Professional Documents
Culture Documents
th
10 International Masonry Conference
G. Milani, A. Taliercio and S. Garrity (eds.)
Milan, Italy, July 9-11, 2018
Abstract. Buildings constructed of reinforced concrete frames with masonry infill (RCFMI) are
comprised of unreinforced masonry walls that are tightly infilled into the space between the reinforced
concrete frames. Poor seismic performance of RCFMI buildings has been observed during past earth-
quakes and it has been repeatedly acknowledged that damage to masonry infills, in many cases, re-
stricted the subsequent use of the buildings despite the main frames having sustained no more than
minor structural damage. Partial or complete out-of-plane (OOP) collapse of masonry infills has also
been frequently observed following large earthquakes, often causing collateral damage to surrounding
properties and injuries to passers-by. Despite these concerns, limited literature exists on the residual
OOP strength of in-plane (IP) damaged infill walls, particularly those that have been strengthened
using fibre reinforced matrix (FRCM) prior to the earthquake. Therefore, an experimental program
was undertaken to evaluate the residual OOP capacity of IP damaged FRCM strengthened infill walls
constructed using un-grouted unreinforced hollow core concrete masonry. A total of eight single bay
RCFMI assemblies were constructed, including one non-retrofitted control specimen and with the re-
mainder strengthened by applying diagonally oriented FRCM bands with varying widths onto both
wall faces. The variables investigated were FRCM type and width of the applied FRCM band. The
RCFMI assemblies were subjected to reversed cyclic displacement-controlled IP loading gradually
increasing to 1% storey drift, to develop damage that would be expected from a moderate earthquake.
The IP damaged RCFMI assemblies were then subjected to gradually increasing OOP loading to as-
sess their residual capacity. Performance metrics that were observed and measured included observed
damage patterns, failure mechanisms, force-displacement response, displacement ductility, and stiff-
ness characteristics.
2200
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
1 INTRODUCTION
Reinforced concrete frames with hollow core concrete masonry infill (RCFMI) panels con-
structed in full contact with the frame have been widely used in low to high seismic risk re-
gions around the world as the main lateral load resisting system in residential apartment,
industrial, and commercial buildings. Despite having a significant influence on the seismic
behaviour of a RCFMI building, in the majority of pre-1980s non-ductile RCFMI buildings,
these infills were either neglected in the design or had not been designed to sustain the seis-
mic forces which they may be subjected to due to their stiffness. It is now widely acknowl-
edged that, in addition to in-plane (IP) loads, out-of-plane (OOP) loading may result in partial
or complete collapse (see Fig. 1b) of infill panels, with this effect exacerbated when an infill
panel pre-damaged in the IP direction is subsequently subjected to OOP loading or when the
infill panel experiences concurrent IP and OOP loading. The OOP collapse of the infill, with
shedding of masonry into streets or egress routes, poses a significant safety hazard to passer-
by and occupants of the building.
One option to alleviate the hazard described above is the introduction of a strengthening in-
tervention capable of delaying the onset of IP damage and allowing a controlled ductile fail-
ure mode. Such an infill strengthening intervention is thus expected to increase strength,
displacement capacity, and energy-dissipation capacity, and to decrease the rate of strength
degradation. Numerous strengthening techniques have been developed and used over time to
limit damage to infill panels in RCFMI buildings. One relatively new composite material is
fibre reinforced cementitious matrix (FRCM), which consists of high strength dry fibre grid
embedded within an inorganic cementitious matrix. In this system, the matrix used to transfer
stresses between the substrate and the surface applied fibre grid reinforcement has been re-
ported to outperform epoxy-based organic matrices used in conventional fibre reinforced pol-
ymer applications [1]. The development of FRCM is advancing rapidly and several technical
articles have been published on its performance in the last few decades (e.g. [2] and [3]).
However, the seismic performance of FRCM strengthened RCFMI is not well established in
the previous experimental research. In particular, literature on the performance of FRCM
strengthened masonry infill panels when subjected to sequential IP-OOP loading is scarce.
Hence, an experimental program to investigate the OOP behaviour of IP-damaged FRCM
strengthened hollow core concrete masonry infill panels (referred to as infill panels hereafter)
was undertaken in this study.
