Definitions Of Terms:
All forces in units kN and m
All reinforcement details like area, spacing in mm
Neutral axis angle for resultant design moment is with respect to local major axis.
Ratio to account for reduction of stiffness of
1 βdns =
columns due to sustained axial loads
Moment magnification factor for frames not braced
2 δns =
against sidesway
First-order relative deflection between the top and
3 Δo =
bottom of the story due to Vu in mm
Total factored vertical load in the story
4 ∑Pu = corresponding to the lateral loading case for which
∑Pu is greatest, kN (Clause 10.10.5)
5 δu = Design displacement in mm
Modification factor reflecting the reduced
6 λ =
mechanical properties of lightweight concrete
7 Φ = Strength reduction factor
Coefficient defining the relative contribution of
8 ac =
concrete strength to nominal wall shear strength
Cross-sectional area of a structural member
9 Ach = measured to the outside edges of transverse
reinforcement in sqmm
Gross area of concrete section bounded by web
10 Acv = thickness and length of section in the direction of
shear force considered in sqmm
Effective cross-sectional area within a joint in a
11 Aj = plane parallel to plane of reinforcement generating
shear in the joint in sqmm
Area of non-prestressed longitudinal tension
12 As =
reinforcement in sqmm
Minimum area of shear reinforcement within
13 Avmin =
spacing 's' in sqmm
14 B = Width of column/ wall in mm
15 B' = width of beam along B / column width in mm
Cross-sectional dimension of member core
16 bc = measured to the outside edges of the transverse
reinforcement composing area Ash in mm
Distance from extreme compression fiber to neutral
17 c =
axis in mm
18 Cc = Clear cover of reinforcement in mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 2 of 109
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 3 of 109
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 4 of 109
Code References:
ACI 318M-2011
Sr.No Element Clause / table
Minimum area of longitudinal
1 : 21.6.3
reinforcement for column
Maximum area of longitudinal
2 : 21.6.3
reinforcement for column
Minimum longitudinal and transverse
3 : 21.9.2.1
reinforcement for wall
4 Minimum diameter of transverse ties : 7.10.5
5 Minimum spacing of transverse ties : 7.10.5
Maximum spacing of longitudinal and
6 : 21.9.2.1
transverse reinforcement for wall
7 Applicability of boundary element : 21.9.6
Area and spacing of special confining
8 : 21.6.4
reinforcement
9 Slenderness Moments : 10.10
Shear Strength provided by concrete for
10 : 11.2
column
11 Design of shear for non-ductile wall : 11.9
12 Design of shear for ductile wall : 21.9.4
13 Minimum Flexural Strength of Columns : 21.6.2.2
14 Shear Check at Column Joint : 21.7.4.1
15 Shear Strength of Column : 21.3.3 & 21.5.4
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 5 of 109
1.3m to LOAD 2:
3 2343.605 6.116 218.257 0.022 Non Sway
4.3m EZ
4.3m to LOAD 2:
2.8 397.819 2.012 37.708 0.008 Non Sway
7.1m EZ
General Data
Column No. : C1
Level : 0m To 1.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 1
Critical Analysis Load Combination : 19
[15] : 1.42 (LOAD 3: DEAD LOAD) +1.25 (LOAD
Load Combination =
1: EX)
Critical Location = Top Joint
Put = 489.04 kN
Muxt = 71.79 kNm
Muyt = 16.28 kNm
Vuxt = 18.12 kN
Vuyt = -79.93 kN
Pub = 492.96 kN
Muxb = -32.09 kNm
Muyb = -7.28 kNm
Vuxb = 18.12 kN
Vuyb = -79.93 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 6 of 109
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 9.04
M1 = -32.09 kNm
M2 = 71.79 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 9.04
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 7 of 109
M1 = -7.28 kNm
M2 = 16.28 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 15
[11] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) +1.25 kN
(LOAD 1: EX)
Nu = 507.78 kN
Muy = 31.73 kNm
Vuy = -79.0389 kN
λ = 1
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 8 of 109
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 28.44 kNm
Vcy Permissible = 194.97 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 9 of 109
Column No. : C1
Level : 1.3m To 4.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 10
Critical Analysis Load Combination : 19
[15] : 1.42 (LOAD 3: DEAD LOAD) +1.25 (LOAD
Load Combination =
1: EX)
Critical Location = Top Joint
Put = 441.04 kN
Muxt = -77.26 kNm
Muyt = -40.88 kNm
Vuxt = -16.2 kN
Vuyt = 41.35 kN
Pub = 450.08 kN
Muxb = 46.74 kNm
Muyb = 7.7 kNm
Vuxb = -16.2 kN
Vuyb = 41.35 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 10 of 109
Axis = 0.83
