LINE-UP

OUTDOOR UNITS LINE-UP


Unit : HP / ○ 220V, 1Ø / ● 380V, 3Ø / CO � 220V, 1Ø

Features Appearance 3 4 5 6 8 10 12 14 16 18 20

� � � �

• Space saving
• Flexible design applications ○● ○● ○●
- Slim, light, and broad range (4 - 12 HP)
- Large number of connectable indoor units
(Up to 20 Units)
• For small / medium building

● ● ●

000 / 001
OUTDOOR
UNITS
300m 150m (175m)
TOTAL PIPING LENGTH Longest piping length
* ARUV series : 80-100m (Depends on model) from ODU ~ IDU (Equivalent)
- Air cooled VRF Heat pump & Heat Recovery * A R U V s e r ie s : 4 0 - 5 0 m
(Depends on model)

MULTI V S
- 9.2 ~ 33.6kW (Cooling capacity based)
- Both 1Ø, 220 ~ 240V, 50Hz and 3Ø, 380 ~ 415V, 50Hz
- Side discharge outdoor unit
- Includes the industry’s first single phase Heat Recovery system

TOTAL PIPING LENGTH

* ARUV series : 15m


between ODU ~ IDU
Height Difference
50m

* ARUV series : 7.5m


between IDU ~ IDU
Height Difference
15m
Only applies to MULTI V S with R410A refrigerant

How does it work?


Available in Heat Pump and
Heat Recovery Configurations

Energy savings Energy saving by heat


recovery unit

Compact yet
Combination of Cooling,
powerful VRF Heating and Hot Water Solution
For premium Reliability

residences and INDOOR UNIT

small offices
HYDRO KIT
MULTI V S
Heat Recovery
Convenience Heat Pump and Recovery are separated models.

002 / 003
OUTDOOR UNITS _ MULTI V S _ KEY FEATURES

ENERGY SAVINGS RELIABILITY

OUTDOOR
UNITS
EER / COP / Part Load Inverter Twin Rotary & Reliable Refrigerant Components
Cost savings with energy efficiency Inverter Scroll Compressor LG technology allows for superior performance and component durability
Heat Pump Adapted High Efficient Compressor according to Capacity
EER (Cooling) COP (Heating) Inverter Twin Rotary Inverter scroll compressor Refrigerant
❶ Cyclonic oil separator

MULTI V S
(12.1kW ~ 15.5kW) (22.4kW ~ 33.6kW) Refrigerant
+ Oil
Compressor Efficiency Comparison - H ig h ly re lia b le a n d e fficie n t o il se p a ra tio n b y
43% centrifuge using cyclonic methods Cyclone
16% Scroll Compressor

Efficiency
3.90 5.30 Rotary Compressor Centrifuges
3.35 3.71 - H ig h co lle ctio n e fficie n cy a s w e ll a s o u tsta n d in g
Oil
resistance to high temperature and pressure Oil Separator

Conventional MULTI V S HR Conventional MULTI V S HR


(MULTI V S H/P) (MULTI V S H/P)
Comparison Based on 15.5kW in cooling mode Comparison Based on 15.5kW in heating mode
12.1 19.6
Based on internal test data
28 kW
(Cooling capacity) ❷ Large Volume Accumulator
- Improved reliability by adopting the large volume accumulator
Heat Recovery Inverter Twin Rotary (38% volume up compared to conventional) Accumulator
Cooling Mode Heating Mode Concentrated Winding Motor - Prevents the liquid refrigerant entering the compressor suction
Oil path area is improved by over 50% by increasing the extra stator cavity. Due to
Cooling EER is 5% higher than Heating COP is 5% higher than - Maximize efficiency by optimal amount of refrigerant
conventional on average. conventional on average. this, caloric value of motor is reduced, improving the cooling function of stator coil.
- Protects compressor breakdown to increase product lifetime
Twin Rotary Rotor

5% 5% 4.39
Upper and lower part rotor offset imbalance in shaft rotor rotation. Vibration and
40% 20%
3.90 noise is reduced. Max torque load decreased by 45% compared to single rotor. ❸ BLDC Fan Motor

100
BLDC

Efficiency (%)
4.18
3.71 Motor
Surface Coating - The BLDC Fan motor is more efficient than a conventional

