You are on page 1of 11

Index

A Burden, 24, 150-160 live tank vs. dead tank, 84


ABCD parameters defined, 24, 150 magnetic-air, 84
of long, mutually coupled in undereized CT, 159-160 making current, defined, 78
transmission lines, 447-453 maximum, by calculation, 159-160 manual operation, 21
of relay apparent impedance, Bus differential protection, 649-653 oil, 77, 83
329-332 concepts and problems, 650--653 oiIless, 83-84
of faulted system, 332-336 CT selection, 649--650 operating time, defined, 79
Abnormal unavailability, 1233-1241 high inlpedance, 657--663 operating voltage, defined, 78
Admittance example, 657--663 operation, 22
circles of with linear couplers, 655--656 permissible tripping delay, 82
constant III and variable (J, with overcurrent relays, 653--654 rated permissible tripping delay, 82
357-358 with percent differential relays, 655 rated voltage range factor, 80
diagrams, 355-356 Bus fault statistics, 646
rating, rated quantities, 79-82
input, 358-361 Bus protection, 645--670
symmetrical current method,
input loci, 356-357 auxiliary tripping relays, 669-670
79-80
combined bus and transformer, 664
input plot, for various operating total current method, 79
differential, 649--663
conditions, 360 ratings, 79-82
directional comparison, 669
loci recovery voltage, defined, 78
requirements, 647--648
for constant Ill, 357-358 reignition, defined, 79
using auxiliary CT's, 644-669
for constant e, 358-359 restrike current, defined, 79
using backup line relays, 648-649
relay characteristic, 359-364 restrike voltage, defined, 78
AND logic, 105
Anti-pumping, 22
c standard operating duty, defined, 81
sulfur hexaflouride, 77
Capacitive potential devices, 30-32
Apparent impedance symmetrical current component,
Carrier current, 477
of distance relay, defined, 258 CCVT,30-32 defined, 78
Argand diagrams, 283-285 Circuit breaker, 21-22, 77-84 vacuum, 77
Asymmetry factor, 155-156 air, 77, 82-83 Circuit switchers, 90-91
Automatic circuit reclosers, see arc extinction, 82-84 Clearing time, 7
reclosers, 84-89 asymmetrical current, defined, 78 Coherent logic, 1113-1125
Automatic line sectionalizer, see asymmetry factor, 81 2-relay system, 1114-1116
sectionalizer, 89-90 compressed-air, 84 3-relay system, 1116-1118
control circuit, 21 analysis, 1118-1125
B de current component, defined, 78 Comparator, 127-139
Backup, 8 definitions, 77-79 alpha and beta planes, 129
relays, defined, 9-10 designs, 82-84 amplitude, 128-129, 132-133
Blocking, 489-492 fluids, 82-83 distance relay, 135-137
directional comparison, 490-492 graph of operating time, 79 general equations, 129-132
scheme, direct, 489-490 latching current, defined, 78 phase, 133-135