Along B
Q = 0.022
0.022< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.83
r = 86.6 mm
Kluy /r = 24.92
M1 = 46.74 kNm
M2 = -77.26 kNm
34 - 12 x (M1/M2) = 41.26
24.92 < 41.26, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.82
r = 86.6 mm
Klux /r = 24.62
M1 = 7.7 kNm
M2 = -40.88 kNm
34 - 12 x (M1/M2) = 36.26
24.62 < 36.26, Column not slender along B
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 11 of 109
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 25
[21] : 0.68 (LOAD 3: DEAD LOAD) -
Critical Load Combination = kN
1.25 (LOAD 1: EX)
Nu = 239.84 kN
Muy = 40.76 kNm
Vuy = -31.6455 kN
λ = 1
φ = 0.65
deff = 250 mm
ρw = 0.014
mm = 12.28 kNm
Vcy Permissible = 69.18 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 12 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C1
Level : 4.3m To 7.1m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 13 of 109
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2400 mm
Clear Floor Height @ luy = 2400 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 19
Critical Analysis Load Combination : 21
[17] : 1.42 (LOAD 3: DEAD LOAD) -1.25 (LOAD
Load Combination =
1: EX)
Critical Location = Bottom Joint
Put = 39.37 kN
Muxt = 10.58 kNm
Muyt = -10.96 kNm
Vuxt = -20.49 kN
Vuyt = 6.82 kN
Pub = 47.81 kN
Muxb = 29.68 kNm
Muyb = 46.39 kNm
Vuxb = -20.49 kN
Vuyb = 6.82 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 14 of 109
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.65
r = 86.6 mm
Kluy /r = 18.01
M1 = 10.58 kNm
M2 = 29.68 kNm
34 - 12 x (M1/M2) = 29.72
18.01 < 29.72, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.64
r = 86.6 mm
Klux /r = 17.74
M1 = -10.96 kNm
M2 = 46.39 kNm
34 - 12 x (M1/M2) = 36.84
17.74 < 36.84, Column not slender along B
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 15 of 109
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 14
[10] : 1.2 (LOAD 3: DEAD LOAD)
Critical Load Combination = kN
+1.6 (LOAD 4: LIVE LOAD)
Nu = 48.78 kN
Muy = 5.68 kNm
Vuy = 5.9327 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 0.1 kNm
Vcy Permissible = 129.18 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 16 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C2
Level : 0m To 1.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 17 of 109
Load Data
Analysis Reference No. = 2
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 1: EX)
Critical Location = Top Joint
Put = 524.74 kN
Muxt = -55.83 kNm
Muyt = 16.47 kNm
Vuxt = 18.34 kN
Vuyt = 62.16 kN
Pub = 528.66 kN
Muxb = 24.95 kNm
Muyb = -7.36 kNm
Vuxb = 18.34 kN
Vuyb = 62.16 kN
= 0.87
Effective Length Factor along Minor
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 18 of 109
axis
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 9.04
M1 = 24.95 kNm
M2 = -55.83 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 9.04
M1 = -7.36 kNm
M2 = 16.47 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 19 of 109
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 25
[21] : 0.68 (LOAD 3: DEAD LOAD) -
Critical Load Combination = kN
1.25 (LOAD 1: EX)
Nu = 244.22 kN
Muy = 21.72 kNm
Vuy = 54.1076 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 7.22 kNm
Vcy Permissible = 160.52 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 20 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C2
Level : 1.3m To 4.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 11
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 1: EX)
Critical Location = Top Joint
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 21 of 109
Put = 428.67 kN
Muxt = 87.31 kNm
Muyt = -44.89 kNm
Vuxt = -17.8 kN
Vuyt = -56.84 kN
Pub = 437.7 kN
Muxb = -83.17 kNm
Muyb = 8.48 kNm
Vuxb = -17.8 kN
Vuyb = -56.84 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 22 of 109
Along B
Q = 0.022
0.022< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 30.02
M1 = -83.17 kNm
M2 = 87.31 kNm
34 - 12 x (M1/M2) = 45.43
30.02 < 45.43, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.82
r = 86.6 mm
Klux /r = 24.62
M1 = 8.48 kNm
M2 = -44.89 kNm
34 - 12 x (M1/M2) = 36.27
24.62 < 36.27, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 23 of 109
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) -1.25 kN
(LOAD 1: EX)
Nu = 437.7 kN
Muy = 83.17 kNm
Vuy = -56.8402 kN
λ = 1
φ = 0.65
deff = 247.5 mm
ρw = 0.018
mm = 31.05 kNm
Vcy Permissible = 68.89 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 24 of 109
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 6.25 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 320 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C2