50
Surface coating of outstanding abrasion resistance property on vane and crank shaft. AC motor, offering an additional 40% energy savings AC
Conventional MULTI V S HR Conventional MULTI V S HR
at low speeds and 20% at high speeds Motor
(MULTI V S H/P) (MULTI V S H/P)
500 1,000
Comparison Based on 15.5kW in cooling mode Comparison Based on 15.5kW in heating mode Inverter scroll compressor Motor Speed (RPM)

Best-in-class Compressor Speed 150


❹ Double Sub-cool Interchanger

Operation Range (Hz)


Smart Load Control Applied - Rapid response capability
- Compact core design (Concentrated motor)
120

20 - Reliability is enhanced by minimizing pressure drop due to high


Enhanced comfort and up to 23% energy savings with - Down to 15Hz : Part load efficiency improvement 15 MULTI V S improved reliability with advanced technology :
efficiency spiral structure and 2 times larger size
Conventional
MULTI V load control 6 Bypass Valve - Oil separator Long pipe is possible (up to* 175m) and high elevation (up to* 50m)
Compressor reliability is maximized with 6 Bypass Valve - Accumulator Reduction of indoor refrigerant noise level
MULTI V S changes indoor discharge air temperature continuously - Prevent compressor damage due to excessively compressed refrigerant more - Sub-cooling * Based on equivalent pipe length Double Sub-cool Interchanger
according to load, to save energy. efficiently than 4 Bypass valve

SLC (Smart Load Control) operation Direct Oil Injection


Startup Operation Real Time Operation ... - E lim in a te su ctio n re frig e ra n t g a s h e a t lo ss th ro u g h d ire ct o il in je ctio n in to

Startup After 20 minutes


compression chamber (Efficiency increases)
- In cre a se d re lia b ility w ith re g u la te d o il su p p ly Smart Control Corrosion Resistance Proven by Certified Tests
Pressure control applied for smart, quick and precise LG Corrosion Resistance solution passed ISO 21207 accelerated
Startup Operation Scroll Profile
response to user's temperature request corrosion test conducted by an independent test organization and the
- The enhanced reliability by Increased reliability with regulated oil supply.
Basic Operation Smart Load Control - Efficiency increases by expanding 96% Bypass area and 17% improved volume ratio by non- result has been certified by prestigious global certification organization,
Indoor
Discharge Air
uniform scroll thickness Temperature + Pressure Control TUV.
Temperature
Senses and controls pressure directly
Certified protection
Power
Input
Optimal Heat Exchanger using pressure sensor for faster and more
exact response to load variation.
Maximize Efficiency according to different Heat Exchanger
Indoor air discharge temperature
Until 20 minutes after startup operation path by cooling and heating High Pressure Low Pressure
- Energy efficiency increased by 3-step Smart Load Control during startup phase Sensor Sensor
- Discharge air temperature adjusted according to outdoor and indoor temperature
Variable Heat Exchanger Circuit intelligently selects the optimal
- Comfort level in cooling / heating operations ensured Quick Operating Response Outlet Temp (°C)
path for both heating and cooling operations. With this smart path
Max.10% Energy saving selection technology, an average of 6% increase in the efficiency of
Desired temperature can be 27

reached up to 14% faster in 14%


both operations has been achieved. The paths number and circuit Quicker
Real Time Operation cooling mode with pressure Verification of corrosion resistance performance
velocity are adjusted to match temperatures and operation modes in 12
Basic Operation Smart Load Control
order to maximize efficiency instead of compromising efficiency for
control, allowing more accurate 14% - Declared by TUV Rheinland
- Test Method B of ISO21207
control of indoor environment for - Test condition : Salt contaminated condition
3°C 10°C each operation when the number and direction of paths are fixed 2min Time + seve re in d u stria l /
Refrigerant Refrigerant maximized comfort. Pressure + Temperature Control
independently of temperature operation mode. traffic environment (NO 2 / SO 2 )
20°C 20°C Temperature Control
Specifications may vary for each model.

