You are on page 1of 28

CAST RESIN DRY TYPE

TRANSFORMERS
UP TO 4 MVA

www.alfanar.com
Contents
1. General Information ........................................................................................................................................................4
A. Standard ................................................................................................................................................................4
B. Quality...................................................................................................................................................................4
C. Climatic, environmental and fire behaviour classes..............................................................................................5
• Climatic classes.................................................................................................................................................5
• Environmental classes.......................................................................................................................................5
• Fire behaviour classes.......................................................................................................................................6
D. Cooling code and classes of insulations................................................................................................................6
E. Short circuit impedance.........................................................................................................................................7
F. Altitude..................................................................................................................................................................7

2. Manufacturing Process ..................................................................................................................................................8


Magnetic core.............................................................................................................................................................8
Windings....................................................................................................................................................................8
• Low voltage windings............................................................................................................................................7
• High voltage windings...........................................................................................................................................7
3. Application ......................................................................................................................................................................9
4. Product’s breakdown......................................................................................................................................................12
5. Product’s features...........................................................................................................................................................13
6. Technical Information .....................................................................................................................................................14
alfanar Eco-design cast resin transformers..............................................................................................................14
alfanar Cast Resin Transformers family according to KSA standard (Aluminium foil).........................................15
alfanar Cast Resin Transformers family according to KSA standard (Copper foil)...............................................16
alfanar Cast Resin Transformers family according to International Standards (Copper foil).................................17
alfanar Cast Resin Transformers family according to International Standards (Aluminium foil)..........................18

7. Accessories .....................................................................................................................................................................19
Standard accessories...................................................................................................................................................19
Additional accessories................................................................................................................................................20
1. Enclosures.........................................................................................................................................................20
2. HV & LV connections.......................................................................................................................................21
3. Temperature protective relay............................................................................................................................22
4. Ventilation fans.................................................................................................................................................23
5. Surge arrestors...................................................................................................................................................23
6. Antivibration Pads Kit ......................................................................................................................................23

8. Tests ................................................................................................................................................................................24
Routine Tests..............................................................................................................................................................24
Type Tests..................................................................................................................................................................24
Special Test................................................................................................................................................................24

Notes.....................................................................................................................................................................................25
1 - General Information
A. Standard
alfanar Dry Type Transformers are manufactured according to:
• IEC 60076-11 – Power transformers – Part. 11: Dry – type
• IEC 60076-12 – Power transformers – Part. 12: Loading guide for dry-type power transformers
• IEC 60076-1 – Power transformers – Part. 1: General
• IEC 60076-2 – Power transformers – Part. 2: Temperature rise
• IEC 60076-3 – Power transformers – Part. 3: Insulation levels, dielectric test and external
clearances in air
• IEC 60076-5 – Power transformers – Part. 5: Ability to withstand short circuit
• IEC 60076-10 – Power transformers – Part. 10: Determination of sound levels
• IEC 60085 – Thermal evaluations and designation
• IEC 60270 – High-voltage techniques – Partial discharge measurement
• IEC 60529 – Degree of protection provided by enclosures (IP code)

B. Quality
alfanar Electrical Systems is certified by renowned international evaluation companies for their
Quality Management according to ISO 9001:2015.

alfanar is also certified for Environmental Management according to ISO 14001:2015.

4
C. Climatic, environmental and fire behaviour classes
alfanar products are designed to withstand the toughest environmental conditions and offer an extremely high level
of reliability even under the toughest conditions.

According to the highest environmental, climate, and fire specifications, alfanar Dry Type Transformers are
manufactured according to international standard IEC 60076-11 Edition 2.0 2018-08.

• Climatic classes

Several climatic classes are defined in IEC 60076-11


such as:

- Class C1: The transformer is suitable for operation at


ambient temperatures above -5 °C but may be exposed
during transport and storage to ambient temperatures
down to -25 °C

- Class C2: The transformer is suitable for operation,


transport and storage at ambient temperatures down to
-25 °C

- Class C3: The transformer is suitable for transport and


storage at -40 °C and operation at -25 °C

- Class C4: The transformer is suitable for transport and


storage at -50 °C and operation at -40 °C

- Class C5: The transformer is suitable for transport and


storage at -60 °C and operation at -50 °C

• Environmental classes

Environmental conditions for dry-type transformers are


identified in terms of humidity, condensation, pollution
and ambient temperature

- Class E0: No condensation occurs on the transformers


and pollution is negligible. This is commonly achieved
in a clean, dry indoor installation.

