Professional Documents
Culture Documents
+BG1
CIRCUIT DIAGRAM SHOWS OPERATING MECHANISM WHEN CIRCUIT BREAKER IS OPEN, WITHOUT PRESSURE, CLOSING SPRING NOT CHARGED AND CIRCUITS DE-ENERGIZED. CIRCUIT BREAKER
EL DIAGRAMA MUESTRA EL MECÁNISMO DE MANIOBRA CUANDO EL INTERRUPTOR CORRESPONDIENTE DE ALTA TENSION ESTA EN POSICION ABIERTA, NO PRESURISADO INTERRUPTOR
LOS RESORTES DEL MECÁNISMO NO ESTAN TENSADOS Y BOBINAS DESENRGIZADAS.
CLOSE CIRCUIT 1
CIRCUITO DE CIERRE 1 +S1 +S4
A REMOTE REMOTO A
I
- LOCAL LOCAL
O
+ 602 1 2 24 21 A1 A2
22
- 625
+X21 +SX21 +SXY3
626 1 1 2 2
627 5 6
CLOSE CIRCUIT 2
608
We reserve all rights in this document and in the in-
CLOSE 2 +, REMOTE 24 21 12
CIERRE 2 +, REMOTO 710 17 18 22 9 9
34 31
+X12 +SX12 +SX12 +X12
32
9 9 61 62 10 10
+K4
C 24 21 A1 A2 C
22
725
+SXY4
726 2 2
Based on 1HSB543200-ACK Prepared 2013-11-22 Domert Magnus Circuit Diagram DIAGRAMA DE CIRCUITO CD
Approved 2013-11-22 Gutman Anton OPERATING MECHANISM FSA +FSA.1
MECANISMO DE OPERACION FSA Resp dept PPHB/BOD Rev ind B Lang es
Sheet 1/11
1HSB543200-ADL
Cont 2
1 2 3 4 5 6
1 2 3 4 5 6
TRIP CIRCUIT 1 +S1 +S4 +K9 +K10 +BG1 +BW1
CIRCUITO DE DISPARO 1
689
A +Y1 A
+X11 +SXY1
TRIP 1 +, REMOTE 14 11 2 2 03 04 1 1 1 2
DISPARO 1 +, REMOTO 630 7 8 12
TRIP 1 +, LOCAL
DISPARO 1 +, LOCAL 631 5 6
+ 600 3 4
601
+X2
61
B 21[3] B
+BD1
23 22[4]
66 A1 A2
We reserve all rights in this document and in the in-
C +X1 C
- 606
605
(TRIP 1 -) +X11 +SXY1
(DISPARO 1 -) 645 3 3 2 2
652
653 7 8
INTERRUPTOR CERRADO
O
D D
Based on 1HSB543200-ACK Prepared 2013-11-22 Domert Magnus Circuit Diagram DIAGRAMA DE CIRCUITO CD
Approved 2013-11-22 Gutman Anton OPERATING MECHANISM FSA +FSA.1
MECANISMO DE OPERACION FSA Resp dept PPHB/BOD Rev ind B Lang es
Sheet 2 /11
1HSB543200-ADL
Cont 3
1 2 3 4 5 6
1 2 3 4 5 6
TRIP CIRCUIT 2 +S4 +K10 +BG1 +BW1
CIRCUITO DE DISPARO 2
789
A +Y2 A
+X21 +SX21 +SXY2
TRIP 2 +, REMOTE 14 11 4 4 13 14 1 1 1 2
DISPARO 2 +, REMOTO 730 9 10 12
TRIP 2 +, LOCAL
DISPARO 2 +, LOCAL 731 11 12
+
700
701
+X2
71
31[5]
B B
+BD1
33 32[6]
76 A1 A2
We reserve all rights in this document and in the in-
C C
+X1
- 705
706
(TRIP 2 -) +X21 +SX21 +SXY2
(DISPARO 2 -) 745 2 2 2 2
D D
Based on 1HSB543200-ACK Prepared 2013-11-22 Domert Magnus Circuit Diagram DIAGRAMA DE CIRCUITO CD
Approved 2013-11-22 Gutman Anton OPERATING MECHANISM FSA +FSA.1
MECANISMO DE OPERACION FSA Resp dept PPHB/BOD Rev ind B Lang es
Sheet 3 /11
1HSB543200-ADL
Cont 4
1 2 3 4 5 6
1 2 3 4 5 6
+S4
SIGNAL CONTACTS +BG1 +BW1
CONTACTOS DE SENALIZACION
+X1
902
REMOTE
903 13 14
A REMOTO A
LOCAL
904 15 16
LOCAL
REMOTE REMOTO
LOCAL LOCAL
+
628
+X2
51
B B
11[1]
+BD1
13 12[2] +K25
56 A1 A2
We reserve all rights in this document and in the in-
+X1
is strictly forbidden. c ABB
870
871 14 11
12
C C
- 607
Based on 1HSB543200-ACK Prepared 2013-11-22 Domert Magnus Circuit Diagram DIAGRAMA DE CIRCUITO CD
Approved 2013-11-22 Gutman Anton OPERATING MECHANISM FSA +FSA.1
