You are on page 1of 160

ELEKTRISCHE STELLANTRIEBE

ELECTRIC ACTUATORS
for industrial applications and civil vessels

TECHNICAL DOCUMENTATIONS 2017


TECHNISCHE UNTERLAGEN 2017

BASIC RANGE
SBA 06 – SBA 200
NR 2.1 – NR 2.3
ED 25 – ED 450 / EQ 60 – EQ 600
SMART RANGE
SD 05 – SD 25 / SDL 50 – SDL 100 SGC
04.1 – SGC 12.1
SGCR 04.1 – SGCR 12.1
SVC 05.1 – SVC 07.5
SVCR 05.1 – SVCR 07.5
Manual
Technical documentation
1st edition 2017

We reserve the right to alter data according to improvements made.

Please refer to our website: www.auma.com to access


the individual documents included in this folder.
Previous documents become invalid with the issue of this document.
Table of contents

1 Technical data Actuators 5


Basic Range 6
Smart Range 14

2 Technical data Miscellaneous 43


Connectors 44
Corrosion protection 46
Painting specifications 52
Lubricants 54

3 Electrical data Actuators 59


Basic Range 60
Smart Range 84

4 Dimensions Actuators 91
Basic Range 92
Smart Range 102

5 Dimensions Output drives 109


Couplings 112

6 Spare parts lists 115


Basic Range 117
Smart Range 118

7 Wiring diagrams 133


Basic Range 134
Smart Range 147
1. Technical data
Actuators
1 Technical data Actuators

Basic Range 6

for modulating duty


SBA 06 – SBA 200 6
NR 2.1 – NR 2.3 Fail-Safe 9

for open-close and modulating duty


ED 25 – ED 50, EQ 40 – EQ 600 11

Smart Range 14

for open-close and modulating duty


SD 05 – SD 25 14
SDL 50 – SDL 100 16

SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1 18


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1 Profibus DP 22
SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1 Modbus RTU 26

SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5 30


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5 Profibus DP 34
SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5 Modbus RTU 38
SBA 06 – SBA 200

Technical data Linear actuators for modulating duty

Type Stroke Operating Motor Valve attachment Trapezoidal Positioning speed2) Weight
force protection1) thread

Standard
Max. EN ISO 5210 approx.
[mm] [kN] DIN 3210 [mm/min] [kg]
8
SBA 06-1 0.6 B F05 8 x 1,5 2.1
10
35 13.2
SBA 06-2 0.9 B F05 8 x 1,5 2.1
16
SBA 06-3 1.2 B F05 8 x 1,5 20 2.1
8
SBA 06-4 35 2.0 B F05 10 x 2 10 2.1
13.2
SBA 12 75 1.2 B F05 14 x 3 25 8.0
SBA 20 75 2.0 B F05 14 x 3 15 8.0
25
SBA 45-2 75 3.5 B F05 14 x 3 8.0
50
25
SBA 45-3 75 4.5 B F05 14 x 3 8.0
50
17
SBA 45-4 75 6.0 B F05 14 x 3 8.0
34
SBA 80-1 6.0 B G0 20 x 4 13.5 13
SBA 80-2 80 8.0 B G0 20 x 4 25 13
SBA 80-3 12 T G0 20 x 4 50 13
B 13.5
SBA 80-4 80 15 B G0 20 x 4 22 13
T 40
SBA 200-1 15 B G0 26 x 5 15 19
100 T 25
SBA 200-2 20 G0 26 x 5 19
T 50
SBA 200-3 100 25 T G0 26 x 5 25 19

General information
Linear actuators for modulating and open-close automation

Notes on table
1) Motor protection B = stall-proof motor (S1 - 100 %), T = thermoswitch for temperature monitoring
2) 50 Hz For 60 Hz, operating times and power consumption increase by 20 %

Features and functions of actuator


Type of duty Modulating Intermittent duty S3 - 50 %, with maximum number of starts of 600 starts per hour
duty: Intermittent duty S1 - 100 %, with maximum number of starts of 1,200 starts per hour;
not available for all versions (option)
Motor Sychronous motor, asynchronous motor

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.966/003/en Issue 1.16 Page 1/3


SBA 06 – SBA 200

Technical data Linear actuators for modulating duty

Mains voltage, mains frequency Standard voltages:


1-phase AC current
Voltages/frequencies
Volt 230 220
Hz 50 60

Options:
3-phase AC current 1-phase AC current
Voltages/frequencies Voltages/frequencies
Volt 380 400 400 440 Volt 24 24 115 110
Hz 50 50 60 60 Hz 50 60 50 60

DC current
Voltages
Volt 24

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
Further supply voltages on request
Motor protection Stall-proof motor or thermoswitch for temperature monitoring
Heater (option) Heating resistor with thermoswitch against moisture with automatic temperature control, max. 15 Watt, sup-
ply voltage 24, 115, 230 V/50/60 Hz [HZ/WP]
Cable entry
SBA 06-1/-2/-3 SBA 06-4
3 x M16 x 1.5

SBA 12 SBA 20 SBA 45-2/-3 SBA 45-4 SBA 80-1/-2/-3 SBA 80-4
2 x M16 x1.5 and 1 blanking plug M16 x 1.5

SBA 200-1/-2 SBA 200-3


2 x M20 x 1.5 and 1 blanking plug M20 x 1.5

Manual operation Handwheel


Electrical connection Standard: Internal terminal rail, for terminal assignment refer to terminal plan
Option: 10-pole compact plug silver/24-pole with additional compartment at actuator [KS]
Local controls (option) Local controls with MANUAL/AUTO change-over. Push button for directions OPEN and CLOSE.

Features and functions of actuator controls


End position seating Standard: 2 load-dependent switches, 250 V AC
 Switching capacity for resistive load, max. 5 A, for inductive load, max. 3 A
(SBA 06 – SBA 45)
 Switching capacity for resistive load, max. 10 A, for inductive load, max. 5 A
(SBA 80 – SBA 200)
Options:  Additional limit switches for signalling the end positions or intermediate positions, freely
adjustable max. 250 V AC max. 5 A (resistive load), max. 3 A (inductive load), max. 2
switches for SBA 06 – SBA 45 [2WE], max. 4 switches for SBA 80 – SBA 200 [4WE]
 Additional limit switches for signalling the end positions or intermediate positions, freely
adjustable with gold contacts for low voltage, max. 30 V AC, max. 0.1 A (resistive load),
max. 2 switches for SBA 06 – SBA 45 [2WE-G], max. 4 switches for SBA 80 – SBA 100
[4WE-G]
Digital inputs Standard: None
Option: With 2 inputs (reversing contactors) for OPEN and CLOSE, option for:
 24 V DC; 1.7 W appropriate for PLC [WSE]
 24 V AC/DC
 110 V AC
 230 V AC
Positioner (option) Positioning electronics for actuator control [PEL]
Input 0 – 10 V, 0/4 – 20 mA, output 0 – 10 V, 0/4 – 20 mA

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.966/003/en Issue 1.16 Page 2/3


SBA 06 – SBA 200

Technical data Linear actuators for modulating duty

Position feedback signal, analogue  Potentiometer 100/130/200/500/1,000/5,000 Ω or 10 kΩ [POT]


(options) Linearity fault ≤ 0.5 %, max. 1.5 W, wiper current 30 mA, max. 2 units, max. 1 unit for SBA 06
 Electronic position feedback, 2-/3-/4-wire system [ESR]
Output 0/4 – 20 mA, supply voltage 24 V DC (not possible for SBA 06)
 Potentiometer tested by TÜV for fails-safe position feedback
(also appropriate for Lamtec regulation systems) [C-POT]
Fieldbus (option) Profibus DP-V0 for actuator control in housing IP66 [PBD100]
Mounted to actuator with plug/socket connector M12, 5-pole, 2 x M20 cable glands

Service conditions
Mounting position Any position, but not suspended downward
Installation altitude ≤ 2 000 m above sea level
> 2,000 m above sea level on request
Ambient temperature Standard: –20 °C to +60 °C
Options: –40 °C to +60 °C
Other options on request
Enclosure protection according to IP43 (SBA 06-1/-2/-3), IP54 (SBA06-4), IP65 (SBA 12 – SBA 200)
EN 60529
Corrosion protection Standard: C2 according to EN ISO 12944-2
Option: C3/C4 according to EN ISO 12944-2
Coating Standard: Powder coating
Option: Special coating for corrosion protection C3/C4
Colour Standard: Grey: RAL 7015 (housing)
Green: RAL 5021 (hood)
Option: Available colours on request
Lifetime AUMA linear actuators meet or even exceed the lifetime requirements of EN 15714-2.
Detailed information can be provided on request.

Further information
Inspection certificate On request
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions Linear actuators SBA 06 – SBA 200
Electrical data Linear actuators SBA 06 – SBA 200

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.966/003/en Issue 1.16 Page 3/3


NR 2.1 – NR 2.3

Technical data Linear actuators with fail safe unit for modulating duty

Type Stroke Operating force Motor Valve Positioning speed for Positioning speed at Weight
protection2) attachment modulating duty3) power failure

Max. CLOSE1) OPEN1) Standard approx.


[mm] [kN] [kN] EN ISO 5210 [mm/min] [mm/s] [kg]
NR 2.1 35 0.9 5.3 B F05 17.5 4.1 8.7
NR 2.2 35 2.2 4.0 B F05 17.5 4.1 9.3
NR 2.3 46 2.2 4.0 B F05 17.5 4.1 10

General information
Linear actuators for modulating and open-close automation with fail safe unit

Notes on table
1) Applicable for extending effective spring direction
2) Motor protection B = Stall-proof motor
3) 50 Hz For 60 Hz, operating times and power consumption increase by 20 %

Features and functions of actuator


Type of duty Modulating Intermittent duty S4 - 30 %, with maximum number of starts of 1,200 starts per hour
duty: Intermittent duty S1 - 100 %
Motor Synchronous motor
Mains voltage, mains frequency Standard voltages:
1-phase AC current
Voltages/frequencies
Volt 230 220
Hz 50 60

Options:
1-phase AC current
Voltages/frequencies
Volt 24 24 115 110
Hz 50 60 50 60

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
Further supply voltages on request
Insulation class E
Motor protection Stall-proof motor
Cable entry 2 cable entries x M20 x 1.5 and 2 blanking plugs M20 x 1.5
Manual operation Handwheel
Electrical connection Internal terminal rail, for terminal assignment refer to terminal plan
Local controls (option) Electric operation via push buttons (only possible if voltage is applied)

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.982/003/en Issue 1.16 Page 1/2


NR 2.1 – NR 2.3

Technical data Linear actuators with fail safe unit for modulating duty

Features and functions of actuator controls


Limit switching Standard: 2 switches, max. 250 V AC, max. 10 A (resistive load), max. 10 A (inductive load)
(digital outputs)
Option: • Additional limit switches for signalling the end position or intermediate positions, freely
adjustable max. 250 V AC, max. 10 A (resistive load), max. 10 A (inductive load), max. 2
switches [2WE]
• Additional limit switches for signalling end positions or intermediate positions, freely
adjustable with gold-plated contacts for low voltage, max. 30 V AC, max. 0.1 A (resistive
load), max. 2 switches [2WE-G]
Positioner (option) Positioning electronics for actuator control [PEL]
Input 0 – 10 V, 0/4 – 20 mA, output 0 – 10 V, 0/4 – 20 mA
Position feedback signal, analogue • Potentiometer 100/130/200/500/1,000/5,000 Ω or 10 kΩ [POT]
(options) Linearity fault ≤ 0.5 %, max. 1.5 W, wiper current 30 mA, max. 2 units
• Electronic position feedback, 2-/3-wire system [ESR]
Output 0/4 – 20 mA, supply voltage 24 V DC

Service conditions
Mounting position Any position, but not suspended downward
Installation altitude ≤ 2 000 m above sea level
> 2,000 m above sea level on request
Ambient temperature –20 °C to +50 °C
Enclosure protection according to Standard: IP67
EN 60529
Option: IP65 with rounded hood [A-IP65]
Corrosion protection Standard: C2 according to EN ISO 12944-2
Option: C3/C4 according to EN ISO 12944-2
Coating Standard: Powder coating
Option: Special coating for corrosion protection C3/C4
Colour Standard: RAL 7030
Option: Available colours on request
Lifetime AUMA linear actuators meet or even exceed the lifetime requirements of EN 15714-2. Detailed information
can be provided on request.

Further information
Inspection certificate On request
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions Linear actuators NR 2.1 – NR 2.3
Electrical data Linear actuators NR 2.1 – NR 2.3

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.982/003/en Issue 1.16 Page 2/2


ED 25 – ED 50, EQ 40 – EQ 600

Technical data Part-turn actuators for open-close and modulating duty

Type Torque range Operating time Motor Valve attachment Handwheel Weight
for 90° in seconds protection2)
Open-close duty Modulating duty
max. max. Open-close duty Standard Ø approx.
[Nm] [Nm] 50 Hz1) EN ISO 5211 [mm] [kg]
15 B
ED 25 25 25 30 B F03, (F04)4), F05, F07 – 4.0
70 B
15 T
ED 50 50 50 30 B F03, (F04), F05, F07 – 4.0
70 B
15 B
EQ 40 40 20 30 B (F04)4), F05, F07, F10 100 7.5
60 B
20 T
EQ 60 60 40 30 T F05, F07, F10 100 7.5
60 B
203) B
EQ 100 100 60 30 T F05, F07, F10 100 7.5
60 T
203) T
EQ 150 150 80 303) B F05, F07, F10 100 7.5
60 T
403) T
EQ 300 300 180 803) B F07, F10, (F12)4) 100 15
160 T
803) T
EQ 600 600 300 F07, F10, (F12)4) 100 15
1603) B

General information
Part-turn actuators for controlling and automating final elements within the field of process engineering with swivel movements between 90° and
180° for e.g. butterfly valves, ball valves.

Notes on table
1) 50 Hz For 60 Hz, operating time reduces and power consumption increases by 20 %
2) Motor protection B = stallproof motor (S1 - 100 %), T = thermoswitch for temperature monitoring
3) Aluminium hood required for optional positioner
4) Offset by 45°, F12 on request

Features and functions of actuator


Type of duty Open-close Short-time duty S2 - 15 min, class A
duty:
Modulating Intermittent duty S4 - 50 %, with maximum number of starts of 1,200 starts per hour
duty: Intermittent duty S1 - 100 % with maximum number of starts of 1,200 starts per hour; not
available for all versions (option)
Motor Synchronous motor
Mains voltage, mains frequency Standard voltages:
1-phase AC current
Voltages/frequencies
Volt 230 220
Hz 50 60

Options:
3-phase AC current 1-phase AC current
Voltages/frequencies Voltages/frequencies
Volt 380 400 400 440 Volt 24 24 115 110
Hz 50 50 60 60 Hz 50 60 50 60

DC current
Voltages
Volt 24

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
Further supply voltages on request
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.637/003/en Issue 1.16 Page 1/3


ED 25 – ED 50, EQ 40 – EQ 600

Technical data Part-turn actuators for open-close and modulating duty

Insulation class E, B, F
Motor protection Stallproof motor or thermoswitch for temperature monitoring
Heater (option) Heating resistor with thermoswitch against moisture with automatic temperature regulation, max. 15 Watt,
supply voltage 24, 115, 230 V/50/60 Hz [HZ/WP]
Self-locking Yes
Swing angle (option) Standard: EQ: 90° ±15°
ED: 90°, 120°, 150°, 180°
Options: EQ: 120° ±15°
[SWE] 150° ±15°
180° ±15°
Cable entry EQ: 3 blanking plugs M20 x 1.5
ED: 2 blanking plugs M16 x 1.5
Manual operation EQ: Handwheel
ED: Emergency manual operation with hexagon socket
Electrical connection Standard: Internal terminal rail, for terminal assignment refer to terminal plan
Options: • Separate electrical terminal compartment at actuator with 32-pole terminal rail [ASK]
• Compact connector 10-pole silver/24-pole silver [KS1, KS3]
End positions EQ: Mechanical end stops, adjustable from outside
ED: None
Hood Standard: Polycarbonate (flammability class V0)
Option: Aluminium with inspection glass
Local controls (option), IP66 • MANUAL/AUTO change-over
• Rotary switch (non latching) for OPEN and CLOSE [VSE]

With base and lever (option for EQ)


Lever size • With lever size 100 mm (distance from axis to bore) [LAG-HEB]
• With lever size 150/200 mm

Features and functions of actuator controls


Limit switching Standard: 2 switches, max. 250 V AC, max. 10 A (resistive load), max. 5 A (inductive load)
(digital outputs)
Options: • Additional limit switches for signalling end positions or intermediate positions, freely
adjustable max. 250 V AC, max. 10 A (resistive load), max. 5 A (inductive load),
2 switches [2WE]
• Additional limit switches for signalling end positions or intermediate positions, freely
adjustable with gold-plated contacts for low voltage, max. 30 V AC, max. 0.1 A (resistive
load), 2 switches [2WE-G]
Torque switching EQ: Standard: 2 switches, max. 250 V AC, max. 10 A (resistive load), max. 5 A (inductive load)
(digital outputs)
Option: 2 additional potential-free torque switches [2DE]
ED: None
Digital inputs Standard: None
Options: With 2 inputs (reversing contactors) for OPEN and CLOSE, option for:
• 24 V DC; 1,7 W appropriate for PLC [WSE]
• 24 V AC/DC
• 110 V AC
• 230 V AC
Positioner (option) Positioning electronics for actuator control [PEL100, PEL-GL]
Input 0 – 10 V, 0/4 – 20 mA, Output 0 – 10 V, 0/4 – 20 mA
Position feedback signal, analogue • Potentiometer 100/130/200/500/1,000/5,000 Ω or 10 kΩ [POT]
(options) Linearity fault ≤ 0.5 %, max. 1.5 W, wiper current 30 mA, max. 2 units
• Electronic position feedback, 2/3-wire system [ESR100]
output 0/4 – 20 mA, supply voltage 24 V DC
Fieldbus (option) Profibus DP-V0 for actuator control in housing IP66 [PBD100]
Mounted to actuator with plug/socket connector M12, 5-pole, 2 x M20 cable glands

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.637/003/en Issue 1.16 Page 2/3


ED 25 – ED 50, EQ 40 – EQ 600

Technical data Part-turn actuators for open-close and modulating duty

Emergency operation module (option)


Emergency operation module • 250 Nm, supply voltage 24 V DC [FSC20-24]
• 250 Nm, supply voltage 90 – 264 V AC [FSC20-230]
• 450 Nm, supply voltage 90 – 264 V AC [FSC40-230]

Service conditions
Mounting position Any position, but not suspended downward
Installation altitude ≤ 2,000 m above sea level
> 2,000 m above sea level, on request
Ambient temperature Standard: –20 °C to +70 °C
Options: –40 °C to +70 °C
Other options on request
Enclosure protection according to Standard: IP67
EN 60529
Option: IP68 [A-IP68]
Explosion-protection (option) Ex II 3D IP65 T 150°C Dc [A-Ex]
Corrosion protection Standard: C2 according to EN ISO 12944-2
Option: C3/C4 according to EN ISO 12944-2
Coating Standard: Powder coating
Option: Special painting for corrosion protection C3/C4
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime AUMA part-turn actuators meet or even exceed the lifetime requirements of EN 15714-2.
Detailed information can be provided on request.

Further information
Inspection certificate On request
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions Part-turn actuators EQ 40 – EQ 600
Dimensions Part-turn actuators ED 25 – ED 50
Electrical data Part-turn actuators EQ 40 – EQ 600
Electrical data Part-turn actuators ED 25 – ED 50

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.637/003/en Issue 1.16 Page 3/3


SD 05 – SD 25

Technical data Multi-turn actuators for open-close and modulating duty

Type Output speed Torque range Motor Valve attachment Handwheel Weight
protection1)
Modulating
Open-close duty duty
Max. max. max. Standard Ø approx.
[rpm] [Nm] [Nm] EN ISO 5210 [mm] [kg]
SD 05 8 6 5 E F10 100/752) 8.0
SD 10 20 10 10 E F10 100/752) 8.0
SD 25 20 30 25 E F10 100/752) 8.0

General information
Multi-turn actuators for modulating and open-close automation

Notes on table
1) Motor protection E = electronic cut-out
2) Handwheel For ATEX / IECEx approvals

Features and functions of actuator


Type of duty Modulating duty: Intermittent duty S4 - 30 %, with maximum number of starts of 1,200 starts per hour
Open-close duty: Short-time duty S2 - 15 min, class A
Motor Step motor (SD 05), brushless DC motor (SD 10/SD 25)
Mains voltage, mains frequency Standard voltages:
1-phase AC current
Voltages/frequencies
Volt 100 – 240 100 – 240
Hz 50 60

Options:
3-phase AC current
Voltages/frequencies
Volt 200 – 500 200 – 500
Hz 50 60

DC current
Voltages
Volt 24

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
Further supply voltages on request
Motor protection Electronic cut-out
Self-locking None
Turns 15/30/60 turns/stroke
Cable entry 3 blanking plugs M20 x 1.5
Manual operation Handwheel
Electrical connection Spring-loaded terminal rail in separate terminal compartment, "Ex e" increased safety,
cross section max. 4 mm²
End position seating Electronic selection of torque or travel for both directions
Local controls (option) Local controls at actuator [VSS] (for weatherproof version only)

Features and functions of actuator controls


Interface (option) • I/O board; 2 limit switches 1 A, 260 V AC [2WE]
• I/O board; 2 limit switches and 1 intermediate position switch 1 A, 260 V AC [2WE + 1WE]
Control • Analogue 0 – 10 V input impedance > 100 kOhm, 0/4 – 20 mA input impedance 50 Ohm
• Control inputs 24 V DC, galvanic isolation Ri = 1,500 Ohm (I > 10 mA)
OPEN, CLOSE, MODE
Position feedback signals Analogue 0 – 10 V, 0/4 – 20 mA, load max. 500 Ohm via contactless sensor

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.805/003/en Issue 1.16 Page 1/2


SD 05 – SD 25

Technical data Multi-turn actuators for open-close and modulating duty

Status signals Collective fault signal 24 V DC, Imax. 60 mA, galvanically isolated
Configuration • Setting via remote:
- Initialisation/zero point reset
• Setting via DIP switches:
- Input signal/output signal
- Rising, falling signal
- Type of duty
• Setting via programming switches:
- Torque, speed, number of turns), type of seating, operating parameters, configuration parameters
Display (option) Display with 2x16 LCD blue [ANZ-DIS]

Service conditions
Positioning accuracy < 0.5 %
Mounting position Any position, but not suspended downward
Installation altitude ≤ 2 000 m above sea level
> 2,000 m above sea level on request
Ambient temperature Standard: –20 °C to +60 °C (SD 05/ D 10)
–20 °C to +55 °C (SD 25)
Options: –40 °C to +60 °C (SD 10)
–40 °C to +55 °C (SD 25)
Other options on request
Enclosure protection according to Standard: IP67
EN 60529
Option: IP68 [A-IP68]
Explosion protection according to II 2G EEx de IIB T4
EN 60079-1
Corrosion protection Standard: C2 according to EN ISO 12944-2
Option: C3/C4 according to EN ISO 12944-2
Coating Standard: Powder coating (weatherproof)
Option: Wet painting (explosion-proof)
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime AUMA multi-turn actuators meet or even exceed the lifetime requirements of EN 15714-2.
Detailed information can be provided on request.

Further information
Inspection certificate On request
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions Multi-turn actuators SD 05 – SD 25
Electrical data Multi-turn actuators SD 05 – SD 25

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.805/003/en Issue 1.16 Page 2/2


SDL 50 – SDL 100 / SDG 40

Technical data Linear actuators for open-close and modulating duty

Type Stroke Operating force Positioning speed1) Motor Valve attach- Trapezoidal Weight
protection2) ment thread

Open-close Modulating-
Max. duty Max. duty Max. Min. Max. Standard approx.
[mm] [kN] [kN] [mm/s] [mm/s] EN ISO 5210 [kg]
SDL 50-10 55 6.0 5.0 0.2 0.5 E F05 14 x 3 14
SDL 50-20 55 6.0 4.0 0.4 2.5 E F05 14 x 3 14
SDL 50-30 55 4.0 2.5 1.2 7.0 E F05 14 x 3 14
SDL 100-20 85 6.0 6.0 0.3 1.8 E F07 20 x 5 15
SDL 100-30 85 15 10 0.3 1.8 E F07 20 x 5 15
SDG 40-13 300 3.0 2.0 0.3 0.7 E F10 16 x 4 18
SDG 40-23 300 4.0 4.0 0.2 1.2 E F10 16 x 4 18

General information
Linear actuators for modulating and open-close automation

Notes on table
1) Positioning speed Maximum positioning speed and operating force cannot appear simultaneously.
2) Motor protection E = electronic cut-out

Features and functions of actuator


Type of duty Modulating Intermittent duty S4 - 30 %, with maximum number of starts of 1,200 starts per hour
duty:
Open-close Short-time duty S2 - 15 min, class A
duty:
Motor Step motor, brushless DC motor
Mains voltage, mains frequency Standard voltages:
1-phase AC current
Voltages/frequencies
Volt 100 – 240 100 – 240
Hz 50 60

Options:
3-phase AC current
Voltages/frequencies
Volt 200 – 500 200 – 500
Hz 50 60

DC current
Voltages
Volt 24

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
Further supply voltages on request
Motor protection Electronic cut-out
Self-locking Yes
Cable entry 3 blanking plugs M20 x 1.5
Manual operation Handwheel
Electrical connection Spring-loaded terminal rail in separate terminal compartment,
"Ex e" increased safety, cross section max. 4 mm²
End position seating Electronic selection of torque or travel for both directions
Local controls (option) Local controls at actuator [VSS] (for watertight version only)

Features and functions of actuator controls


Interface (option)  I/O board; 2 limit switches 1 A, 260 V AC [2WE]
 I/O board; 2 limit switches and 1 intermediate position switch 1 A, 260 V AC [2WE + 1WE]

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.928/003/en Issue 1.16 Page 1/2


SDL 50 – SDL 100 / SDG 40

Technical data Linear actuators for open-close and modulating duty

Control  Analogue 0 – 10 V input impedance > 100 kOhm, 0/4 – 20 mA input impedance 50 Ohm
 Control inputs 24 V DC, galvanic isolation Ri = 1,500 Ohm (I > 10 mA)
OPEN, CLOSE, MODE
Position feedback signals Analogue 0 – 10 V, 0/4 – 20 mA, load max. 500 Ohm via contactless sensor
Status signals Collective fault signal 24 V DC, Imax. 50 mA, galvanically isolated
Configuration  Setting via remote:
- Initialisation/zero point reset
 Setting via DIP switches:
- Input signal/output signal
- Rising, falling signal
- Type of duty
 Setting via programming switches:
- Torque, speed, number of turns), type of seating, operating parameters, configuration parameters
Display (option) Display with 2x16 LCD blue [ANZ-DIS]

Service conditions
Positioning accuracy < 0.5 %
Mounting position Any position, but not suspended downward
Installation altitude ≤ 2,000 m above sea level
> 2,000 m above sea level on request
Ambient temperature Standard: –20 °C bis +60 °C (SDL 50-10/SDL 50-20/SDL 100-20/SDG 40-13/SDG 40-23)
–20 °C bis +55 °C (SDL 50-30/SDL 100-30)
Options: –40 °C bis +60 °C (SDL 50-10/SDL 50-20/SDL 100-20/SDG 40-13/SDG 40-23)
–40 °C bis +55 °C (SDL 50-30/SDL 100-30)
Other options on request
Enclosure protection according to Standard: IP67
EN 60529
Option: IP68 [A-IP68]
Explosion protection according to Option: II 2G EEx de IIB T4
EN 60079-1
Corrosion protection Standard: C2 according to EN ISO 12944-2
Option: C3/C4 according to EN ISO 12944-2
Coating Standard: Powder coating (weatherproof)
Option: Wet painting (explosion-proof)
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime AUMA linear actuators meet or even exceed the lifetime requirements of EN 15714-2.
Detailed information can be provided on request.