3°C 3°C
Refrigerant Refrigerant Enhanced Coating Layers
Fixed heat
35°C 35°C exchanger circuit The black coating with enhanced epoxy resin is applied for strong
Cooling Heating
protection from various corrosive external conditions such as salt
Fixed refrigerant temperature Variable refrigerant temperature Efficiency performance Efficiency up due to Fin shape Corrosion Resistance Black Fin contamination and air pollution. Moreover, the hydrophilic film keeps
Efficiency
Strong Durability against high salinity and heavily polluted air water from accumulating on the heat exchanger’s fin, minimizing
Max. 13% Energy saving Improved heat exchanger efficiency of up to 28%
Conventional Wide Louver Plus Fin moisture buildup and eventually making it even more corrosion resistant.
How to set up : By dip switch in outdoor unit (Referred to Product Data Book) Factory default setting is Off. Heating Ocean Black Fin ensures continued operation of MULTI V S in highly
ESEER (European seasonal energy efficiency Ratio) conditions based on 15.5kW unit Cooling 100% Cooling 128% corrosive environments like salt concentration in coastal towns or severe air Hydrophilic film (Water flow)
- O u td o o r te m p e ra tu re co n d itio n :
The Hydrophilic coating minimizes moisture buildup on the fin .
EER 100% / 75% / 50% / 25% = 35°C (DB) / 30°C (DB) / 25°C (D B) / 20°C (DB) Cooling pollution in industrial cities keeps. This improvement in durability prolongs the
- Indoor temperature condition : 27°C (DB) / 19°C (WB) Heating 100% Heating 123%
product’s lifespan and lowers both the operational and maintenance costs. Acryl + Epoxy + Melamine resin (Corrosion resistant)
D u a l se n sin g (Te m p e ra tu re & h u m id ity) S m a r t L o a d C o n tro l is p o ssib le w ith R e m ote co n tro lle r
PTEMTB100 (White) /PREMTBB10 (Black)
Previous Design
(Fixed)
Number of
circuit
The Black coating provides strong protection from corrosion .
Aluminum fin

004 / 005
OUTDOOR UNITS _ MULTI V S _ KEY FEATURES OUTDOOR UNIT _ MULTI V S _ TECHNICAL DATA

IMPROVED USER CONVENIENCE Nomenclature [Unit : mm] Symbols

OUTDOOR
A 165 620 Piping Direction

UNITS
A Datum Iine
ARU N 100 L S S 0 Piping

Sufficient Piping Length Fan Technology and RPM Control Direction

390
360
Serial number

Increased piping length allows for flexible design External static pressure control for outdoor unit fan to adapt Model Type
S : Standard 4 holes for Anchor Bolts (M10)
and installation more flexibly to various installation conditions of outdoor unit L : Compact C A
330 (34) 26 950
Air Discharge Type C
(7) 81 26 97 82 244
S : Side Discharge
MULTI V S inverter technology and sub cooling control circuit For enhanced efficiency, new axial fan boasts higher air volume, increased

MULTI V S
Electrical Ratings 5 5
technology allows greater piping length and outstanding elevation static pressure and decreased noise. L : 3Ø, 380-415V, 50Hz
5 5
differences. A cooling system can be implemented more flexibly in a G : 1Ø, 220-240V, 50Hz

834
Total Cooling Capacity in Horse Power(HP) unit
shop, office and even high-rise building, reducing the designer’s work

660
Fan Technology EX) 8HP '080', 10HP '100'

627
3

466
476
time and providing more efficient design. Combination of Inverter Type and Cooling Only
The new axial fan has a mogul trailing edge, narrow hub blade and reverse hub,

24
or Heat Pump B B B

141
83
this provides a high efficiency, low noise, wide fan, as well as improving the air N : Inverter and H/P, V : Inverter and C/O 51 148
1 64
2 4
Piping Capabilities (ARUN series) flow rate. MULTI V System Outdoor Unit using R410A 416
40

111
291
276
Reverse
300m Mogul hub
Total piping length trailing edge Outdoor Units Function 5-1.D. Ø20 holes for drain connection 91
250 696
Category Functions MULTI V S
50m 526mm Variable Path of Outdoor Unit HEX -
A