Level : 4.3m To 7.1m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2400 mm
Clear Floor Height @ luy = 2400 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 20
Critical Analysis Load Combination : 21
[17] : 1.42 (LOAD 3: DEAD LOAD) -1.25 (LOAD
Load Combination =
1: EX)
Critical Location = Bottom Joint
Put = 37.91 kN
Muxt = 33.43 kNm
Muyt = -13.67 kNm
Vuxt = -23.05 kN
Vuyt = -22.9 kN
Pub = 46.35 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 25 of 109
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 26 of 109
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.82
r = 86.6 mm
Kluy /r = 22.72
M1 = -30.68 kNm
M2 = 33.43 kNm
34 - 12 x (M1/M2) = 45.01
22.72 < 45.01, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.64
r = 86.6 mm
Klux /r = 17.74
M1 = -13.67 kNm
M2 = 50.85 kNm
34 - 12 x (M1/M2) = 37.23
17.74 < 37.23, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 27 of 109
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 21
[17] : 1.42 (LOAD 3: DEAD LOAD) -
Critical Load Combination = kN
1.25 (LOAD 1: EX)
Nu = 46.35 kN
Muy = 30.68 kNm
Vuy = -22.9016 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 25.19 kNm
Vcy Permissible = 68.41 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 28 of 109
General Data
Column No. : C3
Level : 0m To 1.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 3
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 1: EX)
Critical Location = Top Joint
Put = 260.43 kN
Muxt = -76.89 kNm
Muyt = 11.17 kNm
Vuxt = 12.44 kN
Vuyt = 85.6 kN
Pub = 264.34 kN
Muxb = 34.37 kNm
Muyb = -4.99 kNm
Vuxb = 12.44 kN
Vuyb = 85.6 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 29 of 109
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 9.04
M1 = 34.37 kNm
M2 = -76.89 kNm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 30 of 109
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 9.04
M1 = -4.99 kNm
M2 = 11.17 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 21
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 31 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 32 of 109
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C3
Level : 1.3m To 4.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 12
Critical Analysis Load Combination : 19
[15] : 1.42 (LOAD 3: DEAD LOAD) +1.25 (LOAD
Load Combination =
1: EX)
Critical Location = Top Joint
Put = 243.34 kN
Muxt = -71.59 kNm
Muyt = -22.44 kNm
Vuxt = -6.98 kN
Vuyt = 42.11 kN
Pub = 252.38 kN
Muxb = 54.7 kNm
Muyb = -1.52 kNm
Vuxb = -6.98 kN
Vuyb = 42.11 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 33 of 109
Along B
Q = 0.022
0.022< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 34 of 109
Kluy /r = 30.02
M1 = 54.7 kNm
M2 = -71.59 kNm
34 - 12 x (M1/M2) = 43.17
30.02 < 43.17, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.82
r = 86.6 mm
Klux /r = 24.62
M1 = -1.52 kNm
M2 = -22.44 kNm
34 - 12 x (M1/M2) = 33.19
24.62 < 33.19, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 35 of 109
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) -1.25 kN
(LOAD 1: EX)
Nu = 215.08 kN
Muy = 31.53 kNm
Vuy = -26.6295 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 6.05 kNm
Vcy Permissible = 68.7 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 36 of 109
General Data
Column No. : C3
Level : 4.3m To 7.1m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2400 mm
Clear Floor Height @ luy = 2400 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 21
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 1: EX)
Critical Location = Bottom Joint
Put = 18.63 kN
Muxt = 7.84 kNm
Muyt = -1.89 kNm
Vuxt = -9.32 kN
Vuyt = 5.35 kN
Pub = 27.07 kN
Muxb = 22.81 kNm
Muyb = 24.21 kNm
Vuxb = -9.32 kN
Vuyb = 5.35 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 37 of 109
(Length x (Length x
Width x Width x
Depth) Depth)
N-M mm mm N-M N-M
5000 x 200 x
Bottom 26.408 No Beam - 23.369 2.193
400
5000 x 200 x
Top 26.408 No Beam - 23.369 1.134
400
Sway Condition (as per Stability
= Non Sway
Index)
Effective Length Factor along Major
= 1
Axis
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 27.71
M1 = 7.84 kNm
M2 = 22.81 kNm
34 - 12 x (M1/M2) = 29.87
27.71 < 29.87, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 38 of 109
K = 0.64
r = 86.6 mm
Klux /r = 17.74
M1 = -1.89 kNm
M2 = 24.21 kNm
34 - 12 x (M1/M2) = 34.94
17.74 < 34.94, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 18
[14] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) -1.25 kN
(LOAD 2: EZ)