1295
Index
1296

optical,32-34 frequency response, 118


Comparator, (Continued)
optical, types, 34 linear transformations, 117
phase and amplitude, 128-129
polarity conventions, 29 periodic sequences, 118-1 19
relay design, 127
saturation,23-29,159-160 phasor method, 121-123
Compensation theorem, 186-189
ANSI standard accuracy class relaying applications, 123-125
applications, 189-193
method, 23-24 Directional comparison, 490-495
Complex line protection, 531-570
ANSI standard CT accuracy blocking, 490-492
multiterminal lines, 539-546
class method, 25-27 ground fault protection, 495
mutually coupled lines, 547-570
excitation curve method, 25-26 high speed reclosing, 494-495
single-phase switching, 531-539
power swing blocking, 495
Complex Z and Y loci, 283-314 formula method, 26-27
simulation method, 28-29 selectivity, 493-494
admittance inversion, 296-299 switch-onto-fault function, 495
circle equations, 294-296 C-Rating, 159-160
unblocking, 492-493
conformal mapping, 307-308 terminal markings, 29
Disjoint, 1005-1006
half plane mapping, 287-293 wye connection, 30
Digital relay applications, 123-125
impedance at the relay, 312-314 CTl, coordination time interval
distance protection, 123
impedance inversion, 284-286 defined,228
example, 125-126
inversion of a circle with center at Cnrrent
generator protection, 124
(1,0),302-304 let-through,47
Kalman filter, 125
an arbitrary circle, 304-306 Current transformer, see CT
transformer protection, 124
an arbitrary straight line, Cutout
logic, also see relay logic
301-302 distribution, 44-45
Distance protection, 257-268,
line through (1,0),299-301 379-417
line and circle mapping, 286--293 D analysis, 379-417
line equations, 293-294 Definitions description, 257-268
orthogonal trajectories, 308-312 protection, 9-10 Distance relay, 57-58, 257-268
properties of, 286-287 Degree of series compensation apparent impedance
summary of line and circle defined, 576 ground faults, 389-394
inversions, 307 Digital relay logic, 115-126 line-to-line line fault, 386--389
with respect to the unit circle, 285 Kalman filter, 125 three-phase line fault, 382-386
Connection overcurrent, 123 typical Z plane plots, 400-406
90 degree, 20 substation protection, 124 characteristics, 257-262
Contacts, 18 transformer protection, 124 coordination, 57-58, 412-414
a,18 generator protection, 124 dependence on system parameters,
b, 18 unique concepts, 124-125 258-260
back, 18 Walsh function, 125 effect of fault resistance, 265-267
front, 18 Digital circuit, 91-93, 109-112 ground protection, 410-412
graphic symbol for, 18 sampling of analog signals, R-X plane display, 259
normally closed, 18 109-110 reach, as a function of system
normally open, 18 the AID converter, 110-112 conditions, 259-260
Control configuration, redundant, 35 Digital fault recorders, 91-93 sequential tripping, 258
Control circuit, 19-21,35 Digital logic circuits, 104-112 settings, GCX example, 406-410
de, 19 AND,105 trip threshold, 258
dc, for circuit breaker, 20 buffer, 107 types, 261-262
series trip, 21 exclusive OR, 106 underreach,259-260
typical configurations, 35 flip-flop, 109 zoned,262-265
X-Y, 21 graphic symbols, 105 Distribution feeder, 201-207
Coordination NAND,108 coordination, 203-207
defined,9 NOR, 107 main and lateral, 202
Coordination time interval (CTl) normal,104 sectionalizing, 202
defined, 231 NOT,107 also see "Radial"
CT and VT graphic symbols, 17-18 OR,106 Distribution transformer
CT, 17-18,24,29-34,230-231 reversed, 104 fusing, 202
time delay, 108 Disturbance, 11-12, 1093-1104
burden defined, 24
Digital relay, 120-126 classification of, 11-12,1097-1099
bushing type, 29-30
Digital signal processing, 116--120 defined, 11
delta connection, 31
common discrete sequences, 116 joint probability density, 1104
equivalent circuit, 24
data window method, 120-121 probabilistic model, 1093-1096,
graphic symbol for, 18
fast Fourier transform, 119-120 1099-1104
markings, 29
Index 1297