ODU ~ IDU
Height Narrow HiPOR TM (High Pressure Oil Return) -
150m difference hub blade Key Refrigerant
Humidity Sensor ARUB060GSS4 only
(1Ø) 4 / 5HP (1Ø) 5 / 6HP Components
(175m) (3Ø) 4 / 5 / 6 / 8HP Corrosion Resistance Black Fin ○
Longest
pipe length
15m Oil Sensor -
IDU ~ IDU Super cannon fan increases the air volume in 50 CMM and the noise level is
(Equivalent) Dual Sensing ARUB060GSS4 only
Height decreased by 4dB(A). 3D View
Low Noise Operation ○
difference
Hgih Static Mode of Outdoor Unit Fan ○
Grooved Piping
[Unit : mm] 620
suction surface Partial Defrosting - Direction

Auto Dust Removal of Outdoor Unit

14
-
Special Function (Fan reverse rotation)

390
360
Indoor Cooling Comfort Mode Based

Tip vortex Outdoor Temperature C A
suppressor Smart Load Control (SLC) 4 holes for Anchor Bolts (M10)
(Changing indoor discharge air ○
temperature according to load) C
4 Way Piping Super Canon Fan 330 26
A 950
(3Ø) 10 / 12HP Outdoor Unit Control Refer to 90
- Fre e d e sig n a n d in sta lla tio n b y 4 w ay p ip in g . ARUB060GSS4 only C
Humidity
Defrost / Deicing ○
Fan RPM control High Pressure Switch ○
Flow of air is straight due to fan shroud and Fan RPM control even in high-rise
Phase Protection ○ 5

1380
building.
Basic Function Restart Delay (3-minutes) ○
2
Self Diagnosis ○

606
Soft Start ○

80
Fan RPM 80
52
control Test Run Function -
+ + (Fan Max
25 26
7

52
B 1
AC Ez (Simple Controller) PQCSZ250S0 6 96 B 96
RPM Up)
695
AC Ez Touch PACEZA000 416
250
Fan Shroud AC Smart IV PACS4B000 91
40 164
Central Controller AC Smart 5 PACS5A000
• Straight air flow

111
Low Noise Operation

291
276
- New shroud adopted ACP (Advanced Control Platform) IV PACP4B000
- Performs high static pressure ACP (Advanced Control Platform) 5 PACP5A000 5-1.D. Ø
Decreased noise during operation with low noise functionality 20 holes for drain connection
AC Manager 5 PACM5A000
75
ACP Lonworks PLNWKB000 A
At night mode, noise reduced maximum 14% compared to normal mode. BNU (Building
Upgraded Fault Detection and Diagnosis Network Unit) ACP BACnet PQNFB17C0

60
44
IO Module (ODU Dry Contact) PVDSMN000
Capacity Easy and convenient maintenance with self-diagnosis 42
91

PDI (Power Standard PPWRDB000 4


Load
The inclusion of FDD elements - Auto start-up, auto refrigerant check, Distribution Indicator) Premium PQNUD1S40 3
black box functionality, simultaneous evaluation, and auto refrigerant Cool / Heat Selector PRDSBM

606

536
557
collection, provides the optimal solution for user reliability and ease LGMV PRCTIL0
Sound Level
Night Cycle Monitoring

85
58
Mode Start Mode End of maintenance. Device Mobile LGMV PLGMVW100 24

52
25 8
56 Step 1 ○ 3D View B 81

53 Step 2
- Auto commissioning Mode (Logical operation) Piping connection port
Refrigerant Charging Kit 94
- Auto Refrigerant Collection Not applied to
50 Step 3
Additional kit ARUB060GSS4
8:00 12:00 16:00 20:00 0:00 4:00 8:00 12:00 16:00
- Auto evaluation of refrigerant amount Note No. Part Name Description
Low Ambient Kit -
Time
and charging FDD 1. Unit should be installed in compliance with the 1
2
Air Outlet
Power and communication cable Hole
-
-
Max. - Able to access LGMV (LG Monitoring MICOM Variable Water Flow Valve Control Kit - installation manual in the product box.
3 Gas Pipe Connection Welding joint
2. Unit should be grounded in accordance with the 4 Liquid Pipe Connection Welding joint
58 8dB(A) View) by smartphone ○ : Applied, - : Not Applied local regulation or applicable national codes. 5 Handle -
3. All electrical components and materials to be 6 Pipe routing hole (front) -
- Black box function 7 Pipe routing hole (side) -
supplied from the site must comply with the local
8 Pipe routing hole (back) -
- Piping & wiring error check-up regulations or international codes.
50 4. Electrical characteristics chapter should be
Normal mode noise level (28kW) : 58dB(A) considered for electrical work and design.
50dB(A) Night 3 step noise level (28kW) : Especially the power cable and circuit breaker
56dB(A),53dB(A), 50dB(A)
should be selected in accordance with that.
Sound pressure tested by following conditions :
Day Night 1m distance / 1.5m height

