 10 mm wcl and airflow
30%-40% during purging.
• Fan amperage changes accordingly.
• Oxygen percentage varies accordingly.
• Wind box pressure also varies, with FD fan loading.
• MAINTAIN the Wind box to furnace DP as per boiler loading.
• Wind box to furnace DP should be maintained as shown:
• Boiler load<30% 30 to 40 mm of wcl
• Boiler load>30% 100 mm of wcl

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 22


FD FAN OPERATION
• WHEN ONE FAN IS RUNNING
• All pre-start checks are OVER.
• Both ID fans are in SERVICE.
• START the FD fan
• Discharge damper of the fan starts opening
• Furnace pressure and total airflow increases slightly.
• ADJUST the blade pitch to maintain desired airflow and wind box
pressure.
• Fan discharge pressure increases
• Fan amperage increases accordingly
• Furnace pressure increases slightly
• CHECK vibration and bearing temperatures.
• TRANSFER FD fans blade pitch control to AUTO.
• FD fan blades modulate maintain set oxygen percentage.
• Oxygen in flue gas varies accordingly
Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 23
FURNACE PURGE PROCEDURE
• Start APHs and at least one ID and one FD fan. Maintain furnace
draft between -5 to -10 mm of WCL and maintain air flow
between 30 % to 40 % of boiler full load air flow.
• CHECK ALL THE PURGE PERMISSIVE IS satisfied on the FSSS
console.
• "No boiler trip" command is AVAILABLE.
• Drum lvl not high ( > 125 mm)
• Drum lvl not low ( < - 125 mm)
• All ignitor valves are CLOSED.
• All HFO nozzle valves are CLOSED.
• HFO and ignitor trip valves are CLOSED.
• All pulverisers and associated raw coal feeders are OFF.
• All mill hot air gates are CLOSED
• Both PA fans are OFF.
Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 24
FURNACE PURGE PROCEDURE
• All fire ball and oil discriminating flame scanners must be sensing
NO FLAME.
• AC/DC electrical power supplies to FSSS panels are AVAILABLE.
• All auxiliary air dampers of the wind box are MODULATING&
furnace to wind box DP > 40 mm wcl.
• Oil elevation dampers also modulate with aux. air dampers when
no oil gun is in service
• Boiler airflow less than 30% annunciation goes off.
• Boiler airflow and wind box pressure are maintained at less than
40% and 40 mm wcl, respectively.
• All burners at all elevations and in all corners, come to horizontal
position "Burner tilts horizontal and Airflow less than 40%“
permissive comes ON.
• If all other permissive are satisfied, "Purge Ready” indication
comes ON.
Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 25
FURNACE PURGE PROCEDURE
• PRESS "push to purge" button on the FSSS
console
• "Purging" indication comes on the FSSS console.
• If in the meanwhile none of the permissive are
lost, "Purge complete" indication comes on FSSS
console, with a time delay of 5 minutes.
• MFR-A & MFR-B get reset. Boiler Trip "cause"
also resets.
• "Boiler MFR Trip" annunciation clears off.
Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 26
Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 27
BOILER LIGHT-UP
• CHECK these conditions before the boiler light up
• Boiler "MFR TRIP" is RESET.
• Pre-start checks for boiler light up have been COMPLETED.
• Fuel oil system is adequately LINED-UP.
• Super heater / Reheater air vents are OPEN.
• SH/RH start-up vents are OPEN.
• Ignition air fans are LINEDUP for operation.
• Open heavy fuel oil recirculation valve
• OPEN heavy fuel oil trip valve
• Short re-circulation valve closes.
• OPEN heavy fuel oil control valve.
• HFO header pressure rises up to 10 Kg/cm2 (approx.)

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 28


BOILER LIGHT-UP
• "HFO" inlet and re-circulation flow start increasing
• "HFO header pressure very low" alarms clear off.
• HFO temperature in the HFO header increases up to 110 oC.
• OPEN Ignitor oil trip valve
• Ignitor oil trip valve opens up.
• Ignitor air fans A & B, start automatically.
• Ignitor oil and ignitor air pressure increase up to 23 Kg/cm2 and
400 mm wcl, respectively.
• "Ignitor air to furnace DP low“ & "Ignitor oil/Atomising air
pressure low" & "Ignitor oil/HFO trip valve closed" alarms clear off.
• CHECK these parameters are within their operation limits.
• Drum level normal (-60 mm. to 0, preferably on lower side).

