VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.

6 Page: 1
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020

Project: Data Center Zetta


Project-No: 12731_3_5
Building: Zona Franca Bogotá
Object: Pasillo PDU
Contractor: UPSistemas S.A.S.
Owner:
Project engineer: mrg
Date: 9/18/2020
Regulation rule for calculation of FK-5-1-12 quantities: NFPA 2001, Edition 2018
Altitude above sealevel: 2600 m
Atmospheric correction factor: 0.704

Project description:
1 x 2.0" 180° Sidewall Nozzle 10109
2 x 1.5" 180° Sidewall Nozzles 10114 - 10117
4 x 1.0" 180° Sidewall Nozzles 10119 - 10121 - 10123 - 10128
2 x 0.5" 180° Sidewall Nozzles 10132 - 10134

Pipe catalogue: schedule40.rkl


Component catalogue: SEVOcomp_1_2.arm
Nozzle catalogue: SEVO.noz
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 2
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 3
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020

Pipesystem data:

Section- Starting- Endnode Length Height Pipetype Diameter Fitting Component Nb of containers
No: node [m] [m] [inch] ** * code coefficient FK-5-1-12 quantity

1 0 1 1.378 1.378 10 2 1/2 C 602 7.800 1.0


2 1 2 0.254 0.000 13 2 1/2 E - - 0.0
3 2 3 2.170 2.170 13 2 1/2 E - - 0.0
4 3 4 0.800 0.000 13 2 1/2 E - - 0.0
5 4 5 1.000 0.000 13 2 T-0° - - 0.0
6 5 36 9.530 0.000 13 2 E - - 0.0
7 36 37 0.300 0.000 13 2 E - - 0.0
8 37 10 4.430 0.000 13 2 T-90° - - 0.0
9 10 11 0.260 0.000 13 2 E - - 0.0
10 11 15 4.550 0.000 13 1 1/2 T-90° - - 0.0
11 15 16 0.150 0.000 13 1 1/2 T-0° - - 0.0
12 16 10117 0.150 -0.150 13 1 1/2 E - - 0.0
13 15 20 0.150 0.000 13 1 T-90° - - 0.0
14 20 10121 0.500 0.500 13 1 E - - 0.0
15 11 12 4.000 0.000 13 1 1/2 T-90° - - 0.0
16 12 18 0.150 0.000 13 1 T-90° - - 0.0
17 18 10119 0.500 0.500 13 1 E - - 0.0
18 12 13 0.150 0.000 13 1 1/2 T-0° - - 0.0
19 13 10114 0.150 -0.150 13 1 1/2 E - - 0.0
20 37 6 8.000 0.000 13 1 1/2 T-90° - - 0.0
21 6 7 0.150 0.000 13 1 1/2 E - - 0.0
22 7 22 0.150 0.000 13 1 1/2 T-90° - - 0.0
23 22 10123 0.500 0.500 13 1 1/2 E - - 0.0
24 7 8 0.150 0.000 13 1 1/2 T-0° - - 0.0
25 8 10109 0.150 -0.150 13 1 1/2 E - - 0.0
26 4 24 0.200 0.000 13 2 T-90° - - 0.0
27 24 25 4.200 -4.200 13 2 E - - 0.0
28 25 26 1.220 0.000 13 2 E - - 0.0
29 26 30 8.660 0.000 13 1 T-90° - - 0.0
30 30 31 0.200 0.000 13 1 E - - 0.0
31 31 32 4.300 0.000 13 1/2 T-90° - - 0.0
32 32 10133 0.450 0.450 13 1/2 E - - 0.0
33 31 34 4.300 0.000 13 1/2 T-90° - - 0.0
34 34 10135 0.450 0.450 13 1/2 E - - 0.0
35 26 27 2.330 0.000 13 1 1/2 T-90° - - 0.0
36 27 28 0.200 0.000 13 1 1/2 E - - 0.0
37 28 10129 0.450 0.450 13 1 1/2 E - - 0.0

* C=Component, B=Bend, T=T-Piece, E=Elbow


** If a pipe diameter is equal zero see the extra table of the calculated diameters

Legend of pipetypes
Type Pipeclass Pipe roughness
10 schedule 40 smooth
13 schedule 40 black pipe
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 4
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020

Nozzle data:

No. Calculation zone Diameter [mm]


10109 Ambiente Inf. 17.6
10114 Ambiente Inf. 18.3
10117 Ambiente Inf. 18.4
10119 Ambiente Sup. 10.8
10121 Ambiente Sup. 10.8
10123 Ambiente Sup. 10.9
10129 Piso falso 8.3
10133 Piso falso 10.1
10135 Piso falso 10.1