006 / 007
OUTDOOR UNITS _ MULTI V S _ SPECIFICATION

MULTI V S COOLING ONLY MULTI V S HEAT PUMP

OUTDOOR
UNITS
ARUV030GSD0 / ARUV040GSD0 ARUN040GSS5 / ARUN050GSS5 / ARUN060GSS5
ARUV050GSD5 / ARUV060GSD5

MULTI V S
HP 3 4 5 6 HP 4 5 6
Model Name Combination Unit ARUV030GSD0 ARUV040GSD0 ARUV050GSD5 ARUV060GSD5 Model Name Combination Unit ARUN040GSS5 ARUN050GSS5 ARUN060GSS5
kW 9.2 11.0 14.5 16.0 kW 12.1 14.0 15.5
Cooling kcal/h 7,911 9,458 12,470 13,800 Cooling kcal/h 10,400 12,000 13,300
Btu/h 31,400 37,600 49,500 54,600 Btu/h 41,300 47,800 52,900
Capacity (Rated) Capacity (Rated)
kW - - - - kW 12.5 16.0 18.0
Heating kcal/h - - - - Heating kcal/h 10,800 13,800 15,500
Btu/h - - - - Btu/h 42,700 54,600 61,400
Cooling kW 2.10 2.75 3.45 4.50 Cooling kW 3.43 3.33 3.97
Input (Rated) Input (Rated)
Heating kW - - - - Heating kW 2.45 3.48 4.29
Power Factor Rated - 1 1 1 1 Power Factor Rated - 0.93 0.93 0.93
Casing Color Warm Gray Warm Gray Warm Gray Warm Gray Casing Color Warm Gray Warm Gray Warm Gray
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus
Hermetic Motor Hermetic Motor Type LG Inverter Scroll LG Inverter Scroll LG Inverter Scroll
Type LG Inverter Scroll LG Inverter Scroll
Compressor Compressor
Piston Displacement cm 3 /rev 31.6 31.6 31.6
Piston Displacement cm /rev 3
24 24 31.6 31.6
Motor Output x Number W x No. 3,198 x 1 3,198 x 1 3,198 x 1
Number of Revolution rev/min 6,600 6,600 Compressor
Compressor Starting Method DC Inverter Starting DC Inverter Starting DC Inverter Starting
Motor Output x Number W x No. 2,137 x 1 2,137 x 1 3,198 x 1 3,198 x 1
Oil Type FW68D FW68D FW68D
Starting Method DC Inverter Starting DC Inverter Starting DC Inverter Starting DC Inverter Starting
Oil Charge cc 1,100 1,100 1,100
Oil Type FVC68D (PVE) FVC68D (PVE) FW68D FW68D
Type Axial Flow Fan Axial Flow Fan Axial Flow Fan
Oil Charge 900 900 1,100 1,100
Motor Output x Number W 124 x 1 198 x 1 198 x 1
Type Axial Flow Fan Axial Flow Fan Axial Flow Fan Axial Flow Fan
m 3 /min 60 80 80
Motor Output x Number W 124.0 x 1 124.0 x 1 198 x 1 198 x 1 Fan Air Flow Rate (High)
ft3 /min 2,118 2,824 2,824
m 3 /min 60 60 80 80
Fan Air Flow Rate (High) Drive DC INVERTER DC INVERTER DC INVERTER
ft3 /min 2,118 2,118 2,824 2,824
Discharge Side / Top Side Side Side
Drive DC INVERTER DC INVERTER DC INVERTER DC INVERTER
Liquid mm (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Discharge Side / Top Side Side Side Side Pipe Connections
Gas mm (inch) 15.88 (5/8) 15.88 (5/8) 19.05 (3/4)
Liquid mm (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Pipe Connections mm 950 x 834 x 330 950 x 834 x 330 950 x 834 x 330
Gas mm (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8) 19.05 (3/4) Dimensions (W x H x D)
inch 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13
mm 950 x 834 x 330 950 x 834 x 330 950 x 834 x 330 950 x 834 x 330
Dimensions (W x H x D) kg 65 72 72
inch 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 Net Weight
lbs 143.3 158.7 158.7
kg 59 59 66 67
Net Weight Cooling dB(A) 51 57 57
lbs 130 130 146 148 Sound Pressure Level
Heating dB(A) 55 60 63
Cooling dB(A) 50 50 51 56
Sound Pressure Level Sound Power Level dB(A) - - -
Heating dB(A) - - - -
High pressure sensor / High pressure sensor / High pressure sensor /
Sound Power Level dB(A) - - - - High pressure protection -
High pressure switch High pressure switch High pressure switch
High pressure sensor / High pressure sensor / Over-heat protection / Over-heat protection / Over-heat protection /
High pressure protection - Low pressure sensor Low pressure sensor Protection Devices Compressor/Fan -
High pressure switch High pressure switch Fan driver overload protector Fan driver overload protector Fan driver overload protector