Joint shear
Lateral loading Rebar pullout
Beam hinging Veneer OOP failure
Corner crushing
Stair cracking/sliding
(a). RCFMI damage patterns (b). OOP failure of masonry infills during the 2009
L’Aquila earthquake [4]
Figure 1: IP and OOP damage of masonry infilled frames.
2201
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
An infill panel subjected to IP loading can exhibit a sliding shear, diagonal cracking, or toe
crushing failure mode (see Figure 1a). The governing failure mode is likely to be influenced
by the mechanical characteristics of the infill masonry and the bounding concrete frame, the
infill aspect ratio, and the infill boundary conditions. Sliding shear occurs along mortar joints
(either along a bed joint or a diagonal stair-step joint) when a combination of weak mortar and
strong bricks are used, whereas diagonal cracking through masonry units and mortar is likely
to occur when the principal tensile stress at the centroid of a panel having strong mortar and
weak bricks reaches the masonry modulus of rupture. Such tensile cracking propagates from
the centre region towards the loaded corners along a diagonal orientation. In a flexure domi-
nated failure modes, rocking to high drift levels can lead to crushing at the compressed corner.
Numerous studies have investigated the OOP behaviour of infill panels both experimental-
ly and analytically. Timoshenko [5] proposed using the theory of elastic-plate analysis, which
was later modified by others (e.g. [6-8]) to incorporate two-way action by using the modified
yield-line approach. However, both the elastic-plate analysis and the yield line approach re-
lied on the tensile strength of masonry that is only physically active until crack initiation and
therefore fails to explain the high resistance to OOP forces beyond first cracking, (i.e., in the
non-linear range). Thomas [9] introduced the concept of arching action based on the results of
an experimental program, which was validated in several subsequent studies (e.g. [10-11]).
The results of the above mentioned studies led to one-way spanning masonry beam idealisa-
tion with rigid supports being used widely to represent the arching effect analytically. Dawe
and Seah [12] studied OOP behaviour of nine hollow core concrete masonry infilled steel
frames using finite element analysis and pseudo-static testing. The results of their study sug-
gested that masonry compressive strength, infill panel dimensions, and frame rigidity have
significant effects on the OOP behaviour of infill panels and on the governing damage pat-
terns.
In general, the seismic behaviour of un-damaged infill panels has been well researched but
the OOP behaviour of pre-damaged infill panels is not yet well–understood. Abrams et al. [13]
reported experimental program involving OOP testing of eight full-scale RCFMI assemblies,
with infills constructed using clay bricks and hollow core concrete masonry. Based on exper-
imental results, OOP strength reduction factors were proposed to be used accounting for prior
IP damage. However, these factors were determined based on limited test results and one of
the recommendations of the study was to study this aspect further. The OOP strength descent
due to prior damage was noted to be significant when infill walls were slender, which was at-
tributed to the absence of arching action. Henderson et al. [14] investigated the effect of se-
quential bidirectional loading and reported OOP damage to cause significant IP stiffness
degradation but otherwise to have limited effect on IP strength. Whereas, prior in-plane dam-
age (0.4% drift) reduced the OOP capacity by 20% and increased the OOP deformation by
65% at the same magnitude of applied OOP force when compared to that from the one tested
un-damaged.
Calvi and Bolognini [15] also performed sequential IP-OOP tests on RCFMI assemblies
containing hollow clay brick infill panels by first loading test assemblies up to two IP drift
levels, being 0.1-0.4% (corresponding to serviceability limit state or immediate occupancy
performance criteria) and 1.2% (corresponding to ultimate limit state or life safety perfor-
mance criteria). The IP damaged infill panels were then loaded in OOP direction until col-
lapse on a shake table. The analogous pseudo-acceleration required to induce OOP collapse in
undamaged infill panels was 2.5 g, which was reduced by 73% and 82% when tested after
been loaded to an IP drift of 0.4% and 1.2% respectively. Some other studies [e.g. 4, 16-21]
have also performed OOP testing of IP damaged infill panels, resulting in similar results.