Nu = 26.11 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 39 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 40 of 109
General Data
Column No. : C4
Level : 0m To 1.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 4
Critical Analysis Load Combination : 19
[15] : 1.42 (LOAD 3: DEAD LOAD) +1.25 (LOAD
Load Combination =
1: EX)
Critical Location = Top Joint
Put = 399.87 kN
Muxt = 70.62 kNm
Muyt = -5.93 kNm
Vuxt = -6.6 kN
Vuyt = -78.62 kN
Pub = 403.79 kN
Muxb = -31.56 kNm
Muyb = 2.65 kNm
Vuxb = -6.6 kN
Vuyb = -78.62 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 41 of 109
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 9.04
M1 = -31.56 kNm
M2 = 70.62 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 9.04
M1 = 2.65 kNm
M2 = -5.93 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along B
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 42 of 109
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 15
[11] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) +1.25 kN
(LOAD 1: EX)
Nu = 435.65 kN
Muy = 31.25 kNm
Vuy = -77.8293 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 20.38 kNm
Vcy Permissible = 186.18 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 43 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C4
Level : 1.3m To 4.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 44 of 109
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 13
Critical Analysis Load Combination : 22
[18] : 1.42 (LOAD 3: DEAD LOAD) -1.25 (LOAD
Load Combination =
2: EZ)
Critical Location = Top Joint
Put = 331.19 kN
Muxt = -19.74 kNm
Muyt = 78.97 kNm
Vuxt = 52.8 kN
Vuyt = 4.35 kN
Pub = 340.22 kN
Muxb = -6.7 kNm
Muyb = -79.37 kNm
Vuxb = 52.8 kN
Vuyb = 4.35 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 45 of 109
(Length x (Length x
Width x Width x
Depth) Depth)
N-M mm mm N-M N-M
4000 x 200 x 4000 x 200 x
Bottom 24.648 29.212 29.212 1.398
400 400
4000 x 200 x 4000 x 200 x
Top 24.648 29.212 29.212 0.875
400 400
Sway Condition (as per Stability
= Non Sway
Index)
Effective Length Factor along Minor
= 0.85
axis
Along B
Q = 0.022
0.022< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.83
r = 86.6 mm
Kluy /r = 24.92
M1 = -6.7 kNm
M2 = -19.74 kNm
34 - 12 x (M1/M2) = 29.93
24.92 < 29.93, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.85
r = 86.6 mm
Klux /r = 25.52
M1 = 78.97 kNm
M2 = -79.37 kNm
34 - 12 x (M1/M2) = 45.94
25.52 < 45.94, Column not slender along B
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 46 of 109
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 15
[11] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) +1.25 kN
(LOAD 1: EX)
Nu = 359.46 kN
Muy = 45.2 kNm
Vuy = 39.2478 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 2.6 kNm
Vcy Permissible = 68.77 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 47 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C4
Level : 4.3m To 7.1m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 48 of 109
Load Data
Analysis Reference No. = 22
Critical Analysis Load Combination : 22
[18] : 1.42 (LOAD 3: DEAD LOAD) -1.25 (LOAD
Load Combination =
2: EZ)
Critical Location = Bottom Joint
Put = 39.35 kN
Muxt = 0.38 kNm
Muyt = 29.36 kNm
Vuxt = 19.94 kN
Vuyt = 8.61 kN
Pub = 47.78 kN
Muxb = 24.47 kNm
Muyb = -26.47 kNm
Vuxb = 19.94 kN
Vuyb = 8.61 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 49 of 109
400 400
4000 x 200 x 4000 x 200 x
Top 26.408 29.212 29.212 0.453
400 400
Sway Condition (as per Stability
= Non Sway
Index)
Effective Length Factor along Minor
= 0.71
axis
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.65
r = 86.6 mm
Kluy /r = 18.01
M1 = 0.38 kNm
M2 = 24.47 kNm
34 - 12 x (M1/M2) = 33.81
18.01 < 33.81, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 86.6 mm
Klux /r = 19.68
M1 = -26.47 kNm
M2 = 29.36 kNm
34 - 12 x (M1/M2) = 44.82
19.68 < 44.82, Column not slender along B
Where
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 50 of 109
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 14
[10] : 1.2 (LOAD 3: DEAD LOAD)
Critical Load Combination = kN
+1.6 (LOAD 4: LIVE LOAD)
Nu = 79.52 kN
Muy = 8.35 kNm
Vuy = 3.6894 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 1.07 kNm
Vcy Permissible = 134.59 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 51 of 109
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 1.38 kNm
Vcx Permissible = 134.59 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C5
Level : 0m To 1.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 52 of 109
Load Data
Analysis Reference No. = 5
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 1: EX)
