Professional Documents
Culture Documents
Industries
SHORT CIRCUIT (FAULT) ANALYSIS
FAULT PROOF SYSTEM
➢ Not practical
➢ Neither economical
➢ Faults or failures occur in any power system
• Lightning surges
• Switching surges
• Temporary and
dynamic over
voltages (TOV)
CAUSES OF FAULTS
Mechanical
• Wind
• Contamination
• Trees falling the
lines
• Conductor/
connector failures
• Broken/ rotten
wood poles
CAUSES OF FAULTS
Man or Animal Made
• Over-current
• Over-voltage
According to
Location
• Inter-phase Fault
• Inter-circuit Fault
• Cross Country
Fault
Consequences of Power System Faults
Electro-dynamic forces, resulting
in
➢ Deformation of the bus-
bars
➢ Disconnection of cables
➢ Excessive temperature with
the risk of damage to
insulation
➢ Electromagnetic
interference with
conductors in the vicinity
(disturbance to
communication lines,
personal danger)
➢ Mechanical and thermal
stress, resulting in damage
of equipment, personal
danger)
Consequences of Power System Faults
➢ Voltage dips during the time
required to clear the fault,
ranging from a few
milliseconds to a few hundred
milliseconds
➢ Shutdown of a part of the
network, the extent of that
part depending on the design
of the network and the
discrimination levels offered
by the protection devices;
➢ Dynamic instability and/or the
loss machine synchronization;
disturbances in
control/monitoring circuits,
etc.
Application of Fault Analysis
1. The determination of the required mechanical strength of
electrical equipment to withstand the stresses brought
about by the flow of high short circuit currents.
2. The selection of circuit breakers and switch ratings
3. The selection of protective relay and fuse ratings
4. The setting and coordination of protective devices
5. The selection of surge arrester and insulation ratings of
electrical equipment
6. The determination of fault impedances for use in stability
studies.
Application of Fault Analysis
7. The calculation of voltage
sags resulting from short
circuits
8. The sizing of series
reactors to limit the short
circuit currents to a
desired value
9. To determine the short
circuit capability of series
capacitors used in series
compensation of long
transmission lines
10.To determine the size of
grounding transformers,
resistances, or reactors
Factors to be Considered when
Performing Short Circuit Studies
Factors Affecting Fault
➢ Circuit configuration
➢ Grounding system design/methods
➢ Voltage class
➢ Relative insulation levels to ground and
between phases
➢ System characteristics
Most Common Power System Studies
• Load Flow Studies
• Short Circuit Studies
• Stability Studies
• Insulation
Coordination
• System Protection
Coordination
• Electromagnetic
Transients
• Harmonic Analysis
• Motor-starting
Studies
• Cable Ampacity
Studies
• Ground Mat Studies
• Arc Flash Analysis
Types of Currents
Various Types
of Currents
• Line-to-line faults
• Three-phase faults
Series Faults
• One-line open faults
Synchronous Generator
Induction Motor
Synchronous Motor
Sources of Short Circuit Current
• Synchronous Generators – when
a short circuit occurs
downstream of a synchronous
generator, it may continue to
produce output voltage and
current.
• Synchronous Motors – delivers
short circuit current into the
fault until the motor completely
stops.
• Induction Motors – short circuit
current decays very quickly.
• Supply Transformers –
Transformer Impedances will
also limit the amount of short
circuit current from the utility
generators.
Symmetrical and Asymmetrical Fault
Currents
Solution:
Example 2
Using the base quantities in example
1, what are the actual physical values of
1.1 per unit voltage and 50 per unit power?
Solution:
S = 50 pu x 100MVA = 5,000MVA
Example 3
A three-phase 125 MVA 13.2kV generator
has a subtransient reactance of 7%. Using
100MVA and 13.8kV base values, calculate the
new percent reactance of the generator
Solution:
Z[old] = 7%
MVA[old] = 125 MVA
kV[old] = 13.2kV
MVA[new] = 1000MVA
kV[new] = 13.8kV
Symmetrical Components
Charles Legeyt Fortescue discussed
in his 114-page paper “Method of
Symmetrical Coordinates Applied to the
Solution of Polyphase Networks”, which
was published in 1918 by the then AIEE
(now IEEE), that any set of N unbalanced
vectors can be represented by N sets of
balanced vectors.