Over-heat protection Over-heat protection Over-heat protection / Over-heat protection Over-heat protection / Over-heat protection / Over-heat protection /
Inverter -
Protection Devices Compressor / Fan - / Fan driver overload / Fan driver overload Fan driver overload / Fan driver overload Over-current protection Over-current protection Over-current protection
protector protector protector protector mm 2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Over-heat protection / Over-heat protection / Over-heat protection / Over-heat protection / (VCTF-SB)
Inverter -
Over-current protection Over-current protection Over-current protection Over-current protection Refrigerant name R410A R410A R410A
mm 2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C kg 1.8 2.4 2.4
(VCTF-SB) Refrigerant Precharged Amount
Refrigerant name R410A R410A R410A R410A lbs 4.0 5.3 5.3
kg 1.4 1.4 2.0 2.0 Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Refrigerant Precharged Amount
lbs 3.1 3.1 4.4 4.4 Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve Number of maximum connectable indoor units 6 8 9
Power Supply Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
Number of maximum connectable indoor units 5 6 8 9 Note
1. Eurovent Test Condition : Type of indoor unit connected is only Ceiling Concealed Duct.
- Refer to EUROVENT certification regulation for more detail test conditions.
- Refer to EUROVENT website for test values connected Ceiling Cassette type indoors.
Note 2. Performances are based on the following conditions :
1. Eurovent Test Condition : Type of indoor unit connected is only Ceiling Concealed Duct. - Cooling Temperature : Indoor 27°C (80.6°F) DB / 19°C (66.2°F) WB / Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB
- Refer to EUROVENT certification regulation for more detail test conditions. - Refer to EUROVENT website for test values connected Ceiling Cassette type indoors. - Heating Temperature : Indoor 20°C (68°F) DB / 15°C (59°F) WB / Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB
2. Performances are based on the following conditions : - Cooling Temperature : Indoor 27°C (80.6°F) DB / 19°C (66.2°F) WB / Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB 3. The maximum combination ratio is 160%. (the maximum combination ratio of ARUN050GSL0 is 130%.)
- Heating Temperature : Indoor 20°C (68°F) DB / 15°C (59°F) WB / Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB 4. Wiring cable size must comply with the applicable local and national codes.
3. The maximum combination ratio is 160%. (the maximum combination ratio of ARUN050GSL0 is 130%.) 5. Due to our policy of innovation some specifications may be changed without notification.
4. Wiring cable size must comply with the applicable local and national codes. 5. Due to our policy of innovation some specifications may be changed without notification. 6 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd . S o u n d p o w e r l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e re v e r b e r a t i o n ro o m s
6 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd . S o u n d p o w e r l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e re v e r b e r a t i o n ro o m s by ISO 3741 standard. Therefore, these values can be increased owing to ambient conditions during operation.
by ISO 3741 standard. Therefore, these values can be increased owing to ambient conditions during operation. 7. Power factor could vary less than ±1% according to the operating conditions.
7. Power factor could vary less than ±1% according to the operating conditions. 8. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 8. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)