Critical Location = Top Joint
Put = 502.51 kN
Muxt = -57.26 kNm
Muyt = -6.33 kNm
Vuxt = -7.05 kN
Vuyt = 63.75 kN
Pub = 506.43 kN
Muxb = 25.59 kNm
Muyb = 2.83 kNm
Vuxb = -7.05 kN
Vuyb = 63.75 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 53 of 109
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 9.04
M1 = 25.59 kNm
M2 = -57.26 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 9.04
M1 = 2.83 kNm
M2 = -6.33 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 54 of 109
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) -1.25 kN
(LOAD 1: EX)
Nu = 506.43 kN
Muy = 25.59 kNm
Vuy = 63.7523 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 34.42 kNm
Vcy Permissible = 194.81 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 55 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C5
Level : 1.3m To 4.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 14
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 1: EX)
Critical Location = Top Joint
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 56 of 109
Put = 373.92 kN
Muxt = 93 kNm
Muyt = 13.5 kNm
Vuxt = 8.5 kN
Vuyt = -59.71 kN
Pub = 382.96 kN
Muxb = -86.08 kNm
Muyb = -11.98 kNm
Vuxb = 8.5 kN
Vuyb = -59.71 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 57 of 109
Along B
Q = 0.022
0.022< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 30.02
M1 = -86.08 kNm
M2 = 93 kNm
34 - 12 x (M1/M2) = 45.11
30.02 < 45.11, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.85
r = 86.6 mm
Klux /r = 25.52
M1 = -11.98 kNm
M2 = 13.5 kNm
34 - 12 x (M1/M2) = 44.65
25.52 < 44.65, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 58 of 109
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 15
[11] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) +1.25 kN
(LOAD 1: EX)
Nu = 275.5 kN
Muy = 33.5 kNm
Vuy = 24.8988 kN
λ = 1
φ = 0.65
deff = 250 mm
ρw = 0.011
mm = 0.79 kNm
Vcy Permissible = 68.44 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 59 of 109
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C5
Level : 4.3m To 7.1m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2400 mm
Clear Floor Height @ luy = 2400 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 23
Critical Analysis Load Combination : 21
[17] : 1.42 (LOAD 3: DEAD LOAD) -1.25 (LOAD
Load Combination =
1: EX)
Critical Location = Top Joint
Put = 58.74 kN
Muxt = 44.53 kNm
Muyt = 10.66 kNm
Vuxt = 8.75 kN
Vuyt = -30.22 kN
Pub = 67.17 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 60 of 109
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 61 of 109
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.82
r = 86.6 mm
Kluy /r = 22.72
M1 = -40.07 kNm
M2 = 44.53 kNm
34 - 12 x (M1/M2) = 44.8
22.72 < 44.8, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.71
r = 86.6 mm
Klux /r = 19.68
M1 = 10.66 kNm
M2 = -13.82 kNm
34 - 12 x (M1/M2) = 43.26
19.68 < 43.26, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 62 of 109
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 25
[21] : 0.68 (LOAD 3: DEAD LOAD) -
Critical Load Combination = kN
1.25 (LOAD 1: EX)
Nu = 58.34 kN
Muy = 26.37 kNm
Vuy = -22.5941 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 19.45 kNm
Vcy Permissible = 68.73 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 63 of 109
General Data
Column No. : C6
Level : 0m To 1.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 6
Critical Analysis Load Combination : 25
[21] : 0.68 (LOAD 3: DEAD LOAD) -1.25 (LOAD
Load Combination =
1: EX)
Critical Location = Top Joint
Put = 112.48 kN
Muxt = -66.62 kNm
Muyt = -2.26 kNm
Vuxt = -2.52 kN
Vuyt = 74.17 kN
Pub = 114.36 kN
Muxb = 29.78 kNm
Muyb = 1.01 kNm
Vuxb = -2.52 kN
Vuyb = 74.17 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 64 of 109
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 9.04
M1 = 29.78 kNm
M2 = -66.62 kNm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 65 of 109
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 9.04
M1 = 1.01 kNm
M2 = -2.26 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 17
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 66 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 67 of 109
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C6
Level : 1.3m To 4.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 15
Critical Analysis Load Combination : 15
[11] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) +1.25 (LOAD 1: EX)
Critical Location = Top Joint
Put = 213.09 kN
Muxt = -82.43 kNm
Muyt = 11.52 kNm
Vuxt = 7.86 kN
Vuyt = 47.24 kN
Pub = 222.12 kN
Muxb = 59.25 kNm
Muyb = -12.05 kNm