probability distribution, 1096-1097 niles and methods of analysis, types, 44-48


also see "System disturbance" 1158-1169 types K and T, 50-52
system nomenclature, 1159 vacuum, 46
E system parameters, 1165-1169 zero current clearing, 46
Environmental effect in protection transmission protection, Fusing, special, 47-48
analysis, 1115 1169-1193 capacitor banks, 47-48
breaker failure, 1175-1180 parallel, recommendation, 48
F functional specification,
Fail dangerous, 1109 1169-1173 G
Fail safe, 1109-1110 minimal cut sets, 1198-1199 Generator protection, 713-745
Failure protection failure, 1180-1193 bearing failure, 738-739
control of, 4 special cases, 1199-120 I breaker failure, 743-745
definitions, 1027 the top event, 1173-1175 coolant failure, 739
Failure modes, 1027-1028, Fault trees, 1052-1064 excitation, loss of field, 732-737
1109-1116 analysis methods, 1054-1055 induction generator effect, 732
definition, 1027-1028 component failures, 1055-1057 loss of field, 732-737
dual, 1108-1109 construction, 1057-1060 fire protection, 739
operational (fail dangerous), conventions, 1053-1054 loss of plant auxiliaries, 739-740
1109-1110 decision tables, 1060-1062 loss of voltage measurement, 739
optimization, 1110 signal flow graphs, 1062-1064 motoring, 737-738
security (fail safe), I J09-1110 systems and components, 1055 overspeed,737
Failure to trip Faults on power systems, 147-160 rotor protection, 728-731
defined,lO calculation of,I 50-I 52 grounded field winding,
False tripping characteristics of, 148-149 729-731
defined,lO near synchronous machines, open field winding, 731
Faraday effect, 32-33 152--159 overheated field winding, 731
Fast Fourier transform, 119-120 FM, see frequency modulation shorted field winding, 729
Fault characteristics, 148-J52 Frequency, effects of, 807-847 stator, 715-728
Fault current, 150-159 also see "system frequency" backup protection, 728
initial dc component, J58 Frequency modulation, 508-509 ground fault, 717-724
measurement of, 150-151 for pilot communications, 509 open circuit, 724-725
near synchronous machines, principles of, 508 overheating, 725
152-J59 Front contacts, also see "contacts," 18 overvoltage, 726
synchronous generator, example, Function numbers phase fault, 716-717
155-157 of devices, 17-18 turn to turn fault, 724
unloaded generator, 157 Fuse, 44-56,220-222 unbalanced current, 726-728
Fault current computation, 168-172 characteristics, 44-56 stator protection, 715-728
description, 168-169 coordination, 51-55 summary, 740-745
2 line-to-ground, 170-171 example, 55-56 types of protection, 714-715
3-phase, 169-170 current limiting, 46-47 unit generator-transformer
line-to-line, 171 cutout, 44-45 protection, 740-743
II-port sequence network, 168-169 defined,46-48 overview, 740-741
one line-to-ground, 171-172 distribution, 44 protective devices, 742
Fault recorders E rated, 48-49 trip modes, 742-743
digital,91-93 electronic, 48 vibration, 738
Fault tree analysis of protective expulsion, 46 Graphic symbols, 17-18
systems, 1157-1201 filled,46 Ground fault protection, 270-277
analytical methods, 1158-1169 heating and cooling cycles, characteristics of, 271-272
conditional intensities, 1162-1163 220-222 importance of, 270-271
parameters, 1159-1163 link, described, 45 relay polarization, 272-276
unavailability, 1162 link, example of, 45 types of ground relays, 276-277
unconditional intensities, power, 44, 49 Ground relay polarization, 272-276
IJ59-1161 protected, 52 using current, 273-276
evaluation, 1193-1201 protecting, 52 using voltage, 272-273
expected number of failures and ratings, 48, 49
repairs, 1161-1162 special types, 47, 48 H
minimal cut set parameters, speed ratio, 50 High-voltage direct current (HVDe)
1163-1165 time-current characteristics, 48-55 protection, 913-952
1298 Index