• Negative-sequence
components consisting of three
phasors equal in magnitude,
displaced from each other by
120 in phase and having a
phase sequence opposite that
of the original phasors.
Symmetrical Components
• Zero sequence components consisting of
three phasors equal in magnitude and with
zero phase displacement between each
other.
Vc1 Va1
Va2
Vb2 = aVa2 Va0 = Vb0 = Vc0
Vc2 = a2Va2
Vb1 = a2Va1
Vb2
Vc1 = aVa1
• Negative-sequence
impedance (Z2)
• Zero-sequence
impedance (Z0)
Positive-and Negative-Sequence
Reactance of Transformer
• The positive – and
negative-sequence
reactances of
transformers are equal,
regardless of the
construction of the
transformer.
Impedance Values of Three-Phase
Medium Voltage Transformers
VOLTAGE RATING kVA RATING % IMPEDANCE
Q P Q
P
ZPQ
P Q P Q
ZPQ
P Q P Q
ZPQ
Transformers (Zero-Sequence
Circuit Model)
(Representation from Analysis of Faulted Power System by P.M.
Anderson)
Transformer Connection Zero-Sequence Circuit Equivalent
P Q P Q
ZPQ
P Q P Q
ZPQ
P Q P Q
ZPQ
Transformers (Zero-Sequence Circuit
Model)
(Representation from Analysis of Faulted Power System by P.M.
Anderson) Zero-Sequence Circuit Equivalent
ZP ZQ
Transformer Connection P Q
P ZR
Q R
R
ZQ ZP
P Q
P Q
ZR
R
R
ZP ZQ
P Q
P Q
ZR
R
R
Three phase fault
If Zf = 0
Single line-to-ground fault
If Zf = 0 and Zg = 0,
Line-to-line fault:
If Zf = 0,
Double line-to-ground fault
Assumptions Made to Simplify Short
Circuit Calculations
1. Pre-fault load currents are neglected, otherwise,
If = If(no load) + Iload, where Iload is determined from load
flow studies.
2. Pre-fault voltages are assumed equal to 1.0 per unit
3. Resistances are neglected (only for 115kV & up)
4. Mutual impedances, when not appreciable are neglected.
5. Off-nominal transformer taps are equal to 1.0 per unit
6. Positive- and negative-sequence impedances are equal.
7. All line capacitances are ignored.
8. All non-motor shunt impedances are ignored; motor loads
may be treated the same way as generators, i.e., voltage
sources.
Assumptions Made to Simplify Short
Circuit Calculations
9. The voltage magnitude and phase angle of generators
and in feeds are all set to the same value.
10.All tap changing transformers are in middle position.
11.Motors that are 50 hp and above are included in the
model
12.Studies have shown that the shunt elements and loads
have little influence on the short circuit currents (0.5%
to 4% and may compensate each other.
13.However, disregarding the actual generator pole
voltages and the actual positions of tap changing
transformers may sometimes lead to errors of up to
30%
Outline Procedures for Short Circuit
Calculations
1. Setup the network impedances expressed in per unit
on a common MVA base in the form of a single-line
diagram.
2. Determine the single equivalent (Thevenin’s)
impedance of each sequence network as seen from
the fault point.
3. Determine the distribution factor giving the current
in the individual branches for unit total sequence
current.
4. Interconnect the three sequence networks for the
type of fault under consideration and calculate the
sequence currents at the fault point.
Outline Procedures for Short Circuit
Calculations
6. Synthesis the phase currents from the
sequence currents.
7. Determine the sequence voltages throughout
the different sequence network from the
sequence current distribution and branch
impedances.
8. Synthesize the phase voltages from the
sequence voltages components.