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 29


BOILER LIGHT-UP
• HFO temp. 110 oC . (Min. temp. required is 95 oC).
• HFO atomising steam pressure 8.75 Kg/cm2
• Light oil pressure more than 15 Kg/cm2.
• Ignitor atomising air pressure 5 to 7 Kg/cm2
• Wind box pressure between 35 to 40 mm wcl
• ADJUST HFO header pressure set point to 50%(13 Kg/cm2) and
TRANSFER its control to auto.
• HFO pressure controller transfers to auto and modulates to
maintain the set HFO header pressure.
• CLOSE heavy fuel oil re-circulation valve.
• HFO re-circulation flow valve closes.
• HFO re-circulation flow comes to minimum position

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 30


BOILER LIGHT-UP
• HFO header pressure goes up and is brought down to set HFO
pressure by auto controller.
• PUSH " Pair 1-3 or 2-4 Start" push button.
• In the first 10 secs of the pair start trial time; ignitors 1-3 and 2-4
are proven, in the associated oil elevation.
• "Ignitor Stop" light goes off in the associated elevation.
• If minimum 3 ignitors are proven on, command goes to corner 1
or 2, for the gun to advance to the firing position, provided
associated ignitor is on
• Command is given to open the associated atomising steam valve
after the gun is fully advanced.
• After the atomising steam valve is fully open, command is given
to open the corresponding HFO corner nozzle valve.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 31


BOILER LIGHT-UP
• 25 second later command goes to corner 3 or 4, as the case may
be, HFO nozzle valve open.
• Associated discriminating oil flame scanners start sensing flame.
• HFO control valve modulates to maintain set HFO header
pressure.
• ADJUST heavy oil pressure controller to desired firing
• HFO header pressure changes accordingly
• Oil scanner performance improves with increasing header
pressure.
• PUSH second pair.
• "Start"(Pair 1-3/2-4) push button.
• HFO guns advance and corresponding nozzle valves open up.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 32


BOILER LIGHT-UP
• PUSH "Ignitor Stop" push button to remove ignitors if the oil
flame is stable in every corner in the elevation
• All the elevation ignitors go off.
• If any discriminating scanner flickers to show 'no flame',
corresponding oil nozzle valve is closed automatically.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 33


PA FAN OPERATION
• CHECK that all PA fans start permissive is satisfied.
• PA fan bearing temp NOT HIGH (<60oC.).
• PA lub oil pressure is ADEQUATE.
• PA fan inlet guide vanes are at MINIMUM position.
• PA fan FSSS start command is AVAILABLE (BOILER MFR: RESET &
all mill cold air dampers are less than 5% OPEN).
• PA fan discharge damper is CLOSED.
• CHECK that PA fan is locally line up for starting.
• PA fan lub oil coolers are CHARGED from waterside.
• PA Fan LOP : ON and other pump is on AUTO
• PA fan lub oil tank level is ADEQUATE.
• PA fans EPBS are in RELEASED position.
• PA fan guide vanes are on REMOTE. Instrument air pre. is
AVAILABLE.
• PA fan discharge damper is OPERATIONAL and power supply is
AVAILABLE.
Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 34
PA FAN OPERATION
• CHECK. if air system is lined up before starting PA fan.
• APHs primary air isolation dampers are OPEN.
• Seal air fans are LINEDUP and their suction dampers are OPEN.
• Mills' cold air dampers on REMOTE. Instrument air pre. is
AVAILABLE.
• Furnace purging is COMPLETED and MFRs are in RESET condition.
• All man material is removed from the pulverisers.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 35