- Class E1: Occasional condensation can occur on the


transformer (for example, when the transformer is
de-energized). Limited pollution is possible.

- Class E2: Frequent condensation or light pollution or


combination of both

- Class E3: Frequent condensation or medium pollution


or combination of both

- Class E4: Frequent condensation or heavy pollution or


combination of both
1 - General Information
• Fire behaviour classes
Two fire behaviour classes are defined:

- Class F0: There is no special fire risk to consider. Except


for the characteristics inherent in the design of the trans
former, no special measures are taken to limit flamma
bility. Nevertheless, the emission of toxic substances and
opaque smoke shall be minimized.

- Class F1: Transformers subject to a fire hazard. Restricted


flammability is required. The emission of toxic substances
and opaque smokes shall be minimised.

D. Cooling code and classes of insulation


For dry type transformers there are two types of cooling
methods:
• Air natural (AN)
• Air forced (AF)

The main features of insulation are to provide dielectric


strength and to be able to withstand certain thermal limits.

The insulation class could be F or H.


- 180°C for Class H insulation
- 155°C for Class F insulation

6
E. Short circuit impedance
The short circuit impedance is the transformer’s impedance, usually between 4% and 6% for distribution transformers
and higher than 7% for power transformers. The short circuit impedance is the percentage of the primary rated
voltage that must be applied at the transformer primary winding when the secondary winding is shorted in order
to have the rated currents in the primary and secondary windings. If the short circuit impedance increases, it will
result in an unnecessary voltage drop across the power transformer and will limit its ability to deliver power to the
secondary-connected equipment.

• Transformers working in parallel should have identical short circuit impedance.

F. Altitude
The transformers are suitable for operation at altitudes of up to 1000m above sea level. Site altitudes above
1000m require the use of special designs and should be mentioned in the order.
2 - Manufacturing Process
Magnetic core
The purpose of the core is to provide a low reluctance path for the magnetic flux linking primary and secondary windings.
The magnetic circuit in a transformer is made of steel lamination sheets whose basic components are iron and approximately
3% silicon as an alloy element.

alfanar uses high-quality, low-hysteresis Cold-Rolled Grain-Oriented Steel Sheet (CRGO) transformer laminations
complying with the IEC 60404-8-7 standard. Both sides of the lamination have a thin inorganic, oil-resistant and rustproof
insulation coating of at least 100Ω.mm2 insulation resistivity.

As most of the losses in transformer cores arise from the yoke-limb joints, alfanar transformers have the ends of the
yokes and limbs mitered and stacked together by a simple overlapping arrangement (step-lapped joints). This arrangement
allows for the gradual and smooth transfer of flux through the joints ultimately lowering the corner losses. The advantages
for using the step-lapped technology are the reduction in no-load current, no-load losses and sound level.

For precise core cutting and step-lap core cutting alfanar uses sophisticated LAE’s model TE40 and TE60 core cutting
machines, respectively. During the tilting and unloading phase of production, our highly-skilled operators precisely and
firmly assemble the cores using special assembly benches by perfectly aligning the cores to the right positioning references.

Windings
The windings consist of current-carrying conductors
wound over the sections of cores. alfanar transformers
are made of high-conductivity windings made of electro-
lytic copper or aluminium conductors. In a transformer,
the right type of windings is particularly significant for
space saving and minimization of load losses.
• Low voltage windings
Low voltage windings are made of a foil copper or aluminium
sheet and insulated with multiple layers of insulation materials.
The windings are multi-layered helical type, a characteristic
that provides the highest mechanical stability during short circuit
stress.The greatest advantages of using a foil copper/aluminium
conductor are the “No Effect” of axial short circuit compressing
forces and to reduce losses resulting from the skin effect.
• High voltage windings
Depending on the rated current of a transformer, the high
voltage windings are either made of enameled round copper/
aluminium wires or strips. The windings are multi-layer helical/
desk type and the inter-layer insulation is made of high quality
insulation materials class F or H as per customer requirements.

