Professional Documents
Culture Documents
l=1,5m
Sensor KTY81-210
Ø9
45
! 24VAC, 50Hz
Dimensions:
90°
AUTO
1
2
MAX
AUTO-MAN
UNI TEMP
MAN
T
®
78
24V , 50Hz, 5VA
MIN
IP44, max 12Nm
90
888
MR-B-01
T(°C)
24V
rjava/brown
modra/blue
POWER
125
Order information:
Enclosed mounting kit for following mixing valves: FIRŠT (ROTOMIX, ROTOMIX G), ESBE
(VRG, VRB), ACASO (TERMOMIX), BARBERI, FEROTERM, PAW, EURONORM, ESBE,
IMP, DANFOSS, BESSER, SELTRON, LOVATO, TUXHORN, STRAWA, CIMBERIO.
Safety notes:
The actuator has been designed for use in stationary heating, ventilation and air-
?
conditioning systems and is not allowed to be used outside the specified field of
application, especially in aircraft or in any other airborne means of transport.
Caution power supply voltage – 24VAC.
?
It may only be installed by suitably trained personnel. All applicable legal or
?
institutional installation regulations must be complied with.
The device must be protected from moisture and is not recommended for use in
?
external applications.
The device may only be opened at the manufacturer's site. It does not contain any
?
parts that can be replaced or repaired by the user.
The cable must not be removed from the device.
?
The device contains electrical and electronic components and is not allowed to be
?
disposed of as household refuse. All locally valid regulations and requirements
must be observed.
www.first.si 2
UNI TEMP
Mounting on the valve:
3-way mixing brass valve FIRŠT (ROTOMIX G), ESBE, ACASO Mixing valves ESBE VRB, VRG
(TERMOMIX), BARBERI, FEROTHERM,
ROTOMIX F3 PAW, EURONORM, IMP, DANFOSS,
ROTOMIX F4 1
BESSER
Mounting kit
By special request
58025 SELTRON, LOVATO, PAW
58026 LAZZARI, LANDIS
58027 HONEYWELL MS
58028 SIEMENS
58029 MUT
58030 W.I.L.B
58031 CENTRA
58032 MEIBES, WITA, OVENTROP, HOLTER HORA
BR80 SMD/SMV
58033 TEHNOPLANT, EXCELSIOR, KRAMER, DE
PALA
www.first.si 3
UNI TEMP
Settings:
1 Mechanical indication.
Indicator can be set according to the valve assembly
3 Handle for manually controlling the drive, which also serves for the
indication position of the valve
MAN
www.first.si 4
UNI TEMP
Controller behavior diagram as a function of temperature:
Example:
-Desired temperature: 50°C
-Xp parameter – proportional control range of valve (10K)
T (°C)
100% closing
Tset=50°C
Xp = 10K 50
closing area
Nearer the desired
temperature (50°C),
45 shorter pulses.
100% opening
set temperature
45°C 50°C 55°C
permanent impulse valve impulse valve permanent
valve opening opening closing valve closing
Xp =10K
When the temperature is When the temperature is When the temperature is When the temperature is
less than 45°C, controller between 45°C and 50°C, between 50°C and 55°C, higher than 55°C,
gives continuous signal controller pulsating controller pulsating controller gives
for opening mixing valve. opens mixing valve. closes mixing valve. continuous signal for
Nearer the desired Nearer the desired closing mixing valve.
temperature (50°C), temperature (50°C),
shorter pulses. shorter pulses.
90°
90° 90°
Note: when the button
for manual operation is
in <MAN> position,
90° controller stays in
temporary position
irrespective of control
signal.
www.first.si 5
UNI TEMP
Examples:
UNI TEMP
M M
UNI TEMP
UNI TEMP
Solid fuel boiler - Maintain a constant temperature in Maintain a constant temperature of heat reservoir
heating circuit
UNI M
TEMP
UNI TEMP
DTC100/2
UNI TEMP
ROTOTERM
MR-TR UNI
TEMP
www.first.si 6
UNI TEMP
We reserve the right to modify the instructions and the technical data of the product without prior notice.
PE VELENJE:
Koroška c. 56a, 3320 Velenje
tel: 03 / 898 35 00, fax: 03 / 898 35 35
FIRŠT-ROTOTEHNIKA, s.p.,
Radegunda 54, 3330 Mozirje
info@?rst.si, http://www.?rst.si