9. Convert the per unit currents and voltages to
actual physical units.
Example Calculation
Assumed Common Power Base
Used: 2.5 MVA as my power base
400V as my voltage base
2.5 MVAB
IB =
3 400VB
IB = 3,608.44 Amperes
IA = IB x Ipu
IA = 3∅ symmetrical Fault
Per Unit Conversion
2.5 MVAB
Zu = tan−1 12 = 0.00167∠85.24°pu
1,500 MBAA
2.5 𝑀𝑉𝐴𝐵
𝑍𝑇 = 0.05 𝑡𝑎𝑛−1 7 = 0.05∠81.87°𝑝𝑢
2.5 𝑀𝑉𝐴𝐴
0.048Ω
ZC1 = 0.029 + j = 0.056∠58.86 → ohmic value
305m
Assumed Common Power Base (cont.)
Used: 2.5 MVA as my power base
400V as my voltage base
2
12 2.5 MVAB 380V
ZM1 = tan−1 8 = 0.271∠82.87°pu
100 1000 kVA 400
2
10 2.5 MVAB 380V
ZM2 = tan−1 8 = 0.301∠82.87°pu
100 750 kVA 400
Impedance Diagram Based On Fault Point 1
Determining Fault Current at Fault point 1
IA = IB x Ipu
Vpu
Ipu =
ZTpu
1
Ipu =
0.0446
Ipu = 22.42
∴ 𝐼𝐴 = 𝐼𝐹3∅𝑠𝑦𝑚 = 3,608.44 (22.42)
= 80,901.22 𝑎𝑚𝑝𝑒𝑟𝑒𝑠
𝑋 0.0038
= = 0.168
𝑅 0.0226
Asymmetrical Peak Short Circuit
𝑥
− ∕3
𝜏 = 0.49 − 0.1𝑒 𝑅
𝜏 = 0.49 − 0.1𝑒
𝜏 = 0.3954
X
−2πt∕
MF = 2 1 + e R
𝑀𝐹 = 1.414
∴ IFasypeak = MF x IF3∅sym
= 1.414 x 80,901.22
= 114,394.32 Amperes
Asymmetrical RMS Short Circuit
𝑋
−2𝜋∕𝑅
𝑀𝐹𝑎𝑠𝑦𝑚 = 1 + 2𝑒
= 1 + 2𝑒 −2𝜋∕0.168
= 1
=1
𝐼𝐴𝑆𝑌𝑀𝑅𝑀𝑆 = 1 𝑥 80,901.22
= 80,901.22
Impedance Diagram @ Fault Point 2
ZTpu = Zu + ZT + ZC1 (ZM2 + ZC3 ) + ZC2 ZM1
ZTpu = 0.0627∠54.71 0.312∠73.03 + 0.0717 0.271∠82.87
ZTpu = 0.0869 ∠ 39.95°pu
1
IA = IF3∅SYM = 3,608.44 x
0.0861
= 41,524.05 Amperes
Impedance Diagram @ Fault Point 3
1
IA = IF3∅SYM = 3,608.44 x
0.0769
= 46,923.79 Amperes
Single Line to Ground Fault
Impedance Network 7.5 MVA
• Positive Sequence ZUpu = tan−1 12
1000 MVA
• Negative Sequence
• Zero Sequence ZUpu = 0.075∠85.24°
𝑍1 = 0.0678∠57.51°
𝑍0 = 0.0612∠53.92°
3Vpu
Ipu =
Z1 + Z2 + Z0
3Vpu
=
0.197
= 15.23
IA = ISLG = IB x Ipu
= 3,608.44 15.23
= 54,956.54 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
Reactance Value for Induction Motors
Subtransient X” (pu)
NAMEPLATE H P
Figure 19 – X/R range for small solid rotor and salient pole
generators and synchronous motors at 60 Hz
ANSI Short-circuit Calculation Methods
Resistance of system and typical X/R ratio
Equivalent system X/R ratio (at 60 Hz) at typical
locations for quick approximations)