2202
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
Few experimental programs also investigated the behaviour of RCFMI assemblies when
subjected to concurrent IP-OOP loading. Flanagan and Bennett [22] studied the simultaneous
application of IP and OOP forces to structural clay tile masonry infilled steel frames. Com-
bined effect of thrust force due to OOP loading and strut mechanism due to IP loading caused
crushing of tiles in the bottom course, resulting in OOP capacity reduction of 43%. Even after
notable damage, the infill panels remained stable and continued to sustain more damage until
OOP collapse. Komaranemi et al. [23] tested three half-scaled clay brick RCFMI assemblies
by subjecting these to slow cyclic IP displacement cycles and OOP ground motions using
shake table. The infill panels were reported to maintain structural integrity and remain stable
in OOP direction even when severely damaged. In-plane damaged infill panels were noted to
exhibit OOP rocking leading to OOP collapse, which was attributed to displacement instabil-
ity rather than fracture under inertial forces.
Da porto et al. [17] studied the behaviour of non-ductile FRCM strengthened RCFMI as-
semblies under sequential IP-OOP loading. The experimental program involved testing of
eight full scale strengthened RCFMI assemblies. The strengthening systems considered were:
1). special lime-based plaster with geo-polymer binder; 2). FRCM without anchors; and 3).
FRCM anchored to the surrounding frame. The specimens were subjected to first IP cyclic
loading (with the drift amplitude gradually increased up to 1.2%) and then to a monotonic
OOP loading applied to destruction. It was concluded that application of special plasters and
FRCM strengthening systems did not significantly change the initial stiffness or maximum IP
resistance of the reference frame but significantly improved the deformation capacity, energy
dissipation capacity, and strength retention.
2 EXPERIMENTAL PROGRAM
The performance of FRCM systems containing three different fibre reinforcements (i.e. al-
kali resistant glass, carbon, and basalt) as a seismic strengthening solution was investigated
herein. An experimental program involved sequential IP-OOP testing of eight RCFMI assem-
blies, consisting of one as-built control specimen and seven specimens strengthened using
varying FRCM configurations. The test assemblies were first subjected to quasi-static IP cy-
clic loading to create known level of IP damage, representing ultimate strength limit state
event loading. Afterwards, the IP-damaged RCFMI assemblies were subjected to a gradually
increasing monotonic OOP load. This represented a situation when a RCFMI pre-damaged
during a large earthquake experiences an aftershock with an orientation perpendicular to the
main event, such as that observed during the 2010/2011 Christchurch earthquake sequence
[18]. The OOP load was applied monotonically at four points wherein each load point was
located at the middle third of the length as well as height of the infill panel.
2203
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
fers to retrofitted; X represents fibre type i.e. basalt (B), carbon (C), and glass (G); Y denotes
FRCM configuration; and N denotes test number. Table 1 provides the test specimens details.
A
2270
R10-200
Cavity for anchors 2D12 3D16
R10-200 2D12
3D16 300
D - Deformed bars (Grade 500)
R - Round bars (Grade 300) Section A
N.T.S
170 R6-130 R6-130
R6-130 6D12 230
6D12 6D12
830 230 2270 230 830
4390 170
Section B Section C
N.T.S N.T.S
Figure 2: Test assembly geometry (in mm), and reinforcement details with location of strain gauges.
S. No Test panel FRCM FRCM band width FRCM thickness FRCM thickness
type (mm) (mm) (mm)
1 BF-1 - - - -
2 IF-2 - - - -
3 RFG-D3-3 AR Glass 986 10 15
4 RFG-D6-4 AR Glass 493 10 15
5 RFC-D3-5 Carbon 986 10 15
6 RFC-D6-6 Carbon 493 10 15
7 RFB-D3-7 Basalt 986 10 15
8 RFB-D6-8 Basalt 493 10 15
9 RFB-FU-9 Basalt Full face 10 15
Table 1: Test specimen details.
2204
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
were tested for indirect tensile strength in accordance with ASTM-C496 [26]. The concrete
slump was determined in accordance with ASTM-C143 [27], which was found to be 115 mm.