MECANISMO DE OPERACION FSA Resp dept PPHB/BOD Rev ind B Lang es
Sheet 4 /11
1HSB543200-ADL
Cont 5
1 2 3 4 5 6
1 2 3 4 5 6
+BG1 +BW1
AUXILIARY CONTACTS
CONTACTOS AUXILIARES
A A
B B
+X22 +SX22
241 1 1 71 72
242 2 2
243 3 3 73 74
244 4 4
251 5 5 81 82
We reserve all rights in this document and in the in-
252 6 6
253 7 7 83 84
is strictly forbidden. c ABB
254 8 8
261 9 9 91 92
262 10 10
263 11 11 93 94
264 12 12
C 309 C
300 07 08
289
280 10 19
299
290 20 29
Based on 1HSB543200-ACK Prepared 2013-11-22 Domert Magnus Circuit Diagram DIAGRAMA DE CIRCUITO CD
Approved 2013-11-22 Gutman Anton OPERATING MECHANISM FSA +FSA.1
MECANISMO DE OPERACION FSA Resp dept PPHB/BOD Rev ind B Lang es
Sheet 5 /11
1HSB543200-ADL
Cont 6
1 2 3 4 5 6
1 2 3 4 5 6
- 604
+X21 +SX21
A 201 7 7 31 32 A
202 8 8
+Q2
A1 A2
271 1 2
272
281 3 4
282
291 5 6
292
301 53 54
302
B 311 63 64 B
312
321 73 74
322
We reserve all rights in this document and in the in-
203 9 9 33 34
204 10 10
is strictly forbidden. c ABB
+Q3
A1 A2
C 273 1 2 C
274
283 3 4
284
293 5 6
294
303 53 54
304
313 63 64
INTERRUPTOR CERRADO
324
A
D D
/7
/7
Based on 1HSB543200-ACK Prepared 2013-11-22 Domert Magnus Circuit Diagram DIAGRAMA DE CIRCUITO CD
Approved 2013-11-22 Gutman Anton OPERATING MECHANISM FSA +FSA.1
MECANISMO DE OPERACION FSA Resp dept PPHB/BOD Rev ind B Lang es
Sheet 6 /11
1HSB543200-ADL
Cont 7
1 2 3 4 5 6
1 2 3 4 5 6
+BW1
/6
/6
SIGNAL CONTACTS
CONTACTOS DE SENALIZACION
B
+X1 +X11
LIMIT SWITCH (SPRING CHARGED) 886 4 4 12 11
SUICHE DE FIN CARRERA
887 5 5
(RESORTE CARGADO)
A 888 6 6 10 9 A
+K16
889 A2 A1 7 7
890
24 21
891 22
892
893 14 11
12
B B
We reserve all rights in this document and in the in-
+F1
878 21 22
ALARM MOTOR CIRCUIT
879
ADVERTENCIA CIRCUITO DE MOTOR
876 31 32
C 877 C
+/L
450 1 2 +X11 +M1
451 3 4 11 11 2 1 1 M 2
I>
-/N
465 5 6 12 12 4 3 ~
466
1
0
D D
Based on 1HSB543200-ACK Prepared 2013-11-22 Domert Magnus Circuit Diagram DIAGRAMA DE CIRCUITO CD
Approved 2013-11-22 Gutman Anton OPERATING MECHANISM FSA +FSA.1
MECANISMO DE OPERACION FSA Resp dept PPHB/BOD Rev ind B Lang es
Sheet 7 /11
1HSB543200-ADL
Cont 8
1 2 3 4 5 6
1 2 3 4 5 6
DC OUTLET
+X1 +F2A +X4A
TOMADA CC
502 2 1 1
517 4 3 2
I>
A A
1
0
908 11 12
909
AC AUXILIARY CIRCUIT
910 21 22
CIRCUITO DE CA. AUXILIAR
911
+BT1
+F2
884 21 22
ALARM AC CIRCUIT
885
ADVERTENCIA CIRCUITO +E2
DE CA. AUXILIAR 1 2 1 2
13 14
+XC1
B L 2 1 1 +E1 B
500 1 2
I>
501
1
0 +XC2
N 1
515
We reserve all rights in this document and in the in-
516
is strictly forbidden. c ABB
+BX1 +E3
2
21 22 1 2
2
C C
+X4
1
2
PE
E
D D
Based on 1HSB543200-ACK Prepared 2013-11-22 Domert Magnus Circuit Diagram DIAGRAMA DE CIRCUITO CD
Approved 2013-11-22 Gutman Anton OPERATING MECHANISM FSA +FSA.1
MECANISMO DE OPERACION FSA Resp dept PPHB/BOD Rev ind B Lang es
Sheet 8 /11
1HSB543200-ADL
Cont 9
1 2 3 4 5 6
1 2 3 4 5 6
CIRCUIT DIAGRAM SHOWS OPERATING MECHANISM WHEN CIRCUIT BREAKER IS OPEN, WITHOUT PRESSURE, CLOSING SPRING NOT CHARGED AND CIRCUITS DE-ENERGIZED.