Further information
Inspection certificate On request
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions Linear actuators SDL 50 – SDL 100
Electrical data Linear actuators SDL 50 – SDL 100

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.928/003/en Issue 1.16 Page 2/2


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Type Operating time for 90° Torque range1) Running Valve attach- Valve shaft Handwheel Weight4)
in seconds torque2)/ ment
(adjustable in 9 steps) Modulating
torque3)
Max. Max. Standard Cylindrical Square Two-flat Ø Turns approx.
50 Hz/60 Hz [Nm] [Nm] EN ISO 5211 max. [mm] max. [mm] max. [mm] [mm] for 90° [kg]
SGC/SGCR 04.1 4 – 63 25 – 63 32 F05/F07 20 17 17 100 13.5 7.0
SGC/SGCR 05.1 4 – 63 50 – 125 63 F05/F07 20 17 17 100 13.5 7.0
SGC/SGCR 07.1 4 – 63 100 – 250 125 F07 25.4 22 22 125 13.5 10
SGC/SGCR 10.1 5.6 – 90 200 – 500 250 F10 38 30 27 160 13.5 15
SGC/SGCR 12.1 20 – 275 400 – 1,000 500 F12 50 36 41 125 35 25

Notes on table
1) Unseating torque The “Torque by-pass” function (can be activated) allows increasing the pre-set torque to 130 %. This increase
only applies during actuator start for an adjustable time period, allowing safer unseating of blocked valves.
2) Running torque Maximum permissible torque for 15 min. running time.
3) Modulating torque Maximum permissible torque for modulating duty
4) Weight Indicated weight includes part-turn actuator with controls, electrical connection in standard version, unbored
coupling and handwheel

Features and functions of actuator


Type of duty Open-close Short-time duty S2 - 15 min, classes A and B according to EN 15714-2
duty
SGC:
Modulating Intermittent duty S4 - 40 % class C in compliance with EN 15714-2
duty with maximum number of starts of 1,800 cycles per hour (option)
SGCR:
For nominal voltage and +40 °C ambient temperature and at running or modulating torque load. The type of
duty must not be exceeded.
Motor Variable speed, brushless motor
Insulation class F, tropicalized
Motor protection PTC thermistors (according to DIN 44081)
Self-locking Yes
Swing angle Standard: SGC/SGCR 04.1 – 10.1: 82° – 98° adjustable between min. and max. values
SGC/SGCR 12.1: 75 ° – 105 °
Options: Available swing angles on request
Limit switching Via position transmitter potentiometer, status signals for directions OPEN and CLOSE
Torque switching Via electronic current measurement, status signals for directions OPEN and CLOSE, adjustable in 8 steps
Mechanical position indicator Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Manual operation Manual drive for setting and emergency operation, handwheel does not rotate during electrical operation
Coupling Standard: Coupling unbored
Options:  Coupling unbored extended
 Finish machining of coupling (standard or extended)
- Bore according to EN ISO 5211 with 1 keyway according to DIN 6885-1
- Square bore according to EN ISO 5211
- Two-flat according to EN ISO 5211
Valve attachment Dimensions according to EN ISO 5211

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.986/003/en Issue 1.16 Page 1/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Features and functions of actuator controls


Power supply Standard voltages:
1-phase AC current
Voltages/frequencies
Volt 115 230
Hz 50/60 50/60

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
For current consumption, refer to Electrical data Part-turn actuators SGC/SGCR
External supply of the electronics 24 V DC +20 %/–15 %,
(option) Current consumption: With options up to 200 mA
The external power supply must have reinforced insulation against mains voltage in accordance with IEC
61800-5-1 and may only be supplied by a circuit limited to 150 VA in accordance with IEC 61800-5-1.
Overvoltage category Category III according to IEC 60364-4-443
Power electronics Power electronics with integral motor controller
Rated power Controls are designed for rated motor power, refer to Electrical Data Part-turn actuators SGC/SGCR
Control  4 digital inputs (via opto-isolator, with one common)
(input signals) - Control voltage 24 V DC, current consumption: approx. 15 mA per input
- Minimum pulse duration for shortest operation pulse: 100 ms
- All digital inputs must be supplied with the same potential.
Assignment for open-close actuators:
- OPEN, STOP, CLOSE (standard)
- OPEN, STOP, CLOSE, EMERGENCY (option)
- OPEN, STOP, CLOSE, MODE in combination with positioner (option)
- OPEN, EMERGENCY, CLOSE, MODE in combination with positioner (option)
Assignment for modulating actuators:
- OPEN, STOP, CLOSE, MODE (standard)
- OPEN, EMERGENCY, CLOSE, MODE (option)
 Analogue input 0/4 – 20 mA (galvanically isolated) (option)
Used as input signal for position setpoint E1 (in combination with positioner) or as input signal for motor
speed E3.
Status signals  Output contacts:
(output signals) 4 programmable semi-conductor output contacts, per contact max. 24 V DC, 1 A (resistive load)
- 2 NO contacts with one common
Default configuration: End position OPEN, end position CLOSED
- 1 potential-free NO contact for collective fault signal
Default configuration: Torque fault, motor protection tripped
- 1 potential-free change-over contact
Default configuration: Push button REMOTE
 Analogue output:
Galvanically isolated position feedback 0/4 – 20 mA (load 500 Ω).
Voltage output Auxiliary voltage 24 V DC, max. 40 mA for supply of control inputs, galvanically isolated from internal voltage
supply.
Not available for option "external electronics supply".
Local controls Standard:  Push buttons OPEN, STOP (LOCAL - REMOTE), CLOSE
 2 multi-colour indication lights:
- End position CLOSED (yellow), fault/failure (red), end position OPEN (green),
operation mode LOCAL (blue)
Option: Local controls mounted separately on wall bracket

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.986/003/en Issue 1.16 Page 2/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Functions  Switch-off mode adjustable:


- Limit or torque seating for end positions OPEN and CLOSED
 Torque monitoring across the whole travel
 Torque by-pass
 Programmable EMERGENCY behaviour
- Digital input low active,
- Reaction can be selected: Stop, run to end position CLOSED, run to end position OPEN
 Positioner (for modulating actuators):
- Position setpoint via analogue input E1 = 0/4 – 20 mA
- Programmable behaviour on loss of signal
- Automatic adaptation of dead band (adaptive behaviour selectable)
- Selection between open-close duty and modulating duty via digital MODE input
Electrical connection Standard: Plug/socket connector with crimp connection
Option: AUMA plug/socket connector with screw-type connection
Wiring diagram (basic version) Open-close TPC B-0E6-2C7-0530 TPA 50R200-0A0-000
duty:
Modulating TPC B-1H6-2C7-0530 TPA 50R200-0A0-000
duty:

Service conditions
Mounting position Any position
Installation altitude ≤ 2 000 m above seal level
> 2,000 m above sea level on request
Ambient temperature –25 °C to +70 °C
Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection according to IP68
EN 60529 According to AUMA definition, enclosure protection IP68 meets the following requirements:
 Depth of water: maximum 8 m head of water
 Duration of continuous immersion in water: Max. 96 hours
 Up to 10 operations during continuous immersion
 Modulating duty is not possible during continuous immersion
Pollution degree according to IEC Pollution degree 4 (when closed), pollution degree 2 (internal)
60664-1
Vibration resistance according to 2 g, from 10 Hz to 200 Hz
IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
GL approval (option) Environmental categories D, G, EMC2
Corrosion protection Standard: KS Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option: KX Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime Open-close 20,000 operating cycles OPEN - CLOSE - OPEN
duty: An operating cycle is based on an operation from CLOSED to OPEN and back to CLOSED, at a
respective rotary movement of 90°.
Modulating 5 million modulating steps
duty:
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the
modulating accuracy. To reach the longest possible maintenance and fault-free operating time, the number of
starts per hour chosen should be as low as permissible for the process.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.986/003/en Issue 1.16 Page 3/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Further information
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions SGC 04.1– SGC 12.1/SGCR 04.1 – SGCR 12.1
Electrical data SGC 04.1– SGC 12.1/SGCR 04.1 – SGCR 12.1

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.986/003/en Issue 1.16 Page 4/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1, Profibus DP
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Type Operating time for 90° Torque range1) Running Valve attach- Valve shaft Handwheel Weight4)
in seconds torque2)/ ment
(adjustable in 9 steps) Modulating
torque3)
Max. Max. Standard Cylindrical Square Two-flat Ø Turns approx.
50 Hz/60 Hz [Nm] [Nm] EN ISO 5211 max. [mm] max. [mm] max. [mm] [mm] for 90° [kg]
SGC/SGCR 04.1 4 – 63 25 – 63 32 F05/F07 20 17 17 100 13.5 7.0
SGC/SGCR 05.1 4 – 63 50 – 125 63 F05/F07 20 17 17 100 13.5 7.0
SGC/SGCR 07.1 4 – 63 100 – 250 125 F07 25.4 22 22 125 13.5 10
SGC/SGCR 10.1 5.6 – 90 200 – 500 250 F10 38 30 27 160 13.5 15
SGC/SGCR 12.1 20 – 275 400 – 1,000 500 F12 50 36 41 125 35 25

Notes on table
1) Unseating torque The “Torque by-pass” function (can be activated) allows increasing the pre-set torque to 130 %. This increase
only applies during actuator start for an adjustable time period, allowing safer unseating of blocked valves.
2) Running torque Maximum permissible torque for 15 min. running time.
3) Modulating torque Maximum permissible torque for modulating duty
4) Weight Indicated weight includes part-turn actuator with controls, electrical connection in standard version, unbored
coupling and handwheel

Features and functions of actuator


Type of duty Open-close Short-time duty S2 - 15 min, classes A and B according to EN 15714-2
duty
SGC:
Modulating Intermittent duty S4 - 40 %, class C according to EN 15714-2
duty with maximum number of starts of 1,800 cycles per hour (option)
SGCR:
For nominal voltage and +40 °C ambient temperature and at running or modulating torque load. The type of
duty must not be exceeded.
Motor Variable speed, brushless motor
Insulation class F, tropicalized
Motor protection PTC thermistors (according to DIN 44081)
Self-locking Yes
Swing angle Standard: SGC/SGCR 04.1 – 10.1: 82° – 98° adjustable between min. and max. values
SGC/SGCR 12.1: 75 ° – 105°
Options: Available swing angles on request
Limit switching Via position transmitter potentiometer, status signals for directions OPEN and CLOSE
Signalling via fieldbus interface
Torque switching Via electronic current measurement, status signals for directions OPEN and CLOSE, adjustable in 8 steps
Signalling via fieldbus interface
Mechanical position indicator Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Manual operation Manual drive for setting and emergency operation, handwheel does not rotate during electrical operation
Coupling Standard: Coupling unbored
Options:  Coupling unbored extended
 Finish machining of coupling (standard or extended)
- Bore according to EN ISO 5211 with 1 keyway according to DIN 6885-1
- Square bore according to EN ISO 5211
- Two-flat according to EN ISO 5211
Valve attachment Dimensions according to EN ISO 5211

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.987/003/en Issue 1.16 Page 1/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1, Profibus DP
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Features and functions of actuator controls


Power supply Standard voltages:
1-phase AC current
Voltages/frequencies
Volt 115 230
Hz 50/60 50/60

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
For current consumption, refer to Electrical data Part-turn actuators SGC/SGCR
External supply of the electronics 24 V DC +20 %/–15 %,
(option) Current consumption: With options up to 200 mA
The external power supply must have reinforced insulation against mains voltage in accordance with IEC
61800-5-1 and may only be supplied by a circuit limited to 150 VA in accordance with IEC 61800-5-1.
Overvoltage category Category III according to IEC 60364-4-443
Power electronics Power electronics with integral motor controller
Rated power Controls are designed for rated motor power, refer to Electrical Data Part-turn actuators SGC/SGCR
Control Operation commands and setpoint via fieldbus interface
(input signals)
Status signals Via fieldbus interface
(output signals)
Profibus DP-V1 (option) Access to parameters, the electronic name plate and the operating and diagnostic services with acyclic write/
read services
Local controls Standard:  Push buttons OPEN, STOP (LOCAL - REMOTE), CLOSE
 2 multi-colour indication lights:
- End position CLOSED (yellow), fault/failure (red), end position OPEN (green),
operation mode LOCAL (blue)
Option: Local controls mounted separately on wall bracket
Functions  Switch-off mode adjustable:
- Limit or torque seating for end positions OPEN and CLOSED
 Torque monitoring across the whole travel
 Torque by-pass
 Programmable EMERGENCY behaviour
- via fieldbus interface
- Reaction can be selected: Stop, run to end position CLOSED, run to end position OPEN
 Positioner:
- Position setpoint via fieldbus interface
- Programmable behaviour on loss of signal
- Automatic adaptation of dead band (adaptive behaviour selectable)
- Selection between open-close duty and modulating duty via fieldbus interface
Electrical connection Standard: Plug/socket connector with crimp connection
Option: AUMA plug/socket connector with screw-type connection
Wiring diagram (basic version) TPCBA000-2A7-0540 TPA50R200-0A0-000

Settings/programming the Profibus DP interface


Baud rate setting Automatic baud rate recognition
Setting the Profibus DP interface Setting of the Profibus DP address is performed via switches, alternatively also via parameters
Configurable process representation For an optimum adaptation to the process control system, the process representation can be configured as
via GSD file desired.

General Profibus DP interface data


Communication protocol Profibus DP according to IEC 61158 and IEC 61784-1
Network topology  Line (fieldbus) structure.
 When using repeaters, tree structures can also be implemented.
 Coupling and uncoupling of devices during operation without affecting other devices is possible.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.987/003/en Issue 1.16 Page 2/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1, Profibus DP
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Transmission medium Twisted, screened copper cable according to IEC 61158


Fieldbus interface EIA-485 (RS485)
Transmission rate/cable length  Baud rate and maximum cable length (segment length) without repeater:
- between 9.6 and 93.75 kbit/s: 1,200 m
- for 187.5 kbit/s: 1,000 m
- for 500 kbit/s: 400 m
- for 1,500 kbit/s: 200 m
 Baud rate and possible cable length with repeater (total network cable length):
- between 9.6 and 93.75 kbit/s: approx. 10 km
- for 187.5 kbit/s: approx. 10 km
- for 500 kbit/s: approx. 4 km
- for 1,500 kbit/s: approx. 2 km
Device types  DP master class 1, e.g. central controllers such as PLC, PC, ...
 DP master class 2, e.g. programming/configuration tools
 DP slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators, sensors
Number of devices 32 devices without repeater, with repeater expandable to 126
Fieldbus access  Token-passing between masters and polling for slaves
 Mono-master or multi-master systems are possible
Supported fieldbus functions Cyclic data exchange, sync mode, freeze mode, fail-safe mode
Profibus DP ident no. 0x0C77: Standard applications with Profibus DP-V0 and DP-V1

Commands and signals of the Profibus DP interface


Process representation output OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, motor speed
(command signals)
Process representation input  End positions OPEN, CLOSED
(feedback signals)  Actual position value
 Selector switch in position LOCAL/REMOTE
 Torque switches OPEN, CLOSED
 Limit switches OPEN, CLOSED
Process representation input  Motor protection tripped
(fault signals)  Torque switch tripped in mid-travel
Behaviour on loss of communication The behaviour of the actuator is programmable:
- Stop in current position
- Travel to end position OPEN or CLOSED
- Travel to any intermediate position
- Execute last received operation command

Service conditions
Mounting position Any position
Installation altitude ≤ 2 000 m above seal level
> 2,000 m above sea level on request
Ambient temperature –25 °C to +70 °C
Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection according to IP68
EN 60529 According to AUMA definition, enclosure protection IP68 meets the following requirements:
 Depth of water: maximum 8 m head of water
 Duration of continuous immersion in water: Max. 96 hours
 Up to 10 operations during continuous immersion
 Modulating duty is not possible during continuous immersion
Pollution degree according to IEC Pollution degree 4 (when closed), pollution degree 2 (internal)
60664-1
Vibration resistance according to 2 g, from 10 Hz to 200 Hz
IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.987/003/en Issue 1.16 Page 3/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1, Profibus DP
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

GL approval (option) Environmental categories D, G, EMC2


Corrosion protection Standard: KS Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option: KX Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime Open-close 20,000 operating cycles OPEN - CLOSE - OPEN
duty: An operating cycle is based on an operation from CLOSED to OPEN and back to CLOSED, at a
respective rotary movement of 90°.
Modulating 5 million modulating steps
duty:
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the
modulating accuracy. To reach the longest possible maintenance and fault-free operating time, the number of
starts per hour chosen should be as low as permissible for the process.

Further information
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions SGC 04.1– SGC 12.1/SGCR 04.1 – SGCR 12.1
Electrical data SGC 04.1– SGC 12.1/SGCR 04.1 – SGCR 12.1

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.987/003/en Issue 1.16 Page 4/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1, Modbus RTU
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Type Operating time for 90° Torque range1) Running Valve attach- Valve shaft Handwheel Weight4)
in seconds torque2)/ ment
(adjustable in 9 steps) Modulating
torque3)
Max. Max. Standard Cylindrical Square Two-flat Ø Turns approx.
50 Hz/60 Hz [Nm] [Nm] EN ISO 5211 max. [mm] max. [mm] max. [mm] [mm] for 90° [kg]
SGC/SGCR 04.1 4 – 63 25 – 63 32 F05/F07 20 17 17 100 13.5 7.0
SGC/SGCR 05.1 4 – 63 50 – 125 63 F05/F07 20 17 17 100 13.5 7.0
SGC/SGCR 07.1 4 – 63 100 – 250 125 F07 25.4 22 22 125 13.5 10
SGC/SGCR 10.1 5.6 – 90 200 – 500 250 F10 38 30 27 160 13.5 15
SGC/SGCR 12.1 20 – 275 400 – 1,000 500 F12 50 36 41 125 35 25

Notes on table
1) Unseating torque The “Torque by-pass” function (can be activated) allows increasing the pre-set torque to 130 %. This increase
only applies during actuator start for an adjustable time period, allowing safer unseating of blocked valves.
2) Running torque Maximum permissible torque for 15 min. running time.
3) Modulating torque Maximum permissible torque for modulating duty
4) Weight Indicated weight includes part-turn actuator with controls, electrical connection in standard version, unbored
coupling and handwheel

Features and functions of actuator


Type of duty Open-close Short-time duty S2 - 15 min, classes A and B according to EN 15714-2
duty
SGC:
Modulating Intermittent duty S4 - 40 %, class C according to EN 15714-2
duty with maximum number of starts of 1,800 cycles per hour (option)
SGCR:
For nominal voltage and +40 °C ambient temperature and at running or modulating torque load. The type of
duty must not be exceeded.
Motor Variable speed, brushless motor
Insulation class F, tropicalized
Motor protection PTC thermistors (according to DIN 44081)
Self-locking Yes
Swing angle Standard: SGC/SGCR 04.1 – 10.1: 82° – 98° adjustable between min. and max. values
SGC/SGCR 12.1: 75 ° – 105°
Options: Available swing angles on request
Limit switching Via position transmitter potentiometer, status signals for directions OPEN and CLOSE
Signalling via fieldbus interface
Torque switching Via electronic current measurement, status signals for directions OPEN and CLOSE, adjustable in 8 steps
Signalling via fieldbus interface
Mechanical position indicator Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Manual operation Manual drive for setting and emergency operation, handwheel does not rotate during electrical operation
Coupling Standard: Coupling unbored
Options:  Coupling unbored extended
 Finish machining of coupling (standard or extended)
- Bore according to EN ISO 5211 with 1 keyway according to DIN 6885-1
- Square bore according to EN ISO 5211
- Two-flat according to EN ISO 5211
Valve attachment Dimensions according to EN ISO 5211

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.203/003/en Issue 1.16 Page 1/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1, Modbus RTU
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Features and functions of actuator controls


Power supply Standard voltages:
1-phase AC current
Voltages/frequencies
Volt 115 230
Hz 50/60 50/60

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
For current consumption, refer to Electrical data Part-turn actuators SGC/SGCR
External supply of the electronics 24 V DC +20 %/–15 %,
(option) Current consumption: With options up to 200 mA
The external power supply must have reinforced insulation against mains voltage in accordance with IEC
61800-5-1 and may only be supplied by a circuit limited to 150 VA in accordance with IEC 61800-5-1.
Overvoltage category Category III according to IEC 60364-4-443
Power electronics Power electronics with integral motor controller
Rated power Controls are designed for rated motor power, refer to Electrical Data Part-turn actuators SGC/SGCR
Control Operation commands and setpoint via fieldbus interface
(input signals)
Status signals Via fieldbus interface
(output signals)
Local controls Standard:  Push buttons OPEN, STOP (LOCAL - REMOTE), CLOSE
 2 multi-colour indication lights:
- End position CLOSED (yellow), fault/failure (red), end position OPEN (green),
operation mode LOCAL (blue)
Option: Local controls mounted separately on wall bracket
Functions  Switch-off mode adjustable:
- Limit or torque seating for end positions OPEN and CLOSED
 Torque monitoring across the whole travel
 Torque by-pass
 Programmable EMERGENCY behaviour
- via fieldbus interface
- Reaction can be selected: Stop, run to end position CLOSED, run to end position OPEN
 Positioner:
- Position setpoint via fieldbus interface
- Programmable behaviour on loss of signal
- Automatic adaptation of dead band (adaptive behaviour selectable)
- Selection between open-close duty and modulating duty via fieldbus interface
Electrical connection Standard: Plug/socket connector with crimp connection
Option: Plug/socket connector with screw-type connection
Wiring diagram (basic version) TPCBC000-2A7-0540 TPA50R200-0A0-000

Settings/programming the Modbus RTU interface


Setting the Modbus RTU interface The Modbus address is set via switches (DIP switches in the actuator), alternatively also via parameters (using
AUMA Software CDT and AUMA service cable Z100.999). Parity and baud rate are set via parameters.

General data of the Modbus RTU interface


Communication protocol Modbus RTU according to IEC 61158 and IEC 61784
Network topology Line (bus) structure. When using repeaters, tree structures can also be implemented. Coupling and uncoupling
of devices during operation without affecting other devices is possible.
Transmission medium Twisted, screened copper cable according to IEC 61158
Fieldbus interface EIA-485 (RS485)

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.203/003/en Issue 1.16 Page 2/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1, Modbus RTU
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Transmission rate/cable length Line topology:


Baud rate (kbit/s) Max. cable length Possible cable length with
(segment length) without repeater (total network cable
repeater length):
9.6 – 38.4 1,200 m approx. 10 km

Redundant loop topology:


Baud rate (kbit/s) Max. cable length Max. possible cable length of
between actuators redundant loop
(without repeater)
9.6 – 38.4 1,200 m approx. 290 km

Device types Modbus slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators, sensors
Number of devices 32 devices without repeater, with repeater expandable to 247
Fieldbus access Polling between master and slaves (query response).
Supported Modbus functions 01 Read Coil Status
(services)
02 Read Input Status
03 Read Holding Registers
04 Read Input Registers
05 Force Single Coil
15 (0FHex) Force Multiple Coils
06 Preset Single Register
16 (10Hex) Preset Multiple Registers
17 (11Hex) Report Slave ID
08 Diagnostics:
 00 00 Loopback
 00 10 (0AHex) Clear Counters and Diagnostic Register
 00 11 (0BHex) Return Bus Message Count
 00 12 (0CHex) Return Bus Communication Error Count
 00 13 (0DHex) Return Bus Exception Error Count
 00 14 (0EHex) Return Slave Message Count
 00 15 (0FHex) Return Slave No Response Count
 00 16 (10Hex) Return Slave NAK Count
 00 17 (11Hex) Return Slave Busy Count
 00 18 (12Hex) Return Character Overrun Count

Commands and signals of the Modbus RTU interface


Process representation output OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, motor speed
(command signals)
Process representation input  End positions OPEN, CLOSED
(feedback signals)  Actual position value
 Selector switch in position LOCAL/REMOTE
 Torque switches OPEN, CLOSED
 Limit switches OPEN, CLOSED
Process representation input  Motor protection tripped
(fault signals)  Torque switch tripped in mid-travel
Behaviour on loss of communication The behaviour of the actuator is programmable:
- Stop in current position
- Travel to end position OPEN or CLOSED
- Travel to any intermediate position
- Execute last received operation command

Service conditions
Mounting position Any position
Installation altitude ≤ 2 000 m above seal level
> 2,000 m above sea level on request

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.203/003/en Issue 1.16 Page 3/4


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1, Modbus RTU
Technical data Part-turn actuators with integral actuator controls
for open-close and modulating duty

Ambient temperature –25 °C to +70 °C


Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection according to IP68
EN 60529 According to AUMA definition, enclosure protection IP68 meets the following requirements:
 Depth of water: maximum 8 m head of water
 Duration of continuous immersion in water: Max. 96 hours
 Up to 10 operations during continuous immersion
 Modulating duty is not possible during continuous immersion
Pollution degree according to IEC Pollution degree 4 (when closed), pollution degree 2 (internal)
60664-1
Vibration resistance according to 2 g, from 10 Hz to 200 Hz
IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
GL approval (option) Environmental categories D, G, EMC2
Corrosion protection Standard: KS Suitable for use in areas with high salinity, almost permanent condensation,
and high pollution.
Option: KX Suitable for use in areas with extremely high salinity, permanent condensation,
and high pollution.
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime Open-close 20,000 operating cycles OPEN - CLOSE - OPEN
duty: An operating cycle is based on an operation from CLOSED to OPEN and back to CLOSED, at a
respective rotary movement of 90°.
Modulating 5 million modulating steps
duty:
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the
modulating accuracy. To reach the longest possible maintenance and fault-free operating time, the number of
starts per hour chosen should be as low as permissible for the process.

Further information
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions SGC 04.1– SGC 12.1/SGCR 04.1 – SGCR 12.1
Electrical data SGC 04.1– SGC 12.1/SGCR 04.1 – SGCR 12.1

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.203/003/en Issue 1.16 Page 4/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Type Output speed Torque Running Valve Valve shaft Stem Stem Handwheel Weight5)
rpm range1) torque2)/ attachment stroke diameter
Modulating
torque3)
for for
(adjustable in 9 Standard Cylindrical Square Two-flat rising valve rising valve Reduc-
steps) Max. Max. EN ISO max. max. max. stem4) stem4) Ø tion approx.
50 Hz/60 Hz [Nm] [Nm] 5211 [mm] [mm] [mm] max. [mm] max. [mm] [mm] ratio [kg]
SVC/SVCR
1.6 – 22 10 – 25 13 F05/F07 20 17 17 60 23 100 13 : 1 7.0
05.1
SVC/SVCR
1.6 – 22 20 – 50 25 F07 25.4 22 22 70 26 125 13 : 1 10
07.1
SVC/SVCR
0.6 – 8.0 40 – 100 50 F07 25.4 22 22 70 26 125 13 : 1 10
07.5

Notes on table
1) Unseating torque The “Torque by-pass” function (can be activated) allows increasing the pre-set torque to 130 %. This increase
only applies during actuator start for an adjustable time period, allowing safer unseating of blocked valves.
2) Running torque Maximum permissible torque for 15 min. running time.
3) Modulating torque Maximum permissible torque for modulating duty.
4) Rising valve stem For output drive type A
5) Weight Indicated weight includes globe valve actuator with controls, electrical connection in standard version,
unbored coupling and handwheel

Features and functions of actuator


Type of duty Open-close Short-time duty S2 - 15 min, classes A and B according to EN 15714-2
duty
SVC:
Modulating Intermittent duty S4 - 40 %, class C according to EN 15714-2
duty with maximum number of starts of 1,800 cycles per hour
SVCR:
For nominal voltage and +40 °C ambient temperature and at running or modulating torque load. The type of
duty must not be exceeded.
Motor Variable speed, brushless motor
Insulation class F, tropicalized
Motor protection PTC thermistors (according to DIN 44081)
Self-locking Yes
Limit switching  Via position transmitter potentiometer, status signals for directions OPEN and CLOSE
 Turns per stroke: Available in subranges out of a total range between 1 – 40 (heed max. stem stroke).
However, the turns per stroke can only be set within the subrange ordered. More than 40 turns per
stroke on request.
Torque switching Via electronic current measurement, status signals for directions OPEN and CLOSE, adjustable in 8 steps
Mechanical position indicator Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Manual operation Manual drive for setting and emergency operation, handwheel does not rotate during electrical operation
Coupling Standard: Coupling unbored
Options:  Coupling unbored extended
 Finish machining of coupling (standard or extended)
- Bore according to EN ISO 5211 with 1 keyway according to DIN 6885-1
- Square bore according to EN ISO 5211
- Two-flat according to EN ISO 5211
Valve attachment Standard: With coupling, dimensions according to EN ISO 5211
Options: With output drive type A
With LE linear thrust unit
With GS worm gearbox

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.988/003/en Issue 1.16 Page 1/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Features and functions of actuator controls


Power supply Standard voltages:
Wechselstrom
Spannungen/Frequenzen
Volt 115 230
Hz 50/60 50/60

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
For current consumption, refer to Electrical data Globe valve actuators SVC/SVCR
External supply of the electronics 24 V DC +20 %/–15 %,
(option) Current consumption: With options up to 200 mA
The external power supply must have reinforced insulation against mains voltage in accordance with IEC
61800-5-1 and may only be supplied by a circuit limited to 150 VA in accordance with IEC 61800-5-1.
Overvoltage category Category III according to IEC 60364-4-443
Power electronics Power electronics with integral motor controller
Rated power Controls are designed for rated motor power, refer to Electrical data Globe valve actuators SVC/SVCR
Control  4 digital inputs (via opto-isolator, with one common)
(input signals) - Control voltage 24 V DC, current consumption: approx. 15 mA per input
- Minimum pulse duration for shortest operation pulse: 100 ms
- All digital inputs must be supplied with the same potential.
Assignment for open-close actuators:
- OPEN, STOP, CLOSE (standard)
- OPEN, STOP, CLOSE, EMERGENCY (option)
- OPEN, STOP, CLOSE, MODE in combination with positioner (option)
- OPEN, EMERGENCY, CLOSE, MODE in combination with positioner (option)
Assignment for modulating actuators:
- OPEN, STOP, CLOSE, MODE (standard)
- OPEN, EMERGENCY, CLOSE, MODE (option)
 Analogue input 0/4 – 20 mA (galvanically isolated) (option)
Used as input signal for position setpoint E1 (in combination with positioner) or as input signal for motor
speed E3.
Status signals  Output contacts:
(output signals) 4 programmable semi-conductor output contacts, per contact max. 24 V DC, 1 A (resistive load)
- 2 NO contacts with one common
Default configuration: End position OPEN, end position CLOSED
- 1 potential-free NO contact for collective fault signal
Default configuration: Torque fault, motor protection tripped
- 1 potential-free change-over contact
Default configuration: Push button REMOTE
 Analogue output:
Galvanically isolated position feedback 0/4 – 20 mA (load 500 Ω).
Voltage output Auxiliary voltage 24 V DC, max. 40 mA for supply of control inputs, galvanically isolated from internal voltage
supply.
Not available for option "external electronics supply".
Local controls Standard:  Push buttons OPEN, STOP (LOCAL - REMOTE), CLOSE
 2 multi-colour indication lights:
- End position CLOSED (yellow), fault/failure (red), end position OPEN (green),
operation mode LOCAL (blue)
Option: Local controls mounted separately on wall bracket

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.988/003/en Issue 1.16 Page 2/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Functions  Switch-off mode adjustable:


- Limit or torque seating for end positions OPEN and CLOSED
 Torque monitoring across the whole travel
 Torque by-pass
 Programmable EMERGENCY behaviour
- Digital input low active,
- Reaction can be selected: Stop, run to end position CLOSED, run to end position OPEN
 Positioner (for modulating actuators):
- Position setpoint via analogue input E1 = 0/4 – 20 mA
- Programmable behaviour on loss of signal
- Automatic adaptation of dead band (adaptive behaviour selectable)
- Selection between open-close duty and modulating duty via digital MODE input
Electrical connection Standard: Plug/socket connector with crimp connection
Option: AUMA plug/socket connector with screw-type connection
Wiring diagram (basic version) Open-close TPC B-0E6-2C7-0530 TPA 50R200-0A0-000
duty:
Modulating TPC B-1H6-2C7-0530 TPA 50R200-0A0-000
duty:

Service conditions
Mounting position Any position
Installation altitude ≤ 2 000 m über NN
> 2,000 m above sea level on request
Ambient temperature –25 °C to +70 °C
Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection according to IP68
EN 60529 According to AUMA definition, enclosure protection IP68 meets the following requirements:
 Depth of water: maximum 8 m head of water
 Duration of continuous immersion in water: Max. 96 hours
 Up to 10 operations during continuous immersion
 Modulating duty is not possible during continuous immersion
Pollution degree according to IEC Pollution degree 4 (when closed), pollution degree 2 (internal)
60664-1
Vibration resistance according to 2 g, from 10 Hz to 200 Hz
IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
GL approval Environmental categories D, G, EMC2
Corrosion protection Standard: KS Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option: KX Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime Open-close 20,000 operating cycles OPEN - CLOSE - OPEN
duty: An operating cycle is based on an operation from CLOSED to OPEN and back to CLOSED
Modulating 5 million modulating steps
duty:
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the
modulating accuracy. To reach the longest possible maintenance and fault-free operating time, the number of
starts per hour chosen should be as low as permissible for the process.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.988/003/en Issue 1.16 Page 3/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Further information
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions SVC 05.1– SVC 07.5/SVCR 05.1 – SVCR 07.5
Electrical data SVC 05.1– SVC 07.5/SVCR 05.1 – SVCR 07.5

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.988/003/en Issue 1.16 Page 4/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5, Profibus DP
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Type Output speed Torque Running Valve Valve shaft Stem Stem Handwheel Weight5)
rpm range1) torque2)/ attachment stroke diameter
Modulating
torque3)
for for
(adjustable in 9 Standard Cylindrical Square Two-flat rising valve rising valve Reduc-
steps) Max. Max. EN ISO max. max. max. stem4) stem4) Ø tion approx.
50 Hz/60 Hz [Nm] [Nm] 5211 [mm] [mm] [mm] max. [mm] max. [mm] [mm] ratio [kg]
SVC/SVCR
1.6 – 22 10 – 25 13 F05/F07 20 17 17 60 23 100 13 : 1 7.0
05.1
SVC/SVCR
1.6 – 22 20 – 50 25 F07 25,4 22 22 70 26 125 13 : 1 10
07.1
SVC/SVCR
0.6 – 8.0 40 – 100 50 F07 25,4 22 22 70 26 125 13 : 1 10
07.5