8
3 - Applications
Application
alfanar Dry transformers are widely used in the following applications:

A. High rise buildings

B. Hospitals
3 - Applications
C. Hotels

D. Underground

10
E. Factories

F. Shopping center
4 - Product Breakdown

9 1 1 3 1 5 3 9

13

2
4

6 11 14

14

7
10

10
8 8

ID Number DESCRIPTION 13 1 3 1 5

2
1 Low voltage terminals
1
2 Low voltage neutral terminal
9
3 Lifting eyebolt lugs
4 High voltage terminals 12 4

5 Rating plate
6
6 Off load de-energized tap changer
7 Earthling terminal 14

8 Dual direction scrolls wheels


11
9 PT100 connection terminal box
10 Pulling hole at bottom side 8

11 High voltage cast coil winding


12 Low voltage winding
8
Low voltage winding terminal 7
13
supports
14 High voltage delta connection pipes 10

12
5 - Product features

alfanar offers an optimized design for full range of Cast Rein Transformers made in KSA.
 Smart interface for LV and HV connection terminals.
 Magnetic core manufactured with high performance grain-oriented steel.
 Low voltage winding made by foil conductor (Al or Cu) full insulated with pre-impregnated insulation material (Pre-preg).
 High voltage winding made with a series of tape conductor (Al or Cu) sections vacuum cast processed by epoxy
resin properly filled to obtain: extensive maintenance-free, moistureproof for any environment, pollution resistant,
fire resistant and self-extinguishing.
 High voltage delta connection tubes with HV terminals at its terminations.
 Lifting eyes lugs made by standard certified and approved components.
 Basement profiles equipped with by-directional convertible scrolling wheels.
 Pulling hole on basement profiles for an easy movement to reach operation site.
 Clamping and belting hole on top core profiles ensure the easy and safe transport to the installation site on a truck deck.
 High voltage tapping selector for ±2x2,5% (other range available at request) easily operable at de-energized condition,
located on HV terminal side to adapt the primary voltage to the network value AC connection point.
 Temperature monitoring sensors PT 100 (other alternative available upon request) located on each LV winding top
side in strict contact with hot spot winding part.
 Steel parts are painted with a high temperature coating RAL 5012, (other colors and galvanized coating are available
upon request), make them suitable for highly aggressive environments.
 Smart mechanical structure made with simple bolt assembled parts, for an easy interface with a long list of available
accessories.
6 - Technical Information
alfanar Eco-design Cast Resin Transformers

European ECODESIGN According to EN 50588-1

Weight
Rating Pcc (W) Vcc% P0 (W) Lp(A) Dim. IP 00 LxDxH
(kg)

100 kVA 2050 W 6% 280 W 51 dB 750 kg 1240 x 600 x 1000

160 kVA 2900 W 6% 400 W 54 dB 850 kg 1260 x 600 x 1100

250 kVA 3800 W 6% 520 W 57 dB 1200 kg 1350 x 600 x 1150

400 kVA 5500 W 6% 750 W 60 dB 1400 kg 1400 x 750 x 1300

500 kVA 6400 W 6% 900 W 61 dB 1550 kg 1450 x 750 x 1350

630 kVA 7600 W 6% 1100 W 62 dB 1850 kg 1500 x 750 x 1500

800 kVA 8000 W 6% 1300 W 64 dB 2200 kg 1600 x 800 x 1550

1000 kVA 9000 W 6% 1550 W 65 dB 2550 kg 1650 x 800 x 1600

1250 kVA 11000 W 6% 1800 W 67 dB 3050 kg 1700 x 1000 x 1700

1600 kVA 13000 W 6% 2200 W 68 dB 3600 kg 1750 x 1000 x 2200

2000 kVA 16000 W 6% 2600 W 69 dB 4800 kg 1850 x 1310 x 2250

2500 kVA 19000 W 6% 3100 W 70 dB 5400 kg 1950 x 1310 x 2300

3150 kVA 22000 W 6% 3800 W 72 dB 6800 kg 2100 x1310 x 2380

All the above cast resin transformers fulfill the following common technical data:

Distance measures in : Millimetres


11±2x2,5% / 0,4kV
Voltage ratio :
or 10±2x2,5% / 0,4kV;
Insulation levels
12 - 28 - 75 / 1,1 - 3kV
Primary / Secondary :
H

Partial discharge level : < 10 pC

Insulation thermal class : F / F - 100 / 100 K

Vector group : Dyn11

Frequency : 50 Hz

Available environmental classes : E2 / E3 D

Available climatic classes : C1 / C2

Fire classification: F1

Conductor material: Aluminium foil


L

NOTE: Power ratings higher than 3150 kVA, and or different voltage ratio, or impedance value, as well as particular design for
special dedicate application will be available under request and submission of technical specification.