Vuxb = 7.86 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 68 of 109
Vuyb = 47.24 kN
Along B
Q = 0.022
0.022< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 69 of 109
K = 1
r = 86.6 mm
Kluy /r = 30.02
M1 = 59.25 kNm
M2 = -82.43 kNm
34 - 12 x (M1/M2) = 42.62
30.02 < 42.62, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.85
r = 86.6 mm
Klux /r = 25.52
M1 = 11.52 kNm
M2 = -12.05 kNm
34 - 12 x (M1/M2) = 45.48
25.52 < 45.48, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 70 of 109
= 0.964 < 1
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 21
[17] : 1.42 (LOAD 3: DEAD LOAD) -
Critical Load Combination = kN
1.25 (LOAD 1: EX)
Nu = 181.74 kN
Muy = 24.12 kNm
Vuy = -23.2489 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 2.59 kNm
Vcy Permissible = 69.04 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 71 of 109
General Data
Column No. : C6
Level : 4.3m To 7.1m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2400 mm
Clear Floor Height @ luy = 2400 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 24
Critical Analysis Load Combination : 18
[14] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 27.19 kN
Muxt = -3.22 kNm
Muyt = 23.01 kNm
Vuxt = 15.4 kN
Vuyt = 11.73 kN
Pub = 35.63 kN
Muxb = 29.63 kNm
Muyb = -20.11 kNm
Vuxb = 15.4 kN
Vuyb = 11.73 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 72 of 109
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 27.71
M1 = -3.22 kNm
M2 = 29.63 kNm
34 - 12 x (M1/M2) = 35.3
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 73 of 109
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 17
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 74 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 75 of 109
General Data
Column No. : C7
Level : 0m To 1.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 7
Critical Analysis Load Combination : 19
[15] : 1.42 (LOAD 3: DEAD LOAD) +1.25 (LOAD
Load Combination =
1: EX)
Critical Location = Top Joint
Put = 343.72 kN
Muxt = 69.08 kNm
Muyt = -12.46 kNm
Vuxt = -13.87 kN
Vuyt = -76.91 kN
Pub = 347.64 kN
Muxb = -30.88 kNm
Muyb = 5.57 kNm
Vuxb = -13.87 kN
Vuyb = -76.91 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 76 of 109
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 9.04
M1 = -30.88 kNm
M2 = 69.08 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 9.04
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 77 of 109
M1 = 5.57 kNm
M2 = -12.46 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 15
[11] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) +1.25 kN
(LOAD 1: EX)
Nu = 370.79 kN
Muy = 30.51 kNm
Vuy = -75.9898 kN
λ = 1
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 78 of 109
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 13.43 kNm
Vcy Permissible = 177.9 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 79 of 109
Column No. : C7
Level : 1.3m To 4.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 16
Critical Analysis Load Combination : 18
[14] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 315.15 kN
Muxt = 1.19 kNm
Muyt = 60.38 kNm
Vuxt = 41.73 kN
Vuyt = -7.55 kN
Pub = 324.19 kN
Muxb = -21.46 kNm
Muyb = -64.78 kNm
Vuxb = 41.73 kN
Vuyb = -7.55 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 80 of 109
Axis = 0.83
Along B
Q = 0.022
0.022< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.83
r = 86.6 mm
Kluy /r = 24.92
M1 = 1.19 kNm
M2 = -21.46 kNm
34 - 12 x (M1/M2) = 34.66
24.92 < 34.66, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.79
r = 86.6 mm
Klux /r = 23.72
M1 = 60.38 kNm
M2 = -64.78 kNm
34 - 12 x (M1/M2) = 45.18
23.72 < 45.18, Column not slender along B
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 81 of 109
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 15
[11] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) +1.25 kN
(LOAD 1: EX)
Nu = 328.47 kN
Muy = 42.77 kNm
Vuy = 35.8781 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 3.84 kNm
Vcy Permissible = 68.68 kN
Vuy < Vcy Permissible
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 82 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C7
Level : 4.3m To 7.1m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 83 of 109
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2400 mm
Clear Floor Height @ luy = 2400 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 25
Critical Analysis Load Combination : 22
[18] : 1.42 (LOAD 3: DEAD LOAD) -1.25 (LOAD
Load Combination =
2: EZ)
Critical Location = Top Joint
Put = 29.05 kN
Muxt = 7.83 kNm
Muyt = 25.31 kNm
Vuxt = 13.48 kN
Vuyt = 1.52 kN
Pub = 37.48 kN