Notes on table
1) Unseating torque The “Torque by-pass” function (can be activated) allows increasing the pre-set torque to 130 %. This increase
only applies during actuator start for an adjustable time period, allowing safer unseating of blocked valves.
2) Running torque Maximum permissible torque for 15 min. running time.
3) Modulating torque Maximum permissible torque for modulating duty
4) Rising valve stem For output drive type A
5) Weight Indicated weight includes globe valve actuator with controls, electrical connection in standard version,
unbored coupling and handwheel

Features and functions of actuator


Type of duty Open-close Short-time duty S2 - 15 min, classes A and B according to EN 15714-2
duty
SVC:
Modulating Intermittent duty S4 - 40 %, class C according to EN 15714-2
duty with maximum number of starts of 1,800 cycles per hour
SVCR:
For nominal voltage and +40 °C ambient temperature and at running or modulating torque load. The type of
duty must not be exceeded.
Motor Variable speed, brushless motor
Insulation class F, tropicalized
Motor protection PTC thermistors (according to DIN 44081)
Self-locking Yes
Limit switching  Via position transmitter potentiometer, status signals for directions OPEN and CLOSE
 Turns per stroke: Available in subranges out of a total range between 1 – 40 (heed max. stem stroke).
However, the turns per stroke can only be set within the subrange ordered. More than 40 turns per
stroke on request.
 Signalling for fi eldbus interface
Torque switching Via electronic current measurement, status signals for directions OPEN and CLOSE, adjustable in 8 steps
Signalling for fieldbus interface
Mechanical position indicator Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Manual operation Manual drive for setting and emergency operation, handwheel does not rotate during electrical operation
Coupling Standard: Coupling unbored
Options:  Coupling unbored extended
 Finish machining of coupling (standard or extended)
- Bore according to EN ISO 5211 with 1 keyway according to DIN 6885-1
- Square bore according to EN ISO 5211
- Two-flat according to EN ISO 5211
Valve attachment Standard: With coupling, dimensions according to EN ISO 5211
Options: With output drive type A
With LE linear thrust unit
With GS worm gearbox

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.989/003/en Issue 1.16 Page 1/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5, Profibus DP
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Features and functions of actuator controls


Power supply Standard voltages:
1-phase AC current
Voltages/frequencies
Volt 115 230
Hz 50/60 50/60

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
For current consumption, refer to Electrical data Globe valve actuators SVC/SVCR
External supply of the electronics 24 V DC +20 %/–15 %,
(option) Current consumption: With options up to 200 mA
The external power supply must have reinforced insulation against mains voltage in accordance with IEC
61800-5-1 and may only be supplied by a circuit limited to 150 VA in accordance with IEC 61800-5-1.
Overvoltage category Category III according to IEC 60364-4-443
Power electronics Power electronics with integral motor controller
Rated power Controls are designed for rated motor power, refer to Electrical data Globe valve actuators SVC/SVCR
Control Operation commands and setpoint via fieldbus interface
(input signals)
Status signals Via fieldbus interface
(output signals)
Profibus DP-V1 (option) Access to parameters, the electronic name plate and the operating and diagnostic services with acyclic write/
read services
Local controls Standard:  Push buttons OPEN, STOP (LOCAL - REMOTE), CLOSE
 2 multi-colour indication lights:
- End position CLOSED (yellow), fault/failure (red), end position OPEN (green),
operation mode LOCAL (blue)
Option: Local controls mounted separately on wall bracket
Functions  Switch-off mode adjustable:
- Limit or torque seating for end positions OPEN and CLOSED
 Torque monitoring across the whole travel
 Torque by-pass
 Programmable EMERGENCY behaviour
- via fieldbus interface
- Reaction can be selected: Stop, run to end position CLOSED, run to end position OPEN
 Programmable behaviour in case of loss of bus communication
 Positioner:
- Position setpoint via fieldbus interface
- Programmable behaviour on loss of signal
- Automatic adaptation of dead band (adaptive behaviour selectable)
- Selection between open-close duty and modulating duty via fieldbus interface
Electrical connection Standard: Plug/socket connector with crimp connection
Option: AUMA plug/socket connector with screw-type connection
Wiring diagram (basic version) TPCBA000-2A7-0540 TPA50R200-0A0-000

Settings/programming the Profibus DP interface


Baud rate setting Automatic baud rate recognition
Setting the Profibus DP interface Setting of the Profibus DP address is performed via switches, alternatively also via parameters
Configurable process representation For an optimum adaptation to the process control system, the process representation can be configured as
via GSD file desired.

General Profibus DP interface data


Communication protocol Profibus DP according to IEC 61158 and IEC 61784-1
Network topology  Line (fieldbus) structure.
 When using repeaters, tree structures can also be implemented.
 Coupling and uncoupling of devices during operation without affecting other devices is possible.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.989/003/en Issue 1.16 Page 2/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5, Profibus DP
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Transmission medium Twisted, screened copper cable according to IEC 61158


Fieldbus interface EIA-485 (RS485)
Transmission rate/cable length  Baud rate and maximum cable length (segment length) without repeater:
- between 9.6 and 93.75 kbit/s: 1,200 m
- for 187.5 kbit/s: 1,000 m
- for 500 kbit/s: 400 m
- for 1,500 kbit/s: 200 m
 Baud rate and possible cable length with repeater (total network cable length):
- between 9.6 and 93.75 kbit/s: approx. 10 km
- for 187.5 kbit/s: approx. 10 km
- for 500 kbit/s: approx. 4 km
- for 1,500 kbit/s: approx. 2 km
Device types  DP master class 1, e.g. central controllers such as PLC, PC, ...
 DP master class 2, e.g. programming/configuration tools
 DP slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators, sensors
Number of devices 32 devices without repeater, with repeater expandable to 126
Fieldbus access  Token-passing between masters and polling for slaves
 Mono-master or multi-master systems are possible
Supported fieldbus functions Cyclic data exchange, sync mode, freeze mode, fail-safe mode
Profibus DP ident no. 0x0C77: Standard applications with Profibus DP-V0 and DP-V1

Commands and signals of the Profibus DP interface


Process representation output OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, motor speed
(command signals)
Process representation input  End positions OPEN, CLOSED
(feedback signals)  Actual position value
 Selector switch in position LOCAL/REMOTE
 Torque switches OPEN, CLOSED
 Limit switches OPEN, CLOSED
Process representation input  Motor protection tripped
(fault signals)  Torque switch tripped in mid-travel
Behaviour on loss of communication The behaviour of the actuator is programmable:
- Stop in current position
- Travel to end position OPEN or CLOSED
- Travel to any intermediate position
- Execute last received operation command

Service conditions
Mounting position Any position
Installation altitude ≤ 2 000 m über NN
> 2,000 m above sea level on request
Ambient temperature –25 °C to +70 °C
Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection according to IP68
EN 60529 According to AUMA definition, enclosure protection IP68 meets the following requirements:
 Depth of water: maximum 8 m head of water
 Duration of continuous immersion in water: Max. 96 hours
 Up to 10 operations during continuous immersion
 Modulating duty is not possible during continuous immersion
Pollution degree according to IEC Pollution degree 4 (when closed), pollution degree 2 (internal)
60664-1
Vibration resistance according to 2 g, from 10 Hz to 200 Hz
IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
GL approval (option) Environmental categories D, G, EMC2

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.989/003/en Issue 1.16 Page 3/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5, Profibus DP
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Corrosion protection Standard: KS Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option: KX Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime Open-close 20,000 operating cycles OPEN - CLOSE - OPEN
duty: An operating cycle is based on an operation from CLOSED to OPEN and back to CLOSED
Modulating 5 million modulating steps
duty:
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the
modulating accuracy. To reach the longest possible maintenance and fault-free operating time, the number of
starts per hour chosen should be as low as permissible for the process.

Further information
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions SVC 05.1– SVC 07.5/SVCR 05.1 – SVCR 07.5
Electrical data SVC 05.1– SVC 07.5/SVCR 05.1 – SVCR 07.5

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.989/003/en Issue 1.16 Page 4/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5, Modbus RTU
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Type Output speed Torque Running Valve Valve shaft Stem Stem Handwheel Weight5)
rpm1) range torque2)/ attachment stroke diameter
Modulating
torque3)
for for
(adjustable in 9 Standard Cylindrical Square Two-flat rising valve rising valve Reduc-
steps) Max. Max. EN ISO max. max. max. stem4) stem4) Ø tion approx.
50 Hz/60 Hz [Nm] [Nm] 5211 [mm] [mm] [mm] max. [mm] max. [mm] [mm] ratio [kg]
SVC/SVCR
1.6 – 22 10 – 25 13 F05/F07 20 17 17 60 23 100 13 : 1 7.0
05.1
SVC/SVCR
1.6 – 22 20 – 50 25 F07 25.4 22 22 70 26 125 13 : 1 10
07.1
SVC/SVCR
0.6 – 8.0 40 – 100 50 F07 25.4 22 22 70 26 125 13 : 1 10
07.5

Notes on table
1) Unseating torque The “Torque by-pass” function (can be activated) allows increasing the pre-set torque to 130 %. This increase
only applies during actuator start for an adjustable time period, allowing safer unseating of blocked valves.
2) Running torque Maximum permissible torque for 15 min. running time.
3) Modulating torque Maximum permissible torque for modulating duty.
4) Rising valve stem For output drive type A
5) Weight Indicated weight includes globe valve actuator with controls, electrical connection in standard version,
unbored coupling and handwheel

Features and functions of actuator


Type of duty Open-close Short-time duty S2 - 15 min, classes A and B according to EN 15714-2
duty
SVC:
Modulating Intermittent duty S4 - 40 %, class C according to EN 15714-2
duty with maximum number of starts of 1,800 cycles per hour (option)
SVCR:
For nominal voltage and +40 °C ambient temperature and at running or modulating torque load. The type of
duty must not be exceeded.
Motor Variable speed, brushless motor
Insulation class F, tropicalized
Motor protection PTC thermistors (according to DIN 44081)
Self-locking Yes
Limit switching  Via position transmitter potentiometer, status signals for directions OPEN and CLOSE
 Turns per stroke: Available in subranges out of a total range between 1 – 40 (heed max. stem stroke).
However, the turns per stroke can only be set within the subrange ordered. More than 40 turns per
stroke on request
 Signalling for fieldbus interface
Torque switching Via electronic current measurement, status signals for directions OPEN and CLOSE, adjustable in 8 steps
Signalling for fieldbus interface
Mechanical position indicator Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Manual operation Manual drive for setting and emergency operation, handwheel does not rotate during electrical operation
Coupling Standard: Coupling unbored
Options:  Coupling unbored extended
 Finish machining of coupling (standard or extended)
- Bore according to EN ISO 5211 with 1 keyway according to DIN 6885-1
- Square bore according to EN ISO 5211
- Two-flat according to EN ISO 5211
Valve attachment Standard: With coupling, dimensions according to EN ISO 5211
Options: With output drive type A
With LE linear thrust unit
With GS worm gearbox

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.206/003/en Issue 1.16 Page 1/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5, Modbus RTU
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Features and functions of actuator controls


Power supply Standard voltages:
Wechselstrom
Spannungen/Frequenzen
Volt 115 230
Hz 50/60 50/60

Permissible variation of mains voltage: ±10 %


Permissible variation of mains frequency: ±5 %
For current consumption, refer to Electrical data Globe valve actuators SVC/SVCR
External supply of the electronics 24 V DC +20 %/–15 %,
(option) Current consumption: With options up to 200 mA
The external power supply must have reinforced insulation against mains voltage in accordance with IEC
61800-5-1 and may only be supplied by a circuit limited to 150 VA in accordance with IEC 61800-5-1.
Overvoltage category Category III according to IEC 60364-4-443
Power electronics Power electronics with integral motor controller
Rated power Controls are designed for rated motor power, refer to Electrical data Globe valve actuators SVC/SVCR
Control Operation commands and setpoint via fieldbus interface
(input signals)
Status signals Via fieldbus interface
(output signals)
Local controls Standard:  Push buttons OPEN, STOP (LOCAL - REMOTE), CLOSE
 2 multi-colour indication lights:
- End position CLOSED (yellow), fault/failure (red), end position OPEN (green),
operation mode LOCAL (blue)
Option: Local controls mounted separately on wall bracket
Functions  Switch-off mode adjustable:
- Limit or torque seating for end positions OPEN and CLOSED
 Torque monitoring across the whole travel
 Torque by-pass
 Programmable EMERGENCY behaviour
- via fieldbus interface
- Reaction can be selected: Stop, run to end position CLOSED, run to end position OPEN
 Programmable behaviour in case of loss of bus communication
 Positioner:
- Position setpoint via fieldbus interface
- Programmable behaviour on loss of signal
- Automatic adaptation of dead band (adaptive behaviour selectable)
- Selection between open-close duty and modulating duty via fieldbus interface
Electrical connection Standard: Plug/socket connector with crimp connection
Option: AUMA plug/socket connector with screw-type connection
Wiring diagram (basic version) TPCBC000-2A7-0540 TPA50R200-0A0-000

Settings/programming the Modbus RTU interface


Setting the Modbus RTU interface The Modbus address is set via switches (DIP switches in the actuator), alternatively also via parameters (using
AUMA Software CDT and AUMA service cable Z100.999). Parity and baud rate are set via parameters.

General data of the Modbus RTU interface


Communication protocol Modbus RTU according to IEC 61158 and IEC 61784-1
Network topology Line (bus) structure. When using repeaters, tree structures can also be implemented. Coupling and uncoupling
of devices during operation without affecting other devices is possible.
Transmission medium Twisted, screened copper cable according to IEC 61158
Fieldbus interface EIA-485 (RS485)

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.206/003/en Issue 1.16 Page 2/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5, Modbus RTU
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Transmission rate/cable length Line topology:


Baud rate (kbit/s) Max. cable length Possible cable length with
(segment length) without repeater (total network cable
repeater length):
9.6 – 38.4 1,200 m approx. 10 km

Redundant loop topology:


Baud rate (kbit/s) Max. cable length Max. possible cable length of
between actuators redundant loop
(without repeater)
9.6 – 38.4 1,200 m approx. 290 km

Device types Modbus slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators, sensors
Number of devices 32 devices without repeater, with repeater expandable to 247
Fieldbus access Polling between master and slaves (query response).
Supported Modbus functions 01 Read Coil Status
(services)
02 Read Input Status
03 Read Holding Registers
04 Read Input Registers
05 Force Single Coil
15 (0FHex) Force Multiple Coils
06 Preset Single Register
16 (10Hex) Preset Multiple Registers
17 (11Hex) Report Slave ID
08 Diagnostics:
 00 00 Loopback
 00 10 (0AHex) Clear Counters and Diagnostic Register
 00 11 (0BHex) Return Bus Message Count
 00 12 (0CHex) Return Bus Communication Error Count
 00 13 (0DHex) Return Bus Exception Error Count
 00 14 (0EHex) Return Slave Message Count
 00 15 (0FHex) Return Slave No Response Count
 00 16 (10Hex) Return Slave NAK Count
 00 17 (11Hex) Return Slave Busy Count
 00 18 (12Hex) Return Character Overrun Count

Commands and signals of the Modbus RTU interface


Process representation output OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, motor speed
(command signals)
Process representation input  End positions OPEN, CLOSED
(feedback signals)  Actual position value
 Selector switch in position LOCAL/REMOTE
 Torque switches OPEN, CLOSED
 Limit switches OPEN, CLOSED
Process representation input  Motor protection tripped
(fault signals)  Torque switch tripped in mid-travel
Behaviour on loss of communication The behaviour of the actuator is programmable:
- Stop in current position
- Travel to end position OPEN or CLOSED
- Travel to any intermediate position
- Execute last received operation command

Service conditions
Mounting position Any position
Installation altitude ≤ 2 000 m above seal level
> 2,000 m above sea level on request

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.206/003/en Issue 1.16 Page 3/4


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5, Modbus RTU
Technical data Globe valve actuators with integral actuator controls
for open-close and modulating duty

Ambient temperature –25 °C to +70 °C


Humidity Up to 100 % relative humidity across the entire permissible temperature range
Enclosure protection according to IP68
EN 60529 According to AUMA definition, enclosure protection IP68 meets the following requirements:
 Depth of water: maximum 8 m head of water
 Duration of continuous immersion in water: Max. 96 hours
 Up to 10 operations during continuous immersion
 Modulating duty is not possible during continuous immersion
Pollution degree according to IEC Pollution degree 4 (when closed), pollution degree 2 (internal)
60664-1
Vibration resistance according to 2 g, from 10 Hz to 200 Hz
IEC 60068-2-6 Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
GL approval (option) Environmental categories D, G, EMC2
Corrosion protection Standard: KS Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Option: KX Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Coating Double layer powder coating
Two-component iron-mica combination
Colour Standard: AUMA silver-grey (similar to RAL 7037)
Option: Available colours on request
Lifetime Open-close 20,000 operating cycles OPEN - CLOSE - OPEN
duty: An operating cycle is based on an operation from CLOSED to OPEN and back to CLOSED
Modulating 5 million modulating steps
duty:
The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the
modulating accuracy. To reach the longest possible maintenance and fault-free operating time, the number of
starts per hour chosen should be as low as permissible for the process.

Further information
EU Directives Electromagnetic Compatibility (EMC): (2014/30/EU)
Low Voltage Directive: (2014/35/EU)
Machinery Directive: (2006/42/EC)
Reference documents Dimensions SVC 05.1– SVC 07.5/SVCR 05.1 – SVCR 07.5
Electrical data SVC 05.1– SVC 07.5/SVCR 05.1 – SVCR 07.5

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.206/003/en Issue 1.16 Page 4/4


2 Technical data Miscellaneous

Connectors

2. Technical Data
Miscellaneous
Connectors SGC/SGCR, SVC/SVCR Parallel interface 44
Connectors SGC/SGCR, SVC/SVCR Profibus DP, Modbus RTU 45

Corrosion protection
Types of corrosion protection 46
Corrosion protection KS in acc. to painting spec. P1.001 47
Corrosion protection KS in acc. to painting spec. P1.002 48
Corrosion protection KX in acc. to painting spec. P1.002 50

Painting specifications
Painting specification P1.001 52
Painting specification P1.002 53

Lubricants
Grease and oil quantities 54
Ambient temperatures/lubricant in the gear housing 57
SGC/SGCR, SVC/SVCR
Parallel interface
Technical data Connector

Phoenix connectors Power contacts Protective earth Control contacts

No. of contacts max. 2 (+3) 1 19


Designation 1, 2 (4, 5, 6) PE 1 – 19
Connection voltage max. 230 V (630 V) – 24 V (150 V)
Rated current max. 10 A (30 A) – 1 A (8 A)
Type of customer termina-
Crimp
tion
Connection diameter max. 1.5 mm² 1.5 mm² 1 mm²
Material - pin socket carrier Polyamide
Material - contacts Brass/gold

General information
Mating plugs used as connecting plug for the customer are called plug and socket assemblies. The plug and socket assembly is the interface to the
actuator.
Cable diameter Power plug (power sup- 2 – 14.5 mm
ply):
Signal connector 2 – 10.5 mm
(parallel interface):
AUMA article numbers Plug and socket assembly for power supply and parallel interface: Z100.935A
including:
6-pin K007.818A Power connector (1x) in KS (KX on request)
K007.814 Crimp contact (6x) [RC-5CS2000]
19-pin K007.819 Signal connector (1x) in KS (KX on request)
K007.816 Crimp contact (16x) [RC-67S2000]
K007.877 Crimp contact (2x) [RC-6ES2000]
K007.817 Crimp contact (1x) [RC-6FS2000]
Crimping pliers (for signal and power Phoenix designation: 4-arbor crimping pliers with digital display for turned contacts: RC-Z2514
connectors) AUMA article number: K008.074
Phoenix designation: 4-arbor crimping pliers for turned contacts: RC-Z2504
AUMA article number: K008.106
Crimping pliers settings
AUMA Phoenix designation Cross section Crimp arbor setting Locator
(RC-Z2514/RC-Z2504)
article number crimp contact [mm²] [mm]
(for signal and power connectors)
1.00 0.97
K007.814 RC-5CS2000 5
1.50 1.02
0.75 0.85
K007.816 RC-67S2000 7
1.00 0.88
0.75 0.85
K007.877 RC-6ES2000 9
1.00 0.88
0.75 0.85
K007.817 RC-6FS2000 9
1.00 0.88

Insertion and ejection tool Phoenix designation: Insertion and ejection tool for RC crimp contacts Ø 1 mm: RC-Z2494
(for signal and power connectors) AUMA article number: K008.107
Phoenix designation: Insertion and ejection tool for RC crimp contacts Ø 1.5 mm: RC-Z2274
AUMA article number: K008.108
Ready-made mating connectors
Phoenix designation Power connectors Signal connectors
with cables
cable length as desired in xxx cable length as desired in xxx
metres metres
Straight KC-03018EKC1xxx KC-01618EBK1xxx
90° angled KC-0301TEKC1xxx KC-0161TEBK1Axxx

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y005.471/003/en Issue 1.13 Page 1/1


SGC/SGCR, SVC/SVCR
Profibus DP, Modbus RTU
Technical data Connector

Phoenix connectors Power contacts Protective earth Control contacts

No. of contacts max. 2 (+3) 1 5


Designation 1, 2 (4, 5, 6) PE 1–5
Connection voltage max. 230 V (630 V) – 24 V (60 V)
Rated current max. 10 A (30 A) – 1 A (4 A)
Type of customer termina-
Crimp Screw
tion
Connection diameter max. 1.5 mm² 1.5 mm² 0.75 mm²
Material - pin socket carrier Polyamide
Material - contacts Brass/gold

General information
Mating plugs used as connecting plug for the customer are called plug and socket assemblies. The plug and socket assembly is the interface to the
actuator.
Cable diameter Power plug (power supply): 2 – 14.5 mm
Signalstecker (Businter- 6 – 8.5 mm
face):
AUMA article numbers Connection set power supply and bus interface: Z107.125
consisting of:
6-pin K007.818 Power connector (1x) in KS (KX on request)
K007.814 Crimp contact (6x) [RC-5CS2000]
5-pin K007.885 Signal connector complete (1x) in KS (KX on request)
K007.884 Female contact complete (1x) in KS (KX on request)
Crimping pliers (for power connectors) Phoenix designation: 4-arbor crimping pliers with digital display for turned contacts: RC-Z2514
AUMA article number: K008.074
Phoenix designation: 4-arbor crimping pliers for turned contacts: RC-Z2504
AUMA article number: K008.106
Crimping pliers settings
AUMA Phoenix designation Cross section Crimp arbor setting Locator
(RC-Z2514/RC-Z2504)
article number crimp contact [mm²] [mm]
(for power connectors)
1.00 0.97
K007.814 RC-5CS2000 5
1.50 1.02

Insertion and ejection tool Phoenix designation: Insertion and ejection tool for RC crimp contacts Ø 1.5 mm: RC-Z2274
(for power connectors) AUMA article number: K008.108
Ready-made mating connectors
Phoenix designation Power connectors Signal connector (bus interface)
with cables
cable length as desired in xxx Cable length 15 metres with male and
metres female connectors at each end, respectively
made of plastic material
Straight KC-03018EKC1xxx K008.217
90° angled KC-0301TEKC1xxx K008.260

T or Y connector for bus interface Alternatively for bus interface: 1 connector (type T or Y) instead of to separate connectors (IN and OUT)
Used as additional intermediate component to maintain bus communication in case AUMA actuator is
switched off or disconnected from bus.
AUMA article numbers:
T connector: K008.456 (large)
K005.816 (small)
Y connector: K006.135

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y005.472/003/en Issue 1.13 Page 1/1


Types of corrosion protection

Technical description Types of corrosion protection

This overview accounts for atmospheric ambient conditions, but not for special chemical atmospheres, requiring absence
of aluminium or nonferrous heavy metal, for example.

Corrosivity categories in accordance with ISO 12944-2 AUMA


and EN 15714-2
Classification of environments Painting specification
Corrosion protection
(total film thickness)
Powder coating Liquid paint
C1 (very low):
Heated buildings with clean atmospheres
N1.001
C2 (low): KN
(60 µm)
Unheated buildings and rural areas with low level of
pollution
C3 (medium):
Production rooms with humidity and moderate pollu-
tion. Urban and industrial areas with moderate pollution N1.003
P1.001
(140 µm)
C4 (high): (140 µm)
KS
Chemical plants and areas with moderate salinity
C5-M (very high, marine):
Coastal and offshore areas with high salinity, almost
permanent condensation and high pollution
C5-I (very high, industrial):
N1.008
Industrial areas with almost permanent condensation KX (220 µm)
and aggressive atmosphere
Extreme (cooling tower): KX
P1.002
Areas with extremely high salinity, permanent condensa- KX-G (200 µm)
tion and aggressive atmosphere (KX-aluminium-free)

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.628/003/en Issue 1.17 Page 1/1


Corrosion protection
Technical description Corrosion protection KS with powder coating
in accordance with painting specification P1.001

This description applies to AUMA products with powder coating in accordance with painting specification P1.001.

Corrosion protection KS based on painting specification P1.001 is suitable for use in areas with high salinity, almost permanent conden-
sation, and high pollution. Corrosion protection includes the use of suitable material for outer parts and structure of the painting.

1. Materials
1.1 Outside fasteners (e.g. screws) are made of stainless steel with additional metallic surface protection.

1.2 Name plates are made of aluminium.

2. Surface treatment
2.1 After machining, steel parts are covered with metallic surface protection (except SQ/GS coupling and internal GS coupling
compartment)
2.2 Aluminium parts such as the handwheel are electrophoretically coated.

3. General information
3.1 Housing parts made of GJL/GJS are blasted: Sa 2 ½ in accordance with EN ISO 12944-4.
3.2 Aluminium housing parts are not blasted.

4. Painting system
4.1 During preliminary treatment, housing parts are chemically cleaned and painted with an Oxsilan® conversion coating.
4.2 Housing parts are primer coated with:
Product: FREOPOX PE 1204A
Manufacturer: Emil Frei GmbH & Co. KG
Structure: Thermally hardening powder coating based on epoxy resin.
Colour: RAL 7035
Film thickness: 70 µm

4.3 Housing parts are finish coated with:


Product: FREIOTHERM PU 4003M
Manufacturer: Emil Frei GmbH & Co. KG
Structure: Thermally hardening powder coating based on polyurethane.
Colour: A0001, AUMA silver-grey (similar to RAL 7037 dust grey)
Film thickness: 70 µm

5. Total film thickness (dry)


The average total film thickness (dry) of the powder coated housing is 140 µm.
For reasons of geometry, powder coating thickness varies between 60 µm and 220 µm. Variation of film thickness has no
impact on corrosion protection.

6. Notes
6.1 The top coat can be painted with all common 1- or 2-component coating materials (i.e. artificial resin, epoxy resin, PVC, polyu-
rethane, polyamide and acrylic enamels).
We recommend verifying the compatibility of the paints before applying a new wet painting layer.
For this, the surfaces to be painted must be slightly ground and carefully cleaned, i. e. free of foreign substance, grease, oily
dirt and dust.
6.2 Mounting surface to the valve is powder coated.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.714/003/en Issue 1.15 Page 1/1


Corrosion protection
Technical description Corrosion protection KS with powder coating
in accordance with painting specification P1.002

This description applies to AUMA products with powder coating in accordance with painting specification P1.002.

Corrosion protection KS based on painting specification P1.002 is suitable for use in areas with high salinity, almost permanent conden-
sation, and high pollution. Corrosion protection includes the use of suitable material for outer parts and structure of the painting.

1. Materials
1.1 Outside fasteners (e.g. screws) are made of stainless steel with additional metallic surface protection.
1.2 Name plates are made of aluminium.

2. Surface treatment
2.1 After machining, steel parts are covered with metallic surface protection (except SQ/GS coupling and internal GS coupling
compartment)
2.2 Aluminium parts such as the handwheel are electrophoretically coated.

3. General information
3.1 Housing parts made of GJL/GJS are blasted: Sa 2 ½ in accordance with EN ISO 12944-4.
3.2 Aluminium housing parts are not blasted.

4. Painting system
4.1 During preliminary treatment, housing parts are chemically cleaned and painted with an Oxsilan® conversion coating.
4.2 Housing parts are primer coated with:
Product: FREOPOX PE 1204A
Manufacturer: Emil Frei GmbH & Co. KG
Structure: Thermally hardening powder coating based on epoxy resin.
Colour: RAL 7035
Film thickness: 70 µm
4.3 Housing parts are finish coated with:
Product: FREIOTHERM PU 4003M
Manufacturer: Emil Frei GmbH & Co. KG
Structure: Thermally hardening powder coating based on polyurethane.
Colour: A0001, AUMA silver-grey (similar to RAL 7037 dust grey)
Film thickness: 70 µm

4.4 Finish painting


The finish painting is applied after device assembly and depends on the desired colour.

4.4.1 Housing parts are finish painted with:


Product: SikaCor EG 4
Manufacturer: Sika Deutschland GmbH
Structure: 2-component finish painting based on polyurethane with micaceous iron oxide
Colour: A0001, AUMA silver-grey (similar to RAL 7037 dust grey) or DB colour according to work order
Film thickness: 60 µm (dry)

4.4.2 Housing parts are coated with finish painting for special colours:
Product: SikaCor EG 5
Manufacturer: Sika Deutschland GmbH
Structure: 2-component finish painting based on polyurethane
Colour: Special colour according to work order
Film thickness: 60 µm (dry)

5. Total film thickness (dry)


Average total film thickness (dry) of the powder coated housings including finish painting is 200 µm.
For reasons of geometry, powder coating thickness varies between 60 µm and 220 µm. Variation of film thickness has no
impact on corrosion protection.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y005.628/003/en Issue 1.15 Page 1/2


Corrosion protection
Technical description Corrosion protection KS with powder coating
in accordance with painting specification P1.002

6. Notes
6.1 The top coat can be painted with all common 1- or 2-component coating materials (i.e. artificial resin, epoxy resin, PVC, polyu-
rethane, polyamide and acrylic enamels).
Subsequent finishing with chlorine rubber paints subject to restrictions.
We recommend verifying the compatibility of the paints before applying a new wet painting layer. For this, the surfaces to be
painted must be slightly ground and carefully cleaned, i. e. free of foreign substance, grease, oily dirt and dust.
6.2 Mounting surface to the valve is powder coated.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y005.628/003/en Issue 1.15 Page 2/2


Corrosion protection
Technical description Corrosion protection KX with powder coating
in accordance with painting specification P1.002

This description applies to AUMA products with powder coating in accordance with painting specification P1.002.

Corrosion protection KX based on painting specification P1.002 is suitable for use in areas with high salinity, almost permanent con-
densation, and high pollution. Corrosion protection includes the use of suitable material for outer parts and structure of the painting.