HVDC ac side protection, 936--938 problems, 782-788 Load imbalance definition, 836-837
ac bus, 937 external hazards, 783-788 relay characteristics, 835-846
ac line, 936--937 low supply frequency, 787 relay connections, 846--847
converter transformer, 937 low supply voltage, 786--787 turbine protective margin, 844-846
filters and reactive support, 938 reversed phase sequence, 787 Load shedding protection, 834-846
HVDC conversion, 913-929 single phasing, 785-786 criteria, 835-836
basic control concepts, 926--929 stalling due to excessive design concepts, 839-844
control structure, 931-934 load,787-788 example, 837
converter station design, 929-936 unbalanced supply voltage, example illustrating settings,
inverter operation, 921-924 784-785 838-839
multibridge converters, 924-926 internal hazards, 782-783 Local backup relays
protection categories, 936 defined,lO
starting performance, 763-769
protection philosophy, 934-935 Logic
thermal model, 773-782
rectifier operation, 914-921 defined, 97
electric analog, 776
HVDC dc protection, 938-948 Logic analog, 99-104
limits, 779-780
commutation failure, 940-941 active filter, 103
lumped,775-777
converter overcurrent, 939-940 comparator, 100-101
parameters, 777
de filter, 947 electronic, 99-112
performance, 777-779 integrator, 102-103
dc harmonics, 943
thermal relay, 780-782 isolator, 100-101
dc line, 944-945
Induction motor analysis, 752-769 level detector, 100-102
dc minimum voltage, 945-946
normalization, 753-754 op amp, 100
dc overvoltage, 946
de side differential, 944 symmetrical component summer, 102
electrode open circuit, 947 transformation, 754-756 Logic, digital, 104-112
excessive delay angle, 942 the swing equation, 752 AID, III
pole dc differential, 946--947 Inspected system modeling, AND,105
valve misfire, 941 1211-1226 Boolean, 104-105
valve short circuit, 939 Instrument transformer, 17-18,23-34 buffer, 107
valves, 939-943 analysis, 23-34 exclusive OR, 106
VDCOL, 947-948 connections, 28-34 flip-flop, 109
voltage stress, 941-942 graphic symbols, 17-18 NAND,108
HVDC fundamentals, 913-929 selection, 23-28 NOR,107
HVDC protection, 913-952 NOT, 107
ac side, 936--938 K OR,I06
de side, 938-948 k-out of-n G systems, 1220-1226 sampling, 110
dynamic overvoltage, 950-951 time delay, 108
reverse power, 949 l Long transmission line, 445-465
self-excitation, 950 isolated line, 445-447
Line fault
settings, 951-952 equations, 445
analysis, 380-381
torsional interaction, 949-950 ABCD parameters, 446-447
definition of d phasor operators,
mutually coupled lines, 447-453
392
distance parameters, 447-451
equivalent circuit, 380
Impedance,317-349,356 identical parameters, 451-452
ground, 389-394 representation, 453
input, 356
one-line-to-ground, 389-392 Equivalent circuits, 453-461
seen by relay, 317-319
tabulation of results, 391 admittance matrix, 453-457
Impedance matrix, line, 420-430
phase-to-phase, 386--389 type I equivalent, 459-460
mutual symmetry, 427
tabulation of results, 388 type 2 equivalent, 460-461
of a transposed line, 423
sequence network reduction, type 3 equivalent, 457-459
Importance, 1066, 1071
Induction motor, 751-799 381-382 solution for long lines, 461-465
accelerating torque, 761-763 three phase, 382-386 sequence networks, 461-463
analysis, 752-769 tabulation of results, 386 sequence impedances, 463-464
equivalent circuits, 756--761 two-line-to-ground, 392-394 currents and voltages, 464-465
heating, 769~782 tabulation of results, 394 Loss of synchronism protection,
conduction, 769-772 Line impedance, 167-168,420-423 894-902
fundamentals, 769~773 earth resistivity, 422 circuit breaker considerations, 901
convection, 772-773 equations, 167-168 out-of-step blocking and tripping,
radiation, 773 matrix, self and mutual, 420-423 898-901
Index