Legend of nozzles:
Type Number of C1 C2 C3 C4 C5 C6
orifices
1 Nozzle 1 1 0.10652 0.26900 0.23203 -0.20251 0.00000 0.00000
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 5
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020

Calculation zone data:

Calculation of design quantity:

Zone Total Volume of Calculated Total Max. Over- Design Extinguish- Design Design Design
volume building volume surface pressure temp. conc. factor conc. quantity
[m3] parts [m3] [m3] [mbar] [°C] [% Vol] [% Vol] [kg]

1 Ambiente Inf. 269.5 35.3 234.3 358.2 1.000 20.0 3.3 1.35 4.5 108.14
2 Ambiente Sup. 92.2 12.1 80.1 215.9 1.000 20.0 3.3 1.35 4.5 36.95
3 Piso falso 56.8 7.4 49.3 187.4 1.000 20.0 3.3 1.35 4.5 22.75

Regulation rule for calculation of FK-5-1-12 quantities: NFPA 2001, Edition 2018
Calczone no. 1: Class C Fire, NFPA 2001 (Edition 2018)
Calczone no. 2: Class C Fire, NFPA 2001 (Edition 2018)
Calczone no. 3: Class C Fire, NFPA 2001 (Edition 2018)
Altitude above sealevel: 2600.0 m
Atmospheric correction factor: 0.704

FK-5-1-12 storage input data:

Container volume: 227.0 l


Maximum filling ratio of a container: 1.200 kg/l
Filling pressure: 34.5 bar abs
Storage temperature: 20.0 °C
Supplement factor: 1.01
Minimum storage quantity: 168.43 kg
Number of containers: 1

Discharge time (input value): 10.0 s

Further information:
Design with included gas discharge time
Design with predeterminated orifice diameters
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 6
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020

Calculation results:

FK-5-1-12 storage data:


Design quantity: 167.7 kg
Supplement factor: 1.01
Minimum storage quantitiy: 169.4 kg

Container volume: 227.0 l


Filling ratio: 0.75 kg/l
Filling pressure: 34.5 bar abs
FK-5-1-12 -mass per container: 169.4 kg
Number of containers: 1
Actual storage quantity: 169.4 kg

Storage temperature: 20.0 °C


Starting container pressure: 34.5 bar abs

Discharge time:
Discharge time air: 0.4 s
Total gas discharge time: 1.3 s
Two-phase discharge time: 7.0 s
Total discharge time: 8.3 s

System information:
Container working pressure: 16.4 bar abs
Container working temperature: 20.0 °C
Total network volume: 95.0 l
Medium pipe content: 112.9 kg FK-5-1-12
Filling portion in pipe system: 0.67 kg FK-5-1-12 /kg FK-5-1-12 -storage
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 7
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020

Pipe system:
Section- Starting- Endnode Pressure Flowrate Pipedimension
No: node [bar abs] [kg/s] Di [mm] DN

1 0 1 14.68 22.73 62.7 2 1/2


2 1 2 14.32 22.73 62.7 2 1/2
3 2 3 13.56 22.73 62.7 2 1/2
4 3 4 13.15 22.73 62.7 2 1/2
5 4 5 12.96 19.64 52.5 2
6 5 36 11.56 19.64 52.5 2
7 36 37 11.00 19.64 52.5 2
8 37 10 10.33 13.10 52.5 2
9 10 11 10.06 13.10 52.5 2
10 11 15 9.64 6.56 40.9 1 1/2
11 15 16 9.59 4.89 40.9 1 1/2
12 16 10117 9.49 4.89 40.9 1 1/2
13 15 20 9.46 1.67 26.6 1
14 20 10121 9.31 1.67 26.6 1
15 11 12 9.66 6.53 40.9 1 1/2
16 12 18 9.49 1.67 26.6 1
17 18 10119 9.33 1.67 26.6 1
18 12 13 9.61 4.86 40.9 1 1/2
19 13 10114 9.52 4.86 40.9 1 1/2
20 37 6 10.20 6.55 40.9 1 1/2
21 6 7 10.01 6.55 40.9 1 1/2
22 7 22 9.84 1.65 40.9 1 1/2
23 22 10123 9.78 1.65 40.9 1 1/2
24 7 8 9.96 4.90 40.9 1 1/2
25 8 10109 9.88 4.90 40.9 1 1/2
26 4 24 12.83 3.09 52.5 2
27 24 25 13.03 3.09 52.5 2
28 25 26 12.99 3.09 52.5 2
29 26 30 12.62 2.07 26.6 1
30 30 31 12.33 2.07 26.6 1
31 31 32 11.43 1.03 15.8 1/2
32 32 10133 10.74 1.03 15.8 1/2
33 31 34 11.43 1.03 15.8 1/2
34 34 10135 10.74 1.03 15.8 1/2
35 26 27 12.96 1.02 40.9 1 1/2
36 27 28 12.95 1.02 40.9 1 1/2
37 28 10129 12.91 1.02 40.9 1 1/2-
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 8
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020