1. Materials
1.1 Outside fasteners (e.g. screws) are made of stainless steel with additional metallic surface protection.
1.2 Name plates are made of aluminium.

2. Surface treatment
2.1 After machining, steel parts are covered with metallic surface protection (except SQ/GS coupling and internal GS coupling
compartment)
2.2 Aluminium parts such as the handwheel are electrophoretically coated.

3. General information
3.1 Housing parts made of GJL/GJS are blasted: Sa 2 ½ in accordance with EN ISO 12944-4.
3.2 Aluminium housing parts are not blasted.

4. Painting system
4.1 During preliminary treatment, housing parts are chemically cleaned and painted with an Oxsilan® conversion coating.
4.2 Housing parts are primer coated with:
Product: FREOPOX PE 1204A
Manufacturer: Emil Frei GmbH & Co. KG
Structure: Thermally hardening powder coating based on epoxy resin.
Colour: RAL 7035
Film thickness: 70 µm
4.3 Housing parts are finish coated with:
Product: FREIOTHERM PU 4003M
Manufacturer: Emil Frei GmbH & Co. KG
Structure: Thermally hardening powder coating based on polyurethane.
Colour: A0001, AUMA silver-grey (similar to RAL 7037 dust grey)
Film thickness: 70 µm

4.4 Finish painting


The finish painting is applied after device assembly and depends on the desired colour.

4.4.1 Housing parts are finish painted with:


Product: SikaCor EG 4
Manufacturer: Sika Deutschland GmbH
Structure: 2-component finish painting based on polyurethane with micaceous iron oxide
Colour: A0001, AUMA silver-grey (similar to RAL 7037 dust grey) or DB colour according to work order
Film thickness: 60 µm (dry)

4.4.2 Housing parts are coated with finish painting for special colours:
Product: SikaCor EG 5
Manufacturer: Sika Deutschland GmbH
Structure: 2-component finish painting based on polyurethane
Colour: Special colour according to work order
Film thickness: 60 µm (dry)

5. Total film thickness (dry)


Average total film thickness (dry) of the powder coated housings including finish painting is 200 µm.
For reasons of geometry, powder coating thickness varies between 60 µm and 220 µm. Variation of film thickness has no
impact on corrosion protection.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.716/003/en Issue 1.15 Page 1/2


Corrosion protection
Technical description Corrosion protection KX with powder coating
in accordance with painting specification P1.002

6. Notes
6.1 The top coat can be painted with all common 1- or 2-component coating materials (i.e. artificial resin, epoxy resin, PVC, polyu-
rethane, polyamide and acrylic enamels).
Subsequent finishing with chlorine rubber paints subject to restrictions.
We recommend verifying the compatibility of the paints before applying a new wet painting layer. For this, the surfaces to be
painted must be slightly ground and carefully cleaned, i. e. free of foreign substance, grease, oily dirt and dust.
6.2 Mounting surface to the valve is powder coated.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.716/003/en Issue 1.15 Page 2/2


Painting specification P1.001

Technical description Powder coating, primer coating and finish coating

1. General information
1.1 Housing parts made of GJL/GJS are blasted: Sa 2 ½ in accordance with EN ISO 12944-4.
1.2 Aluminium housing parts are not blasted.

2. Painting system
2.1 During preliminary treatment, housing parts are chemically cleaned and painted with an Oxsilan® conversion coating.
2.2 Housing parts are primer coated with:
Product: FREOPOX PE 1204A
Manufacturer: Emil Frei GmbH & Co. KG
Structure: Thermally hardening powder coating based on epoxy resin.
Colour: RAL 7035
Film thickness: 70 µm

2.3 Housing parts are finish coated with:


Product: FREIOTHERM PU 4003M
Manufacturer: Emil Frei GmbH & Co. KG
Structure: Thermally hardening powder coating based on polyurethane.
Colour: A0001, AUMA silver-grey (similar to RAL 7037 dust grey)
Film thickness: 70 µm

3. Total film thickness (dry)


Average total film thickness (dry) of the powder coated housing is 140 µm.
For reasons of geometry, powder coating thickness varies between 60 µm and 220 µm. Variation of film thickness has no
impact on corrosion protection.

4. Notes
4.1 The top coat can be painted with all common 1- or 2-component coating materials (i.e. artificial resin, epoxy resin, PVC, polyu-
rethane, polyamide and acrylic enamels).
We recommend verifying the compatibility of the paints before applying a new wet painting layer.
For this, the surfaces to be painted must be slightly ground and carefully cleaned, i. e. free of foreign substance, grease, oily
dirt and dust.
4.2 Mounting surface to the valve is powder coated.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.477/001/de Issue 1.15 Page 1/1


Painting specification P1.002

Technical description Powder coating, primer coating, finish coating and wet painting layer

1. General information
1.1 Housing parts made of GJL/GJS are blasted: Sa 2 ½ in accordance with EN ISO 12944-4.
1.2 Aluminium housing parts are not blasted.

2. Painting system
2.1 During preliminary treatment, housing parts are chemically cleaned and painted with an Oxsilan® conversion coating.
2.2 Housing parts are primer coated with:
Product: FREOPOX PE 1204A
Manufacturer: Emil Frei GmbH & Co. KG
Structure: Thermally hardening powder coating based on epoxy resin.
Colour: RAL 7035
Film thickness: 70 µm

2.3 Housing parts are finish coated with:


Product: FREIOTHERM PU 4003M
Manufacturer: Emil Frei GmbH & Co. KG
Structure: Thermally hardening powder coating based on polyurethane.
Colour: A0001, AUMA silver-grey (similar to RAL 7037 dust grey)
Film thickness: 70 µm

2.4 Finish painting


The finish painting is applied after device assembly and depends on the desired colour.

2.4.1 Housing parts are finish painted with:


Product: SikaCor EG 4
Manufacturer: Sika Deutschland GmbH
Structure: 2-component finish painting based on polyurethane with micaceous iron oxide
Colour: A0001, AUMA silver-grey (similar to RAL 7037 dust grey) or DB colour according to work order
Film thickness: 60 µm (dry)

2.4.2 Housing parts are coated with finish painting for special colours:
Product: SikaCor EG 5
Manufacturer: Sika Deutschland GmbH
Structure: 2-component finish painting based on polyurethane
Colour: Special colour according to work order
Film thickness: 60 µm (dry)

3. Total film thickness (dry)


Average total film thickness (dry) of the powder coated housings including wet painting layer is 200 µm.
For reasons of geometry, powder coating thickness varies between 60 µm and 220 µm. Variation of film thickness has no
impact on corrosion protection.

4. Notes
4.1 The top coat can be painted with all common 1- or 2-component coating materials (i.e. artificial resin, epoxy resin, PVC, polyu-
rethane, polyamide and acrylic enamels). Subsequent finishing with chlorine rubber paints subject to restrictions.
We recommend verifying the compatibility of the paints before applying a new wet painting layer.
For this, the surfaces to be painted must be slightly ground and carefully cleaned, i. e. free of foreign substance, grease, oily
dirt and dust.
4.2 Mounting surface to the valve is powder coated.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.522/003/en Issue 1.15 Page 1/1


AUMA products

Technical data Grease and oil quantities

This data applies to1):


Multi-turn actuators SA 07.1 – SA 48.1; SAR 07.1 – SAR 30.1; SA 07.2 – SA 16.2; SAR 07.2 – SAR 16.2
SAExC 07.1 – SAExC 16.1; SARExC 07.1 – SARExC 16.1; SAEx 25.1 – SAEx 40.1; SAREx 25.1 – SAREx 30.1
SAEx 07.2 – SAEx 16.2; SAREx 07.2 – SAREx 16.2
SAN 07.1 – SAN 25.1; SARN 07.1 – 25.1; SAN 07.2 – SAN 16.2; SARN 07.2 – SARN 16.2
SAI 07.2 – SAI 16.2; SARI 07.2 – SARI 16.2
Part-turn actuators SQ 05.2 – SQ 14.2; SQR 05.2 – SQR 14.2; SQEx 05.2 – SQEx 14.2; SQREx 05.2 – SQREx 14.2
SG 05 – SG 12; SG 05.1 – SG 12.1; SGR 05.1 – SGR 12.1; SGExC 05.1 – SGExC 12.1
SG 04.2 – SG 10.2; SG 03.3 – SG 05.3
SGM 04.1 – SGM 10.1; SGMR 04.1 – SGMR 10.1; SGC 04.1 – SGC 10.1; SGCR 04.1 – SGCR 10.1
Globe valve actuators SV 05.1 – SV 07.1; SVM 05.1 – SVM 07.5; SVMR 05.1 – SVMR 07.5; SVC 05.1 – SVC 07.5; SVCR 05.1 – SVCR 07.5
Worm gearboxes GS 50.3 – GS 250.3; GS 315 – GS 500; GS 630.3
Primary reduction gearing GZ 16 – GZ 40; GZ 630.3
Coaxial planetary gearing GP 10.1 – GP 30.1
Spur gearboxes GST 10.1 – GST 40.1
Bevel gearboxes GK 10.2 – GK 40.2
Linear thrust units LE 12.1 – LE 200.1
Multi-turn gearboxes GHT 320.3 – GHT 1200.3

Multi-turn actuators
SA 07.1/07.5 10.0/10.1 14.1/14.5 16.1 25.1 30.1 35.1 40.1 48.1
3 0.62 -0.03 0.93 -0.04 2.3 -0.1 4.5 ±0.1 11.0 ±0.2 16.0 ±0.2 29.0 +0.4 36.0 +0.4 56.0 +0.5
Qty dm
Weight kg2) 0.56 -0.03 0.84 -0.04 2.1 -0.1 4.1 ±0.1 9.9 ±0.2 14.4 ±0.2 26.1 +0.4 32.4 +0.4 50.4 +0.5
SA 07.2/07.6 10.2 14.2/14.6 16.2
F07 F10/G0
Qty dm3 0.58 ±0.02 0.525 ±0.02 0.9 ±0.02 1.76 ±0.05 3.1 ±0.05
Weight kg2) 0.52 ±0.02 0,47 ±0,02 0.81 ±0.02 1.58 ±0.05 2.8 ±0.05

Part-turn actuators
SQ 05.2 07.2 10.2 12.2 14.2
3 0.7 ±0.02 0.7 ±0.02 1.3 ±0.02 1.7 ±0.02 1.8 ±0.05
Qty dm
Weight kg2) 0.63 ±0.02 0.63 ±0.02 1.17 ±0.02 1.53 ±0.02 1.62 ±0.05
SG 05 07 10 12
3 0.3 0.3 0.52 0.8
Qty dm
Weight kg2) 0.27 0.27 0.47 0.72
SG 05.1 07.1 10.1 12.1
3 0.3 0.3 0.52 0.8
Qty dm
Weight kg2) 0.27 0.27 0.47 0.72
SG 04.2 05.2 07.2 10.2
3 0.09 0.14 0.30 0.52
Qty dm
Weight kg3) 0.07 0.12 0.25 0.43
SG 03.3 04.3 05.3
Qty dm3 0.14 0.14 0.23
Weight kg3) 0.12 0.12 0.19
SGM/SGC 04.1 05.1 07.1 10.1
3 0.11 0.11 0.24 0.40
Qty dm
Weight kg3) 0.09 0.09 0.20 0.33

Globe valve actuators


SV 05.1 07.1
3 0.14 0.30
Qty dm
3) 0.12 0.25
Weight kg

1) – 2) Refer to notes on page 3.


We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y003.176/003/en Issue 1.16 Page 1/3


AUMA products

Technical data Grease and oil quantities

SVM/SVC 05.1 07.1/07.5


3 0.11 0.24
Qty dm
3) 0.09 0.20
Weight kg

Worm gearboxes
GS 50.3 63.3 80.3 100.3 100.3 100.3 100.3 125.3 125.3 125.3
(52:1) (126:1) (160:1) (208:1) (52:1) (126:1) (160:1)
Qty dm3 0.1 0.3 0.4 1 1.35 1.35 1.35 1.3 1.65 1.65
2) 0.09 0.27 0.36 0.9 1.22 1.22 1.22 1.17 1.49 1.49
Weight kg
GS 125.3 160.3 160.3 160.3 160.3 200.3 200.3 200.3 200.3 200.3
(208:1) (54:1) (218:1) (442:1) (880:1) (53:1) (67:1) (214:1) (434:1) (864:1)
Qty dm3 1.65 3.3 4.3 4.3 4.3 6.6 6.6 8.1 8.1 8.6
2) 1.49 3 3.9 3.9 3.9 6 6 7.4 7.4 7.8
Weight kg
GS 200.3 250.3 250.3 250.3 250.3 250.3
(1 752:1) (52:1) (210:1) (411:1) (848:1) (1 718:1)
Qty dm3 8.6 12.2 14.4 14.4 14.7 14.7
2) 7.8 11 13 13 13.3 13.3
Weight kg
GS 315 400 500 630.3
Qty dm3 27.5 55.0 110.0 216.7
2) 25.0 50.0 100.0 195.0
Weight kg

Primary reduction gearing


GZ 30 35 40 40/16
Qty dm3 17.6 18.7 57.2 61.9
Weight kg2) 16.0 17.0 52.0 56.3
GZ 630.3 630.3 630.3
(4:1/8:1) (16:1/32:1) (64:1/133:1)
Qty dm3 11.1 16.7 21.1
2) 10.0 15.0 19.0
Weight kg

Coaxial planetary gearing


GP 10.1/14.1 10.1/14.1 10.1/14.1 16.1 25.1 25.1 30.1 30.1
(2, 4:1) (3:1) (4:1) (4:1/8:1) (16:1) (4:1/8:1) (16:1)
Qty dm3 0.35 0.35 0.35 1.0 1.5 2.0 2.2 2.5
Weight kg2) 0.32 0.32 0.32 0.9 1.4 1.8 2.0 2.25

Spur gearboxes
GST 10.1 14.1/14.5 16.1 25.1 30.1 35.1 40.1
3 0.7 1.5 3.0 8.0 12.0 20.0 27.0
Qty dm
Weight kg2) 0.62 1.3 2.7 7.1 10.7 17.8 24.0

Bevel gearboxes
GK 10.2 14.2/14.6 16.2 25.2 30.2 35.2 40.2
3 0.25 0.6 1.0 4.0 14.0 20.0 22.0
Qty dm
Weight kg2) 0.22 0.53 0.9 3.6 12.5 17.8 19.6

Multi-turn gearboxes
GHT 320.3 500.3 800.3 1200.3
3 30.0 71.5 93.5 146.5
Qty dm
2) 27 64.4 84.2 131.9
Weight kg

Linear thrust units


LE 12.1-50 12.1-100 12.1-125 12.1-200 12.1-250 12.1-400 12.1-500 50.1-63 50.1-125 50.1-250
25.1-50 25.1-100 25.1-125 25.1-200 25.1-250 25.1-400 25.1-500
Qty dm3 0.10 0.13 0.16 0.28 0.36 0.54 0.65 0.26 0.41 0.65
2) 0.09 0.12 0.15 0.26 0.33 0.50 0.60 0.28 0.38 0.70
Weight kg
1) – 2) Refer to notes on page 3.
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y003.176/003/en Issue 1.16 Page 2/3


AUMA products

Technical data Grease and oil quantities

LE 50.1-400 70.1-80 70.1-160 70.1-320 70.1-400 200.1-100 200.1-200 200.1-400 200.1-500


100.1-80 100.1-160 100.1-320 100.1-400
Qty dm3 1.09 0.52 0.88 1.48 1.79 1.71 2.80 4.92 6.11
2) 1.01 0.48 0.81 1.37 1.65 1.58 2.58 4.53 5.63
Weight kg

Notes on tables on pages 1 and 2


1) This overview is not applicable for products with F21.
2) For ρ = approx. 0.9 kg/dm3
3) For ρ = approx. 0.83 kg/dm3

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y003.176/003/en Issue 1.16 Page 3/3


Actuators

Technical data Ambient temperatures/lubricant in the gear housing

Temperature range
Type Extreme low temper-
Normal (standard) Low temperature ature High temperature
List designation N L EL-60 H
Actuator Grease/
Version °C oil °C Grease °C Grease °C Grease
SA 07.2 – 16.2 Standard –40/+80 F15 – – –60/+60 F2 0/+120 F3
SA 25.1 – 48.1 Standard –40/+80 F15 – – –60/+60 F2 0/+120 F3
1)
SA 07.2 – 16.2 With oil –25/+80 O9 – – – – – –
SAR 07.2 – 16.2 Standard –40/+70 F15 – – –60/+60 F2 0/+100 F3
SAR 25.1 – 30.1 Standard –40/+70 F15 – – –60/+60 F2 0/+100 F3
SAR 07.2 – 16.2 With oil1) –25/+70 O9 – – – – – –
SAEx 07.2 Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
4 – 32 rpm Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAEx 07.6
45 – 180 rpm Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
4 – 11 rpm Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAEx 10.2
16 – 180 rpm Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
4 – 11 rpm Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAEx 14.2
16 – 180 rpm Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAEx 14.6 Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAEx 16.2 Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAEx 25.1 – 48.1 Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAEx 07.2 – 16.2 With oil1) –25/+70 O9 – – – – – –
4 – 45 rpm Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAREx 07.2
63 – 90 rpm Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
4 – 45 rpm Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAREx 07.6
63 – 90 rpm Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
4 – 32 rpm Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAREx 10.2
45 – 90 rpm Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
4 – 11 rpm Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAREx 14.2
16 – 90 rpm Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAREx 14.6 Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAREx 16.2 Ex –30/+40 (+60/+80) F11 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAREx 25.1 – 30.1 Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SAREx 07.2 – 16.2 With oil1) –25/+70 O9 – – – – – –
Nuclear power
SAN 07.1 – 35.1 –25/+80 F11 – – – – – –
plants
Nuclear power
SARN 07.1 – SARN 35.1 –25/+80 F11 – – – – – –
plants
Nuclear power
SAI 6 – 100 –20/+80 F11 – – – – – –
plants
Nuclear power
SAI 07.2 – 16.2 –30/+80 F11 – – – – – –
plants
Nuclear power
SARI 07.2 – 16.2 –30/+60 F11 – – – – – –
plants
Nuclear power
SAN 07.2 – 16.2 –30/+80 F11 – – – – – –
plants
Nuclear power
SARN 07.2 – SARN 16.2 –30/+60 F11 – – – – – –
plants
SQ 05.2 – 14.2 Standard –40/+80 F15 – – –60/+60 F2 0/+120 F3
SQR 05.2 – 14.2 Standard –40/+70 F15 – – –60/+60 F2 0/+100 F3
SQEx 05.2 – SQEx 14.2 Ex –30/+60 (+80) F15 –40/+60 F2 –60/+60 F2 – –
SQREx 05.2 – 14.2 Ex –30/+40 (+60/+80) F15 –40/+40 (+60) F2 –60/+40 (+60) F2 – –
SGC 04.1 – 12.1 Marine –25/+70 O2 – – – – – –
SGCR 04.1 – 12.1 Marine –25/+70 O2 – – – – – –
SGM 04.1 – 12.1 Marine –25/+70 O2 – – – – – –
SGMR 04.1 – 12.1 Marine –25/+70 O2 – – – – – –

1) Refer to notes on page 2.


We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y003.808/003/en Issue 2.17 Page 1/2


Actuators

Technical data Ambient temperatures/lubricant in the gear housing

Temperature range
Type Extreme low temper-
Normal (standard) Low temperature ature High temperature
List designation N L EL-60 H
Actuator Grease/
Version °C oil °C Grease °C Grease °C Grease
SVC 05.1 – 07.5 Marine –25/+70 O2 – – – – – –
SVCR 04.1 – 12.1 Marine –25/+70 O2 – – – – – –
SVM 05.1 – 07.5 Marine –25/+70 O2 – – – – – –
SVMR 04.1 – 12.1 Marine –25/+70 O2 – – – – – –

Notes on table on page 1


1) With oil Mounting position: Perpendicular hollow shaft and bearing flange at the bottom stipulated

Lubricants:
F2 = Fuchs Discor R EP 000
F3 = Zepf AR 12 K
F11 = Fuchs Renolit LST
F15 = Shell Alvania 1029
O2 = Fuchs Unisyn SC 32
O9 = Oest SAE 75W-90

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y003.808/003/en Issue 2.17 Page 2/2


3 Electrical data Actuators

Basic Range 60

3-phase AC current
SBA 06 – SBA 200 380 V/50 Hz 60
400 V/50 Hz 61
400 V/60 Hz 62

ED 25 – ED 50, EQ 40 – EQ 600 380 V/50 Hz 63


400 V/50 Hz 64
400 V/60 Hz 65

1-phase AC current
SBA 06 – SBA 200 110 V/60 Hz 66

3. Electrical data
115 V/50 Hz 67

Actuators
220 V/60 Hz 68
230 V/50 Hz 69

NR 2.1 – NR 2.3 Fail Safe 24 V/50 Hz 70


24 V/60 Hz 71
110 V/60 Hz 72
115 V/50 Hz 73
220 V/60 Hz 74
230 V/50 Hz 75

ED 25 – ED 50, EQ 40 – EQ 600 24 V/50 Hz 76


24 V/60 Hz 77
110 V/60 Hz 78
115 V/50 Hz 79
220 V/60 Hz 80
230 V/50 Hz 81

Direct current
ED 25 – ED 50, EQ 40 – EQ 600 24 V DC 82
SBA 06 – SBA 200 24 V DC 83

Smart Range 84

1-phase AC current
SD 05 – SD 25 100 V – 240 V/50 Hz/60 Hz 84
SDL 50 – SDL 100 100 V – 240 V/50 Hz/60 Hz 85

SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1 115 V, 230 V/50 Hz/60 Hz 86
SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5 115 V, 230 V/50 Hz/60 Hz 87

Direct current
SD 05 – SD 25 24 V DC 88
SDL 50 – SDL 100 24 V DC 89
SBA 06 – SBA 200
Electrical data Linear actuators with 3-phase AC motors
380 V/50 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed Nominal Max.
Max. Max.1) Max. Power2) Speed current3) current4) Type of Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  duty class
8 3.1 500 0.015 0.015 ~ 0,935 S1 - 100 % E
SBA 06-1 0.6 syn
10 3.1 500 0.015 0.015 ~ 0,935 S1 - 100 % E
35 13.2 3.1 500 0.015 0.015 ~ 0,935 S1 - 100 % E
SBA 06-2 0.9 syn
16 3.1 500 0.015 0.015 ~ 0,935 S1 - 100 % E
SBA 06-3 1.2 20 syn 3.1 500 0.015 0.015 0.953 S1 - 100 % E
8 3.1 500 0.015 0.015 ~ 0,935 S3 - 50 % E
SBA 06-4 35 2.0 10 syn 3.1 500 0.015 0.015 ~ 0,935 S3 - 50 % E
13.2 3.1 500 0.015 0.015 ~ 0,935 S3 - 50 % E
SBA 12 75 1.2 25 syn 3.1 500 0.015 0.015 0.953 S1 - 100 % E
SBA 20 75 2.0 15 syn 3.1 500 0.015 0.015 0.953 S1 - 100 % E
25 10 1,350 0.110 0.200 0.46 S3 - 50 % F
SBA 45-2 75 3.5 asyn
50 16 2,700 0.080 0.200 0.58 S3 - 50 % F
25 10 1,350 0.110 0.200 0.46 S3 - 50 % F
SBA 45-3 75 4.5 asyn
50 16 2,700 0.080 0.200 0.58 S3 - 50 % F
17 10 1,350 0.110 0.200 0.46 S3 - 50 % F
SBA 45-4 75 6.0 asyn
34 16 2,700 0.080 0.200 0.58 S3 - 50 % F
SBA 80-1 6.0 13.5 21 1,000 0.063 0.063 0.96 S3 - 50 % F
syn
SBA 80-2 80 8.0 22 36 1,500 0.110 0.110 1 S3 - 50 % F
SBA 80-3 12 40 asyn 63 2,750 0.370 1.030 0.64 S3 - 50 % F
13.5 21 1,000 0.063 0.063 0.96 S3 - 50 % F
syn
SBA 80-4 80 15 22 36 1,500 0.110 0.110 1 S3 - 50 % F
40 asyn 63 2,750 0.370 1.030 0.64 S3 - 50 % F
SBA 200-1 15 15 syn 36 1,500 0.110 0.110 1 S3 - 50 % F
100 25 75 1,350 0.470 0.830 0.53 S3 - 50 % F
SBA 200-2 20 asyn
50 215 2,750 0.770 2.200 0.66 S3 - 50 % F
SBA 200-3 100 25 25 asyn 75 1,350 0.470 0.830 0.53 S3 - 50 % F

Notes on table
1) Max operating force Also corresponds to maximum operating force in modulating duty.
2) Power P Output of mechanical power at motor shaft at maximum operating force of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
3) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
4) Max. current Imax Current at maximum operating force. Also corresponds to maximum force in modulating duty. We recom-
mend sizing the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.047/003/en Issue 1.17 Page 1/1


SBA 06 – SBA 200
Electrical data Linear actuators with 3-phase AC motors
400 V/50 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed Nominal Max.
Max. Max.1) Max. Power2) Speed current3) current4) Type of Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  duty class
8 3.1 500 0.015 0.015 ~ 0,935 S1 - 100 % E
SBA 06-1 0.6 syn
10 3.1 500 0.015 0.015 ~ 0,935 S1 - 100 % E
35 13.2 3.1 500 0.015 0.015 ~ 0,935 S1 - 100 % E
SBA 06-2 0.9 syn
16 3.1 500 0.015 0.015 ~ 0,935 S1 - 100 % E
SBA 06-3 1.2 20 syn 3.1 500 0.015 0.015 0.953 S1 - 100 % E
8 3.1 500 0.015 0.015 ~ 0,935 S3 - 50 % E
SBA 06-4 35 2.0 10 syn 3.1 500 0.015 0.015 ~ 0,935 S3 - 50 % E
13.2 3.1 500 0.015 0.015 ~ 0,935 S3 - 50 % E
SBA 12 75 1.2 25 syn 3.1 500 0.015 0.015 0.953 S1 - 100 % E
SBA 20 75 2.0 15 syn 3.1 500 0.015 0.015 0.953 S1 - 100 % E
25 10 1,350 0.110 0.200 0.46 S3 - 50 % F
SBA 45-2 75 3.5 asyn
50 16 2,700 0.080 0.200 0.58 S3 - 50 % F
25 10 1,350 0.110 0.200 0.46 S3 - 50 % F
SBA 45-3 75 4.5 asyn
50 16 2,700 0.080 0.200 0.58 S3 - 50 % F
17 10 1,350 0.110 0.200 0.46 S3 - 50 % F
SBA 45-4 75 6.0 asyn
34 16 2,700 0.080 0.200 0.58 S3 - 50 % F
SBA 80-1 6.0 13.5 21 1,000 0.063 0.063 0.96 S3 - 50 % F
syn
SBA 80-2 80 8.0 22 36 1,500 0.110 0.110 1 S3 - 50 % F
SBA 80-3 12 40 asyn 63 2,750 0.370 1.030 0.64 S3 - 50 % F
13.5 21 1,000 0.063 0.063 0.96 S3 - 50 % F
syn
SBA 80-4 80 15 22 36 1,500 0.110 0.110 1 S3 - 50 % F
40 asyn 63 2,750 0.370 1.030 0.64 S3 - 50 % F
SBA 200-1 15 15 syn 36 1,500 0.110 0.110 1 S3 - 50 % F
100 25 75 1,350 0.470 0.830 0.53 S3 - 50 % F
SBA 200-2 20 asyn
50 215 2,750 0.770 2.200 0.66 S3 - 50 % F
SBA 200-3 100 25 25 asyn 75 1,350 0.470 0.830 0.53 S3 - 50 % F

Notes on table
1) Max operating force Also corresponds to maximum operating force in modulating duty.
2) Power P Output of mechanical power at motor shaft at maximum operating force of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
3) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
4) Max. current Imax Current at maximum operating force. Also corresponds to maximum force in modulating duty. We recom-
mend sizing the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.048/003/en Issue 1.17 Page 1/1


SBA 06 – SBA 200
Electrical data Linear actuators with 3-phase AC motors
400 V/60 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed Nominal Max.
Max. Max.1) Max. Power2) Speed current3) current4) Type of Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  duty class
8 3.1 500 0.013 0.013 0.924 S1 - 100 % E
SBA 06-1 0.6 syn
10 3.1 500 0.013 0.013 0.924 S1 - 100 % E
35 13.2 3.1 500 0.013 0.013 0.924 S1 - 100 % E
SBA 06-2 0.9 syn
16 3.1 500 0.013 0.013 0.924 S1 - 100 % E
SBA 06-3 1.2 20 syn 3.1 600 0.013 0.013 0.924 S1 - 100 % E
8 3.1 600 0.013 0.013 0.924 S3 - 50 % E
SBA 06-4 35 2.0 10 syn 3.1 600 0.013 0.013 0.944 S3 - 50 % E
13.2 3.1 600 0.013 0.013 0.944 S3 - 50 % E
SBA 12 75 1.2 30 syn 3.1 600 0.013 0.013 0.944 S1 - 100 % E
SBA 20 75 2.0 18 syn 3.1 600 0.013 0.013 0.944 S1 - 100 % E
30 12 1,620 0.100 0.150 0.450 S3 - 50 % F
SBA 45-2 75 3.5 asyn
60 16 3,240 0.080 0.200 0.580 S3 - 50 % F
30 12 1,620 0.100 0.150 0.450 S3 - 50 % F
SBA 45-3 75 4.5 asyn
60 16 3,240 0.080 0.200 0.580 S3 - 50 % F
17 12 1,620 0.100 0.150 0.450 S3 - 50 % F
SBA 45-4 75 6.0 asyn
34 16 3,240 0.080 0.200 0.580 S3 - 50 % F
SBA 80-1 6.0 16 21 1,200 0.063 0.063 0.960 S3 - 50 % F
syn
SBA 80-2 80 8.0 30 43 1,800 0.110 0.110 1 S3 - 50 % F
SBA 80-3 12 50 asyn 63 3,300 0.370 1.030 0.640 S3 - 50 % F
13.5 21 1,200 0.063 0.063 0.960 S3 - 50 % F
syn
SBA 80-4 80 15 22 43 1,800 0.110 0.110 1 S3 - 50 % F
40 asyn 63 3,300 1.030 1.030 0.640 S3 - 50 % F
SBA 200-1 15 15 syn 43 1,800 0.110 0.110 1 S3 - 50 % F
100 30 88 1,560 0.412 0.830 0.610 S3 - 50 % F
SBA 200-2 20 asyn
60 235 3,300 0.710 2.030 0.700 S3 - 50 % F
SBA 200-3 100 25 30 asyn 88 1,560 0.412 0.830 0.610 S3 - 50 % F

Notes on table
1) Max operating force Also corresponds to maximum operating force in modulating duty.
2) Power P Output of mechanical power at motor shaft at maximum operating force of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
3) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
4) Max. current Imax Current at maximum operating force. Also corresponds to maximum force in modulating duty. We recom-
mend sizing the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.067/003/en Issue 1.17 Page 1/1


ED 25 – ED 50, EQ 40 – EQ 600
Electrical data Part-turn actuators with 3-phase AC motors
380 V/50 Hz