14
alfanar Cast Resin Transformers family according to KSA standard (Aluminium foil)

Pn Po Pcc120° LpA Weight Length x Depth x Wheel


Io % Vcc%
(kVA) (W) (W) (dB) (kg) Height dist.

100 460 2,2 2200 6 49 560 1110x600x1150 520

160 650 1,8 2900 6 51 800 1220x600x1200 520

200 720 1,7 3500 6 52 880 1250x600x1250 520

250 850 1,6 3800 6 53 1000 1300x600x1280 520

315 1000 1,4 4500 6 54 1100 1320x750x1350 670

400 1150 1,2 5500 6 55 1350 1340x750x1450 670

500 1350 1,0 6400 6 56 1500 1420x750x1480 670

630 1600 0,9 7400 6 57 1700 1450x850x1580 670

750 1800 0,8 8200 6 59 1950 1480x850x1680 670

800 1900 0,8 8800 6 60 2100 1500x850x1700 670

1000 2300 0,7 10000 6 61 2450 1540x1000x1870 820

1250 2600 0,6 12000 6 63 2900 1600x1000x2050 820

1500 3000 0,6 14500 6 64 3400 1720x1000x2100 820

1600 3100 0,6 15500 6 65 3500 1720x1000x2180 820

2000 4000 0,5 16000 6 67 4200 1800x1300x2300 1070

2500 4700 0,4 18000 6 68 4900 2000x1300x2280 1070

3150 5500 0,3 23500 8 69 5850 2150x1300x2340 1070

All the above cast resin transformers fulfill the following common technical data:

Distance measures in : Millimetres

Voltage ratio : 13,8±2x2,5% / 0,4kV;


Insulation levels
17,5 - 38 - 95 / 1,1 - 3kV
Primary / Secondary :
H

Partial discharge level : < 10 pC

Insulation thermal class : F / F - 100 / 100 K

Vector group : Dyn11

Frequency : 60 Hz

Available environmental classes : E2 / E3 D


Available climatic classes : C1 / C2

Fire classification : F1

Conductor material : Aluminium foil


L

NOTE: Power ratings higher than 3150 kVA, and or different voltage ratio, or impedance value, as well as particular design for
special dedicate application will be available under request and submission of technical specification.
6 - Technical Information
alfanar Cast Resin Transformers family according to KSA standard (Copper foil)

Pn Po Pcc120° LpA Weight Length x Depth x Wheel


Io % Vcc%
(kVA) (W) (W) (dB) (kg) Height dist.

100 440 2,2 2200 4 49 560 960x650x1150 520

160 580 1,8 2600 4 50 800 1060x650x1150 520

200 720 1,7 3000 5 52 900 1200x650x1220 520

250 850 1,6 3400 5 53 1100 1240x650x1250 520

315 980 1,4 4100 6 54 1200 1260x750x1260 670

400 1150 1,2 5400 6 55 1350 1400x750x1520 670

500 1350 1,0 6700 6 56 1550 1500x750x1580 670

630 1650 0,9 7800 6 57 1700 1500x850x1680 670

750 1800 0,8 7500 6 59 2200 1460x850x1540 670

800 1900 0,8 7800 6 60 2350 1470x850x1550 670

1000 2300 0,7 9600 6 61 2750 1530x1000x1740 820

1250 2600 0,6 11000 6 63 3000 1580x1000x1870 820

1500 3100 0,6 14900 6 64 3750 1650x1000x1940 820

1600 3300 0,6 15200 6 65 3850 1660x1000x1950 820

2000 4000 0,5 16000 6 67 4800 1830x1300x2050 1070

2500 4800 0,4 21000 6 68 5750 1860x1300x2260 1070

3150 5400 0,3 25000 8 69 6800 1980x1300x2280 1070

All the above cast resin transformers fulfill the following common technical data:

Distance measures in : Millimetres

Voltage ratio : 13,8±2x2,5% / 0,4kV;


Insulation levels
17,5 - 38 - 95 / 1,1 - 3kV
Primary / Secondary :
H

Partial discharge level : < 10 pC

Insulation thermal class : F / F - 100 / 100 K

Vector group : Dyn11

Frequency : 60 Hz

Available environmental classes : E2 / E3 D


Available climatic classes : C1

Fire classification : F1

Conductor material : Copper foil


L
NOTE: Power ratings higher than 3150 kVA, and or different voltage ratio, or impedance value, as well as particular design for
special dedicate application will be available under request and submission of technical specification.