Two concrete cores of 100 mm diameter were taken from each tested RCFMI assembly us-
ing a Hilti diamond coring tool DD 120. The drilled cores were caped using sulphur and were
tested for compression strength in accordance with ASTM C42 [28]. Hollow core concrete
masonry infill panels were constructed following a staggered stack bond pattern using a ce-
ment-sand mortar with a by volume ratio of 1:3. The masonry mortar was used to fill the gap
between the masonry infill and the top beam, whilst the masonry was constructed hard against
columns. The concrete masonry units were 400×200×150 mm3 in size and had a void to gross
area ratio of 0.4. Five masonry units were tested for compression strength in accordance with
ASTM-C140 [29]. The masonry units exhibited splitting failure associated to tensile rupture
of the webs connecting the two faces rather than crushing. Three replicate 50 mm cubes were
casted from each batch of masonry mortar mixed, which were tested for compression strength
in accordance with ASTM-C109 [30]. Constituent concrete, masonry, steel reinforcement,
and mortar properties are shown in Table 2.
Three different types of FRCM systems were used to strengthen the RCFMI assemblies,
with each FRCM system consisting of a reinforcement fabric woven of dry fibres and a ce-
mentitious matrix. The types of fibre fabric used included alkali resistant (AR) glass, carbon,
and basalt. The cementitious matrix derives strength from hydration of cementitious and poz-
zolonic materials and was reinforced using polyvinyl fibres to allow thicker application with-
out shrinkage/temperature cracking. Typically, three matrix cubes were casted for each batch
of prepared FRCM matrix, which were later tested for compression strength. Physical charac-
teristics of FRCM materials are given in Table 3.
Where: ρf = density of fabric in g/m2; ρm = density of fibre; tr = approximate thickness of a fabric roving;
Ft = tensile strength of fibre grid per running meter; εu = rupture strain of the fabric; Ef = fabric modulus of elas-
ticity; f′cj = compressive strength of FRCM matrix; and CoV = coefficient of variation.
Table 3: Mechanical properties of FRCM fibres and matrix.
2205
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
(a). prior to strengthening (b). FRCM matrix mixing (c). first matrix layer
(d). FRCM textile cutting (e). final matrix layer (f). strengthened RCFMI
Figure 5: Strengthening of test assemblies.
2206
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
rods, with one steel plate placed on each end of the top beam of the test assembly (see Fig. 6a).
Of the commonly used loading histories e.g. those proposed by ATC-24 [32] and FEMA-461
[33], the loading history proposed by FEMA-461 [33] was adopted for the IP testing herein.
After IP testing, the actuator and IP loading assembly was removed whilst the column axial
load was retained. The OOP loading assembly consisted of a spreader steel assembly, a
500 kN hydraulic cylinder, and a 500 kN load cell (see Fig. 6b). At loading assembly-infill
contact points, square/cuboid wooden pieces were glued. The four contact points were located
at the middle third of the masonry infill wall (see Fig. 6c). For OOP tests, a gradually increas-
ing monotonic load was applied at a load rate manually maintained to roughly 0.01 mm/sec.
Test was frequently paused to check/note damage development.
For IP testing, the lateral displacement was measured using three linear variable displace-
ment transducers (LVDT) attached at the bottom, mid-height and top of the test assembly.
The top lateral displacement was calculated by subtracting the sliding (if any) measured using
the bottom LVDT from the lateral displacement measured using the top most LVDT.
557
757 757 757
100
557
100
100x100 RHS
Hinge Steel Plate Hinge
STRONG FLOOR
Tie-down yokes Tie-down yokes
Wooden
Piece
Load Cell
LVDT-1 LVDT-2
Cage Jack
LDS
LVDT-3 LVDT-4
Hinges
2207
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
For OOP testing, 4 LVDTs having a gage length of 200 mm were mounted near each con-
tact point to measure displacement at the loaded face (see Fig. 6c). One draw-wire displace-
ment transducer was installed exactly at the mid-point of the masonry infill on the rear face.
Tensile strain in steel reinforcement bars at potential hinge regions was monitored throughout
the testing using 5 mm long steel strain gages.
Where: Vu,i = maximum recorded IP load; Δu,i = maximum IP displacement; V/Vo= retrofitted frame to as-built
frame strength ratio; Vcr,o = OOP cracking load; Vu,o = maximum OOP load; pu,o = maximum OOP pressure; and
Δu,o = average maximum OOP displacement; Ki,o = initial OOP stiffness.
Table 4: Experimental IP and OOP results.