Muxb = 12.1 kNm
Muyb = -12.42 kNm
Vuxb = 13.48 kN
Vuyb = 1.52 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 84 of 109
Depth) Depth)
N-M mm mm N-M N-M
1000 x 200 x 4000 x 200 x
Bottom 26.408 116.847 29.212 0.35
400 400
1000 x 200 x 4000 x 200 x
Top 26.408 116.847 29.212 0.181
400 400
Sway Condition (as per Stability
= Non Sway
Index)
Effective Length Factor along Minor
= 0.61
axis
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.65
r = 86.6 mm
Kluy /r = 18.01
M1 = 7.83 kNm
M2 = 12.1 kNm
34 - 12 x (M1/M2) = 26.23
18.01 < 26.23, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.61
r = 86.6 mm
Klux /r = 16.9
M1 = -12.42 kNm
M2 = 25.31 kNm
34 - 12 x (M1/M2) = 39.89
16.9 < 39.89, Column not slender along B
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 85 of 109
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 15
[11] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) +1.25 kN
(LOAD 1: EX)
Nu = 38.63 kN
Muy = 3.45 kNm
Vuy = 6.0456 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 1.13 kNm
Vcy Permissible = 127.34 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 86 of 109
Nu = 46.19 kN
Mux = 2.01 kNm
Vux = 3.2431 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 3.46 kNm
Vcx Permissible = 128.71 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C8
Level : 0m To 1.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 87 of 109
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 8
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 1: EX)
Critical Location = Top Joint
Put = 436.94 kN
Muxt = -57.25 kNm
Muyt = -14.89 kNm
Vuxt = -16.58 kN
Vuyt = 63.74 kN
Pub = 440.86 kN
Muxb = 25.59 kNm
Muyb = 6.66 kNm
Vuxb = -16.58 kN
Vuyb = 63.74 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 88 of 109
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 9.04
M1 = 25.59 kNm
M2 = -57.25 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 9.04
M1 = 6.66 kNm
M2 = -14.89 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 89 of 109
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) -1.25 kN
(LOAD 1: EX)
Nu = 440.86 kN
Muy = 25.59 kNm
Vuy = 63.7426 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 26.65 kNm
Vcy Permissible = 186.83 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 90 of 109
mm = 13.11 kNm
Vcx Permissible = 69.47 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C8
Level : 1.3m To 4.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 17
Critical Analysis Load Combination : 17
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 91 of 109
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 92 of 109
Along B
Q = 0.022
0.022< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 30.02
M1 = -87.46 kNm
M2 = 94.52 kNm
34 - 12 x (M1/M2) = 45.1
30.02 < 45.1, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.79
r = 86.6 mm
Klux /r = 23.72
M1 = -7.78 kNm
M2 = 11.17 kNm
34 - 12 x (M1/M2) = 42.36
23.72 < 42.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 93 of 109
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 19
[15] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = kN
+1.25 (LOAD 1: EX)
Nu = 314.15 kN
Muy = 40.24 kNm
Vuy = 28.3855 kN
λ = 1
φ = 0.65
deff = 250 mm
ρw = 0.011
mm = 2.93 kNm
Vcy Permissible = 68.3 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design Of Links
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 94 of 109
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 5 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
General Data
Column No. : C8
Level : 4.3m To 7.1m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2400 mm
Clear Floor Height @ luy = 2400 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 26
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 1: EX)
Critical Location = Top Joint
Put = 54.53 kN
Muxt = 40.41 kNm
Muyt = 14.89 kNm
Vuxt = 10.74 kN
Vuyt = -28.62 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 95 of 109
Pub = 62.96 kN
Muxb = -39.69 kNm
Muyb = -15.19 kNm
Vuxb = 10.74 kN
Vuyb = -28.62 kN
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 96 of 109
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.82
r = 86.6 mm
Kluy /r = 22.72
M1 = -39.69 kNm
M2 = 40.41 kNm
34 - 12 x (M1/M2) = 45.78
22.72 < 45.78, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.61
r = 86.6 mm
Klux /r = 16.9
M1 = 14.89 kNm
M2 = -15.19 kNm
34 - 12 x (M1/M2) = 45.76
16.9 < 45.76, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 97 of 109
= 20.22 deg
MRes = 43.07 kNm
( φ ) MCap = 72.52 kNm
Capacity Ratio = MRes/ MCap
= 0.594 < 1