out-of-step detection, 897-898 phase fault, 790-791 Type


out-of-step performance, 894-897 reversed phase rotation, 794 568--569
out-of-step relaying practice, synchronous, loss of excitation, Type 3, distance protection, 570
901-902 795
pilot relaying considerations, 901 synchronous, loss of o
synchronism, 795 Operational amplifier, 99-100
M synchronous, supply voltage Optical cables
M matrix, 317-322 restoration, 795-796 described, 37-38
for relay impedance, 317-319 unbalanced supply voltage, 794 splicing, 38
M parameters, 319-322 undervoltage, 793-794 Optical communications, 36-39
Markov modeling, 1205-1245 Multiterminallines, 539-546 Optical fiber transmission, 36-37
abnormal unavailability, 3-terminal example, 543-545 interstation, 38
1233-1241 common configurations, 540-541 intrastation, 38
modeling inspected systems, distance protection with three Optical transducers, 37
1211-1226 Optical transmission, 37-38
terminals, 542-543
monitoring and self testing, attenuation properties, 37
pilot protection, 545-546
1226-1230 modes, 37
Mutual coupling, 419-465
safeguard systems, 1241-1243 sensor requirements, 38
basic equations, 419-420
testing, protection, 1206-1211 OR logic, 106
effect of, 430-437
unreadiness probability, 1230-1233 Overcurrent relay
equivalent circuit for short lines, described, 56-57
Measurements, 17-39 437-444
circuit breaker controls, 21-22 need for directional element,
equivalent circuits for transformers, 250-252
control configurations, 34-36 439
graphic symbols, 17-18 time dial, 230-231
equivalent networks Type I, 2, and
instrument transformers, 23-34 p
3,439-443
optical communications, 36-39
examples of, 430-437 Phase comparison, 499-507
relay connections, 18-21
general network equivalents for described,499-501
Minimum operation current (MOC),
short lines, 437-439 dual, transfer trip, 503
229-233
general network equivalents for dual, unblocking, 502
computed example, 233
long lines, 453-461 segregated, 504-507
defined,229
line impedances, 420-430 single, blocking, 501-502
Monitoring and self-testing,
short lines with susceptance, Phasor measurement, 73-74
1226-1230
443-444 Pilot protection, 469-527
modeling of inspected protective
solution of the long line case, EHV line example, 509-515
systems, 1211-1226
461-465 description, 510-515
testing of protective systems,
Type I networks, 439-441 general considerations, 509-510
1206-1211
Type 2 networks, 442 general description, 470-472
k-out-of-n G systems,
Type 3 networks, 442-443 monitoring pilot performance,
1220-1226 525-527
optimal inspection interval, Mutual impedance
lattice network equivalents, non-unit pilot schemes, 482-499
1212-1217 blocking and unblocking,
redundant system optimization, 437-439
Mutual induction 489-493
1217-1220 directional comparison, 482
Motor classifications, 788-790 air-core transformer equivalent,
directional comparison
by location, 789 420
selectivity, 493-494
by service, 788-789 equivalent circuit for, 420
distance schemes, 482-483
Motor protection, 790-799 Mutual induction, basic equations, 419
hybrid schemes, 495-499
bearings, 797 Mutually coupled lines protection,
other features, 494-495
for large motors, summary, 547-570
transfer trip schemes, 484-489
798-799 measurement errors on the parallel physical systems, 472-481
multifunction, 797 line,566-568 classifications, 481
rotor, 796-797 Types 1,2, and 3 defined, 547-548 communications selection, 480
heating, 796 Type I, ground distance protection, communucations problems,
problems in detection, 796-797 548-568 480-481
standards for, 751 guidelines for settings, 557-562 fiber-optic pilot, 479
stator, 790-796 reach error, 554-557 general concepts, 473-475
ground fault, 791 Zone 2 settings, 562-563 microwave pilot, 478-479
locked rotor, 791-792 Types 1.1, 1.2, and 1.3, 551-554 PLC pilot, 477-478
overload,792-793 Type 1.3 problems, 563-567 wire pilot, 475-477
1300 Index