PA FAN STARTING PROCEDURE
• WHEN BOTH THE FANS ARE OFF
• CHECK these conditions before starting the PA fan.
• All pre-start checks COMPLETED.
• Fan discharge dampers 100% OPEN.
• Regulating vanes are 100% OPEN.
• Lub. oil pressure is ADEQUATE. (>1.8 Kg)
• FSSS start command (MFR - A&B reset on the FSSS console and all
mills cold air dampers are less than 5% open) is ON.
• Bearing temperature NOT HIGH. (<60 0C).
• START the PA fan motor.
• Discharge damper starts closing.
• Regulating vanes of the fan get closed.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 36


PA FAN STARTING PROCEDURE
• All mills cold air dampers go to less than 5% open and "FSSS start
command" permissive comes on.
• Fan current shoots up to 700A and comes to No load current 70A.
• Discharge damper opens and for the other fan, it closes and
regulating vanes of the other fan also goes to minimum position.
• ADJUST the PA fan guide vanes to get desired hot PA header
pressure of 760 mm wcl
• PA fan discharge pressure goes up.
• PA fan current go up.
• PA header pressure goes up to 760 mm wcl, gradually.
• INSTRUCT the local operator to check bearing Temperature &
vibration locally. There must be no abnormal sound from the fan
or bearings.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 37


PA FAN STARTING PROCEDURE
• WHEN ONE FAN IS RUNNING
• All pre-start checks are COMPLETED.
• LOP: ON. Lub. Oil pressure ADEQUATE (1.8 -2.5 KSC)
• Discharge damper CLOSED.
• Regulating vanes are in MINIMUM position.
• Bearing temperature NOT HIGH (< 600C).
• FSSS start command is AVAILABLE.
• Local operator informed prior to starting of the fan.
• START the PA fan motor.
• Fan current goes up to 700A and comes down to no load current
of 70A.
• Discharge damper open up.
• INSTRUCT the local operator to check bearing vibration and
temperature locally.
Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 38
PA FAN STARTING PROCEDURE
• WHEN ONE FAN IS RUNNING
• ADJUST the fan guide vanes to get desired PA header pressure
and equalise fan loadings.
• Fan discharge pressure read approx. 800 mm wcl.
• PA header pressure rises to 760 mm wcl.
• ADJUST the fan biasing and header pre. set point to 50% & 80%
respectively and transfer vane controllers to auto.
• Header pressure and biasing set points have been provided over
the IGV controllers of PA fan A&B respectively.
• IGVs of both fans modulate to maintain set header pressure.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 39


PA FAN SHUT DOWN PROCEDURE
• WITH BOTH THE FANS RUNNING
• TRANSFER the IGV controls to manual
• STOP all the pulverisers in excess of three from the top.
• Three pulverisers only can be in service with one PA fan.
• Cut-in oil support if odd combination of mills are running.
• REDUCE IGVs of the fan to their minimum position.
• Fan discharge pressure comes down.
• Notice the other fan loading going up, to maintain the set header
pressure.
• STOP the fan motor. The fan breaker opens
• Discharge damper starts closing.
• Regulating vanes go to minimum, position.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 40


PA FAN SHUT DOWN PROCEDURE
• WITH ONE FAN IS RUNNING
• SHUTDOWN all running pulverizes one by one. Take Oil guns in
service.
• Boiler total fuel flow starts decreasing.
• Oxygen percentage the flue gases starts increasing.
• Associated mills cold air dampers start closing.
• Total airflow keeps on decreasing.
• ID fan vanes modulate (on auto), to maintain set furnace draught.
• REDUCE the IGV of the PA fan to its minimum position.
• PA fan discharge pressure starts decreasing.
• PA header pressure decreases to 400 mm wcl, approximately.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 41


PA FAN SHUT DOWN PROCEDURE
• WITH ONE FAN IS RUNNING
• STOP the PA fan & Rack-out the breaker if required for
maintenance.
• Breaker open indication comes on.
• Guide vanes of both PA fans will remain at minimum position.
• Discharge dampers of both PA fans go to 100% open.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 42