16
alfanar Cast Resin Transformers family according to International Standards (Copper foil)

Pn Po Pcc120° LpA Weight Length x Depth x Wheel


Io % Vcc%
(kVA) (W) (W) (dB) (kg) Height dist.

100 400 2,2 2100 4 48 490 960x600x1150 520

160 520 1,8 2650 6 49 680 1140x600x1240 520

200 610 1,7 2950 6 50 800 1140x600x1320 520

250 700 1,6 3650 6 52 900 1200x600x1340 520

315 800 1,5 4250 6 54 1020 1200x750x1440 670

400 980 1,2 5000 6 55 1250 1290x750x1510 670

500 1100 1,1 6000 6 56 1400 1320x750x1580 670

630 1390 0,9 7100 6 57 1700 1410x850x1680 670

750 1550 0,8 7800 6 58 1800 1440x850x1700 670

800 1650 0,8 8500 6 58 1900 1440x850x1800 670

1000 1900 0,7 10000 6 61 2400 1530x1000x1870 820

1250 2300 0,6 11600 6 63 2700 1530x1000x2070 820

1500 2500 0,6 13500 6 64 3100 1620x1000x2090 820

1600 2700 0,6 14000 6 65 3300 1650x1000x2200 820

2000 3400 0,5 17000 6 67 4000 1800x1300x2230 1070

2500 4000 0,4 20000 6 68 4800 2000x1300x2250 1070

3150 4600 0,3 25100 8 69 5800 2100x1300x2270 1070

All the above cast resin transformers fulfill the following common technical data:

Distance measures in : Millimetres


11±2x2,5% / 0,4kV or
Voltage ratio :
10±2x2,5% / 0,4kV;
Insulation levels
12 - 35 - 75 / 1,1 - 3kV
Primary / Secondary :
H

Partial discharge level : < 10 pC

Insulation thermal class : F / F - 100 / 100 K

Vector group : Dyn11

Frequency : 50 Hz

Available environmental classes : E2 / E3 D


Available climatic classes : C1 / C2

Fire classification : F1

Conductor material : Copper foil


L
NOTE: Power ratings higher than 3150 kVA, and or different voltage ratio, or impedance value, as well as particular design for
special dedicate application will be available under request and submission of technical specification.
6 - Technical Information
alfanar Cast Resin Transformers family according to International Standards (Aluminium foil)

Pn Po Pcc120° LpA Weight Length x Depth x Wheel


Io % Vcc%
(kVA) (W) (W) (dB) (kg) Height dist.

315 1400 1,6 4600 6 61 1750 1650x750x1650 670

400 1650 1,4 5400 6 62 1900 1700x750x1700 670

500 1900 1,0 6200 6 63 2100 1750x750x1720 670

630 2200 0,9 8000 6 64 2450 1850x850x1780 670

750 2600 0,8 9400 6 65 2700 1840x850x1860 670

800 2700 0,8 9600 6 65 2750 1860x850x1890 670

1000 2900 0,7 11000 6 66 3250 1920x1000x2040 820

1250 3200 0,6 13000 6 67 3700 1950x1000x2230 820

1500 3600 0,6 14500 6 67 4000 1950x1000x2250 820

1600 3800 0,6 15000 6 68 4200 1980x1000x2350 820

2000 4500 0,5 17500 6 69 5000 2070x1300x2390 1070

2500 5800 0,4 19500 6 70 6300 2260x1300x2450 1070

3150 6600 0,3 25000 8 72 8000 2300x1300x2450 1070

All the above Cast resin Transformers fulfilling following common technical data:

Distance measures in : Millimetres

Voltage ratio : 13,8±2x2,5% / 0,4kV;


Insulation levels
17,5 - 38 - 95 / 1,1 - 3kV
Primary / Secondary :
H

Partial discharge level : < 10 pC

Insulation thermal class : F / F - 100 / 100 K

Vector group : Dyn11

Frequency : 60 Hz

Available environmental classes : E2 / E3


D
Available climatic classes : C1

Fire classification : F1

Conductor material : Aluminium foil

NOTE: Power ratings higher than 3150 kVA, and or different voltage ratio, or impedance value, as well as particular design for
special dedicate application will be available under request and submission of technical specification.