Part-turn actuator Motor


Type Torque range
Open-close Modulating
duty duty Operating time Nominal Max.
max. max. for 90° in Power1) Speed current2) current3) Insulation
[Nm] [Nm] seconds P [W] [rpm] IN [A] Imax [A] cos  Type of duty4) class
15 18.8 1,800 0.12 0.12 0.90 S3 - 30 % F
15 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
ED 25 25 25
30 21 1,000 0.12 0.12 0.96 S1 - 100 % F
70 3.1 500 0.02 0.02 0.95 S1 - 100 % E
15 18.8 1,800 0.12 0.12 0.96 S3 - 30 % F
15 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
ED 50 50 50
30 21 1,000 0.12 0.12 0.96 S1 - 100 % F
70 3.1 500 0.02 0.02 0.95 S1 - 100 % E
15 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
15 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
30 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
EQ 40 40 20
30 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
60 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
60 36 1,500 0.11 0.11 ~1 S1 - 100 % F
20 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
20 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
30 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
EQ 60 60 40
30 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
60 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
60 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
20 36 1,500 0.11 0.11 ~1 S1 - 100 % F
30 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
EQ 100 100 60 30 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
60 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
60 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
20 49 1,500 0.18 0.18 0.90 S3 - 75 % F
30 36 1,500 0.11 0.11 ~1 S1 - 100 % F
EQ 150 150 80
60 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
60 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
40 49 1,500 0.18 0.18 0.90 S3 - 75 % F
80 36 1,500 0.11 0.11 ~1 S1 - 100 % F
EQ 300 300 180
160 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
160 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
80 49 1,500 0.18 0.18 0.90 S3 - 75 % F
EQ 600 600 300
160 36 1,500 0.11 0.11 ~1 S1 - 100 % F

Notes on table
1) Power P Output of mechanical power at motor shaft at maximum torque of part-turn actuator.
The consumed electrical power can be calculated using the following formula: P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.
4) Type of duty All actuators are also suitable for type of duty S2 - 15 min
5) Option: S1 - 100 %

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.066/003/en Issue 1.17 Page 1/1


ED 25 – ED 50, EQ 40 – EQ 600
Electrical data Part-turn actuators with 3-phase AC motors
400 V/50 Hz

Part-turn actuator Motor


Type Torque range
Open-close Modulating
duty duty Operating time Nominal Max.
max. max. for 90° in Power1) Speed current2) current3) Insulation
[Nm] [Nm] seconds P [W] [rpm] IN [A] Imax [A] cos  Type of duty4) class
15 18.8 1,800 0.12 0.12 0.90 S3 - 30 % F
15 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
ED 25 25 25
30 21 1,000 0.12 0.12 0.96 S1 - 100 % F
70 3.1 500 0.02 0.02 0.95 S1 - 100 % E
15 18.8 1,800 0.12 0.12 0.96 S3 - 30 % F
15 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
ED 50 50 50
30 21 1,000 0.12 0.12 0.96 S1 - 100 % F
70 3.1 500 0.02 0.02 0.95 S1 - 100 % E
15 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
15 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
30 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
EQ 40 40 20
30 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
60 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
60 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
20 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
20 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
30 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
EQ 60 60 40
30 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
60 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
60 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
20 36 1,500 0.11 0.11 ~1 S1 - 100 % F
30 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
EQ 100 100 60 30 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
60 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
60 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
20 49 1,500 0.18 0.18 0.90 S3 - 75 % F
30 36 1,500 0.11 0.11 ~1 S1 - 100 % F
EQ 150 150 80
60 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
60 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
40 49 1,500 0.18 0.18 0.90 S3 - 75 % F
80 36 1,500 0.11 0.11 ~1 S1 - 100 % F
EQ 300 300 180
160 18.8 1,500 0.10 0.10 0.90 S3 - 30 % F
160 36 1,500 0.11 0.11 ~1 S1 - 100 %5) F
80 49 1,500 0.18 0.18 0.90 S3 - 75 % F
EQ 600 600 300
160 36 1,500 0.11 0.11 ~1 S1 - 100 % F

Notes on table
1) Power P Output of mechanical power at motor shaft at maximum torque of part-turn actuator.
The consumed electrical power can be calculated using the following formula: P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.
4) Type of duty All actuators are also suitable for type of duty S2 - 15 min
5) Option: S1 - 100 %

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.068/003/en Issue 1.17 Page 1/1


ED 25 – ED 50, EQ 40 – EQ 600
Electrical data Part-turn actuators with 3-phase AC motors
400 V/60 Hz

Part-turn actuator Motor


Type Torque range
Open-close Modulating
duty duty Operating time Nominal Max.
max. max. for 90° in Power1) Speed current2) current3) Insulation
[Nm] [Nm] seconds P [W] [rpm] IN [A] Imax [A] cos  Type of duty4) class
12 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
12 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
ED 25 25 25
25 19 1,200 0.10 0.10 0.96 S1 - 100 % F
59 3.1 600 0.01 0.01 0.94 S1 - 100 % E
12 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
12 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
ED 50 50 50
25 19 1,200 0.10 0.10 0.96 S1 - 100 % F
59 3.1 600 0.01 0.01 0.94 S1 - 100 % E
12.5 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
12.5 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
25 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
EQ 40 40 20
25 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
50 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
50 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
16 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
16 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
25 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
EQ 60 60 40
25 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
50 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
50 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
16 38 1,800 0.10 0.10 0.90 S1 - 100 % F
25 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
EQ 100 100 60 25 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
50 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
50 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
16 53 1,800 0.16 0.16 0.90 S3 - 75 % F
25 38 1,800 0.10 0.10 0.90 S1 - 100 % F
EQ 150 150 80
50 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
50 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
33 53 1,800 0.16 0.16 0.90 S3 - 75 % F
66 38 1,800 0.10 0.10 0.90 S1 - 100 % F
EQ 300 300 180
133 22.6 1,800 0.12 0.12 0.90 S3 - 30 % F
133 38 1,800 0.10 0.10 0.90 S1 - 100 %5) F
66 53 1,800 0.16 0.16 0.90 S3 - 75 % F
EQ 600 600 300
133 38 1,800 0.10 0.10 0.90 S1 - 100 % F

Notes on table
1) Power P Output of mechanical power at motor shaft at maximum torque of part-turn actuator.
The consumed electrical power can be calculated using the following formula: P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.
4) Type of duty All actuators are also suitable for type of duty S2 - 15 min
5) Option: S1 - 100 %

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.069/003/en Issue 1.17 Page 1/1


SBA 06 – SBA 200
Electrical data Linear actuators with 1-phase AC motors
110 V/60 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed Nominal Max.
Max. Max.1) Max. Power2) Speed current3) current4) Type of Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  duty class
8 2 600 0.067 0.067 ~1 S1 - 100 % E
SBA 06-1 0.6 syn
10 2 600 0.067 0.067 ~1 S1 - 100 % E
35 13.2 2 600 0.067 0.067 ~1 S1 - 100 % E
SBA 06-2 0.9 syn
16 2 600 0.067 0.067 ~1 S1 - 100 % E
SBA 06-3 1.2 23.8 syn 2.6 600 0.067 0.067 ~1 S1 - 100 % E
8 2 600 0.067 0.067 ~1 S3 - 50 % E
SBA 06-4 35 2.0 10 syn 2.6 600 0.067 0.067 ~1 S3 - 50 % E
13.2 2.6 600 0.067 0.067 ~1 S3 - 50 % E
SBA 12 75 1.2 30 syn 2.6 600 0.067 0.067 ~1 S1 - 100 % E
SBA 20 75 2.0 18 syn 2.6 600 0.067 0.067 ~1 S1 - 100 % E
30 5.3 1,620 0.310 0.450 0.90 S3 - 50 % F
SBA 45-2 75 3.5 asyn
60 14 3,240 0.370 0.720 0.98 S3 - 50 % F
30 5.3 1,620 0.310 0.450 0.90 S3 - 50 % F
SBA 45-3 75 4.5 asyn
60 14 3,240 0.370 0.720 0.98 S3 - 50 % F
20.4 5.3 1,620 0.310 0.450 0.90 S3 - 50 % F
SBA 45-4 75 6.0 asyn
40 14 3,240 0.370 0.720 0.98 S3 - 50 % F
SBA 80-1 6.0 16 15.6 1,200 0.220 0.220 ~1 S3 - 50 % F
syn
SBA 80-2 80 8.0 30 35 1,800 0.470 0.470 1 S3 - 50 % F
SBA 80-3 12 60 asyn 75 3,300 1.350 2.650 0.97 S3 - 50 % F
13.5 15.6 1,200 0.220 0.220 ~1 S3 - 50 % F
syn
SBA 80-4 80 15 26.5 35 1,800 0.470 0.470 1 S3 - 50 % F
48 asyn 75 3,300 1.350 2.650 0.97 S3 - 50 % F
SBA 200-1 15 15 syn 35 1,800 0.470 0.470 1 S3 - 50 % F
100 30 56 1,560 1.340 2.140 0.86 S3 - 50 % F
SBA 200-2 20 asyn
60 136 3,250 2.740 5.350 0,94 S3 - 50 % F
SBA 200-3 100 25 30 asyn 56 1,560 1.340 2.140 0.86 S3 - 50 % F

Notes on table
1) Max operating force. Also corresponds to maximum operating force in modulating duty.
2) Power P Output of mechanical power at motor shaft at maximum operating force of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
3) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
4) Max. current Imax Current at maximum operating force. Also corresponds to maximum force in modulating duty. We recom-
mend sizing the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.046/003/en Issue 1.17 Page 1/1


SBA 06 – SBA 200
Electrical data Linear actuators with 1-phase AC motors
115 V/50 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed Nominal Max.
Max. Max.1) Max. Power2) Speed current3) current4) Type of Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  duty class
8 2 500 0.043 0.043 ~1 S1 - 100 % E
SBA 06-1 0.6 syn
10 2 500 0.043 0.043 ~1 S1 - 100 % E
35 13.2 2 500 0.043 0.043 ~1 S1 - 100 % E
SBA 06-2 0.9 syn
16 2 500 0.043 0.043 ~1 S1 - 100 % E
SBA 06-3 1.2 20 syn 2.4 500 0.060 0.060 ~1 S1 - 100 % E
8 2 500 0.043 0.043 ~1 S3 - 50 % E
SBA 06-4 35 2.0 10 syn 2.4 500 0.060 0.060 ~1 S3 - 50 % E
13.2 2.4 500 0.060 0.060 ~1 S3 - 50 % E
SBA 12 75 1.2 25 syn 2.4 500 0.060 0.060 ~1 S1 - 100 % E
SBA 20 75 2.0 15 syn 2.4 500 0.060 0.060 ~1 S1 - 100 % E
25 5.3 1,350 0.280 0.370 0.90 S3 - 50 % F
SBA 45-2 75 3.5 asyn
50 12 2,700 0.435 0.800 0.83 S3 - 50 % F
25 5.3 1,350 0.280 0.370 0.90 S3 - 50 % F
SBA 45-3 75 4.5 asyn
50 12 2,700 0.435 0.800 0.83 S3 - 50 % F
17 5.3 1 350 0.280 0.370 0.90 S3 - 50 % F
SBA 45-4 75 6.0 asyn
34 12 2,700 0.435 0.800 0.83 S3 - 50 % F
SBA 80-1 6.0 13.5 13.3 1,000 0.220 0.220 ~1 S3 - 50 % F
syn
SBA 80-2 80 8.0 22 30 1,500 0.470 0.470 1 S3 - 50 % F
SBA 80-3 12 40 asyn 61 2,750 1.250 2.350 0.96 S3 - 50 % F
13.5 13.3 1,000 0.220 0.220 ~1 S3 - 50 % F
syn
SBA 80-4 80 15 22 30 1,500 0.470 0.470 1 S3 - 50 % F
40 asyn 61 2,750 1.250 2.350 0.96 S3 - 50 % F
SBA 200-1 15 15 syn 30 1,500 0.470 0.580 1 S3 - 50 % F
100 25 60 1,560 1.130 2.000 0.86 S3 - 50 % F
SBA 200-2 20 asyn
50 92 2,700 2.140 4.650 0.90 S3 - 50 % F
SBA 200-3 100 25 25 asyn 60 1,560 1.130 2.000 0.86 S3 - 50 % F

Notes on table
1) Max operating force. Also corresponds to maximum operating force in modulating duty.
2) Power P Output of mechanical power at motor shaft at maximum operating force of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
3) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
4) Max. current Imax Current at maximum operating force. Also corresponds to maximum force in modulating duty. We recom-
mend sizing the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.045/003/en Issue 1.17 Page 1/1


SBA 06 – SBA 200
Electrical data Linear actuators with 1-phase AC motors
220 V/60 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed Nominal Max.
Max. Max.1) Max. Power2) Speed current3) current4) Type of Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  duty class
8 2 600 0.032 0.032 ~1 S1 - 100 % E
SBA 06-1 0.6 syn
10 2 600 0.032 0.032 ~1 S1 - 100 % E
35 13.2 2 600 0.032 0.032 ~1 S1 - 100 % E
SBA 06-2 0.9 syn
16 2 600 0.032 0.032 ~1 S1 - 100 % E
SBA 06-3 1.2 23.8 syn 2.6 600 0.032 0.032 ~1 S1 - 100 % E
8 2 600 0.032 0.032 ~1 S3 - 50 % E
SBA 06-4 35 2.0 10 syn 2.6 600 0.032 0.032 ~1 S3 - 50 % E
13.2 2.6 600 0.032 0.032 ~1 S3 - 50 % E
SBA 12 75 1.2 30 syn 2.6 600 0.032 0.032 ~1 S1 - 100 % E
SBA 20 75 2.0 18 syn 2.6 600 0.032 0.032 ~1 S1 - 100 % E
30 5.3 1,620 0.150 0.230 0.90 S3 - 50 % F
SBA 45-2 75 3.5 asyn
60 14 3,240 0.200 0.340 0.90 S3 - 50 % F
30 5.3 1,620 0.150 0.230 0.90 S3 - 50 % F
SBA 45-3 75 4.5 asyn
60 14 3,240 0.200 0.340 0.90 S3 - 50 % F
20.4 5.3 1,620 0.150 0.230 0.90 S3 - 50 % F
SBA 45-4 75 6.0 asyn
40 14 3,240 0.200 0.340 0.90 S3 - 50 % F
SBA 80-1 6.0 16 14.1 1,200 0.110 0.110 0.96 S3 - 50 % F
syn
SBA 80-2 80 8.0 30 35 1,800 0.225 0.225 1 S3 - 50 % F
SBA 80-3 12 60 asyn 86 3,300 1 1.520 0.95 S3 - 50 % F
13.5 14.1 1,200 0.110 0.110 0.96 S3 - 50 % F
syn
SBA 80-4 80 15 26.5 35 1,800 0.225 0.225 1 S3 - 50 % F
48 asyn 86 3,300 1.000 1.520 0.95 S3 - 50 % F
SBA 200-1 15 15 syn 35 1,800 0.225 0.225 1 S3 - 50 % F
100 30 63 1,620 0.870 1.600 0.98 S3 - 50 % F
SBA 200-2 20 asyn
60 120 3,240 1.070 2.170 0.96 S3 - 50 % F
SBA 200-3 100 25 30 asyn 63 1,620 0.870 1.600 0.98 S3 - 50 % F

Notes on table
1) Max operating force Also corresponds to maximum operating force in modulating duty.
2) Power P Output of mechanical power at motor shaft at maximum operating force of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
3) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
4) Max. current Imax Current at maximum operating force. Also corresponds to maximum force in modulating duty. We recom-
mend sizing the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.044/003/en Issue 1.17 Page 1/1


SBA 06 – SBA 200
Electrical data Linear actuators with 1-phase AC motors
230 V/50 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed Nominal Max.
Max. Max.1) Max. Power2) Speed current3) current4) Type of Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  duty class
8 2 500 0.029 0.029 ~1 S1 - 100 % E
SBA 06-1 0.6 syn
10 2 500 0.029 0.029 ~1 S1 - 100 % E
35 13.2 2 500 0.029 0.029 ~1 S1 - 100 % E
SBA 06-2 0.9 syn
16 2 500 0.029 0.029 ~1 S1 - 100 % E
SBA 06-3 1.2 20 syn 2.4 500 0.029 0.029 ~1 S1 - 100 % E
8 2 500 0.029 0.029 ~1 S3 - 50 % E
SBA 06-4 35 2.0 10 syn 2 500 0.029 0.029 ~1 S3 - 50 % E
13.2 2.4 500 0.029 0.029 ~1 S3 - 50 % E
SBA 12 75 1.2 25 syn 2.4 500 0.029 0.029 ~1 S1 - 100 % E
SBA 20 75 2.0 15 syn 2.4 500 0.029 0.029 ~1 S1 - 100 % E
25 5.3 1,350 0.135 0.200 0.90 S3 - 50 % F
SBA 45-2 75 3.5 asyn
50 12 2,700 0.160 0.300 0.89 S3 - 50 % F
25 5.3 1,350 0.135 0.200 0.90 S3 - 50 % F
SBA 45-3 75 4.5 asyn
50 12 2,700 0.160 0.300 0.89 S3 - 50 % F
17 5.3 1,350 0.135 0.200 0.90 S3 - 50 % F
SBA 45-4 75 6.0 asyn
34 12 2,700 0.160 0.300 0.89 S3 - 50 % F
SBA 80-1 6.0 13.5 10.8 1,000 0.110 0.110 ~1 S3 - 50 % F
syn
SBA 80-2 80 8.0 22 30 1,500 0.225 0.225 1 S3 - 50 % F
SBA 80-3 12 40 asyn 72 2,750 0.780 1.580 0.89 S3 - 50 % F
13.5 10.8 1,000 0.110 0.110 ~1 S3 - 50 % F
syn
SBA 80-4 80 15 22 30 1,500 0.225 0.225 1 S3 - 50 % F
40 asyn 72 2,750 0.780 1.580 0.89 S3 - 50 % F
SBA 200-1 15 15 syn 30 1,500 0.225 0.225 1 S3 - 50 % F
100 25 67 1,350 0.730 1.270 0.93 S3 - 50 % F
SBA 200-2 20 asyn
50 110 2,700 1 2.200 0.95 S3 - 50 % F
SBA 200-3 100 25 25 asyn 67 1,350 0.73 1.270 0.93 S3 - 50 % F

Notes on table
1) Max operating force Also corresponds to maximum operating force in modulating duty.
2) Power P Output of mechanical power at motor shaft at maximum operating force of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
3) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
4) Max. current Imax Current at maximum operating force. Also corresponds to maximum force in modulating duty. We recom-
mend sizing the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.043/003/en Issue 1.17 Page 1/1


NR 2.1 – NR 2.3
Electrical data Linear actuators with 1-phase AC motors
24 V/50 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed for Nominal Max.
Max. CLOSE modulating duty Power1) Speed current2) current3) Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  class
NR 2.1 35 0.9 17.5 syn 2.8 375 0.255 0.255 0.99 E
NR 2.2 35 2.2 17.5 syn 2.8 375 0.255 0.255 0.99 E
NR 2.3 46 2.2 17.5 syn 2.8 375 0.255 0.255 0.99 E

Notes on table
1 Power P Output of mechanical power at motor shaft at maximum torque of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.052/003/en Issue 1.15 Page 1/1


NR 2.1 – NR 2.3
Electrical data Linear actuators with 1-phase AC motors
24 V/60 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed for Nominal Max.
Max. CLOSE modulating duty Power1) Speed current2) current3) Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  class
NR 2.1 35 0.9 21 syn 3.2 450 0.274 0.274 ~1 E
NR 2.2 35 2.2 21 syn 3.2 450 0.274 0.274 ~1 E
NR 2.3 46 2.2 21 syn 3.2 450 0.274 0.274 ~1 E

Notes on table
1 Power P Output of mechanical power at motor shaft at maximum torque of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.053/00/en Issue 1.15 Page 1/1


NR 2.1 – NR 2.3
Electrical data Linear actuators with 1-phase AC motors
110 V/60 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed for Nominal Max.
Max. CLOSE modulating duty Power1) Speed current2) current3) Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  class
NR 2.1 35 0.9 21 syn 3.1 450 0.057 0.057 ~1 E
NR 2.2 35 2.2 21 syn 3.1 450 0.057 0.057 ~1 E
NR 2.3 46 2.2 21 syn 3.1 450 0.057 0.057 ~1 E

Notes on table
1 Power P Output of mechanical power at motor shaft at maximum torque of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.055/003/en Issue 1.15 Page 1/1


NR 2.1 – NR 2.3
Electrical data Linear actuators with 1-phase AC motors
115 V/50 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed for Nominal Max.
Max. CLOSE modulating duty Power1) Speed current2) current3) Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  class
NR 2.1 35 0.9 17.5 syn 2.7 375 0.052 0.052 0.99 E
NR 2.2 35 2.2 17.5 syn 2.7 375 0.052 0.052 0.99 E
NR 2.3 46 2.2 17.5 syn 2.7 375 0.052 0.052 0.99 E

Notes on table
1 Power P Output of mechanical power at motor shaft at maximum torque of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.054/003/en Issue 1.15 Page 1/1


NR 2.1 – NR 2.3
Electrical data Linear actuators with 1-phase AC motors
220 V/60 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed for Nominal Max.
Max. CLOSE modulating duty Power1) Speed current2) current3) Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  class
NR 2.1 35 0.9 21 syn 3.4 450 0.0306 0.0306 ~1 E
NR 2.2 35 2.2 21 syn 3.4 450 0.0306 0.0306 ~1 E
NR 2.3 46 2.2 21 syn 3.4 450 0.0306 0.0306 ~1 E

Notes on table
1 Power P Output of mechanical power at motor shaft at maximum torque of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.051/003/en Issue 1.15 Page 1/1


NR 2.1 – NR 2.3
Electrical data Linear actuators with 1-phase AC motors
230 V/50 Hz

Linear actuator Motor


Operating Positioning
Stroke force speed for Nominal Max.
Max. CLOSE modulating duty Power1) Speed current2) current3) Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] IN [A] Imax [A] cos  class
NR 2.1 35 0.9 17.5 syn 2.7 375 0.0255 0.0255 0.99 E
NR 2.2 35 2.2 17.5 syn 2.7 375 0.0255 0.0255 0.99 E
NR 2.3 46 2.2 17.5 syn 2.7 375 0.0255 0.0255 0.99 E

Notes on table
1 Power P Output of mechanical power at motor shaft at maximum torque of linear actuator.
The consumed electrical power can be calculated using the following formula:
P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.049/003/en Issue 1.15 Page 1/1


ED 25 – ED 50, EQ 40 – EQ 600
Electrical data Part-turn actuators with 1-phase AC motors
24 V/50 Hz

Part-turn actuator Motor


Type Torque range
Open-close Modulating
duty duty Operating time Nominal Max.
max. max. for 90° in Power1) Speed current2) current3) Insulation
[Nm] [Nm] seconds P [W] [rpm] IN [A] Imax [A] cos  Type of duty4) class
15 5.1 375 0.5 0.5 ~1 S1 - 100 % E
ED 25 25 25 30 5.1 375 0.5 0.5 ~1 S1 - 100 % E
70 2.4 500 0.3 0.3 ~1 S1 - 100 % E
15 15.7 1,500 2.1 2.1 ~1 S3 - 30 % F
15 30 1,500 2.1 2.1 ~1 S1 - 100 %5) F
ED 50 50 50
30 5.1 375 0.5 0.5 ~1 S1 - 100 % E
70 2.4 500 0.3 0.3 ~1 S1 - 100 % E
15 15.7 1,500 2.1 2.1 ~1 S3 - 30 % F
15 30 1,500 2.1 2.1 ~1 S1 - 100 %5) F
EQ 40 40 20 30 15.7 1,500 2.1 2.1 ~1 S3 - 30 % F
30 30 1,500 2.1 2.1 ~1 S1 - 100 %5) F
60 5.1 375 0.5 0.5 ~1 S1 - 100 % E
20 15.7 1,500 2.1 2.1 ~1 S3 - 30 % F
20 30 1,500 2.1 2.1 ~1 S1 - 100 %5) F
EQ 60 60 40 30 15.7 1,500 2.1 2.1 ~1 S3 - 30 % F
30 30 1,500 2.1 2.1 ~1 S1 - 100 % 5) F
60 5.1 375 0.5 0.5 ~1 S1 - 100 % E
20 30 1,500 2.1 2.1 ~1 S1 - 100 % F
30 15.7 1,500 2.1 2.1 ~1 S3 - 30 % F
EQ 100 100 60 30 30 1,500 2.1 2.1 ~1 S1 - 100 %5) F
60 15.7 1,500 2.1 2.1 ~1 S3 - 30 % F
60 30 1,500 2.1 2.1 ~1 S1 - 100 %5) F
20 35 1,500 2.8 2.8 ~1 S3 - 75 % F
30 30 1,500 2.1 2.1 ~1 S1 - 100 % F
EQ 150 150 80
60 15.7 1,500 2.1 2.1 ~1 S3 - 30 % F
60 30 1,500 2.1 2.1 ~1 S1 - 100 %5) F
40 35 1,500 2.8 2.8 ~1 S3 - 75 % F
80 30 1,500 2.1 2.1 ~1 S1 - 100 % F
EQ 300 300 180
160 15.7 1,500 2.1 2.1 ~1 S3 - 30 % F
160 30 1,500 2.1 2.1 ~1 S1 - 100 %5) F
80 35 1,500 2.8 2.8 ~1 S3 - 75 % F
EQ 600 600 300
160 30 1,500 2.1 2.1 ~1 S1 - 100 % F

Notes on table
1) Power P Output of mechanical power at motor shaft at maximum torque of part-turn actuator.
The consumed electrical power can be calculated using the following formula: P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.
4) Type of duty All actuators are also suitable for type of duty S2 - 15 min
5) Option: S1 - 100 %

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.700/003/en Issue 1.17 Page 1/1


ED 25 – ED 50, EQ 40 – EQ 600
Electrical data Part-turn actuators with 1-phase AC motors
24 V/60 Hz

Part-turn actuator Motor


Type Torque range
Open-close Modulating
duty duty Operating time Nominal Max.
max. max. for 90° in Power1) Speed current2) current3) Insulation
[Nm] [Nm] seconds P [W] [rpm] IN [A] Imax [A] cos  Type of duty4) class
12 5.5 450 0.5 0.5 ~1 S1 - 100 % E
ED 25 25 25 25 5.5 450 0.5 0.5 ~1 S1 - 100 % E
59 2.6 600 0.3 0.3 ~1 S1 - 100 % E
12 18.8 1,800 2.3 2.3 ~1 S3 - 30 % F
12 35 1,800 2.1 2.1 ~1 S1 - 100 %5) F
ED 50 50 50
25 5.5 450 0.5 0.5 ~1 S1 - 100 % E
59 2.6 600 0.3 0.3 ~1 S1 - 100 % E
12.5 18.8 1,800 2.3 2.3 ~1 S3 - 30 % F
12.5 35 1,800 2.1 2.1 ~1 S1 - 100 %5) F
EQ 40 40 20 25 18.8 1,800 2.3 2.3 ~1 S3 - 30 % F
25 35 1,800 2.1 2.1 ~1 S1 - 100 %5) F
50 5.5 450 0.5 0.5 ~1 S1 - 100 % E
16 18.8 1,800 2.3 2.3 ~1 S3 - 30 % F
16 35 1,800 2.1 2.1 ~1 S1 - 100 %5) F
EQ 60 60 40 25 18.8 1,800 2.3 2.3 ~1 S3 - 30 % F
25 35 1,800 2.1 2.1 ~1 S1 - 100 %5) F
50 5.5 450 0.5 0.5 ~1 S1 - 100 % E
16 35 1,800 2.1 2.1 ~1 S1 - 100 % F
25 18.8 1,800 2.3 2.3 ~1 S3 - 30 % F
EQ 100 100 60 25 35 1,800 2.1 2.1 ~1 S1 - 100 %5) F
50 18.8 1,800 2.3 2.3 ~1 S3 - 30 % F
50 35 1,800 2.1 2.1 ~1 S1 - 100 %5) F
16 42.4 1,800 3.0 3.0 ~1 S3 - 75 % F
25 35 1,800 2.1 2.1 ~1 S1 - 100 % F
EQ 150 150 80
50 18.8 1,800 2.3 2.3 ~1 S3 - 30 % F
50 35 1,800 2.1 2.1 ~1 S1 - 100 %5) F
33 42.4 1,800 3.0 3.0 ~1 S3 - 75 % F
66 35 1,800 2.1 2.1 ~1 S1 - 100 % F
EQ 300 300 180
133 18.8 1,800 2.3 2.3 ~1 S3 - 30 % F
133 35 1,800 2.1 2.1 ~1 S1 - 100 %5) F
66 42.4 1,800 3.0 3.0 ~1 S3 - 75 % F
EQ 600 600 300
133 35 1,800 2.1 2.1 ~1 S1 - 100 % F

Notes on table
1) Power P Output of mechanical power at motor shaft at maximum torque of part-turn actuator.
The consumed electrical power can be calculated using the following formula: P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.
4) Type of duty All actuators are also suitable for type of duty S2 - 15 min
5) Option: S1 - 100 %

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.050/003/en Issue 1.17 Page 1/1


ED 25 – ED 50, EQ 40 – EQ 600
Electrical data Part-turn actuators with 1-phase AC motors
110 V/60 Hz

Part-turn actuator Motor


Type Torque range
Open-close Modulating
duty duty Operating time Nominal Max.
max. max. for 90° in Power1) Speed current2) current3) Insulation
[Nm] [Nm] seconds P [W] [rpm] IN [A] Imax [A] cos  Type of duty4) class
18 15.6 1,200 0.2 0.2 ~1 S1 - 100 % F
ED 25 25 25 36 3.1 450 0.6 0.6 ~1 S1 - 100 % E
84 2.6 600 0.1 0.1 ~1 S1 - 100 % E
18 19.5 1,200 0.4 0.4 0,98 S1 - 100 % F
ED 50 50 50 36 15.6 1,200 0.2 0.2 ~1 S1 - 100 % F
84 2.6 600 0.1 0.1 ~1 S1 - 100 % E
18 35 1,800 0.5 0.5 ~1 S1 - 100 % F
EQ 40 40 20 36 35 1,800 0.5 0.5 ~1 S1 - 100 % F
72 35 1,800 0.5 0.5 ~1 S1 - 100 % F
24 35 1,800 0.5 0.5 ~1 S1 - 100 % F
EQ 60 60 40 36 35 1,800 0.5 0.5 ~1 S1 - 100 % F
72 35 1,800 0.5 0.5 ~1 S1 - 100 % F
24 35 1,800 0.5 0.5 ~1 S1 - 100 % F
EQ 100 100 60 36 35 1,800 0.5 0.5 ~1 S1 - 100 % F
72 35 1,800 0.5 0.5 ~1 S1 - 100 % F
24 49 1,800 0.8 0.8 ~1 S3 - 50 % F
EQ 150 150 80 36 35 1,800 0.5 0.5 ~1 S1 - 100 % F
72 35 1,800 0.5 0.5 ~1 S1 - 100 % F
48 49 1,800 0.8 0.8 ~1 S3 - 50 % F
EQ 300 300 180 96 35 1,800 0.5 0.5 ~1 S1 - 100 % F
192 35 1,800 0.5 0.5 ~1 S1 - 100 % F
96 49 1,800 0.8 0.8 ~1 S3 - 50 % F
EQ 600 600 300
192 35 1,800 0.5 0.5 ~1 S1 - 100 % F

