You are on page 1of 2

1.

Where signs are used to indicate fire extinguisher location, the signs shall comply with
the following
(1) They shall be located in close proximity to the extinguisher.
(2) They shall be visible from the normal path of travel.

3. option 1&2 (2. Nfpa 10)

2. Fire extinguishers having a gross weight not exceeding 40 lb (18.14 kg) shall be installed so
that the top of the fire extinguisher is not more than 5 ft (1.53 m) above the floor
a. nfpa10 (6.1.3.8.1)

3. The weight of the system being braced (Wp) shall be taken as ------- times the weight of the
water-filled piping. (See

Ans. 1.15 (9.3.5.9.1.)

4. Schematic for 2b+g+12 apartment. Mark 20 points.

5. out of this, which one is excluded in hydrostatic test

a. Foam bladder tank

b.Valves

C. Foam concentrate pipes

6. A break tank shall be sized for a minimum duration of ------------ rated capacity.
a. 15 minutes with the fire pump operating at 150 percent of (Nfpa 22, 6. 4.1.5)

7. The horsepower capability of the engine, when equipped for fire pump service, shall have a
4-hour minimum horsepower rating not less than 10 percent greater than the listed
horsepower on the engine nameplate.
(11.2.2.2*)

9. The sprinklers shall be kept in a cabinet located where the temperature in which they are
subjected will at no time exceed Ans. 100°F (38°C). (nfpa 25, 5.4.1.5.2)

10. -------------- listed sprinklers shall be used to replace existing sprinklers.


Ans. Only new ( nfpa25, 5.4.1.3,)

Diesel pump should be tested ----------------

Ans. weekly (NFPA 25)

11. Any source of water that is adequate --------------- to fill the tank in accordance with this
standard shall be permitted.
in quality, quantity, pressure, and reliability (nfpa22, 4.2.1.1)

12. listed --------------- should be connected with a fire brigade connection.

Ans. Check valve (nfpa 14)

13. --------------- is fires are fires in flammable liquids, combustible liquids, petroleum greases,
tars, oils, oil-based
paints, solvents, lacquers, alcohols, and flammable gases.

Ans. class b fire (nfpa 10)

14. colour of bulb for extra hazard

A. purple (nfpa13)

15. ---------- is Equipment, materials, or services included in a list published by an organization


that is acceptable to the authority having jurisdiction and concerned with evaluation of
products or services, that maintains periodic inspection of production of listed equipment or
materials or periodic evaluation of services, and whose listing states that either the equipment,
material, or service meets appropriate designated standards
or has been tested and found suitable for a specified purpose
a. Listed.

16. a tank room should be provided ----------------- for maintenance and etc..

Ans. 1 m distance in all the directions

b. a space for 1 man to move around

c. a space to keep the tool kit.

17. The ----------- shall also serve as the water-level indicator by bearing an easily observed
raised arrow.
Ans. nameplate (nfpa 22, 7.1.8.3.1)