18
7 - Accessories
For each one of the CRT sizes included in this catalogue, the following list of accessories are available:

Standard accessories
Standard accessories included in all the Cast Resin Transformers:

3 x PT100 connection box:


PT 100 linear resistance are used as sensors for monitoring and controlling temperature
of the transformers. This system can perform temperature setting, highest temperature
recording, signal for alarm and trip, and start the fan on and off automatically or manually.

4 x Lifting Eyes 2 x Grounding Terminal 3+1 x LV Terminals

4 x Scrolling Wheels 3 x HV Terminals 4 x Pulling Holes

1 x Rating Plate 3 x Off load HV Tapping 4 x Truck Belting Holes


Selector
7 - Accessories
Additional accessories
Available accessories for all cast resin transformers models:

1. Enclosures
There are different sizes of protective enclosures that can cover all the CRT rating range, suitable for inside installation
with the available protective degree IP 21, IP23, IP 31 and IP 33.
The enclosures guarantee enough natural ventilation for CRT natural cooling, and protect the CRT from direct sunlight
in outdoor applications.

Enclosures Dimensions

L D

Lenght Deep Height Weight


kVA
(mm) (mm) (mm) kg
100
160 1600 900 1510 250
200
250
315 1700 950 1710 260
400
500
630 1950 1050 1910 300
750
1000
2050 1100 2210 330
1250
1500
2300 2510 380
2000
2500
2500 1310 2710 400
3150

* This is Approximated dimensions

Note: Special enclosures for particular application will be offered according to customer’s requirements and it
can be equipped with extraction fans, filters, special protection, etc…

20
2. HV & LV Connections
Standared Connection:
Direct Cable Connection

LV Connection

Direct Cable Connection

HV Connection

Special connection:

LV extension busbar HV terminal bushing

Note: Cable box may be used also.


7 - Accessories
3. Temperature Protection and Control Relay
The scope of this relay is to measure the LV winding hot spot temperature through to the installed PT100 on each LV
phase.

An option, if required or already installed, the relay will also measure the top yoke core temperature with separate
alarm and trip set point for this fourth sensor.

The ventilation fans protection and control kit supplies, protects, and controls the forced air ventilation kit in combination
with the temperature monitoring relay.

22
4. Ventilation Fans
The ventilation fans kit is comprised of two ventilation bars
where each one has three radial ventilators with adjustable
position and adjustable supporting stirrup able to be directly
connected on the alfanar CRT predisposition. There is a
different rate of fan kit available that is able to confer with
the cast resin transformer with an overload capability of 25
to 40%, according to customer requirements.

CRT in AF shall be operated only for limited time and gener-


ally in case of emergency.

 CRT on load losses in AF increasing of:

• 156 % when operated at 125% overload


• 169 % when operated at 130% overload
• 200 % when operated at 140% overload

5. Surge Arrestors Kit


The surge arrestors kit is comprised of three surge arrestors
selected according to the CRT insulation level to be directly
connected on the alfanar CRT terminal predisposition.

6. Antivibration Pads Kit


The antivibration pads kit is comprised of four rubber dumpers
selected according to the CRT size and located below to the
alfanar CRT scroll wheels.
8 - Tests
alfanar CRT had been tested according to the latest IEC standards
Routine tests
1 - Measurement of winding resistance according to IEC 60076-1
2 - Measurement of voltage ratio and check of phase displacement according to IEC 60076-1
3 - Measurement of short circuit impedance and load losses according to IEC 60076-1
4 - Measurement of no load-loss and current according to IEC 60076-1
5 - Separate-source AC withstand test according to IEC 60076-3
6 - Induced AC withstand voltage test according to IEC 60076-3
7 - Partial discharges measurement according to IEC 60076-11, IEC 60270 and Annex A of IEC
8 - Measurement of insulation resistance according to IEC 60076-1

Type Tests
1 - Temperature rise test according to IEC 60076-11, and IEC 60076-2
2 - Lightning impulse test according to IEC 60076-11, and IEC 60076-3

Special Tests
1 - Measurement of sound level according to IEC 60076-11, and IEC 60076-10
2 - Short-circuit test according to IEC 60076-11, and IEC 60076-5
3 - Environmental test according to IEC 60076-11, for E2, and IEC 60076- 16
4 - Climatic test according to IEC 60076-11
5 - Fire behaviour test according to IEC 60076-11
6 - Measurement of zero-sequence impedance according to IEC 60076-1

24
Notes
Notes

26
For catalogue soft copy scan QR code MKT_115719_Dry transformer _July19_01

www.alfanar.com