EL DIAGRAMA MUESTRA EL MECÁNISMO DE MANIOBRA CUANDO EL INTERRUPTOR CORRESPONDIENTE DE ALTA TENSION ESTA EN POSICION ABIERTA, NO PRESURISADO
LOS RESORTES DEL MECÁNISMO NO ESTAN TENSADOS Y BOBINAS DESENRGIZADAS.
+F2A MINIATURE CIRCUIT BREAKER (DC OUTLET) +X4A SOCKET OUTLET (DC)
MINI INTERRUPTOR (TOMADA CC) ENCHUFE (DC)
+K9 INTERLOCKING RELAY (GAS SUPERVISION) (CLOSE 1 / TRIP 1) +Y1 SHUNT TRIP COIL 1
RELE DE ENCLAVAMIENTO (SUPERVISION DE GAS) (CIERRE 1/DISPARO 1) BOBINA DE DISPARO 1
+K10 INTERLOCKING RELAY (GAS SUPERVISION) (CLOSE 2 / TRIP 2) +Y2 SHUNT TRIP COIL 2
RELE DE ENCLAVAMIENTO (SUPERVISION DE GAS) (CIERRE 2/DISPARO 2) BOBINA DE DISPARO 2
C AUXILIARY RELAY +Y3 CLOSE COIL 1 C
+K16 BOBINA DE CIERRE 1
RELE AUXILIAR
+Y4 CLOSE COIL 2
+K25 AUXILIARY RELAY (GAS SUPERVISION) (ALARM) BOBINA DE CIERRE 2
RELE DE AUXILIAR (SUPERVISION DE GAS) (ADVERTENCIA)
D D
2) TO BE CONNECTED ON SITE WHEN INSTALLING.
2) A CONECTARSE EN SITIO DURANTE LA INSTALACION.
Based on 1HSB543200-ACK Prepared 2013-11-22 Domert Magnus Circuit Diagram DIAGRAMA DE CIRCUITO CD
Approved 2013-11-22 Gutman Anton OPERATING MECHANISM FSA +FSA.1
MECANISMO DE OPERACION FSA Resp dept PPHB/BOD Rev ind B Lang es
Sheet 9 /11
1HSB543200-ADL
Cont 10
1 2 3 4 5 6
We reserve all rights in this document and in the in-
formation contained therein. Reproduction, use or
disclosure to third parties without express authority
B
D
A
is strictly forbidden. c ABB
Based on
1HSB543200-ACK
1
1
DISPOSICION DE BORNERAS (MONTAJE VERTICAL)
TERMINAL ARRANGEMENT (VERTICAL MOUNT.)
EXT. +X1 +X1 INT.
450
INT. +X1 +X1 EXT.
451
465 201
202
466 203
500 204
211
501 212
515 213
516 214
221
502 222
517 223
224
SPARE
241
SPARE 242
SPARE 243
SPARE 244
251
600 252
2
2
601 253
254
602 261
603 262
604 263
264
605 271
606 272
607 273
274
608 280
Prepared
Approved
610 281
611 282
283
625 284
2013-11-22
2013-11-22
626 289
627 290
291
628 292
630 293
631 294
299
645 300
652 301
Domert Magnus
Gutman Anton
653 302
303
688
3
3
304
689 309
700 311
312
701 313
705 314
706 321
322
710
323
725 324
726 SPARE
730 SPARE
731 +X2 +X2
745 51
56
788
61
789 66
870 71
871 76
876
877
MECANISMO DE OPERACION FSA
OPERATING MECHANISM FSA
Circuit Diagram
878
879
884
885
886
4
4
887
888
889
890
891
892
893
SPARE
DIAGRAMA DE CIRCUITO
SPARE
902
903
904
SPARE
906
907
908
909
910
911
SPARE
SPARE
SPARE
SPARE
SPARE
Resp dept
SPARE
CD
SPARE
5
5
1HSB543200-ADL
SPARE
SPARE
SPARE
PPHB/BOD
931
932
Rev ind
+FSA.1
B
6
6
Cont
Lang
Sheet
es
R1-
10 /11
B
D
A
1 2 3 4 5 6
List of Revisions
B Separate feed to Q1, Q2 and K16 added. 2013-11-22 Domert Magnus Gutman Anton
B B
We reserve all rights in this document and in the in-
C C
D D
Based on 1HSB543200-ACK Prepared 2013-11-22 Domert Magnus Circuit Diagram DIAGRAMA DE CIRCUITO CD
Approved 2013-11-22 Gutman Anton OPERATING MECHANISM FSA
MECANISMO DE OPERACION FSA Resp dept PPHB/BOD Rev ind B Lang es
Sheet R1/
1HSB543200-ADL
Cont
1 2 3 4 5 6