2208
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
2209
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
In specimen RFC-D3-5, the first horizontal crack in the surface of FRCM closer to the
mid-height appeared at an OOP load of 25 kN. After this crack the slope of the graph changed
and a vertical crack at an OOP load of 50 kN developed. At a load of 68 kN and displacement
4.6 mm some diagonal cracks appeared in the FRCM composite, which further reduced the
stiffness. New cracks appeared at the loads of 80 kN and 85 kN (see Fig. 8d).
In specimen RFC-D6-6, the first horizontal crack in the surface of FRCM appeared at load
of 20 kN, with corresponding displacement of 1.24 mm, in the bed joint location between
third and fourth course from the top. Diagonal cracks were first noted to develop in the
FRCM at 50 kN and some vertical cracks in masonry were first observed at lateral loading of
75 kN (see Fig. 8e). In specimen RFB-D3-7, horizontal cracks in FRCM appeared at the loca-
tion where it crossed the bed joints immediately above and below the mid height at applied
OOP loads of 30 kN and 50 kN, respectively. Some minor vertical cracks in FRCM at the lo-
cation of head joints were also noticed. Further horizontal cracks were observed to develop
near existing horizontal cracks at an applied OOP load of 80-85 kN (see Fig. 8f).
In specimen RFB-D6-8, a diagonal crack first appeared in the FRCM at a lateral load of
20 kN that could be noticed in the load-displacement curve as the point where the slope of
force-displacement curve changed. Another diagonal crack appeared on opposite side of the
first crack at a load of 26 kN (see Fig. 8g). At a lateral load of 42 kN a diagonal and a vertical
crack were observed causing stiffness degradation noted in the force displacement curve. Ob-
served crack patterns in RFB-D6-8 are shown in Figure 8g. Test assembly RFB-FU-9 (which
had no visible damage), behaved more like a tilt up reinforced slab showing two way bending
2210
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
action. The first micro horizontal crack in the surface of FRCM appeared at load of 31 kN,
which was located at mid-height. Diagonal cracking was noted to initiate at 60 kN that fol-
lowed extension of existing cracks further towards diagonal corners on further loading. The
damage development and crack patterns observed in test assembly RFB-FU-9 are shown in
Figure 8h.
Figures 10a and 10b show the combined push-over curves obtained from IP and OOP testing,
respectively. Abrams et al. [13] proposed Equation 1 to estimate the residual OOP strength of
IP damaged infill walls in RCFMI assemblies.
(1)
2211
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
(2)
(3)
(4)
4 CONCLUSIONS
An experimental program was undertaken to investigate the effect of FRCM strengthening
on structural performance of RCFMI assemblies when subjected to sequential IP-OOP load-
ing. For this purpose, a total of eight (two-third scaled) non-ductile reinforced concrete frames
infilled tightly with hollow core concrete masonry were constructed, of which seven were
strengthened using FRCM. The test assemblies were first subjected to quasi-static IP cyclic
loading to a drift level to cause a known level of damage in the walls and then subjected to
sequential gradually increasing monotonic OOP loading. Three different types of fibre rein-
forcements, including alkali resistant glass, carbon and basalt, were applied to test assemblies
using varying configurations. Overall, it can be stated that FRCM was effective in improving
the seismic performance of non-ductile RCFMI buildings. The following key conclusions
were drawn based on the observations and experimental results.
2212
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
Damage patterns observed during the sequential OOP testing of as-built infill confirmed
the presence of classical arching mechanism, with horizontal cracks closer to the mid-
height developing first and vertical cracks due to horizontal arching action showing up
later. Tow-way bending resulted in crushing of mortar in joints that lead to loss of arch-
ing action and masonry fragments started to collapse outward. FRCM strengthening de-
layed the onset of OOP cracking, instigated a more controlled failure mode with damage
level limited to that corresponding to a performance criterion somewhere between imme-
diate occupancy and life safety.
Typical failure modes observed in the FRCFM strengthened specimens were cracking
(mostly diagonal) in the surface of FRCM mortar at the location where FRCM crossed
the mortar joints, with these cracks starting from the central region and then propagating
towards corners. The number of cracks were reduced as the FRCM band width was in-
creased, which was attributed to stress re-distribution inside FRCM matrix whilst re-
straining crack openings in the substrate. Slippage at FRCM-masonry interface, fibre
rupture, or deboning of FRCM was not observed in any of the tests, however signs of
slippage along the fibre-matrix interface were noticed in grids with larger openings.