Pilot protection, (Continued) Protection design considerations, 8-9 example of relay coordination,
pilot settings, 515-522 Protection equivalent 232-235
current reversal, 519-520 M parameters, 319-322 heating and cooling of fuses, 222
distance element, 516-517 Protection logic, coherent, 1113-1125 instantaneous relay setting
echo keying, 520-521 analysis, 1118-1125 example, 238-239
instrumental transformer, 516 defined, 1113-1114 protective strategy, 218-220
loss of potential logic, 521 2 relay system, 1114-1116 Recloser-relay coordination, 223-224
maximum torque angle, 516 3 relay sustem, 1116-1118 Relay coordination, 225-239
phase overcurrent, 517-518 Protection of series compensated Relay coordination procedure, 226
residual overcurrent, 518-519 lines, 575-642 setting instantaneous relays,
switch onto fault, 519 Protection strategy, 8 235-237
weak infeedlogic, 521 Protection zones Radial system study, 203-207
traveling wave relays, 522-525 defined,9 available fault current, 203
unit schemes, 499-509 Protective device data requirements, 204
longitudinal schemes, 507-509 ratings, 44 protective equipment data, 205
phase comparison, 499-507 Protective device characteristics, step-by-step procedure, 207
PLC, power line carrier, 477 43-93 substation data requirements, 204
Polarization circuit breakers, 77-84 system data, 205
of ground relays, 272-276 fault recorders, 91-93 Radial system, coordination example,
Potential transformers, see voltage fuses, 44-56 211-214
transformers, 18,30-32 reclosers, 84-89 Random variables, 1010-1026
Power circuit breakers, 77-84 relays, 56-77 common distribution functions,
definitions, 77-79 sectionalizers, 89-90 1015-1023
design, 82-84 switches, 90-91 continuous distributions,
ratings, 79-82 Protective device operation, 7 1013-1014
Power line carrier, 474, 477-478, Protective relaying definitions, 1010-1011
defined,9 discrete distributions, 1012-10 13
511-513
Power system characteristics, 147-193 moments, 1014
R random vectors, 1023-1024
available fault current, 168-172
Radial distribution coordination, stochastic processes, 1024-1026
compensation theorem, 186-189
203-207 the density function, 1011-1012
applications, 189-193
Radial line the distribution function, 1011
faults, 147-160
ILG fault, 210 Reactionary devices, 4-6
faulted system equivalents,
2LG fault, 209-210
172-186 Recloser, 84-89
branch fault example, 217-218
solutions, 193 defined,84
branch faults, 215-217
line impedances, 167-168 definition of operating times, 85
delta- and wye-connected systems,
station arrangements, 160-166 electronic, block diagram of, 88
208
Power system equivalent circuit, see ratings, 85
example of fault calculations,
system equivalent, 172-186 time-current characteristics, 85-89
211-215
Prevention set, 1071 Reclosing, auto, 873-894
fault current calculation, 207-218
Primary relays advantages of high speed, 875
fault impedance, 209
defined,9 arc deionization, 880-881
L-L fault, 210
Primitive impedance at generator buses, 889-894
line impedance formula, 209
defined,421 main line faults, 208-215 bus protection vs. line protection,
Probability distribution, 1015-1023 normalization of impedance, 209 889
binomial,1015-1019 positive sequence impedance, 209 definitions, 877-879
exponential, 1022-1023 summary of fault current formulas, delayed, 889
nonnal,1019-1020 211 description, 873-875
Poisson, 1017-1018 three-phase faults, 209 digital devices, 887-888
uniform, 1015, 1020 zero sequence line impedance, 210 disturbance considerations,
Weibull, 1020-1022 Radial line protection, 201-239 875-877
Programmable logic device, 126 Radial system fault types, 876-877
Protected component, defined, coordination example, 226-228 voltage levels, 876
1105-1106 coordination of phase and ground number of reclosures, 877
Protection, 4-7 relays, 228-232 probability of success, 877
economical design, 4 coordination of reclosers and fuses, switching options, line and bus
reactionary, 4-6 220-225 check systems, 889
safeguards, 6-7 example of recloser-relay switching options, single-phase
Protection design concepts, 469-470 coordination, 224-225 switching, 888
Index 1301