008 / 009
OUTDOOR UNITS _ MULTI V S _ SPECIFICATION

MULTI V S HEAT PUMP MULTI V S HEAT PUMP

OUTDOOR
UNITS
ARUN040LSS5 / ARUN050LSS5 / ARUN060LSS5 ARUN080LSS0 / ARUN100LSS0 / ARUN120LSS0

MULTI V S
HP 4 5 6 HP 8 10 12
Model Name Combination Unit ARUN040LSS5 ARUN050LSS5 ARUN060LSS5 Model Name Combination Unit ARUN080LSS0 ARUN100LSS0 ARUN120LSS0
kW 12.1 14.0 15.5 Cooling (Rated) kW 22.4 28.0 33.6
Capacity
Cooling kcal/h 10,400 12,000 13,300 Heating (Rated) kW 24.5 30.6 36.7
Btu/h 41,300 47,800 52,900 Cooling (Rated) kW 8.30 8.75 14.00
Capacity (Rated) Input
kW 12.5 16.0 18.0 Heating (Rated) kW 6.62 8.12 7.46
Heating kcal/h 10,800 13,800 15,500 EER 2.70 3.20 2.40
Btu/h 42,700 54,600 61,400 SEER 6.03 6.59 5.72
Cooling kW 3.43 3.33 3.97 COP Rated Capacity 3.70 3.77 4.92
Input (Rated)
Heating kW 2.45 3.48 4.29 SCOP 4.33 4.17 3.86
Power Factor Rated - 0.93 0.93 0.93 Color (General) Warm Gray Warm Gray Warm Gray
Exterior
Casing Color Warm Gray Warm Gray Warm Gray RAL Code (Classic), General RAL 7044 RAL 7044 RAL 7044
Heat Exchanger Wide Louver Plus Wide Louver Plus Wide Louver Plus Heat Exchanger Type Wide Louver Plus / Black Fin Wide Louver Plus / Black Fin Wide Louver Plus / Black Fin
Type LG Inverter Scroll LG Inverter Scroll LG Inverter Scroll Type Hermetically Sealed Scroll Hermetically Sealed Scroll Hermetically Sealed Scroll
Piston Displacement cm 3 /rev 31.6 31.6 31.6 Combination x No. (Inverter) x 1 (Inverter) x 1 (Inverter) x 1
Motor Output x Number W x No. 3,198 x 1 3,198 x 1 3,198 x 1 Compressor Motor Output x Number W x No. 4,200 x 1 5,300 x 1 5,300 x 1
Compressor
Starting Method DC Inverter Starting DC Inverter Starting DC Inverter Starting Oil Type FVC68D (PVE) FVC68D (PVE) FVC68D (PVE)
Oil Type FW68D FW68D FW68D Oil Charge cc 2,400 2,600 3,400
Oil Charge cc 1,100 1,100 1,100 Type Propeller fan Propeller fan Propeller fan
Type Axial Flow Fan Axial Flow Fan Axial Flow Fan Motor Output x Number W x No. 124 x 2 250 x 2 250 x 2
Motor Output x Number W 124 x 1 198 x 1 198 x 1 Fan Air Flow Rate (High) m 3 /min x No. 140 x 1 190 x 1 190 x 1
m 3 /min 60 80 80 Drive DC INVERTER DC INVERTER DC INVERTER
Fan Air Flow Rate (High)
ft3 /min 2,118 2,824 2,824 Discharge Side / Top Side Side Side
Drive DC INVERTER DC INVERTER DC INVERTER Liquid Pipe mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø12.7 (1/2)
Pipe Connection
Discharge Side / Top Side Side Side Gas Pipe mm (inch) Ø19.05 (3/4) Ø22.2 (7/8) Ø28.58 (1-1/8)
Liquid mm (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) Dimensions (W x H x D) mm x No. (950 x 1,380 x 330) x 1 (1,090 x 1,625 x 380) x 1 (1,090 x 1,625 x 380) x 1
Pipe Connections
Gas mm (inch) 15.88 (5/8) 15.88 (5/8) 19.05 (3/4) Dimensions (W x H x D) - Shipping mm x No. (1,140 x 1,462 x 461) x 1 (1,215 x 1,795 x 500) x 1 (1,215 x 1,795 x 500) x 1
mm 950 x 834 x 330 950 x 834 x 330 950 x 834 x 330 Net Weight kg x No. 115 x 1 144 x 1 157 x 1
Dimensions (W x H x D)
inch 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 37-13/32 x 32-27/32 x 13 Shipping Weight kg x No. 127 x 1 160 x 1 173 x 1
kg 65 72 72 Cooling dB(A) 57.0 58.0 60.0
Net Weight Sound Pressure Level
lbs 143.3 158.7 158.7 Heating dB(A) 57.0 58.0 60.0
Cooling dB(A) 51 57 57 Cooling dB(A) 81.0 80.0 81.0
Sound Pressure Level Sound Power Level
Heating dB(A) 55 60 63 Heating dB(A) 84.0 84.0 85.0
Sound Power Level dB(A) - - - mm 2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
High pressure sensor / High pressure sensor / High pressure sensor / (VCTF-SB)
High pressure protection - Refrigerant Name R410A R410A R410A
High pressure switch High pressure switch High pressure switch
Over-heat protection / Over-heat protection / Over-heat protection / Precharged Amount in
Protection Devices Compressor/Fan - kg 3.5 4.5 6.0
Fan driver overload protector Fan driver overload protector Fan driver overload protector Refrigerant factory
Over-heat protection / Over-heat protection / Over-heat protection / t-CO 2 eq 7.3 9.4 12.5
Inverter -
Over-current protection Over-current protection Over-current protection
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
mm 2 x No.
Communication Cable 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C Power Supply Ø, V, Hz 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
(VCTF-SB)
Refrigerant name R410A R410A R410A Number of Maximum Connectable Indoor Units 13 16 20
kg 1.8 2.4 2.4
Refrigerant Precharged Amount
lbs 4.0 5.3 5.3
Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Power Supply Ø, V, Hz 3, 380-415, 50 3, 380-415, 50 3, 380-415, 50
Number of maximum connectable indoor units 6 8 9