The residual OOP strength of FRCM strengthened infills ranged between 1.7-2.0 times
that of the control specimen. All FRCM types behaved similarly in composite form, irre-
spective of the strength of individual fibre girds. However, basalt fibre grid was found to
be the best amongst the three tested, which could possibly be due to the smaller opening
size of the mesh that thus provide more contact area between the fibres and the matrix.
It can be seen in the experimental results that the increase in the width of the FRCM di-
agonal bands beyond one third of the diagonal length has no significant contribution in
increasing the lateral strength of the frames. Therefore, it can be stated that strengthening
of RCFMI assemblies can be more economically done by applying a diagonal band of
FRCM with a width equal to a fraction of the infill diagonal length instead of applying it
to the full face of the infill wall. The most efficient FRCM configuration was a band with
width equal to one-sixth of the diagonal length. This will make the strengthening process
economical.
A much larger initial OOP stiffness was noticed for the FRCM strengthened specimens
ranging from 15 to 60 kN/mm compared to 10 kN/mm noted for as-built tested specimen.
2213
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
However, the reported stiffness values were highly sensitive to the damage level and
were observed to decline sharply with increasing damage level.
The analytical equations proposed by Abrams et al. overestimate the OOP strength of
masonry infill frames with prior infill damage (about 2.3 times).
ACKNOWLEDGMENT
Financial support for this study was provided by the United Arab Emirates University under
the research grant G00001603.
REFERENCES
[1] ACI 549.4R-13, Guide to design and construction of externally bonded fabric-
Reinforced Cementitious Matrix (FRCM) systems for repair and strengthening concrete
and masonry structure. Structural use of unreinfroced masonry. American Concrete In-
stitute: 2013.
[2] N. Ismail, J.M. Ingham, In-plane and out-of-plane testing of unreinforced masonry
walls strengthened using polymer textile reinforced mortar. Engineering Structures, 118,
167-177, 2016.
[3] O. Awani, T. El-Maaddawy, N. Ismail, Fabric-reinforced cementitious matrix: A prom-
ising strengthening technique for concrete structures. Construction and Building Mate-
rials, 132, 94-111, 2017.
[4] A. Furtado, H. Rodrigues, A. Arêde, H.Varuma, Experimental evaluation of out-of-
plane capacity of masonry infill walls. Engineering Structures, 111, 48-63, 2016.
[5] S.P. Timoshenko, S. Woinowsky-Krieger, Theory of plates and shells, McGraw-Hill,
1959.
[6] R.G. Drysdale, A.S. Essawy, Out-of-plane bending of concrete block walls. Journal of
Structural Engineering, 114(1), 121-133, 1988.
[7] B. Haseltine, H. West, J. Tutt, The resistance of brickwork to lateral loading – Part 2:
Design of walls to resist lateral loads. The Structural Engineer, 55(10), 22-430, 1977.
[8] A.W. Hendry, The lateral strength of unreinforced brickwork. The Structural Engineer,
51(2), 43-50, 1973.
[9] F. Thomas, The strength of brickwork. The Structural Engineer, 31(2), 35-46, 1953.
[10] E. McDowell, K. McKee, E. Sevin, Arching action theory of masonry walls. Journal of
the Structural Division, 82(2), 1-8, 1956.
[11] C. Anderson, Arching action in transverse laterally loaded masonry wall panels. The
Structural Engineer, 62(1), 12, 1984.
[12] J. Dawe, C. Seah, Out-of-plane resistance of concrete masonry infilled panels. Canadi-
an Journal of Civil Engineering, 16(6), 854-864, 1989.
[13] D.P. Abrams, R. Angel, J. Uzarski, Out-of-plane strength of unreinforced masonry infill
panels. Earthquake Spectra, 12(4), 825-844, 1996.
2214
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
[14] R.C. Henderson, K.E. Fricke, W.D. Jones, J.E. Beavers, R.M. Bennett, Summary of a
large-and small-scale unreinforced masonry infill test program. Journal of Structural
Engineering, 129(12), 1667-1675, 2003.