Reclosing relays, 882-888 M parameters, 319-322 NOR, 107


breaker operation considerations, phase comparison, 344-349 NOT, 107
882-884 the faulted system, 332-336 OR,106
multi shot, 886 the unfaulted system, 330-332 sampling, 109-110
single shot, 884-886 Z loci, 322-323 time delay, 108
synchro check, 886-887 Relay characteristics, 56-75 hybrid relay logic, 126-127
Relay, 43-75, 127-139 Relay connection Relay problems due to series
adaptive, 73 typical, 18-21 compensation, 611-632
as a comparator, 127-139 Relay control configurations, 34-36 mutual induction, 624-625
blinder, analysis of, 65-66 Relay logic, 97-139 phase unbalance, 613
characteristics, 56-75 analog relay logic, 112-115 reach measurement, 625-632
differential, 57, 70-71 directional comparison pilot, subsynchronous resonance (SSR),
digital,71-77 114-115 , 613-614
advantages of, 73 instantaneous overcurrent, transient phenomena, 611-613
configuration, 74-75 112-113 voltage and current inversions,
functional block diagram, 74 phase comparison distance, 614-622
history of, 72-74 112-114 voltage inversions, 623-624
directional, 57 definitions, 97-98 Relay characteristics, 60
distance, 57, 394-406 digital relay logic, I 15-126 induction disk, 60
electromechanical, 59-66 description, 115-116 solenoid type, 60
balanced beam, 64 digital signal processing, Relay tap, 41, 230, 276
induction cup, 64-65 116-120 Reliability, 1003-1245
induction cylinder, 65-66 linear transformations, 117 analysis, minimal eut sets, 1078
induction cylinder, blinder, 65 frequency response, I 18 minimal path sets, 1078-1079
induction disk, 60-64 periodic sequences, 118-119 reliability bloek diagrams,
directional overcurrent, 64 fast Fourier transform, 1072-1073
equations of motion, 61-62 119-120 structure functions, 1076-1078
instantaneous, 60 data window method, 120-121 success trees, 1073-1074
inverse overcurrent, 63 phasor method, 121-123 truth tables, 1074-1076
inverse overcurrent. numerical protection applications, basic concepts, 1003-1039
123-125 coherent logic, 1114
parameters, 63
overcurrent, 123 Markov process, 1079-1087
inverse overcurrent, time-current
distance, 123 basic concepts, 1079-1081
curves, 63
transformer, 124 failure frequency and duration,
nondirectional, 56
generator, 124 1085-1087
overcurrent, 56
substation, 124 general algorithm for
overcurrent, characteristics, 57
other types, 124 computation, 1082-1085
percentage differential, 70-7 I
unique concepts, 124-125 model of two repairable
pilot, 58
example, 125-126 components, 1084-1085
solenoid type, 60
electromechanical logic, 98-99 special failure modes, 1085
static, 66-70
overcurrent, 98 stationary state probahilities,
advantages of, 66
distance, 98-99 1081-1082
overcurrent, 67-68
electronic logic circuits, analog, probability fundamentals,
typical characteristic curves, 69
99-104 1004~101O
Relay apparent admittance, 355-372
active filters, 103 classes and partitions,
admittance characteristics,
comparator, 100-102 1006-1007
359-364
integrator, 102-103 combinatorial rules, 1007-1010
example, 360-364 isolator, 100 events and experiments,
admittance diagrams, 355-356 level detector, 100-102 1004-1005
input loci, 356-359 op amp, 99-100 the axioms, 1004
parallel lines, 364-368 summer, 102 Venn diagrams, 1005-1006
summary, 371-372 electronic logic circuits, digital, random variables, 10 I0-1 026
Y plane characteristics, 368-371 104-112 Reliability concepts in protection,
Relay apparent impedance, 317-349 AID converter. 110-1 12 1093-1152
a special case, 336-340 AND,105 system disturbance models,
construction of M circles, 323-329, Boolean logic, 104-105 1093-1097, 1099-1104
340-344 buffer, 107 disturbance classifications,
equivalent 2 port, 329~336 exclusive OR, 106 1097-1099
for distance relays, 394-406 flip-flop, 109 disturbance density and
mathematical model, 317-319 NAND,108 distribution, 1099-1 103
1302 Index