Milling System
• PRE START CHECKS (Typical: Raymond Bowl Mill) Local
• Ensure R.C. Bunker level satisfactory.
• R.C. feeder and mill properly boxed up and no maintenance staff
working.
• Gear box oil level normal. Lub. oil coolers charged.
• Pulveriser START PERMIT is AVAILABLE. (Boiler total airflow is < 40% and
all burners are HORIZONTAL). Alternatively, if anyone coal feeder is
proven then start permit will come from the proven feeder.
• Tramp iron gate open.
• Cold air gate 100 % open. Hot air gate closed.
• Mill outlet valve open.
• Seal air valve 100 % open.
• "No unsuccessful start" permissive for pulveriser is ON.
• Mill fire fighting system ready.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 43


Milling System
• PRE START CHECKS (Typical: Raymond Bowl Mill) UCB
• Ensure no PTW pending.
• Ensure at least one P.A. fan and a seal air fan is in service. Check
the header pressure for both primary and seal air is normal.
• Check that mill ignition energy is O.K. (Minimum 3 out of 4 gun
nozzle valves in adjacent elevation are open and elevation oil flow
is more than 30% OR adjacent feeder speed is more than 50% and
boiler load is more than 30%.
• Check that mill start permissive as per FSSS are satisfied
• Ensure E.P. zones have been charged (for first mill).
• Get the electrical supply for the mill.
• Inform the local operator to be near mill for start up.
Start the mill

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 44


Milling System
• POST START CHECKS
• Local -Check there is no abnormal sound from mill. Check return
oil flow from upper bearing is satisfactory. Check all the rollers
are rotating and the rate of reject is normal (after the mill is
loaded).
• U.C.B.-Check mill starting time and current. Ensure that they
are normal. Open hot air gate. Warm up the mill.
• Start the RC feeder and load the mill gradually.
• Keep the air flow through mill - 54 T/hr.
• Keep watch on mill differential to avoid mill choking.
• Maintain mill outlet temperature between 75°C to 80°C.
• As the pressure, temperature of main steam shoots up with coal
firing proper check should be kept on these parameters.
(Especially for first mill).

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 45


Milling System
• MILL SHUTDOWN PROCEDURE
• TRANSFER mill feeder and fuel master controller to manual.
• Fuel master and feeder control transfer to manual.
• REDUCE feeder speed to minimum, gradually.
• Coal flow to mill starts coming down.
• Other running feeders start loading up, to maintain boiler loading, if
on auto.
• STOP the mill feeder.
• Hot air gate closes with a time delay of 30 sec approx.
• Mill current and differential pressure start reducing as the mill
becomes empty, gradually.
• EVACUATE the mill reject chamber locally and STOP the mill.
• Mill temperature comes down to less than 50oC.
• Mill CAD goes to <5% open
• Airflow to furnace drops slightly.
Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 46
Milling System
• MILL SHUTDOWN PROCEDURE
• TRANSFER mill feeder and fuel master controller to manual.
• Fuel master and feeder control transfer to manual.
• REDUCE feeder speed to minimum, gradually.
• Coal flow to mill starts coming down.
• Other running feeders start loading up, to maintain boiler loading, if
on auto.
• STOP the mill feeder.
• Hot air gate closes with a time delay of 30 sec approx.
• Mill current and differential pressure start reducing as the mill
becomes empty, gradually.
• EVACUATE the mill reject chamber locally and STOP the mill.
• Mill temperature comes down to less than 500C.
• Mill CAD goes to <5% open
• Airflow to furnace drops slightly.
Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 47
ELECTROSTATIC PRECIPITATORS
• Electrostatic precipitators are not normally taken into service (i.e.
the zones are not changed) when firing on oil only and, if possible,
the EP should be bypassed whilst firing on oil only. This is done to
prevent oil deposition on electrodes which can reduce E.P.
efficiency drastically.
• If EP bypasses are not fitted, the gas flow should be limited to one
of the main passes during the initial oil firing stage of the pressure
raising.
• Anti-condensation heaters & hopper heaters, if provided must be
taken into service well before boiler light up is initiated.
• The EP zones must be taken into service just before coal firing is
started in the boiler. The frequency of rapping should be properly
adjusted and their operation must be locally checked.

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 48


THANK YOU

Saturday, March 27, 2021 Gyanendra Sharma - NPTI Delhi 49