Notes on table
1) Power P Output of mechanical power at motor shaft at maximum torque of part-turn actuator.
The consumed electrical power can be calculated using the following formula: P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.
4) Type of duty All actuators are also suitable for type of duty S2 - 15 min

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.063/003/en Issue 1.15 Page 1/1


ED 25 – ED 50, EQ 40 – EQ 600
Electrical data Part-turn actuators with 1-phase AC motors
115 V/50 Hz

Part-turn actuator Motor


Type Torque range
Open-close Modulating
duty duty Operating time Nominal Max.
max. max. for 90° in Power1) Speed current2) current3) Insulation
[Nm] [Nm] seconds P [W] [rpm] IN [A] Imax [A] cos  Type of duty4) class
15 13,3 1,000 0,2 0,2 ~1 S1 - 100 % F
ED 25 25 25 30 2,7 375 0,1 0,1 0,99 S1 - 100 % E
70 2,4 500 0,1 0,1 ~1 S1 - 100 % E
15 30 1,500 0,5 0,5 ~1 S1 - 100 % F
ED 50 50 50 30 13,3 1,000 0,2 0,2 ~1 S1 - 100 % F
70 2,4 500 0,1 0,1 ~1 S1 - 100 % E
15 30 1,500 0,5 0,5 ~1 S1 - 100 % F
EQ 40 40 20 30 30 1,500 0,5 0,5 ~1 S1 - 100 % F
60 30 1,500 0,5 0,5 ~1 S1 - 100 % F
20 30 1,500 0,5 0,5 ~1 S1 - 100 % F
EQ 60 60 40 30 30 1,500 0,5 0,5 ~1 S1 - 100 % F
60 30 1,500 0,5 0,5 ~1 S1 - 100 % F
20 30 1,500 0,5 0,5 ~1 S1 - 100 % F
EQ 100 100 60 30 30 1,500 0,5 0,5 ~1 S1 - 100 % F
60 30 1,500 0,5 0,5 ~1 S1 - 100 % F
20 44 1,500 0,7 0,7 ~1 S3 - 50 % F
EQ 150 150 80 30 30 1,500 0,5 0,5 ~1 S1 - 100 % F
60 30 1,500 0,5 0,5 ~1 S1 - 100 % F
40 44 1,500 0,7 0,7 ~1 S3 - 50 % F
EQ 300 300 180 80 30 1,500 0,5 0,5 ~1 S1 - 100 % F
160 30 1,500 0,5 0,5 ~1 S1 - 100 % F
80 44 1,500 0,7 0,7 ~1 S3 - 50 % F
EQ 600 600 300
160 30 1,500 0,5 0,5 ~1 S1 - 100 % F

Notes on table
1) Power P Output of mechanical power at motor shaft at maximum torque of part-turn actuator.
The consumed electrical power can be calculated using the following formula: P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.
4) Type of duty All actuators are also suitable for type of duty S2 - 15 min

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.062/003/en Issue 1.15 Page 1/1


ED 25 – ED 50, EQ 40 – EQ 600
Electrical data Part-turn actuators with 1-phase AC motors
220 V/60 Hz

Part-turn actuator Motor


Type Torque range
Open-close Modulating
duty duty Operating time Nominal Max.
max. max. for 90° in Power1) Speed current2) current3) Insulation
[Nm] [Nm] seconds P [W] [rpm] IN [A] Imax [A] cos  Type of duty4) class
12 5.5 450 0.05 0.05 ~1 S1 - 100 % E
ED 25 25 25 25 5.5 450 0.05 0.05 ~1 S1 - 100 % E
59 2.6 600 0.03 0.03 ~1 S1 - 100 % E
12 22.6 1,800 0.30 0.30 ~1 S3 - 30 % F
12 35 1,800 0.23 0.23 ~1 S1 - 100 %5) F
ED 50 50 50
25 5.5 450 0.05 0.05 ~1 S1 - 100 % E
59 2.6 600 0.03 0.03 ~1 S1 - 100 % E
12.5 22.6 1,800 0.30 0.30 ~1 S3 - 30 % F
12.5 35 1,800 0.23 0.23 ~1 S1 - 100 %5) F
EQ 40 40 20 25 22.6 1,800 0.30 0.30 ~1 S3 - 30 % F
25 35 1,800 0.23 0.23 ~1 S1 - 100 %5) F
50 5.5 450 0.05 0.05 ~1 S1 - 100 % E
16 22.6 1,800 0.30 0.30 ~1 S3 - 30 % F
16 35 1,800 0.23 0.23 ~1 S1 - 100 %5) F
EQ 60 60 40 25 22.6 1,800 0.30 0.30 ~1 S3 - 30 % F
25 35 1,800 0.23 0.23 ~1 S1 - 100 %5) F
50 5.5 450 0.05 0.05 ~1 S1 - 100 % E
16 35 1,800 0.23 0.23 ~1 S1 - 100 % F
25 22.6 1,800 0.30 0.30 ~1 S3 - 30 % F
EQ 100 100 60 25 35 1,800 0.23 0.23 ~1 S1 - 100 %5) F
50 22.6 1,800 0.30 0.30 ~1 S3 - 30 % F
50 35 1,800 0.23 0.23 ~1 S1 - 100 %5) F
16 56.5 1,800 0.39 0.39 ~1 S3 - 30 % F
25 35 1,800 0.23 0.23 ~1 S1 - 100 % F
EQ 150 150 80
50 22.6 1,800 0.30 0.30 ~1 S3 - 30 % F
50 35 1,800 0.23 0.23 ~1 S1 - 100 %5) F
33 56.5 1,800 0.39 0.39 ~1 S3 - 50 % F
66 35 1,800 0.23 0.23 ~1 S1 - 100 % F
EQ 300 300 180
133 22.6 1,800 0.30 0.30 ~1 S3 - 30 % F
133 35 1,800 0.23 0.23 ~1 S1 - 100 %5) F
66 56.5 1,800 0.39 0.39 ~1 S3 - 50 % F
EQ 600 600 300
133 35 1,800 0.23 0.23 ~1 S1 - 100 % F

Notes on table
1) Power P Output of mechanical power at motor shaft at maximum torque of part-turn actuator.
The consumed electrical power can be calculated using the following formula: P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.
4) Type of duty All actuators are also suitable for type of duty S2 - 15 min
5) Option: S1 - 100 %

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.065/003/en Issue 1.17 Page 1/1


ED 25 – ED 50, EQ 40 – EQ 600
Electrical data Part-turn actuators with 1-phase AC motors
230 V/50 Hz

Part-turn actuator Motor


Type Torque range
Open-close Modulating
duty duty Operating time Nominal Max.
max. max. for 90° in Power1) Speed current2) current3) Insulation
[Nm] [Nm] seconds P [W] [rpm] IN [A] Imax [A] cos  Type of duty4) class
15 5.5 375 0.05 0.05 ~1 S1 - 100 % E
ED 25 25 25 30 5.5 375 0.05 0.05 ~1 S1 - 100 % E
70 2.4 500 0.03 0.03 ~1 S1 - 100 % E
15 18.9 1,500 0.28 0.28 ~1 S3 - 30 % F
15 30 1,500 0.23 0.23 ~1 S1 - 100 %5) F
ED 50 50 50
30 5.1 375 0.05 0.05 ~1 S1 - 100 % E
70 2.4 500 0.03 0.03 ~1 S1 - 100 % E
15 18.9 1,500 0.28 0.28 ~1 S3 - 30 % F
15 30 1,500 0.23 0.23 ~1 S1 - 100 %5) F
EQ 40 40 20 30 18.9 1,500 0.28 0.28 ~1 S3 - 30 % F
30 30 1,500 0.23 0.23 ~1 S1 - 100 %5) F
60 5.1 375 0.05 0.05 ~1 S1 - 100 % E
20 18.9 1,500 0.28 0.28 ~1 S3 - 30 % F
20 30 1,500 0.23 0.23 ~1 S1 - 100 %5) F
EQ 60 60 40 30 18.9 1,500 0.28 0.28 ~1 S3 - 30 % F
30 30 1,500 0.23 0.23 ~1 S1 - 100 %5) F
60 5.1 375 0.05 0.05 ~1 S1 - 100 % E
20 30 1,500 0.23 0.23 ~1 S1 - 100 % F
30 18.9 1,500 0.28 0.28 ~1 S3 - 30 % F
EQ 100 100 60 30 30 1,500 0.23 0.23 ~1 S1 - 100 %5) F
60 18.9 1,500 0.28 0.28 ~1 S3 - 30 % F
60 30 1,500 0.23 0.23 ~1 S1 - 100 %5) F
20 50 1,500 0.35 0.35 ~1 S3 - 50 % F
30 30 1,500 0.23 0.23 ~1 S1 - 100 % F
EQ 150 150 80
60 18.9 1,500 0.28 0.28 ~1 S3 - 30 % F
60 30 1,500 0.23 0.23 ~1 S1 - 100 %5) F
40 50 1,500 0.35 0.35 ~1 S3 - 50 % F
80 30 1,500 0.23 0.23 ~1 S1 - 100 % F
EQ 300 300 180
160 18.9 1,500 0.28 0.28 ~1 S3 - 30 % F
160 30 1,500 0.23 0.23 ~1 S1 - 100 %5) F
80 50 1,500 0.35 0.35 ~1 S3 - 50 % F
EQ 600 600 300
160 30 1,500 0.23 0.23 ~1 S1 - 100 % F

Notes on table
1) Power P Output of mechanical power at motor shaft at maximum torque of part-turn actuator.
The consumed electrical power can be calculated using the following formula: P = U x I x cos 
2) Nominal current IN Rated current at maximum modulating torque and indicated operating time
3) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.
4) Type of duty All actuators are also suitable for type of duty S2 - 15 min
5) Option: S1 - 100 %

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.064/003/en Issue 1.17 Page 1/1


ED 25 – ED 50, EQ 40 – EQ 600
Electrical data Part-turn actuators with DC motors
24 V DC

Part-turn actuator Motor


Type Torque range
Open-close Modulating
duty duty Operating time Nominal Starting
max. max. for 90° in sec- Power2) Speed3) current4) Max. current5) current
[Nm] [Nm] onds1) P [W] [rpm] IN [A] Imax [A] IA [A] Type of duty6)
7 13 3,500 0.8 0.8 4 S4 - 100 %
15 13 3,500 0.8 0.8 4 S4 - 100 %
ED 25 25 25
30 4 3,000 0.3 0.3 0.8 S4 - 100 %
60 2 1,900 0.2 0.2 4 S4 - 100 %
7 25 2,700 1.9 1.9 5.7 S4 - 50 %
15 17 3,000 1.3 1.3 4 S4 - 50 %
ED 50 50 50
30 18 3,600 0.5 0.5 4 S4 - 100 %
60 2 1,800 0.2 0.2 4 S4 - 100 %
15 18 2,900 0.6 1.3 4 S4 - 50 %
EQ 40 40 20 30 18 2,900 0.6 1.3 4 S4 - 100 %
60 7 1,200 0.5 0.8 4 S4 - 100 %
15 20 2,600 1.2 1.5 4 S4 - 30 %
EQ 60 60 40 30 16 2,900 0.7 1.3 4 S4 - 50 %
60 7 1,200 0.6 0.8 4 S4 - 100 %
15 32 2,700 1.8 2.1 5.7 S4 - 30 %
EQ 100 100 60 30 25 2,900 1.3 1.5 5.7 S4 - 50 %
60 8 1,100 0.7 1.1 4 S4 - 50 %
15 45 3,100 2.2 2.7 18 S4 - 100 %
EQ 150 150 80 30 29 2,700 1.5 2.1 5.7 S4 - 30 %
60 9 1,000 0.8 1.2 4 S4 - 50 %
40 45 3,100 1.8 2.7 18 S4 - 100 %
EQ 300 300 180 80 24 2,800 1.2 1.6 5.7 S4 - 50 %
160 7.2 1,000 0.8 1.2 4 S4 - 50 %
80 45 3,100 1.8 2.7 18 S4 - 100 %
EQ 600 600 300
160 30 2,500 1.3 2.1 5.7 S4 - 30 %

Notes on table
1) Operating time Operating times may vary depending on the load.
2 Power P Output of mechanical power at motor shaft at maximum torque of part-turn actuator.
3) Output speed Motor speed at max. torque
4) Nominal current IN Rated current at maximum modulating torque and indicated operating time.
5) Max. current Imax Current at maximum torque. We recommend selecting the switchgear in compliance with these values.
6) Type of duty All actuators are also suitable for type of duty S2 - 15 min
Number of starts: 600 cycles per hour

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.560/0031/en Issue 1.17 Page 1/1


SBA 06 – SBA 200
Electrical data Linear actuators with DC motors
24 V DC

Linear actuator Motor


Operating
Stroke force Operating speed Max. cur- Starting
Max. Max.1) Max. Power2) Speed rent3) current Insulation
Type [mm] [kN] [mm/min] Motor type P [W] [rpm] Imax [A] IA [A] class
10 7.2 3,200 0.3 0.8 E
SBA 06-1 0.6 17.5 DC 7.2 3,200 0.3 0.8 E
30 7.2 3,200 0.3 0.8 E
35
10 7.2 3,200 0.3 0.8 E
SBA 06-2 0.9 17.5 DC 7.2 3,200 0.3 0.8 E
30 7.2 3,200 0.3 0.8 E
30 8.5 2.100 0.35 1.8 E
SBA 12 75 1.2 DC
50 16.8 3,600 0.7 1.4 E
30 8.5 2.100 0.35 1.8 E
SBA 20 75 2.0 DC
50 16.8 3,600 0.7 1.4 E
30 8.5 2.100 0.35 1.8 E
SBA 45-2 3.5 DC
50 16.8 3,600 0.7 1.4 E
30 8.5 2.100 0.35 1.8 E
SBA 45-3 75 4.5 DC
50 16.8 3,600 0.7 1.4 E
30 8.5 2.100 0.35 1.8 E
SBA 45-4 6.0 DC
50 16.8 3,600 0.7 1.4 E
25 26.5 1,350 1.1 9.5 E
SBA 80-1 6.0 DC
60 64.8 3,300 2.7 24 E
25 26.5 1,350 1.1 9.5 E
SBA 80-2 8.0 DC
80 60 64.8 3,300 2.7 24 E
25 26.5 1,350 1.1 9.5 E
SBA 80-3 12 DC
60 64.8 3,350 2.7 24 E
25 26.5 1,350 1.1 9.5 E
SBA 80-4 15 DC
60 118 3,350 4.9 33 E
30 48 1,350 2 13 E
SBA 200-1 15 DC
100 60 118 3,350 4.9 33 E
30 48 1,350 2 13 E
SBA 200-2 20 DC
60 118 3,350 4.9 33 E
SBA 200-3 100 25 30 DC 48 1,350 2 13 E

Notes on table
1) Max operating force Also corresponds to maximum operating force in modulating duty.
2 Power P Output of mechanical power at motor shaft at maximum operating force of linear actuator.
3) Max. current Imax Current at maximum operating force. Also corresponds to maximum force in modulating duty. We recommend
sizing the switchgear in compliance with these values.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.561/003/en Issue 1.17 Page 1/1


SD 05 – SD 25
Electrical data Multi-turn actuators with 1-phase AC motors
100 V – 240 V/50 Hz/60 Hz

Multi-turn actuator Motor

Output Torque range


speed Open-close duty Modulating duty Nominal Starting
Max. max. max. Power1) Speed current2) current3)
Type [rpm] [Nm] [Nm] Motor type P [W] [rpm] IN [A] Imax [A]
SD 05 8 6 6 sm5) 50 450 0.22 0.22
SD 10 20 10 10 bldc6) 60 4 500 0.26 0.26
SD 25 20 30 25 bldc6) 120 4 500 0.52 0.52

Notes on table
1 Power P Maximum power consumption
2) Nominal current IN Current at running torque
3) Starting current Imax Maximum short-term starting current
4) Step motor
5) Brushless DC motor

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.947/003/en Issue1.15 Page1/1


SDL 50 – SDL 100 / SDG 40
Electrical data Linear actuators with 1-phase AC motors
100 V – 240 V/50 Hz/60 Hz

Linear actuator Motor


Operating force
Stroke Open-close duty Modulating duty Nominal Starting
Max. Max. Max. Power1) Speed current2) current3)
Type [mm] [kN] [kN] Motor type P [W] [rpm] IN [A] Imax [A]
SDL 50-10 55 6.0 5.0 sm4) 60 450 0.26 0.26
SDL 50-20 55 6.0 4.0 bldc5) 60 4,500 0.26 0.26
SDL 50-30 55 4.0 2.5 bldc5) 120 4,500 0.52 0.52
SDL 100-20 85 6.0 6.0 bldc5) 60 4,500 0.26 0.26
SDL 100-30 85 15 10.0 bldc 5)
120 4,500 0.52 0.52
SDG 40-13 300 3.0 2.0 sm4) 60 450 0.26 0.26
SDG 40-23 300 4.0 4.0 bldc5) 60 4,500 0.26 0.26

Notes on table
1 Power P Maximum power consumption
2) Nominal current IN Current at running torque
3) Starting current Imax Maximum short-term starting current
4) Step motor
5) Brushless DC motor

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.952/003/en Issue 1.16 Page 1/1


SGC 04.1 – SGC 12.1/SGCR 04.1 – SGCR 12.1
Electrical data Part-turn actuators with integral actuator controls
Short-time duty S2 - 15 min and intermittent duty S4 - 40 %, 115 V, 230 V/50 Hz/60 Hz

Electrical data for connection to 1-phase AC 115 V, 50 Hz/60 Hz


Type Operating time Torque1) Running torque2)/ Power Motor speed Rated current4) Max. current5)
for 90° Modulating torque3)
Max. Max. Max.
[Seconds] [Nm] [Nm] PN [W] [rpm] IN [A] Imax.[A]
SGC/SGCR 04.1 4 – 63 25 – 63 32 80 2,250 1.1 1.5
SGC/SGCR 05.1 4 – 63 50 – 125 63 120 2,250 1.6 3.0
SGC/SGCR 07.1 4 – 63 100 – 250 125 175 2,250 2.4 4.1
SGC/SGCR 10.1 5.6 – 90 200 – 500 250 225 2,250 3.2 6.0
SGC/SGCR 12.1 20 – 275 400 – 1,000 500 175 2,250 2.4 4.0

Electrical data for connection to 1-phase AC 230 V, 50 Hz/60 Hz


Type Operating time Torque1) Running torque2)/ Power Motor speed Rated current4) Max. current5)
for 90° Modulating torque3)
Max. Max. Max.
[Seconds] [Nm] [Nm] PN [W] [rpm] IN [A] Imax.[A]
SGC/SGCR 04.1 4 – 63 25 – 63 32 80 2,250 0.55 0.75
SGC/SGCR 05.1 4 – 63 50 – 125 63 120 2,250 0.8 1.5
SGC/SGCR 07.1 4 – 63 100 – 250 125 175 2,250 1.2 2.1
SGC/SGCR 10.1 5.6 – 90 200 – 500 250 225 2,250 1.6 3.0
SGC/SGCR 12.1 20 – 275 400 – 1,000 500 175 2,250 1.2 2.0

Notes on table
1) Torque Adjustable tripping torque
2) Running torque Permissible average torque in open-close duty S2 - 15 min
3) Modulating torque Torque in modulating duty S4 - 40 %
4) Rated current Rated current at maximum modulating torque and shortest operating time
5) Max. current Current at maximum torque and maximum speed. We recommend selecting the switchgears in compliance
with these values.

Motor data is approximate. Due to usual manufacturing tolerances, there may be deviations from the values given. The permissible variation of the
nominal voltage is ±10 %. Higher voltage failures cause reduction in nominal output torque.

The output data of the fuses to be provided on site must not exceed the following values:
15 A/250 V at a maximum mains current of 5,000 A AC.
For protection with circuit breakers, devices with 6 A at 230 V AC, or 13 A at 115 V AC with characteristics D according to VDE 0641 and IEC 60898
with at least 15 kA switching power are recommended.
Groups of up to four actuators can be protected via one circuit breaker with at least 15 kA switching power, 20 A at 230 V AC, or 40 A at 115 V AC,
characteristics D according to IEC 60898.

For further information, refer to "Technical data Part-turn actuators SGC/SGCR 04.1 – SGC/SGCR 12.1 with integral actuator controls".

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.976/003/en Issue 2.13 Page 1/1


SVC 05.1 – SVC 07.5/SVCR 05.1 – SVCR 07.5
Electrical data Globe valve actuators with integral actuator controls
Short-time duty S2 - 15 min and intermittent duty S4 - 40 %, 115 V, 230 V/50 Hz/60 Hz

Electrical data for connection to 1-phase AC 115 V, 50 Hz/60 Hz


Type Output speed Torque1) Running torque2)/ Power Motor speed Rated current4) Max. current5)
Modulating torque3)
Max. Max. Max.
[rpm] [Nm] [Nm] PN [W] [rpm] IN [A] Imax.[A]
SVC/SVCR 05.1 1.6 – 22 10 – 25 13 225 2,250 3.2 5.0
SVC/SVCR 07.1 1.6 – 22 20 – 50 25 280 2,250 4.0 6.0
SVC/SVCR 07.5 0.6 – 8.0 40 – 100 50 175 2,250 2.4 4.0

Electrical data for connection to 1-phase AC 230 V, 50 Hz/60 Hz


Type Output speed Torque1) Running torque2) Power Motor speed Rated current4) Max. current5)
Modulating torque3)
Max. Max. Max.
[rpm] [Nm] [Nm] PN [W] [rpm] IN [A] Imax.[A]
SVC/SVCR 05.1 1.6 – 22 10 – 25 13 225 2,250 1.6 2.5
SVC/SVCR 07.1 1.6 – 22 20 – 50 25 280 2,250 2.0 3.0
SVC/SVCR 07.5 0.6 – 8.0 40 – 100 50 175 2,250 1.2 2.0

Notes on table
1) Torque Adjustable tripping torque
2) Running torque Permissible average torque in open-close duty S2 - 15 min
3) Modulating torque Torque in modulating duty S4 - 40 %
4) Rated current Rated current at maximum modulating torque and shortest operating time
5) Max. current Current at maximum torque and maximum speed. We recommend selecting the switchgears in compliance
with these values.

Motor data is approximate. Due to usual manufacturing tolerances, there may be deviations from the values given. The permissible variation of the
nominal voltage is ±10 %. Higher voltage failures cause reduction in nominal output torque.

The output data of the fuses to be provided on site must not exceed the following values:
15 A/250 V at a maximum mains current of 5,000 A AC.
For protection with circuit breakers, devices with 6 A at 230 V AC, or 13 A at 115 V AC with characteristics D according to VDE 0641 and IEC 60898
with at least 15 kA switching power are recommended.
Groups of up to four actuators can be protected via one circuit breaker with at least 15 kA switching power, 20 A at 230 V AC, or 40 A at 115 V AC,
characteristics D according to IEC 60898.

For further information, refer to "Technical data Globe valve actuators SVC/SVCR 05.1 – SVC/SVCR 07.5 with integral actuator controls".

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y005.013/003/3n Issue 2.13 Page 1/1


SD 05 – SD 25
Electrical data Multi-turn actuators with DC motors
24 V DC

Multi-turn actuator Motor

Output Torque range


speed Open-close duty Modulating duty Nominal Starting
Max. max. max. Power1) Speed current2) current3)
Type [rpm] [Nm] [Nm] Motor type P [W] [rpm] IN [A] Imax [A]
SD 05 8 6 6 sm4) 50 450 2.1 2.1
SD 10 20 10 10 bldc5) 60 4 500 2.5 2.5
SD 25 20 30 25 bldc5) 120 4 500 5 5

Notes on table
1 Power P Maximum power consumption
2) Nominal current IN Current at running torque
3) Starting current Imax Maximum short-term starting current
4) Step motor
5) Brushless DC motor

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.056/003/en Issue1.15 Page1/1


SDL 50 – SDL 100 / SDG 40
Electrical data Linear actuators with DC motors
24 V DC

Linear actuator Motor


Operating force
Stroke Open-close duty Modulating duty Nominal cur- Starting cur-
Max. Max. Max. Power1) Speed rent2) rent3)
Type [mm] [kN] [kN] Motor type P [W] [rpm] IN [A] Imax [A]
SDL 50-10 55 6.0 5.0 sm4) 60 450 2.5 2.5
SDL 50-20 55 6.0 4.0 bldc5) 60 4,500 2.5 2.5
SDL 50-30 55 4.0 2.5 bldc5) 120 4,500 5.0 5.0
SDL 100-20 85 6.0 6.0 bldc5) 60 4,500 2.5 2.5
SDL 100-30 85 15 10.0 bldc5) 120 4,500 5.0 5.0
SDG 40-13 300 3.0 2.0 sm4) 60 450 2.5 2.5
SDG 40-23 300 4.0 4.0 bldc5) 60 4,500 2.5 2.5

Notes on table
1 Power P Maximum power consumption
2) Nominal current IN Current at running torque
3) Starting current Imax Maximum short-term starting current
4) Step motor
5) Brushless DC motor

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.057/003/en Issue 1.16 Page 1/1


4 Dimensions Actuators

Basic Range
SBA 06-1/-2/-3/-4 92
SBA 12 –SBA 200 93

NR 2.1 – NR 2.3 94

ED 25 – ED 50 95
EQ 40 – EQ 150 97
EQ 300 – EQ 600 99
EQ 40 – EQ 600 with base and lever 101

Smart Range
SD 05 – SD 25 102
SDL 50 – SDL 100 104

SGC(R) 04.1 – SGC(R) 10.1 / SVC(R) 05.1 – SVC(R) 07.5 105


SGC 12.1 / SGCR 12.1 107

4. Dimensions
Actuators
SBA 06-1/-2/-3/-4

Dimensions Linear actuators

S 2)
Ø d3
Ø d4

h1
H2

H1

h
P

H
L

L4

Ø d9
Ø d5 2)
Ø d8
h2

Ø d2
d1
ØB

1) Dimensions PEL (electronic positioner)


2) Dimensions depending on pillar yoke applied
Dimensions SBA 06-1/-2/-3 SBA 06-4
DIN 3358 F05 F05
ØB 129 129
H (stroke max.) 35 35
H1 226 (265 1)) 288 (327 1))
H2 101 (140 1)) 101 (140 1))
L 68 68
L4 30 30
P 3 x M16 x 1.5 3 x M16 x 1.5
S 2) 90/100 90/100
d1 110 110
Ø d2 35 35
Ø d3 50 50
Ø d5 max. 2) 12 12
Ø d4 8.4 8.4
Ø d8 M12 x 1.25 M12 x 1.25
Ø d9 40 40
h 18 52
h1 18 18
h2 5 5
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.156/003/en Issue 1.15 Page 1/1


SBA 12 – SBA 200

Dimensions Linear actuators

Standard Option: Option:


Compact plug KS1 Profibus DP PBD100
M M1

h1

F1
H2

F
H1

G1
ØD

G
P
h2
h
H

Ø d9
Option:
L4

Local controls VSE


M2 Ø d8
Ø d1

2)
L

F2

X
C1 C

View X

G2
ØB

Ø d4 x h3

Ø d3
Ø d5 2)
Ø D1

1) Dimensions PEL (electronic positioner)


2) Other dimensions on request
Dimensions SBA 12 SBA 20/SBA 45 SBA 80 SBA 200
DIN 3358 F05 F05 G0 G0
ØB 145 145 188 216
M 210 210 222 242
M1 155 155 170 183
M2 213 213 227 241
C 86 86 122 133
C1 30 30 43 43
ØD 54 54 100 100
Ø D1 8 8 18 18
F 100 (115 1)) 100 (115 1)) 155 (178 1)) 134 (175 1))
F1 39 (64 1)) 39 (64 1)) 94 (117 1)) 72 (113 1))
F2 6 (22 1)) 6 (22 1)) 61 (84 1)) 39 (78 1))
…G 124 124 124 124
… G1 184 184 184 184
G2 230 230 230 230
H (stroke max.) 75 75 80 100
H1 247 (262 1)) 253 (268 1)) 304 (327 1)) 378 (419 1))
H2 158 (173 1)) 158 (173 1)) 174 (197 1)) 188 (229 1))
L 2) 58 58 58 58
L4 45 45 45 51
P 3 x M16 x 1.5 3 x M16 x 1.5 3 x M20 x 1.5 3 x M20 x 1.5
Ø d1 74 74 130 130
Ø d3 50 50 102 102
Ø d4 M6 M6 M10 M10
Ø d5 2) 22 22 22 22
Ø d8 max. M20 x 1.5 M20 x 1.5 M20 x 1.5 M20 x 1.5
Ø d9 55 55 55 55
h 41,5 41,5 26 3
h1 15 15 15 15
h2 14 14 16 32
h3 – – – 16
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.164/003/en Issue 1.15 Page 1/1


NR 2.1 – NR 2.3

Dimensions Linear actuators with fail safe unit

Ø d6 2)
Ø d3
Ø d4 x h3

h1
H2

H1

P
h2

h
H

2)
Ø d5
L4

Ø d8 Ø d9
Ø d2 L
Ø d1

1) Dimensions PED (electronic positioner)


2) Dimensions depending on pillar yoke applied
Dimensions NR 2.1 NR 2.2 NR 2.3
DIN 3358 F05
…B 162
H (stroke) 35 35 46
H1 315 352 1) 333 370 1) 354 390 1)
H2 176 (213 1))
L 70
L4 30
P 4 x M20 x 1.5
Ø d1 120
Ø d2 f8 35
Ø d3 50
Ø d4 M6
Ø d5 max. 2) M12
Ø d6 2) 95/100/105
Ø d8 M12 x 1.25
Ø d9 40
h 3
h1 18
h2 20
h3 12
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.037/003/en Issue 1.15 Page 1/1


ED 25 – ED 50

Dimensions Part-turn actuators

h1
1)
H1

H2

H3

L max. 2)
P A
d4 x h2
A1 C2

A2 Ø d3

F07
F05
C1

F04

F03
C

Output drives according to EN ISO 5211


1) Dimensions for actuator with aluminium hood
2) Max. fitting dimension Dimensions of couplings see overleaf
Dimensions ED 25 – ED 50
EN ISO 5211 F03 F04 F05 F07
A 55
A1 98
A2 166
C 131
C1 65
C2 50
H 190
H1 1) 220
H2 82
H3 16
L max. 2) 30
P 2 x M16 x 1.5
Ø d3 36 42 50 70
Ø d4 4 x M5 4 x M5 4 x M6 4 x M8
h 4
h1 12
h2 8 8 9 12
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.787/003/en Issue 1.15 Page 1/2