Note Note
1. Eurovent Test Condition : Type of indoor unit connected is only Ceiling Concealed Duct. 1. Eurovent Test Condition : Type of indoor unit connected is only Ceiling Concealed Duct.
- Refer to EUROVENT certification regulation for more detail test conditions. - Refer to EUROVENT certification regulation for more detail test conditions.
- Refer to EUROVENT website for test values connected Ceiling Cassette type indoors. - Refer to EUROVENT website for test values connected Ceiling Cassette type indoors.
2. Performances are based on the following conditions : 2. Performances are based on the following conditions :
- Cooling Temperature : Indoor 27°C (80.6°F) DB / 19°C (66.2°F) WB / Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB - Cooling Temperature : Indoor 27°C (80.6°F) DB / 19°C (66.2°F) WB / Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB
- Heating Temperature : Indoor 20°C (68°F) DB / 15°C (59°F) WB / Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB - Heating Temperature : Indoor 20°C (68°F) DB / 15°C (59°F) WB / Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB
3. The maximum combination ratio is 160%. (the maximum combination ratio of ARUN050GSL0 is 130%.) 3. The maximum combination ratio is 160%. (the maximum combination ratio of ARUN050GSL0 is 130%.)
4. Wiring cable size must comply with the applicable local and national codes. 4. Wiring cable size must comply with the applicable local and national codes.
5. Due to our policy of innovation some specifications may be changed without notification. 5. Due to our policy of innovation some specifications may be changed without notification.
6 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd . S o u n d p o w e r l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e re v e r b e r a t i o n ro o m s 6 . S o u n d p re s s u re l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e a n e c h o i c ro o m s b y I S O 3 7 4 5 s t a n d a rd . S o u n d p o w e r l e v e l i s m e a s u re d o n t h e r a t e d c o n d i t i o n i n t h e re v e r b e r a t i o n ro o m s
by ISO 3741 standard. Therefore, these values can be increased owing to ambient conditions during operation. by ISO 3741 standard. Therefore, these values can be increased owing to ambient conditions during operation.
7. Power factor could vary less than ±1% according to the operating conditions. 7. Power factor could vary less than ±1% according to the operating conditions.
8. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5) 8. This product contains Fluorinated greenhouse gases. (R410A, GWP(Global warming potential) = 2087.5)