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 21
[17] : 1.42 (LOAD 3: DEAD LOAD) -
Critical Load Combination = kN
1.25 (LOAD 1: EX)
Nu = 47.33 kN
Muy = 38.56 kNm
Vuy = -27.8426 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 32.95 kNm
Vcy Permissible = 68.34 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 98 of 109
General Data
Column No. : C9
Level : 0m To 1.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 900 mm
Clear Floor Height @ luy = 900 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 9
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 1: EX)
Critical Location = Top Joint
Put = 213.59 kN
Muxt = -77.74 kNm
Muyt = -13.55 kNm
Vuxt = -15.08 kN
Vuyt = 86.55 kN
Pub = 217.51 kN
Muxb = 34.75 kNm
Muyb = 6.06 kNm
Vuxb = -15.08 kN
Vuyb = 86.55 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 99 of 109
Along B
Q = 0.01
0.01< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 86.6 mm
Kluy /r = 9.04
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 100 of 109
M1 = 34.75 kNm
M2 = -77.74 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 86.6 mm
Klux /r = 9.04
M1 = 6.06 kNm
M2 = -13.55 kNm
34 - 12 x (M1/M2) = 39.36
9.04 < 39.36, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 101 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 102 of 109
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 20 --- --- 20 ---
Spacing 250 --- --- 250 ---
General Data
Column No. : C9
Level : 1.3m To 4.3m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2600 mm
Clear Floor Height @ luy = 2600 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 18
Critical Analysis Load Combination : 19
[15] : 1.42 (LOAD 3: DEAD LOAD) +1.25 (LOAD
Load Combination =
1: EX)
Critical Location = Top Joint
Put = 193.91 kN
Muxt = -73.97 kNm
Muyt = 8.79 kNm
Vuxt = 5.49 kN
Vuyt = 43.65 kN
Pub = 202.94 kN
Muxb = 56.94 kNm
Muyb = -7.68 kNm
Vuxb = 5.49 kN
Vuyb = 43.65 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 103 of 109
Width x Width x
Depth) Depth)
N-M mm mm N-M N-M
5000 x 200 x
Bottom 24.648 No Beam - 23.369 3.502
400
5000 x 200 x
Top 24.648 No Beam - 23.369 2.193
400
Sway Condition (as per Stability
= Non Sway
Index)
Effective Length Factor along Major
= 1
Axis
Along B
Q = 0.022
0.022< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 30.02
M1 = 56.94 kNm
M2 = -73.97 kNm
34 - 12 x (M1/M2) = 43.24
30.02 < 43.24, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 104 of 109
K = 0.79
r = 86.6 mm
Klux /r = 23.72
M1 = -7.68 kNm
M2 = 8.79 kNm
34 - 12 x (M1/M2) = 44.49
23.72 < 44.49, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 17
[13] : 1.42 (LOAD 3: DEAD LOAD)
Critical Load Combination = +0.5 (LOAD 4: LIVE LOAD) -1.25 kN
(LOAD 1: EX)
Nu = 170.94 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 105 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 106 of 109
General Data
Column No. : C9
Level : 4.3m To 7.1m
Design Code = ACI 318M - 2011
Grade Of Concrete = C30 N/sqmm
Grade Of Steel = Fy414 N/sqmm
Consider Ductile = No
Column B = 300 mm
Column D = 300 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2400 mm
Clear Floor Height @ luy = 2400 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 27
Critical Analysis Load Combination : 18
[14] : 1.42 (LOAD 3: DEAD LOAD) +0.5 (LOAD 4:
Load Combination =
LIVE LOAD) -1.25 (LOAD 2: EZ)
Critical Location = Bottom Joint
Put = 21.63 kN
Muxt = -3.23 kNm
Muyt = 17.94 kNm
Vuxt = 9.99 kN
Vuyt = 9.62 kN
Pub = 30.07 kN
Muxb = 23.71 kNm
Muyb = -10.03 kNm
Vuxb = 9.99 kN
Vuyb = 9.62 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 107 of 109
Along B
Q = 0.008
0.008< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 86.6 mm
Kluy /r = 27.71
M1 = -3.23 kNm
M2 = 23.71 kNm
34 - 12 x (M1/M2) = 35.64
27.71 < 35.64, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.61
r = 86.6 mm
Klux /r = 16.9
M1 = -10.03 kNm
M2 = 17.94 kNm
34 - 12 x (M1/M2) = 40.71
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 108 of 109
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 13
Critical Load Combination = [9] : 1.4 (LOAD 3: DEAD LOAD) kN
Nu = 18.96 kN
Muy = 2 kNm
Vuy = 8.0201 kN
λ = 1
φ = 0.65
deff = 252 mm
ρw = 0.009
mm = 0.25 kNm
Vcy Permissible = 123.7 kN
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021
Column Design: Design Calculations Page 109 of 109
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 20 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal
links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 960 mm
Provided spacing = 250 mm
file:///C:/Users/User/AppData/Local/Temp/tmp17BA.tmp 30/03/2021