ED 25 – ED 50

Dimensions Couplings according to EN ISO 5211

Bore according to Dimensions ED 25 – ED 50


EN ISO 5211
EN ISO 5211 F03, F04, F05, F07
With keyway according to
ØD 24.8
DIN 6885-1
L4 25
Ø d7 H8 2) 10 12 14

Ø d7 H8 from 8 10 12
to 10 12 15
b JS9 1) 3 4 5
t 1) 1.4 +0.1 1.8 +0.1 2.3 +0.1

Square bore Dimensions ED 25 – ED 50


according to EN ISO 5211 EN ISO 5211 F03, F04, F05, F07
ØD 24.8
L4 25
s H11 2) 9 11 14
s H11 max. 14
Ø d8 max. 12.1 14.1 18.1

Bore with two-flats Dimensions ED 25 – ED 50


according to EN ISO 5211 EN ISO 5211 F03, F04, F05, F07
ØD 24.8
L4 25
s H11 2) 9 11 14
s H11 max. 14
Ø d8 max. 12.1 14.1 18.1

1) Dimensions depend on Ø d7, refer to DIN 6885-1


2) Recommended size according to EN ISO 5211

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.787/003/en Issue 1.15 Page 2/2


EQ 40 – EQ 150

Dimensions Part-turn actuators

h1
h3
N
Option:
KS1 compact connector

1)
H1
H

P
G

H2
ØD

H4
F

H3
Lower edge of actuator

L max.2)
A3 d4 x h2
N1
Option: A Ø d3
A1
Profibus DP PBD100
A2

F10

G1

C4
F07

C3
F05

C2
M
F04

C1
C
F1
Lower edge of actuator
N2
Option:
Local controls VSE
Ø D1
G2

F2

Lower edge of actuator

N3
Option:
Emergency operation module FSC20/
transformer housing PEL-DS
G3

F3

Lower edge of actuator


Output drives according to EN ISO 5211
1) Dimensions for actuator with aluminium hood
Dimensions of couplings see overleaf
2) Max. fitting dimension
Dimensions EQ 40 – EQ 150
EN ISO 5211 F04 F05 F07 F10
A 98
A1 162
A2 169
A3 54
C 220
C1 183
C2 146
C3 131
C4 65
ØD 100
Ø D1 18
F 65
F1 70
F2 53
F3 64
G 194
G1 254
G2 180
G3 201
H 246
H1 1) 274
H2 133
H3 27.5
H4 63
L max. 2) 41
M min. 12.9 (~ -15°) Standard 19 (~ -90°) max. 25.1 (~ +15°)
N 144
N1 87
N2 96
N3 188
P 3 x M20 x 1.5
Ø d3 42 50 70 102
Ø d4 4 x M5 4 x M6 4 x M8 4 x M10
h 4
h1 12
h2 8 9 12 15
h3 21
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.788/003/en Issue 1.15 Page 1/2


EQ 40 – EQ 150

Dimensions Couplings according to EN ISO 5211

Bore according to Dimensions EQ 40 – EQ 150


EN ISO 5211
EN ISO 5211 F04, F05, F07, F10
With keyway according to
ØD 31.75
DIN 6885-1
L4 35
Ø d7 H8 2) 12 14 18

Ø d7 H8 from 10 12 17
to 12 17 20
b JS9 1) 4 5 6
t 1.8 +0.1 2.3 +0.1 2.8 +0.1

Square bore Dimensions EQ 40 – EQ 150


according to EN ISO 5211 EN ISO 5211 F04, F05, F07, F10
ØD 31.75
L4 35
s H11 2) 9 11 14 17
s H11 max. 17
Ø d8 max. 12.1 14.1 18.1 22.2

Bore with two-flats Dimensions EQ 40 – EQ 150


according to EN ISO 5211 EN ISO 5211 F04, F05, F07, F10
ØD 31.75
L4 35
s H11 2) 9 11 14 17
s H11 max. 17
Ø d8 max. 12.1 14.1 18.1 22.2

1) Dimensions depend on Ø d7, refer to DIN 6885-1


2) Recommended size according to EN ISO 5211

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.788/003/en Issue 1.15 Page 2/2


EQ 300/EQ 600

Dimensions Part-turn actuators

h1
h3
N
Option:
KS1 compact connector

1)
H1
H

P
G

H2
ØD

H4
F
Lower edge of actuator

H5
L max.2)
N1
Option:

H6
Profibus DP PBD100
A
d4 x h2
Ø d3

G1
A2
A1
M

F1
F10
Lower edge of actuator

C4

Ø d1
C3
C2
N2 F07
Option:

C1
C
Local controls VSE
Ø d2
G2

A3

M
Ø D1
F2

Lower edge of actuator


N3
Option:

Ø d1
Emergency operation module FSC20/ F12
transformer housing PEL-DS
G3

Ø d2
F3

Lower edge of actuator


Output drives according to EN ISO 5211
1) Dimensions for actuator with aluminium hood Dimensions of couplings see overleaf
2) Max. fitting dimension
Dimensions EQ 300 – EQ 600
EN ISO 5211 F07 F10 F12
A 98
A1 162
A2 169
A3 54
C 220
C1 183
C2 146
C3 131
C4 65
ØD 100
Ø D1 18
F 65
F1 70
F2 53
F3 64
G 194
G1 254
G2 180
G3 201
H 246
H1 1) 274
H2 133
H4 63
H5 103
H6 38.5
L max. 2) 50
M min. -3 (~ -15°) Standard 12 (~ 90°) max. 27 (~ +15°)
N 144
N1 87
N2 96
N3 188
P 3 x M20 x 1.5
Ø d1 178
Ø d2 150
Ø d3 70 102 125
Ø d4 4 x M8 4 x M10 4 x M12
h 4
h1 12
h2 12 15 20
h3 21
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.789/003/en Issue 1.15 Page 1/2


EQ 300/EQ 600

Dimensions Couplings according to EN ISO 5211

Bore according to Dimensions EQ300/EQ600


EN ISO 5211
EN ISO 5211 F07, F10, F12
With keyway according to
ØD 51.75
DIN 6885-1
L4 45
Ø d7 H8 2) 22 28 36

Ø d7 H8 from 22 30
to 30 38
b JS9 1) 8 10
t 3.3 +0.1 3.3 +0.2

Square bore Dimensions EQ300/EQ600


according to EN ISO 5211 F07, F10, F12
EN ISO 5211
ØD 51.75
L4 45
s H11 2) 19 22 27
s H11 max. 30
Ø d8 max. 25.2 28.2 36.2

Bore with two-flats Dimensions EQ300/EQ600


according to EN ISO 5211 EN ISO 5211 F07, F10, F12
ØD 51.75
L4 45
s H11 2) 19 22 27
s H11 max. 30
Ø d8 max. 25.2 28.2 36.2

1) Dimensions depend on Ø d7, refer to DIN 6885-1


2) Recommended size according to EN ISO 5211

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.789/003/en Issue 1.15 Page 2/2


EQ 40 – EQ 600

Dimensions Part-turn actuators with base and lever

B2
EQ 40 – EQ 150 EQ 300/EQ 600 B1
with base and lever with base and lever

B2
B1

B B

Ø d1

Ø d1
Ø d2

Ø d2
H

H
H2

H2
H1

H1
h

h
h2

h2
h1

h1
C1 Ø d3 C1 Ø d3
C M C M
tapered hole 1:10

tapered hole 1:10


h3

h3
h1

h1
tapered hole 1:10

tapered hole 1:10


M1 M1
M2 M2

For missing dimensions, refer to Dimensions EQ Part-turn actuators in standard version


Dimensions EQ 40 – EQ 150 EQ 300/EQ 600
B 180 180
B1 80 80
B2 230 230
C 90 90
C1 20 20
H 160 160
H1 40 40
H2 140 140
M 100 100
M1 150 150
M2 200 200
Ø d1 14 15
Ø d2 14 15
Ø d3 H8 16 16
h 24 24
h1 20 20
h2 32 32
h3 13 –
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.790/003/en Issue 1.15 Page 1/1


SD 05 – SD 25

Dimensions Multi-turn actuators

Ø D2

ØD
H2

L max.
P
H3

h2

h
Ø d2
d4
A
Ø d3
Ø d1

C2 C1
C
Ø D1

H1

1) Output drive stem nut A Output drives according to EN ISO 5210


2) Output drive type A, extended version For dimensions see overleaf
Dimensions SD 05 – SD 25 SD 05 – SD 25 1)
EN ISO 5210 F10 F07 F07 2) F10
A 48 48
C 143 143
C1 276 276
C2 53 53
ØD 100 100
Ø D1 18 18
Ø D2 182 182
H 272 329 369 339
… H1 150 150
H2 146 203 243 213
H3 92 149 189 159
L max. 70 130 170 135
P 3 x M20 x 1.5 3 x M20 x 1.5
Ø d1 125 90 90 125
Ø d2 70 55 55 70
Ø d3 102 70 70 102
Ø d4 4 x M10 4 x M8 4 x M8 4 x M10
h 3 3
h2 15 12 12 15
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.916/003/en Issue 1.15 Page 1/2


SD 05 – SD 25

Dimensions Output drive types according to EN ISO 5210

Stem nut Ø d5
Dimensions SD 05 – SD 25
EN ISO 5210 F07 F10
Type F max. kN 40 70
EN ISO 5210 A Ø d1 90 125

L
g

Ø d6
Ø d2 55 70
h3

Ø d3 70 102
h

–h

d4
>

Ø d2 M8 M10
Zxd4
Ø d3 Ø d5 22 27
Ø d1
Ø d6 max. 2) 20 26
g 40 50
F07 F07 3) F10 h 3 3
Arrangement of h3 12 15
holes d4
L 37 47
L max. 130 170 3)
135
L max.

L max.

Z 4 4
L max.

Weight kg 1,1 2,8

Bore according to EN ISO


Dimensions SD 05 – SD 25
5211
With keyway according to EN ISO 5210 F10
DIN 6885-1 ØD 24,8 –
Coupling from Ø d7 ≤ 15 b JS9 1) 3 4 5 5 6
Ø d7 H8 from 8 10 12
16 20
to 10 12 15
L4 25 –
t 1) 1,4 +0,1 1,8 +0,1 2,3 +0,1 2,3 +0,1 2,8 +0,1

Square bore
Dimensions SD 05 – SD 25
According to EN ISO 5211
EN ISO 5210 F10
ØD 24,8
Ø d8 max. 14,1 18,1
L4 25
s H11 min. – 11
s H11 max. 11 14

Bore with two-flats


Dimensions SD 05 – SD 25
According to EN ISO 5211
EN ISO 5210 F10
ØD 24,8
Ø d8 max. 14,1 18,1
L4 25
s H11 min. – 11
s H11 max. 11 14

1) Dimensions depend on Ø d7, refer to DIN 6885-1


2) Max. bore dimensions in mm
3) Extended version
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.916/003/en Issue 1.15 Page 2/2


SDL 50 – SDL 100

Dimensions Linear actuators

with valve connection

Valve attachment

g
F05
h3

h3
h2

h
L

Ø d4

Ø d3
Ø d2
H
L4
L2

Ø d8

Ø d9

Ø d1
Standard version, multi-turn actuator clockwise rotation Stem is extended
For dimmensions of multi-turn actuators refer to "Dimensions SD 05 – SD 25 multi-turn actuators"
Dimensions SDL 50-10/-20/-30 SDL 100-20/-30
DIN 3358 F05 F07
H (stroke) 55 85
L 34 48
L2 28 28
L4 45 51
Ø d1 70 95
Ø d2 35 55
Ø d3 50 70
Ø d4 M6 M8
Ø d8 M12 x 1.25 M16 x 1.5
Ø d9 60 60
g 56 102
h 3 3
h2 – 22
h3 15 15
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.954/003/en Issue 1.16 Page 1/1


SGC 04.1 – SGC 10.1/SVC 05.1 – SVC 07.5
SGCR 04.1 – SGCR 10.1/SVCR 05.1 – SVCR 07.5
Dimensions Part-turn/globe valve actuators with integral actuator controls

C6

Space required for removal C1

C C2
†F †F
HH

H6
Bayonet variant
Plug/socket connector (option)

H2
H3
E2

H1
H8

h1
”X”
H5

H5
H7
H4

AUMA plug/socket z x d4
A3 connector variant (option)
E1 Ø d3
Ø d1
B1
E1
E
20° Screw-type 20°
connector variant (standard)

Detail X
SVC 05.1 – SVC 07.5
SVCR 05.1 – SVCR 07.5 Y version
A1 with spigot

L max.
C5
C4

h
C3

Ø d7
Valve attachment according to
Ø d2 EN ISO 5211
Ø D1
Dimensions of couplings see overleaf

SGC/SGCR 04.1/SGC/SGCR 05.1 SGC/SGCR 07.1


Dimensions SGC(R) 10.1
SVC/SVCR 05.1 SVC/SVCR 07.1/SVC/SVCR 07.5
EN ISO 5211 F05 F07 F07 F10
A1 53.5 66.5 82.5
A3 80 80 80
B1 77 95 111
C 144 155 155
C1 199 210 210
C2 87 99 114
C3 47 47 60
C4 140 150 –
C5 138 153 174
C6 299 310 310
Ø D1 100 125 160
E 125 135 135
E1 90 100 115
E2 115 115 115
F 100 123 152
H1 84.5 101.5 111
H2 194 219 244
H3 165 190 190
H4 144 144 144
H5 4 10 17
H6 20 23 24
H7 81 81 81
H8 62.5 67.5 67.5
HH min. 30 30 30
L max. 40 50 60
Ø d1 90 90 125
Ø d2 f8 35 55 55 70
Ø d3 50 70 70 102
d4 M6 M8 M8 M10
Ø d7 15 15 20
h 3 3 3
h1 12 15 15 14
z 4 4 4
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y005.021/003/en Issue 1.15 Page 1/2


SGC 04.1 – SGC 10.1/SVC 05.1 – SVC 07.5
SGCR 04.1 – SGCR 10.1/SVCR 05.1 – SVCR 07.5
Dimensions Couplings according to EN ISO 5211, DIN 6885

Bore according to SGC(R) 04.1/SGC(R) 05.1 SGC(R) 07.1


Dimensions SGC(R) 10.1
EN ISO 5211 SVC(R) 05.1 SVC(R) 07.1/SVC(R) 07.5
With keyway according EN ISO 5211 F05 F07 F07 F10

L5
to DIN 6885-1 ØD 31.75 41.75 51.75
Detail X b JS9 1) 6 6 8
Detail X Ø d7 H8 2) 18 22 28
Ø d7 max. 20 25.4 38
d9 3) M4 M5 M6
1,5 x d9 L4 35 35 45
L5 3) 8 8 10
M 20 20 35
t 1) 20.8 24.8 31.3

Square bore SGC(R) 04.1/SGC(R) 05.1 SGC(R) 07.1


Dimensions SGC(R) 10.1
SVC(R) 05.1 SVC(R) 07.1/SVC(R) 07.5
according to EN ISO 5211 EN ISO 5211 F05 F07 F07 F10
ØD 31.75 41.75 51.75
Ø d8 min. 2) 18.1 22.2 28.2
Ø d8 max. 22.2 28.2 40.2 4)
L4 35 35 45
L6 min. 30 30 30
M 20 20 35
s H11 2) 14 17 22
s H11 max. 17 22 30 4)

Bore with two-flats SGC(R) 04.1/SGC(R) 05.1 SGC(R) 07.1


Dimensions SGC(R) 10.1
SVC(R) 05.1 SVC(R) 07.1/SVC(R) 07.5
according to EN ISO 5211 EN ISO 5211 F05 F07 F07 F10
ØD 31.75 41.75 51.75
Ø d8 min. 2) 18.1 22.2 28.2
Ø d8 max. 22.2 28.2 36.2
L4 35 35 45
L6 min. 25 25 25
M 20 20 35
s H11 2) 14 17 22
s H11 max. 17 22 27

Mounting position of coupling X max. 2.5 3.5


Y max. 6 10
X
Y

1) Dimensions depend on Ø d7, refer to DIN 6885-1


2) Recommended size according to EN ISO 5211
3) Thread with grub screw
4) According to DIN 79

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y005.021/003/en Issue 1.15 Page 2/2


SGC 12.1/SGCR 12.1

Dimensions Part-turn actuators with integral actuator controls


C6
C1
Space required for removal C C2

Bayonet variant †F †F

H6
Plug/socket connector (option)
HH

H2
H3
E2

H1
H5

H5
A3

H8
H7
H4

AUMA plug/socket
connector variant (option)

h1
1)
"X"

h
E1 Ø d5
Screw-type
20° connector variant (standard) Ø d2
B1
Ø d3 z x d4
E
Ø d1

Detail X E1

J
20°

A1 Valve attachment according to EN ISO


L max.

C5

5211
Dimensions of couplings see overleaf
C3

Ø d7
h 1)

Ø D1

1) Allowance for spigot is not available as standard The spigot ring is a separate component, available as option.
Dimensions SGC/SGCR 12.1
EN ISO 5211 F12 F14 F16
A1 66.5
A3 80
B1 94.5
C 155
C1 210
C2 99
C3 47
C5 150
C6 310
Ø D1 125
E 135
E1 100
E2 115
F 123
H1 101.5
H2 219
H3 190
H4 144
H5 10
H6 23
H7 81
H8 394 434 444
HH min. 30
J 109
L max. 61 101 111
Ø d1 150 175 210
Ø d2 f8 85 100 130
Ø d3 125 140 165
d4 M12 M16 M20
Ø d5 210
Ø d7 15
h 1) 2.5 3.5 4.5
h1 22 25 32
z 4
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.622/003/en Issue 1.14 Page 1/2


SGC 12.1/SGCR 12.1

Dimensions Couplings according to EN ISO 5211, DIN 6885

Bore according to
Dimensions SGC/SGCR 12.1
EN ISO 5211
With keyway according to EN ISO 5211 F12 F14 F16
DIN 6885-1 ØD 67.6

L5
b JS9 1) 10
Detail X Ø d7 H8 2) 36
Detail X Ø d7 max. 50
d9 3) M6
1,5 x d9
L4 55 95 105
L5 3) 10
M 40
t 1) 39.3

Square bore
Dimensions SGC/SGCR 12.1

according to EN ISO 5211 EN ISO 5211 F12 F14 F16


ØD 67.6
Ø d8 min. 2) 36.2
Ø d8 max. 48.2
L4 55 95 105
L6 min. 30 30 40
M 40
s H11 2) 27
s H11 max. 36

Bore with two-flats


Dimensions SGC/SGCR 12.1

according to EN ISO 5211 EN ISO 5211 F12 F14 F16


ØD 67.6
Ø d8 min. 2) 36.2
Ø d8 max. 48.2 (48 5))
L4 55 95 105
L6 min. 30 30 40
M 40
s H11 2) 27
s H11 max. 36 (41 5))

Mounting position of coupling X max. 5 8


Y max. 10 10
X
Y

1) Dimensions depend on Ø d7, refer to DIN 6885-1


2) Recommended size according to EN ISO 5211
3) Thread with grub screw
4) According to DIN 79
5) According to DIN 475

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.622/003/en Issue 1.14 Page 2/2


5 Dimensions Output drives

Valve attachments for actuators and gearboxes 110

Couplings for SG/SV/SQ/GS/GHE


Couplings (standard), bore with keyway according to DIN 6885-1 112
Couplings (standard), bore with two-flats according to ISO 5211 113
Couplings (standard), square bore according to ISO 5211 114

Output drives
5. Dimensions
Dimensions Valve attachments for actuators and gearboxes

EN ISO 5210/EN ISO 5211/DIN 3210/DIN 3338

Comparison between EN ISO 5210/EN ISO 5211 and DIN 3210/DIN 3338
EN ISO 5210 Multi-turn valve actuator attachments
EN ISO 5211 Part-turn valve actuator attachments
DIN 3210 Output drives of electric actuators for valves (Standard withdrawn)
DIN 3338 Multi-turn actuator attachments, type C

Actuator
h1

(d3) (d3)
Ø d4 Ø d2 Ø d2 Ø d4
Designations deviating from EN ISO
Ø d3 (k) Ø d3 (k)
Ø d1 Ø d1 are indicated in brackets

Flange abbreviation Dimensions (in mm) Quantity of


screws and bolts
EN ISO EN ISO DIN EN ISO DIN EN ISO DIN EN ISO DIN EN ISO DIN ENI ISO DIN EN ISO DIN
5210 5211 3210 5210 3210 5210 3210 5210 3210 5210 3210 5210 3210 5210 3210
5211 5211 5211 5211 5211 5211
DIN DIN DIN DIN DIN DIN DIN
3338 3338 3338 3338 3338 3338 3338
Ø d1 Ø d1 Ø d2 Ø d2 Ø d3 (k) Ø d4 (d3) h1 max. h1 max.
– F03 – 46 – 25 – 36 – M5 – 3 – 4 –
– F04 – 54 – 30 – 42 – M5 – 3 – 4 –
– F05 – 65 – 35 – 50 – M6 – 3 – 4 –
F07 F07 – 90 – 55 – 70 – M8 – 3 – 4 –
F10 F10 G0 125 125 70 1) 60 1) 102 102 M10 M10 3 3 4 4
F12 F12 – 150 – 85 – 125 – M12 – 3 – 4 –
F14 F14 G1/2 175 175 100 100 140 140 M16 M16 4 4 4 4
F16 F16 G3 210 210 130 130 165 165 M20 M20 5 5 4 4
F25 F25 G4 300 300 200 1) 160 1) 254 254 M16 M16 5 5 8 8
1) 1) 1) 1)
F30 F30 G5 350 350 230 180 298 300 M20 M20 5 5 8 8
F35 F35 G6 415 1) 410 1) 260 1) 220 1) 356 356 M30 M30 5 5 8 8
1) 1)
F40 F40 G7 475 475 300 230 406 406 M36 M36 8 8 8 8
– F48 – 560 – 370 – 483 – M36 – 8 – 12 –
– F60 – 686 – 470 – 603 – M36 – 8 – 20 –

1) Deviating dimensions between EN ISO 5210/EN ISO 5211/DIN 3338 and DIN 3210

Arrangement of bores for screws Ø d4 (d3)

EN ISO 5210 F07 – F16 F25 – F40 – –


EN ISO 5211 F03 – F16 F25 – F40 F48 F60
DIN 3210 G0 – G3 G4 – G7 – –
DIN 3338 F07 – F16 F25 – F40 – –
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y000.023/003/en Issue 1.13 Page 1/2


Output drives for multi-turn actuators and gearboxes

EN ISO 5210/DIN 3210/DIN3338

stem nut Designation Torque Thrust pos- Application


EN ISO transmission sible
DIN 3210 DIN 3338
5210

rising, non-rotating
A A – X X
valve stem

Output drive plug sleeve

rotating, non-rising
B1
B – X – valve stem or rising,
B2
non-rotating valve stem

Dog coupling

rotating, non-rising
– C C X – valve stem or rising,
non-rotating valve stem

Shaft end

Operation via
– D – X – lever arrangement or
coupling

Bore with keyway

B3 rotating, non-rising
E – X –
B4 valve stem

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y000.023/003/en Issue 1.13 Page 2/2


SG/SV/SQ/GS/GHE

Dimensions Couplings (standard), bore with keyway according to DIN 6885-1

Detail X
X

1) Thread with grub screw made of A2

Z
2) Article number refers to
unbored version, KN, KS
3) Combined flange F05/F07 without spigot (standard).
As an alternative an individual flange F07 can be ordered with/without spigot
Article Splined
Ø d7 Ø d7 H8 b Parallel key Grub screw 1)
Type ØD L4 M coupling Q Ø d9 1) L5 1) Z
no. 2)
DIN 5480 max. over to JS 9 DIN 6885-1 ISO 4029
12 15 5 2.3 + 0.1 5 x 5 x ..
SG 03.3/SG 04.3 Z009.977 24.8 25 17 25x1x24 15 10 12 4 1.8 + 0.1 4 x 4 x .. M4 5 M4 x 4 6
8 10 3 1.4 + 0.1 3 x 3 x ..
12 15 5 2.3 + 0.1 5 x 5 x ..
SG 04.2 Z009.992 24.8 35 17 25x1x24 15 10 12 4 1.8 + 0.1 4 x 4 x .. M4 8 M4 x 4 6
8 10 3 1.4 + 0.1 3 x 3 x ..
SGC 04.1/05.1
17 20 6 2.8 + 0.1 6 x 6 x ..
SVC/SVM 05.1
SG 05.2
SG 05.3 Z010.132 31.75 35 20 32x1.25x24 20 12 17 5 2.3 + 0.1 5 x 5 x .. M4 8 M4 x 4 6
GS 50.3 F05
GHE 05.1
10 12 4 1.8 + 0.1 4 x 4 x ..
SGM 04.1/05.1
SGC/SGM 07.1
22 25.4 8 3.3 + 0.2 8 x 7 x ..
SQ 05.2 – F05/F07 3)
SQ 07.2 – F05/F07 3)
Z010.369 41.75 35 20 42x1.25x32 25.4 17 22 6 2.8 + 0.2 6 x 6 x .. M5 8 M5 x 5 7.5
SG 07.2
GHE 07.1
12 17 5 2.3 + 0.1 5 x 5 x ..
SVC/SVM 07.1/5
22 25.4 8 3.3 + 0.2 8 x 7 x ..
SG 05.1/SG 07.1 Z010.169 41.75 40 20 42x1.25x32 25.4 17 22 6 2.8 + 0.1 6 x 6 x .. M5 8 M5 x 5 7.5
12 17 5 2.3 + 0.1 5 x 5 x ..
22 25.4 8 3.3 + 0.2 8 x 7 x ..
SQ 07.2 – F10 Z010.658 41.75 60 20 42x1.25x32 25.4 17 22 6 2.8 + 0.1 6 x 6 x .. M5 8 M5 x 5 7.5
12 17 5 2.3 + 0.1 5 x 5 x ..
SGC/SGM 10.1
30 38 10 3.3 + 0.2 10 x 8 x ..
SQ 10.2 – F10
GS 50.3 Z010.302 51.75 45 30 52x1.25x40 38 22 30 8 3.3 + 0.2 8 x 7 x .. M6 10 M6 x 6 9
GHE 10.1
17 22 6 2.8 + 0.1 6 x 6 x ..
SG 10.2
30 38 10 3.3 + 0.2 10 x 8 x ..
SG 10.1 Z010.328 51.75 65 35 52x1.25x40 38 22 30 8 3.3 + 0.2 8 x 7 x .. M6 10 M6 x 6 9
17 22 6 2.8 + 0.1 6 x 6 x ..
30 38 10 3.3 + 0.2 10 x 8 x ..
SQ 10.2 – F12 Z044.911 51.75 75 30 52x1.25x40 38 22 30 8 3.3 + 0.2 8 x 7 x .. M6 10 M6 x 6 9
17 22 6 2.8 + 0.1 6 x 6 x ..
SQ 12.2 – F12 44 50 14 3.8 + 0.2 14 x 9 x ..
GS 63.3 Z010.368 67.6 55 40 68x2x32 50 38 44 12 3.3 + 0.2 12 x 8 x .. M6 10 M6 x 6 9
GHE 12.1 30 38 10 3.3 + 0.2 10 x 8 x ..
44 50 14 3.8 + 0.2 14 x 9 x ..
SG 12.1 Z010.184 67.6 75 40 68x2x32 50 38 44 12 3.3 + 0.2 12 x 8 x .. M6 10 M6 x 6 9
30 38 10 3.3 + 0.2 10 x 8 x ..
44 50 14 3.8 + 0.2 14 x 9 x ..
SQ 12.2 – F14 Z006.070 67.6 95 40 68x2x32 50 38 44 12 3.3 + 0.2 12 x 8 x .. M6 10 M6 x 6 9
30 38 10 3.3 + 0.2 10 x 8 x ..
44 50 14 3.8 + 0.2 14 x 9 x ..
SQ 12.2 – F16 Z006.071 67.6 105 40 68x2x32 50 38 44 12 3.3 + 0.2 12 x 8 x .. M6 10 M6 x 6 9
30 38 10 3.3 + 0.2 10 x 8 x ..
SQ 14.2 – F14 58 60 18 4.4 + 0.2 18 x 11 x ..
Z010.394 81.6 65 47 82x2x40 60 50 58 16 4.3 + 0.2 16 x 10 x .. M6 10 M6 x 6 9
GS 80.3 44 50 14 3.8 + 0.2 14 x 9 x ..
58 60 18 4.4 + 0.2 18 x 11 x ..
SQ 14.2 – F16 Z111.676 81.6 115 40 82x2x40 60 50 58 16 4.3 + 0.2 16 x 10 x .. M6 10 M6 x 6 9
44 50 14 3.8 + 0.2 14 x 9 x ..
75 80 22 5.4 + 0.2 22 x 14 x ..
GS 100.3 Z015.955 105.8 80 50 106x2x52 80 65 75 20 4.9 + 0.2 20 x 12 x .. M8 18 M8 x 8 12
58 65 18 4.4 + 0.2 18 x 11 x ..
85 90 25 5.4 + 0.2 25 x 14 x ..
GS 125.3 Z017.441 119.6 110 70 120x2x60 90 75 85 22 5.4 + 0.2 22 x 14 x .. M8 18 M8 x 8 12
65 75 20 4.9 + 0.2 20 x 12 x ..
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y001.039/003/en Issue 3.14 Page 1/1