[15] G.M. Calvi, D. Bolognini, Seismic response of reinforced concrete frames infilled with
weakly reinforced masonry panels. Journal of Earthquake Engineering, 5(02), 153-185,
2001.
[16] F. Akhound, G. Vasconcelos, P.B. Lourenço, C.A.O.F. Palha, L.C. Silva, In-plane and
out-of plane experimental characterization of RC masonry infilled frames. Proc. 6th In-
ternational Conference on Mechanics and Materials in Design, Inegi-Feup, 2015, 427-
440.
[17] F. da Porto, G. Guidi, N. Verlato, C. Modena, Effectiveness of plasters and textile rein-
forced mortars for strengthening clay masonry infill walls subjected to combined in-
plane/out-of-plane actions. Mauerwerk-European Journal of masonry, 19(5), 334-354,
2015.
[18] S.H. Potter, J. S. Becker, D.M. Johnston, K.P. Rossiter, An overview of the impacts of
the 2010-2011 Canterbury earthquakes. International Journal of Disaster Risk Reduc-
tion, 14, 6-14, 2015.
[19] I.S. Misir, O. Ozcelik, S.C. Girgin, U. Yucel, The behavior of infill walls in RC frames
under combined bidirectional loading. Journal of Earthquake Engineering, 20(4), 559-
586, 2016.
[20] M.F.P. Pereira, M.F. Pereira, J.E Ferreira, P.B. Lourenço, Behavior of masonry infill
panels in RC frames subjected to in plane and out of plane loads. Proc. 7th Internation-
al Conference on Analytical Models and New Concepts in Concrete and Masonry Struc-
tures, Kraków, Poland, June 13-15, 2011.
[21] S. Hak, P. Morandi, G. Magenes, Out-of-plane experimental response of strong mason-
ry infills. Proc. 2nd European Conference on Earthquake Engineering and Seismology,
Turkey (Istanbul), 2014.
[22] R.D. Flanagan, R.M. Bennett, Bidirectional behavior of structural clay tile infilled
frames. Journal of Structural Engineering, 125(3), 236-244, 1999.
[23] S. Komaraneni, D.C. Rai, V. Singhal, Seismic behavior of framed masonry panels with
prior damage when subjected to out-of-plane loading. Earthquake Spectra, 27(4), 1077-
1103, 2011.
[24] ASTM-A615: 2016: Standard specification for deformed and plain carbon-steel bars
for concrete reinforcement. ASTM International: West Conshohocken, PA. 2016.
[25] ASTM-C39: 2017: Standard test method for compressive strength of cylindrical con-
crete specimens. ASTM International: West Conshohocken, PA. 2017.
[26] ASTM-C496: 2011: Standard test method for splitting tensile strength of cylindrical
concrete specimens. ASTM International: West Conshohocken, PA. 2011.
[27] ASTM-C143: 2015: Standard test method for slump of hydraulic-cement concrete.
ASTM International: West Conshohocken, PA. 2015.
[28] ASTM-C42: 2016: Standard test method for obtaining and testing drilled cores and
sawed beams of concrete. ASTM International: West Conshohocken, PA. 2016.
2215
Najif Ismail, Tamer El-Maaddawy, Nouman Khattak, Kevin Q. Walsh and Jason M. Ingham
[29] ASTM-C140: 2015: Standard test methods for sampling and testing concrete masonry
units and related units. ASTM International: West Conshohocken, PA. 2015.
[30] ASTM-C109: 2016: Standard test method for compressive strength of hydraulic cement
mortars (using 2-in. Or 50-mm cube specimens). ASTM International: West Con-
shohocken, PA. 2016.
[31] ACI-549.4: 2013: Guide to design and construction of externally bonded fabric-
reinforced cementitious matrix (FRCM) systems for repair and strengthening concrete
and masonry structures. American Concrete Institute: Michigan, USA. 2013.
[32] ATC-24: 1992: Guidelines for cyclic seismic testing of components of steel structures
for buildings. Applied Technology Council: Redwood City, California. 1992.
[33] FEMA-461: 2007: Interim protocols for determining seismic performance characteris-
tics of structural and nonstructural components through laboratory testing. Federal
Emergency Management Agency: Redwood City, CA. 2007.
2216