Tee split table

T-Type Flow in 1th Flow out 2nd Flow out Regulation


Section Flow Section Flow Split Section Flow Split conform
No. kg/s No. kg/s % No. kg/s %

Side Tee 4 22.73 5 19.64 86.406 26 3.09 13.594 Yes


Bull Tee 7 19.64 8 13.10 66.701 20 6.55 33.350 Yes
Bull Tee 9 13.10 10 6.56 50.076 15 6.53 49.847 Yes
Side Tee 10 6.56 11 4.89 74.543 13 1.67 25.457 Yes
Side Tee 15 6.53 16 1.67 25.574 18 4.86 74.426 Yes
Side Tee 21 6.55 22 1.65 25.191 24 4.90 74.809 Yes
Bull Tee 28 3.09 29 2.07 66.990 35 1.02 33.010 Yes
Bull Tee 30 2.07 31 1.03 49.758 33 1.03 49.758 Yes
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 9
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020

Nozzle data:

Calculation- Nozzle Nozzle Number of Pipeconnection Orifice FK-5-1-12 out-


zone no: no. type orifices Di [mm] DN [mm] put [kg]

1 10109 1 1 40.9 1 1/2 17.6 36.1


1 10114 1 1 40.9 1 1/2 18.3 35.9
1 10117 1 1 40.9 1 1/2 18.4 36.1
2 10119 1 1 26.6 1 10.8 12.4
2 10121 1 1 26.6 1 10.8 12.3
2 10123 1 1 40.9 1 1/2 10.9 12.2
3 10129 1 1 40.9 1 1/2 8.3 7.5
3 10133 1 1 15.8 1/2 10.1 7.6
3 10135 1 1 15.8 1/2 10.1 7.6

Two-phase discharge time: 7.0 s

MAXIMUM TRANSPORT TIME DIFF. BETWEEN NOZZLES: 10129./ 10114. IS 0.86 S

Calculation- Nozzle Outlet velocity Transport Jetdistance Evaporation


zone no: no. [m/s] time [s] [m] distance [m]

1 10109 14.3 4.85 6.1 4.9


1 10114 15.1 4.73 6.6 4.9
1 10117 15.0 4.85 6.7 4.9
2 10119 17.5 4.88 4.4 3.1
2 10121 17.6 5.00 4.4 3.1
2 10123 20.9 5.20 5.0 2.9
3 10129 29.5 5.59 4.9 2.0
3 10133 29.6 4.98 6.0 1.9
3 10135 29.6 4.98 6.0 1.9
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 10
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020

Concentrations:

Calculation- Gascomposition after discharge [%]


zone no: O2 FK-5-1-12 N2

1 20.0 4.5 74.6


2 20.0 4.5 74.6
3 20.0 4.5 74.6

Pressure relief opening:

Calculation- Recommended area against overpressure


zone no: Area [m²] Overpressure [mbar] Max. flow [kg/s]

1 0.162 1.0 14.6


2 0.055 1.0 5.0
3 0.034 1.0 3.1
VdS SCHADENVERHÜTUNG FK-5-1-12 -Calculationprogram Version 7.6 Page: 11
Licenced to: Sevo Systems Serial no: [dongle]
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\12731_3_5 Data Cener Zetta - UPSistemas SAS.prj - Results 9/18/2020

Component list:

Component Number Code Coefficient

SEVO 601 LB/2 1/2" ( 1 602 7.800

Nozzle-type Number C1 C2 C3 C4 C5 C6

1 9 0.10650 0.26900 0.23200 -0.20250 0.00000 0.00000

Pipe-type Di [mm] DN Length [m]

10 62.70 2 1/2 1.400


13 62.70 2 1/2 3.300
13 52.50 2 21.100
13 40.90 1 1/2 20.800
13 26.60 1 10.100
13 15.80 1/2 9.600

Number of bends (+) and elbows (-)

Bend-type Di [mm] DN Number

-90 62.70 2 1/2 3


-90 52.50 2 5
-90 40.90 1 1/2 7
-90 26.60 1 3
-90 15.80 1/2 2

Number of T-distributors (in- and outdiameter)

Number Input 90-out 90-out 0-out

1 2 1/2 2 0 2
1 2 2 1 1/2 0
1 2 1 1/2 1 1/2 0
2 1 1/2 1 0 1 1/2
1 1 1/2 1 1/2 0 1 1/2
1 2 1 1 1/2 0
1 1 1/2 1/2 0