SG/SV/SQ/GS/GHE

Dimensions Couplings (standard), two-flat bore according to ISO 5211

L6
Detail X L51) 9 1)
X

d15
Z
1) Thread with grub screw made of A2
2) Article number refers to unbored version, KN, KS M
3) DIN 475
4) Combined flange F05/F07 without spigot (standard).
As an alternative an individual flange F07 can be ordered with/without spigot
Article Splined S H11 Ø d8 Grub screw 1)
Type ØD L4 M coupling L6 Ø d9 1) Ø d15 L5 1) Z
no. 2) DIN 5480 over to max. ISO 4029
11 14.1
SG 03.3/SG 04.3 Z009.977 24.8 25 17 25x1x24 25 M4 16 5 M4 x 4 6
11 14 18.1
11 14.1
SG 04.2 Z009.992 24.8 35 17 25x1x24 25 M4 16 8 M4 x 4 6
11 14 18.1
SGC 04.1/05.1
11 14.1 25 16
SVC/SVM 05.1
SG 05.2
SG 05.3 Z010.132 31.75 35 20 32x1.25x24 11 16 3) 18 3) 25 M4 22.5 8 M4 x 4 6
GS 50.3 F05
GHE 05.1
16 3) 17 22.2 30 25
SGM 04.1/05.1
SGC/SGM 07.1
SQ 05.2 – F05/F07 4) 11 16 3) 18 3) 25 22.5
SQ 07.2 – F05/F07 4)
Z010.369 41.75 35 20 42x1.25x32 M5 8 M5 x 5 7.5
SG 07.2
GHE 07.1 16 3) 22 28.2 30 31
SVC/SVM 07.1/5
11 16 3) 18 3) 25 22.5
SG 05.1/SG 07.1 Z010.169 41.75 40 20 42x1.25x32 M5 8 M5 x 5 7.5
16 3) 22 28.2 30 31
11 16 3) 18 3) 25 22.5
SQ 07.2 – F10 Z010.658 41.75 60 20 42x1.25x32 M5 8 M5 x 5 7.5
16 3) 22 28.2 30 31
SGC/SGM 10.1
11 16 3) 18 3) 25 22.5
SQ 10.2 – F10
3)
GS 50.3 Z010.302 51.75 45 30 52x1.25x40 16 22 28.2 30 M6 31 10 M6 x 6 9
GHE 10.1
22 27 36.2 40 41
SG 10.2
11 16 3) 18 3) 25 22.5
SG 10.1 Z010.328 51.75 65 35 52x1.25x40 16 3) 22 28.2 30 M6 31 10 M6 x 6 9
22 27 36.2 40 41
11 16 3) 18 3) 25 22.5
SQ 10.2 – F12 Z044.911 51.75 75 30 52x1.25x40 16 3) 22 28.2 30 M6 31 10 M6 x 6 9
22 27 36.2 40 41
SQ 12.2 – F12 16 3) 22 28.2 30 31
GS 63.3 Z010.368 67.6 55 40 68x2x32 22 27 36.2 40 M6 41 10 M6 x 6 9
GHE 12.1 27 36 (41 3)) 48.2 (48 3)) 45 53
16 3) 22 28.2 30 31
SG 12.1 Z010.184 67.6 75 40 68x2x32 22 27 36.2 40 M6 41 10 M6 x 6 9
27 36 (41 3)) 48.2 (48 3)) 45 53
16 3) 22 28.2 30 31
SQ 12.2 – F14 Z006.070 67.6 95 40 68x2x32 22 27 36.2 40 M6 41 10 M6 x 6 9
27 36 (41 3)) 48.2 (48 3)) 45 53
16 3) 22 28.2 30 31
SQ 12.2 – F16 Z006.071 67.6 105 40 68x2x32 22 27 36.2 40 M6 41 10 M6 x 6 9
27 36 (41 3)) 48.2 (48 3)) 45 53
SQ 14.2 – F14 22 27 36.2 40 41
Z010.394 81.6 65 47 82x2x40 27 36 (41 3)) 48.2 (48 3)) 45 M6 53 10 M6 x 6 9
GS 80.3 36 (41 3)) 46 60.2 59 64
22 27 36.2 40 41
SQ 14.2 – F16 Z111.676 81.6 115 40 82x2x40 27 36 (41 3)) 48.2 (48 3)) 45 M6 53 10 M6 x 6 9
36 (41 3)) 46 60.2 59 64
27 36 (41 3)) 48.2 (48 3)) 45 53
GS 100.3 Z015.955 105.8 80 50 106x2x52 36 (41 3)) 46 60.2 59 M8 64 18 M8 x 8 12
46 55 72.2 77 85
36 (41 3)) 46 60.2 59 64
GS 125.3 Z017.441 119.6 110 70 120x2x60 46 55 72.2 77 M8 85 18 M8 x 8 12
55 75 98.2 94 95
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y001.040/003/en Issue 2.14 Page 1/1


SG/SV/SQ/GS/GHE

Dimensions Couplings (standard), square bore according to ISO 5211


L
Detail X L 5 1)
X


d15

d9
1)
Z
1) Thread with grub screw made of A2
2) Article number refers to unbored version, KN, KS
3) DIN 79 M
4) Combined flange F05/F07 without spigot (standard). L
As an alternative an individual flange F07 can be ordered with/without spigot
Article Splined S H11 Ø d8 Grub screw 1)
Type ØD L4 M coupling L6 Ø d9 1) Ø d15 L5 1) Z
no. 2)
DIN 5480 over to max. ISO 4029
11 14.1
SG 03.3/SG 04.3 Z009.977 24.8 25 17 25x1x24 25 M4 16 5 M4 x 4 6
11 14 18.1
11 14.1
SG 04.2 Z009.992 24.8 35 17 25x1x24 30 M4 16 8 M4 x 4 6
11 14 18.1
SGC 04.1/05.1
11 14.1 16
SVC/SVM 05.1
SG 05.2
SG 05.3 Z010.132 31.75 35 20 32x1.25x24 11 14 18.1 30 M4 20 8 M4 x 4 6
GS 50.3 F05
GHE 05.1
14 17 22.2 24
SGM 04.1/05.1
SGC/SGM 07.1
11 14 18.1 20
SQ 05.2 – F05/F07 4)
SQ 07.2 – F05/F07 4)
Z010.369 41.75 35 20 42x1.25x32 14 17 22.2 30 M5 24 8 M5 x 5 7.5
SG 07.2
GHE 07.1
17 22 28.2 31.5
SVC/SVM 07.1/5
11 14 18.1 20
SG 05.1/SG 07.1 Z010.169 41.75 40 20 42x1.25x32 14 17 22.2 30 M5 24 8 M5 x 5 7.5
17 22 28.2 31.5
11 14 18.1 20
SQ 07.2 – F10 Z010.658 41.75 60 20 42x1.25x32 14 17 22.2 30 M5 24 8 M5 x 5 7.5
17 22 28.2 31.5
SGC/SGM 10.1
14 17 22.2 30 24
SQ 10.2 – F10
GS 50.3 Z010.302 51.75 45 30 52x1.25x40 17 22 28.2 30 M6 31.5 10 M6 x 6 9
GHE 10.1
22 30 3) 40.2 3) 40 41.5
SG 10.2
14 17 22.2 30 24
SG 10.1 Z010.328 51.75 65 35 52x1.25x40 17 22 28.2 30 M6 31.5 10 M6 x 6 9
22 30 3) 40.2 3) 40 41.5
14 17 22.2 30 24
SQ 10.2 – F12 Z044.911 51.75 75 30 52x1.25x40 17 22 28.2 30 M6 31.5 10 M6 x 6 9
22 30 3) 40.2 3) 40 41.5
SQ 12.2 – F12 17 22 28.2 30 31.5
GS 63.3 Z010.368 67.6 55 40 68x2x32 22 30 3) 40.2 3) 40 M6 41.5 10 M6 x 6 9
GHE 12.1 30 3) 36 48.2 50 50
17 22 28.2 30 31.5
SG 12.1 Z010.184 67.6 75 40 68x2x32 22 30 3) 40.2 3) 40 M6 41.5 10 M6 x 6 9
30 3) 36 48.2 50 50
17 22 28.2 30 31.5
SQ 12.2 – F14 Z006.070 67.6 95 40 68x2x32 22 30 3) 40.2 3) 40 M6 41.5 10 M6 x 6 9
30 3) 36 48.2 50 50
17 22 28.2 30 31.5
SQ 12.2 – F16 Z006.071 67.6 105 40 68x2x32 22 30 3) 40.2 3) 40 M6 41.5 10 M6 x 6 9
30 3) 36 48.2 50 50
SQ 14.2 – F14 22 30 3) 40.2 3) 40 41.5
Z010.394 81.6 65 47 82x2x40 30 3) 36 48.2 50 M6 50 10 M6 x 6 9
GS 80.3 36 46 60.2 50 64
22 30 3) 40.2 3) 40 41.5
SQ 14.2 – F16 Z111.676 81.6 115 40 82x2x40 30 3) 36 48.2 50 M6 50 10 M6 x 6 9
36 46 60.2 50 64
30 3) 36 48.2 50 50
GS 100.3 Z015.955 105.8 80 50 106x2x52 36 46 60.2 50 M8 64 18 M8 x 8 12
46 55 72.2 60 82
36 46 60.2 50 64
GS 125.3 Z017.441 119.6 110 70 120x2x60 46 55 72.2 60 M8 82 18 M8 x 8 12
55 75 98.2 80 95
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y001.041/003/en Issue 2.14 Page 1/1


6 Spare parts lists

Basic Range
EQ 40 – EQ 600 117

Smart Range
SD 118
SDL 100 119

SGC 04.1 – SGC 10.1 120


SGC 12.1 122
SGC 04.1 – SGC 10.1 Fieldbus 124
SGC 12.1 Fieldbus 126

SVC 05.1 – SVC 07.5 128


SVC 05.1 – SVC 07.5 Fieldbus 130

6. Spare parts lists


Ersatzteilliste EQ40–EQ600
Material list EQ40–EQ600

Pos. Bezeichnung designation Pos. Bezeichnung designation


2.1 Drehwinkelskala turn gauge 33.2 Kondensator capacitor
2.2.1 Aluminiumhaube cover aluminium 33.3 Winkel capacitor holder
2.2.2 Sichtfenster inspection glass 34.1 Schalterplatine switch plate
2.2.4 Sicherungsring circlip 38 Kunststoffhaube cover plastic
2.2.6 O-Ring o-seal 39 Schleppzeiger drag indicator
2.3 Sicherungsring circlip 40 Anzeige indicator
2.5 Stellungsanzeiger indicator 44 Zahnrad gear wheel
4.4 Potentiometer potentiometer 45 Schaltnocke cam
5.1 Positionselektronik positioner 47 Bolzen bolt
8 Sicherungsscheibe circlip 50 O-Ring o-seal
8.1 Zusatzschalter additional switches 52 Dichtring seal ring
9.1 ESR 100 ESR 100 54 Sechskantmutter hex-nut
10.1 Heizung heater 56 Passfeder feather key
11.1 Zusatzpotentiometer additional potentiometer 63 Federring split washer
13 Gewindestift setscrew 74 Linsenschraube screw
15 Sechskantmutter hex-nut 77 Exzenter eccentric
21.1 Motorklemme 3~ motor terminal 3~ 78 Kupplung coupling
26.1 Handrad handwheel 83 Scheibe washer
26.2 Zylindergriff grip 84 Zylinderschraube lens head screw
26.3 Sechskantmutter hex-nut 87 Passscheibe shim ring
33 Motor motor 89 Scheibe ring

Bitte geben Sie bei Bestellung von Ersatzteilen die Fertigungsnummer des Antriebes an.
Please provide serial number of actuator (“F-Nr.”), when ordering spare parts.

AUMA Industry & Marine GmbH, 11.2015 10_ETL_EQ_DE_EN.docx Seite 1 von 1


Ersatzteilliste SD
Material list SD

Pos. Bezeichnung Pos. Bezeichnung


2 Haube kpl. hood compl. 40 Stellungsanzeiger indicator
2.7 Sechskantschraube hexagon screw 41 Sicherungsring circlip
5 Motor kpl. motor compl. 63 Sechskantmutter hex-nut
5.4 Zylinderschraube lens head screw 90 Kupplung coupling
6 Handrad kpl. handwheel compl. 91 Sicherungsring circlip
7.2 Winkel kpl. mounting plate compl.
7.10 Logikplatine logic board
7.11 Leistungsplatine power board
7.12 LCD Anzeige LCD display
7.13 Netzteil power supply unit
7.21 Relaisplatine relay interface
10 Abdeckplatte cover
11 Absolutwertgeber absolute encoder
11.7 Zahnscheibe toothed disc
11.8 Zylinderschraube lens head screw
13 Deckel cover
13.1 Zylinderschraube lens head screw
14 Klemmleiste terminal strip
34 Passfeder feather key

Bitte geben Sie bei Bestellung von Ersatzteilen die Fertigungsnummer des Antriebes an.
Please provide serial number of actuator (“F-Nr.”), when ordering spare parts.

AUMA Industry & Marine GmbH, 10.20166 13_ETL_SD_DE_EN.docx Seite 1 von 1


Ersatzteilliste SDL100
Material list SDL100
 

Pos. Bezeichnung designation Pos. Bezeichnung designation


2 Haube kpl. hood compl. 40 Stellungsanzeiger indicator
2.7 Sechskantschraube hexagon screw 41 Sicherungsring circlip
5 Motor kpl. motor compl. 63 Sechskantmutter hex-nut
5.4 Zylinderschraube lens head screw 112 Kupplungsflansch coupling flange
6 Handrad kpl. handwheel compl. 113 Gewindestift setscrew
7.2 Winkel kpl. mounting plate compl. 114 Gewindebuchse threaded bush
7.10 Logikplatine logic board 115 Scheibe washer
7.11 Leistungsplatine power board 116 Sicherungsblech locking plate
7.12 LCD Anzeige LCD display 117 Zylinderschraube lens head screw
7.13 Netzteil power supply unit 118 Federring split washer
7.21 Relaisplatine relay interface
10 Abdeckplatte cover
11 Absolutwertgeber absolute encoder
11.7 Zahnscheibe toothed disc
11.8 Zylinderschraube lens head screw
13 Deckel cover
13.1 Zylinderschraube lens head screw
14 Klemmleiste terminal strip
34 Passfeder feather key

Bitte geben Sie bei Bestellung von Ersatzteilen die Fertigungsnummer des Antriebes an.
Please provide serial number of actuator (“F-Nr.”), when ordering spare parts.

AUMA Industry & Marine GmbH, 11.2015 13_ETL_SDL100_DE_EN.docx Seite 1 von 1


S1 Spare parts list
S1
058.0

Part-turn actuators
SGC 04.1 - SGC 10.1
002.3 - 2 002.0 - 3 SGCR 04.1 - SGCR 10.1

507.0 545.0-3 500.0


501.0
503.0 502.0 S1
S1 S1
504.0 505.0
611.0
506.0

002.0 - 2
S1

002.3 -1
002.0 -1

S1
611.0 S1 542.0
009.0
006.0

539.0

525.0 S1
541.0
545.0-2 545.0-2

542.1

545.0-1 587.0
545.0-3
002.3 -1
002.0 -1

545.0-3
545.0-3 541.0
1.15
Y004.979/003/en
SGC 04.1 - SGC 10.1
SGCR 04.1 - SGCR 10.1
Spare parts list part-turn actuators

Please state type and order no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be
used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary
from the representation.

Ref. No. Designation Type


002.0-1 Local controls Sub-assembly
002.0-2 Cover (for version without local controls) Sub-assembly
002.0-3 Cover with socket for connecting separately mounted local controls Sub-assembly
002.3-1 Board for local controls 002.0-1 Sub-assembly
002.3-2 Board in connecting cover 002.0-3 Sub-assembly
006.0 Power supply / switchgear Sub-assembly
009.0 Logic board
058.0 Wire for protective earth Sub-assembly
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Cover for electrical connection Sub-assembly
525.0 Coupling Sub-assembly
539.0 Screw plug
541.0 Protective earth connection Sub-assembly
542.0 Handwheel Sub-assembly
542.1 Ball handle Sub-assembly
545.0-1 Protective cap with cord Sub-assembly
545.0-2 Protective cap without cord Sub-assembly
545.0-3 Mating plug Sub-assembly
587.0 Wall bracket
611.0 Cover Sub-assembly
S1 Seal kit, small Set

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.979/003/en Issue 1.15


S1 Spare parts list
058.0 S1

Part-turn actuators
002.3 - 2 SGC 12.1
002.0 - 3
SGCR 12.1
507.0 545.0 - 3
501.0
503.0 502.0 500.0
S1 S1
504.0 505.0 S1 002.3 - 1
611.0 S1
506.0

002.0 - 2
S1
587.0

002.0 - 1
002.3 - 1 545.0 - 3
002.0 - 1 541.0

S1
611.0
009.0 S1
006.0 542.0
539.0
541.0

548.0

545.0 - 3
545.0 - 1 010.0
545.0 - 2
542.1
609.1
610.1

522.0
596.0
S1
545.0 - 2
612.0

545.0 - 3 525.0
1.15
Y006.454/003/en
SGC 12.1
SGCR 12.1
Spare parts list part-turn actuators

Please state type and order no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be
used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary
from the representation.

Ref. No. Designation Type


002.0-1 Local controls Sub-assembly
002.0-2 Cover (for version without local controls) Sub-assembly
002.0-3 Cover with socket for connecting separately mounted local controls Sub-assembly
002.3-1 Board for local controls 002.0-1 Sub-assembly
002.3-2 Board in connecting cover 002.0-3 Sub-assembly
006.0 Power supply / switchgear
009.0 Logic board Sub-assembly
010.0 Coupling Sub-assembly
058.0 Wire for protective earth Sub-assembly
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Cover for electrical connection Sub-assembly
522.0 Flange Sub-assembly
525.0 Coupling Sub-assembly
539.0 Screw plug
541.0 Protective earth connection Sub-assembly
542.0 Handwheel
542.1 Ball handle Sub-assembly
545.0-1 Protective cap with cord Sub-assembly
545.0-2 Protective cap without cord Sub-assembly
545.0-3 Mating plug Sub-assembly
548.0 Spigot ring
587.0 Wall bracket
596.0 Output drive flange Sub-assembly
609.1 Angle adapter for main cables Sub-assembly
610.1 Angle adapter for control contacts Sub-assembly
611.0 Cover Sub-assembly
612.0 Screw plug for end stop
S1 Seal kit, small Set

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.454/003/en Issue 1.15


S1 Spare parts list
S1
058.0

Part-turn actuators
SGC 04.1 - SGC 10.1
002.3 - 2 002.0 - 3 SGCR 04.1 - SGCR 10.1
Fieldbus

507.0 545.0-3 500.0


501.0
503.0 502.0 S1
S1 S1
504.0 505.0
611.0
506.0

002.0 - 2
S1

002.3 -1
002.0 -1

S1
611.0 S1 542.0
009.0
006.0

539.0

525.0 S1
541.0
545.0-2 545.0-2

542.1

545.0-1 587.0
545.0-3
002.3 -1
002.0 -1

545.0-3
545.0-3 541.0
1.15
Y004.980/003/en
SGC 04.1 - SGC 10.1 Fieldbus
SGCR 04.1 - SGCR 10.1 Fieldbus
Spare parts list part-turn actuators

Please state type and order no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be
used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary
from the representation.

Ref. No. Designation Type


002.0-1 Local controls Sub-assembly
002.0-2 Cover (for version without local controls) Sub-assembly
002.0-3 Cover with socket for connecting separately mounted local controls Sub-assembly
002.3-1 Board for local controls 002.0-1 Sub-assembly
002.3-2 Board in connecting cover 002.0-3 Sub-assembly
006.0 Power supply / switchgear Sub-assembly
009.0 Logic board
058.0 Wire for protective earth Sub-assembly
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Cover for electrical connection Sub-assembly
525.0 Coupling Sub-assembly
539.0 Screw plug
541.0 Protective earth connection Sub-assembly
542.0 Handwheel Sub-assembly
542.1 Ball handle Sub-assembly
545.0-1 Protective cap with cord Sub-assembly
545.0-2 Protective cap without cord Sub-assembly
545.0-3 Mating plug Sub-assembly
587.0 Wall bracket
611.0 Cover Sub-assembly
S1 Seal kit, small Set

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.980/003/en Issue 1.15


S1 Spare parts list
058.0 S1

Part-turn actuators
002.3 - 2 SGC 12.1
002.0 - 3
SGCR 12.1
507.0 545.0 - 3 Fieldbus
501.0
503.0 502.0 500.0
S1 S1
504.0 505.0 S1 002.3 - 1
611.0 S1
506.0

002.0 - 2
S1
587.0

002.0 - 1
002.3 - 1 545.0 - 3
002.0 - 1 541.0

S1
611.0
009.0 S1
006.0 542.0
539.0
541.0

548.0

545.0 - 3
545.0 - 1 010.0
545.0 - 2
542.1
609.1
610.1
610.1

522.0
596.0
S1
545.0 - 2
612.0

545.0 - 3 525.0
1.15
Y006.455/003/en
SGC 12.1 Fieldbus
SGCR 12.1 Fieldbus
Spare parts list part-turn actuators

Please state type and order no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be
used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary
from the representation.

Ref. No. Designation Type


002.0-1 Local controls Sub-assembly
002.0-2 Cover (for version without local controls) Sub-assembly
002.0-3 Cover with socket for connecting separately mounted local controls Sub-assembly
002.3-1 Board for local controls 002.0-1 Sub-assembly
002.3-2 Board in connecting cover 002.0-3 Sub-assembly
006.0 Power supply / switchgear
009.0 Logic board Sub-assembly
010.0 Coupling Sub-assembly
058.0 Wire for protective earth Sub-assembly
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Cover for electrical connection Sub-assembly
522.0 Flange Sub-assembly
525.0 Coupling Sub-assembly
539.0 Screw plug
541.0 Protective earth connection Sub-assembly
542.0 Handwheel
542.1 Ball handle Sub-assembly
545.0-1 Protective cap with cord Sub-assembly
545.0-2 Protective cap without cord Sub-assembly
545.0-3 Mating plug Sub-assembly
548.0 Spigot ring
587.0 Wall bracket
596.0 Output drive flange Sub-assembly
609.1 Angle adapter for main cables Sub-assembly
610.1 Angle adapter for control contacts Sub-assembly
611.0 Cover Sub-assembly
612.0 Screw plug for end stop
S1 Seal kit, small Set

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y006.455/003/en Issue 1.15


S1 Spare parts list
S1
058.0

Globe valve actuators


SVC 05.1 - SVC 07.5
002.3 - 2 002.0 - 3 SVCR 05.1 - SVCR 07.5

507.0 545.0-3 500.0


501.0
503.0 502.0 S1
S1 S1
504.0 505.0
611.0
506.0

002.0 - 2
S1

002.3 -1
002.0 -1

S1
611.0
542.0
009.0
006.0 S1

539.0

S1
525.0
541.0
545.0-2 545.0-2

542.1

545.0-1 587.0
545.0-3
002.3 -1
002.0 -1

545.0-3
545.0-3 541.0
1.15
Y004.977/002/en
SVC 05.1 - SVC 07.5
SVCR 05.1 - SVCR 07.5
Spare parts list globe valve actuators

Please state type and order no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be
used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary
from the representation.

Ref. No. Designation Type


002.0-1 Local controls Sub-assembly
002.0-2 Cover (for version without local controls) Sub-assembly
002.0-3 Cover with socket for connecting separately mounted local controls Sub-assembly
002.3-1 Board for local controls 002.0-1 Sub-assembly
002.3-2 Board in connecting cover 002.0-3 Sub-assembly
006.0 Power supply / switchgear Sub-assembly
009.0 Logic board
058.0 Wire for protective earth Sub-assembly
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Cover for electrical connection Sub-assembly
525.0 Coupling Sub-assembly
539.0 Screw plug
541.0 Protective earth connection Sub-assembly
542.0 Handwheel Sub-assembly
542.1 Ball handle Sub-assembly
545.0-1 Protective cap with cord Sub-assembly
545.0-2 Protective cap without cord Sub-assembly
545.0-3 Mating plug Sub-assembly
587.0 Wall bracket
611.0 Cover Sub-assembly
S1 Seal kit, small Set

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.977/002/en Issue 1.15


S1 Spare parts list
S1
058.0

Globe valve actuators


SVC 05.1 - SVC 07.5
002.3 - 2 002.0 - 3 SVCR 05.1 - SVCR 07.5
Fieldbus
507.0 545.0-3 500.0
501.0
503.0 502.0 S1
S1 S1
504.0 505.0
611.0
506.0

002.0 - 2
S1

002.3 -1
002.0 -1

S1
611.0
542.0
009.0
006.0 S1

539.0

S1
525.0
541.0
545.0-2 545.0-2

542.1

545.0-1 587.0
545.0-3
002.3 -1
002.0 -1

545.0-3
545.0-3 541.0
1.15
Y004.978/002/en
SVC 05.1 - SVC 07.5 Fieldbus
SVCR 05.1 - SVCR 07.5 Fieldbus
Spare parts list globe valve actuators

Please state type and order no. of the device (see name plate) when ordering spare parts. Only original AUMA spare parts should be
used. Failure to use original spare parts voids the warranty and exempts AUMA from any liability. Delivered spare parts may slightly vary
from the representation.

Ref. No. Designation Type


002.0-1 Local controls Sub-assembly
002.0-2 Cover (for version without local controls) Sub-assembly
002.0-3 Cover with socket for connecting separately mounted local controls Sub-assembly
002.3-1 Board for local controls 002.0-1 Sub-assembly
002.3-2 Board in connecting cover 002.0-3 Sub-assembly
006.0 Power supply / switchgear Sub-assembly
009.0 Logic board
058.0 Wire for protective earth Sub-assembly
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Cover for electrical connection Sub-assembly
525.0 Coupling Sub-assembly
539.0 Screw plug
541.0 Protective earth connection Sub-assembly
542.0 Handwheel Sub-assembly
542.1 Ball handle Sub-assembly
545.0-1 Protective cap with cord Sub-assembly
545.0-2 Protective cap without cord Sub-assembly
545.0-3 Mating plug Sub-assembly
587.0 Wall bracket
611.0 Cover Sub-assembly
S1 Seal kit, small Set

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.978/002/en Issue 1.15


7 Wiring diagrams

Basic Range
Selection of wiring diagrams 134

Smart Range
Selection of wiring diagrams 147

7. Wiring diagrams
Basic Range

Wiring diagram selection

The short designations (B1 etc.) are descriptive numberings.

SBA synchronous motor / 1-phase AC 230 V


B1: 2 x switches for torque, heater
Represented options:
 Additional limit switches
 Potentiometer
 Position feedback signal (0/4 – 20 mA)
 Positioning electronics
28H-170.050.20
SBA asynchronous motor / 1-phase AC 230 V with thermoswitches
B2: 2 x switches for torque, heater
Represented options:
 Additional limit switches
 Additional torque switches
 Potentiometer
 Position feedback signal (0/4 – 20 mA)
28H-170.050.03
SBA asynchronous motor / 1-phase AC 400 V with thermoswitches
B3: External reversing contactor unit
2 x switches for torque, heater
Represented options:
 Additional limit switches
 Additional torque switches
 Potentiometer
 Position feedback signal (0/4 – 20 mA)
28H-170.050.100
SBA DC motor 24 V
B4: External reversing contactor unit
2 x switches for torque, heater
Represented options:
 Additional limit switches
 Potentiometer
 Position feedback signal (0/4 – 20 mA)
28H-170.050.80
SBA DC motor 24 V
B5: 2 x switches for torque, heater
Positioning electronics (including reversing contactor unit)
Represented options:
 Additional limit switches
 Potentiometer
 Position feedback signal (0/4 – 20 mA)
 Positioning electronics
28H-170.050.86

NR / 1-phase AC
C1: 2 x limit switches
Represented options:
 Additional limit switches
 Potentiometer
 Positioning electronics
NR2.1-170.050.10
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.557/003/en Issue 1.17 Page 1/2


Basic Range

Wiring diagram selection

ED / DC 24 V
D1: External reversing contactor unit
2 x limit switches
Represented options:
 Additional limit switches
 Heater
 Potentiometer
 Position feedback signal (0/4 – 20 mA)
ED50-170.050.01
EQ / 1-phase AC 230 V
D2: 2 x limit switches, 2 x torque switches
Represented options:
 Additional limit switches
 Heater
 Potentiometer
 Position feedback signal (0/4 – 20 mA)
EQ150-170.050.00
EQ / Gleichstrom 24 V
D3: External reversing contactor unit
2 x limit switches, 2 x torque switches
Represented options:
 Additional limit switches
 Heater
 Potentiometer
 Position feedback signal (0/4 – 20 mA)
EQ150-170.050.01
EQ / 3-phase AC 400 V
D4: Internal reversing contactor unit
2 x limit switches, 2 x torque switches
Represented options:
 Additional limit switches
 Heater
 Potentiometer
 Position feedback signal (0/4 – 20 mA)
EQ150-170.050.02
EQ / 1-phase AC 230 V
D5: 2 x limit switches, 2 x torque switches
Represented options:
 Additional limit switches
 Heater
 Potentiometer
 Positioning electronics
 Position feedback signal (0/4 – 20 mA)
EQ150-170.050.03

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.557/003/en Issue 1.17 Page 2/2


Code: B1
Code: B2
Code: B3
Code: B4
Code: B5
Code: C1
Code: D1
Code: D2
Code: D3
Code: D4
Code: D5
Smart Range

Wiring diagram selection

The short designations (E1 etc.) are descriptive numberings.

SGC/SVC basic version (I/O) / open-close duty / 1-phase AC 115 V or 230 V


E1: 3 x binary inputs (24 V DC): OPEN, STOP, CLOSE
4 x binary outputs: OPEN, CLOSE, torque fault, REMOTE
Position feedback signal (0/4 – 20 mA)
Industrial plug TPCB-0E6-2C7-0530 TPA50R200-0A0-000
AUMA plug/socket TPCB-0E6-2C7-0000 TPA50R200-0A0-000
connector:
SGC/SVC basic version (I/O) / modulating duty / 1-phase AC 115 V or 230 V
E2: 4 x binary inputs (24 V DC): OPEN, STOP, CLOSE, MODE
4 x binary outputs: OPEN, CLOSE, torque fault, REMOTE
Position feedback signal (0/4 – 20 mA)
Positioner (0/4 – 20 mA)
Industrial plug TPCB-1H6-2C7-0530 TPA50R200-0A0-000
AUMA plug/socket TPCB-1H6-2C7-0000 TPA50R200-0A0-000
connector:
SGC/SVC Profibus DP / open-close duty and modulating duty / 1-phase AC 115 V or 230 V
E3: Position feedback signal and positioner
Industrial plug TPCBA000-2A7-0540 TPA50R200-0A0-000
AUMA plug/socket TPCBA000-2A7-0000 TPA50R200-0A0-000
connector:
SGC/SVC Modbus RTU / open-close duty and modulating duty / 1-phase AC 115 V or 230 V
E4: Position feedback signal and positioner
Industrial plug TPCBC000-2A7-0540 TPA50R200-0A0-000
AUMA plug/socket TPCBC000-2A7-0000 TPA50R200-0A0-000
connector:

SD/SDL 1-phase AC 230 V


F1: 3 x binary inputs: CLOSE, OPEN, MODE (change-over between analogue and 3-point control)
1 x binary output: Fault
Contact for zero adjustment
Position feedback signal(0/4 – 20 mA)
Positioner (0/4 – 20mA)
SD25-170.050.03
SD/SDL 1-phase AC 230 V
F2: 3 x binary inputs: CLOSE, OPEN, MODE (change-over between analogue and 3-point control)
4 x binary outputs (relays): OPEN. CLOSE, intermediate position, fault
Contact for zero adjustment
Position feedback signal(0/4 – 20 mA)
Positioner (0/4 – 20mA)
SD25-170.050.06
SD/SDL DC 24 V
F3: 3 x binary inputs: CLOSE, OPEN, MODE (change-over between analogue and 3-point control)
1 x binary output: Fault
Contact for zero adjustment
Position feedback signal(0/4 – 20 mA)
Positioner (0/4 – 20mA)
SD25-170.050.01

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y007.558/003/en Issue 1.17 Page 1/1


Code: E1
Code: E1
Code: E2
Code: E2
Code: E3
Code: E3
Code: E4
Code: E4
Code: F1
Code: F2
Code: F3
AUMA Industry & Marine GmbH
Eichendorffstraße 42 – 48
D-78054 Villingen-Schwenningen
Tel +49 7720 8540-0
Fax +49 7720 8540-50
info.industry-marine@auma.com

AUMA subsidiaries or representatives


are implanted in more than 70 countries. For
detailed contact information, please refer to
www.auma.com

Subject to changes without notice. The product features and technical data provided do not express or imply any warranty. Y007.568/003/en/1.17