system disturbance models, Reliability, 1003-1245 Series capacitors, unbypassed


(Continued; analysis, 1043-1087 578-590
disturbance distribution, basic concepts, 1003-1039 end-of-line capacitors, 578-586
1095-1097 concepts in protection, 1093-1152 bus-side voltage, 578-585
disturbance joint density, 1104 fault tree analysis, 1157-1201 line-side voltage, 585-586
general probabilistic model, Markov models, 1205-1245 mid-line capacitors, 586-589
1093-1095 Reliability specifications conclusions regarding effects,
time dependent models, 1104--1142 for transmission protection, 589-590
coherent protection logic, 1138-1142 Series compensated line protection,
1113-1125 Reliability state space, 632-635
protection vs. protected frequency and duration, 1085-1087 current phase comparison, 632
component, 1105-1106 general algorithm, 1082-1084 directional comparison schemes,
Markov processes, 1079-1081 632-635
protective system analysis,
special failure modes, 1085 hybrid schemes, 632-633
1125-1138
stationary state probabilities, distance schemes, 633-634
specifications for protection,
1081-1082 traveling wave schemes,
1138-1142
two repairable components, 634-635
system reliability concepts,
1084--1085 directional overcurrent ground, 635
1106-1113
Restoration strategy, 8 Series compensated line protection
time independent models,
problems, see Relay problems
1142-1152
composite protection systems, s due to series compensation
Series compensated line protection
1148-1152 Safeguard devices, 4-6, 1241-1245
Saturation, experience, 634--635
failure distributions, 1143-1148 autoreclosing problems 637
Reliability block diagram, 1043-1052, ofCT's, 23-28, 62, 71,150-151,
effect of transient phenomena, 636
1125-1138 159-160,516,613,637,647,
effect of phase impedance
common control and bus 649-657,662,664--670,791
unbalance, 636
arrangements, 1125-1138 of relays, 62
effect of voltage and current
of common protective systems, of power transformers, 682-685,
inversions, 636
1043-1052 695
effect of fault location error,
Seal-in relay, 19
bridge networks, 1049-1050 636-637
Sectionalizers, 89-90
cut sets, 1050-1052 effect of transducer error, 637
application example, 90
parallel systems, 1046-1047 recommended system studies, 637
Security, 7
series systems, 1044-1045 Series compensation, reasons for,
defined, 9 575-576
series-parallel and parallel-series
failure, 1028 Short circuits, also see "faults," 4-6,
systems, 1047-1048
Selectivity, 8 11-12
standby systems, 1048-1049
defined, 9 Shunt reactor protection, 700-704
Reliability evaluation, 1064-1071
Sensitivity, 9-10 dry type, 701-702
Boolean algebra, 1069 defined, 9
qualitative analysis, 1064-1067 oil immersed type, 702-704, 888,
Series capacitor bank protection, 891
quantitative analysis, 1067-1071 590-611 Single-phase switching, 531-539
system availability, 1067 bank configuration, 59·1-592 control of secondary arcs, 532-536
system reliability, 1068 bypass systems, 592-598 secondary arcs, untransposed lines,
system unavailability, 1068 bypass gaps, 593 536-539
system unreliability, 1068 metal oxide varistors, 594--595 single-phase switching, 888, 891
Reliability model of protection, gaps and varistors, 595-596 Speed ratio, 50-51
1104--1152 typical system, 597 defined,50
time independent, 1104--1142 fundamental frequency varistor examples, 51
time dependent, 1142-1152 model,598-601 Subsynehronous resonance, 955-992
Reliability models, 1028-1039 relay quantities including bypass, also see SSR
constant failure and repair rate 601-604 history of SSR, 962-963
model, 1037-1039 effect of system parameters, overview of problem, 955-963
definition of reliability, 1028-1032 604-611 example, 957-958
the failure process, 1029-1030 assumptions, 604-606 mathematical model, 956-957
the hazard rate, 1030-1032 external impedance, 606-608 spring-mass model, 959
the repair process, 1032-1034 source impedance, 608 SSR system countermeasures,
the whole process, 1034-1037 fault impedance, 608-611 963-969
Index 1303

generator and system synchro-check relays, outage, 5


modification, 968-969 886-887 restorative, 5
generator circuit resonance, reclosing switching options, Static var compensator, also see SVC,
969 888-889 673-674,705,863,866,963,
turbine-generator bus vs, line protection, 889 975
modification, 968-969 dead line-live bus, 889 Station arrangement, 160-166
network and generator controls, delayed reclosing, 889 4 x 6 network, 166
964-968 live line-dead bus, 889 breaker-and-a-half, 164
capacitor voltage control, single-phase switching, 888 breaker-and-a-third, 166
964-965 reclosing at generator buses, crossed ring, 166
system switching, 964 889-894 double bus, double breaker, 163
thyristor controlled loss-of-synchronism protection, double bus, single breaker,
capacitors, 965-968 894-902 162-163
unit tripping, 968 circuit breaker considerations, main and transfer, 161-162
SSR unit countermeasures,
901 pyrimid, 166
969-992
out-of-step blocking and ring bridge, 166
filtering and damping, 970-977
tripping, 898-901 ring bus, 163-164
dynamic filters, 973-974
out-of-step detection, 897-898 ring tripod, 166
dynamic stabilizers, 974-976
out-of-step relaying practice, single bus, single breaker, 160-161
excitation system dampers,
901-902 Strategy, 8
976-977
pilot relaying considerations, protection, 8
line filters, 971-973
901 restoration, 8
static blocking filters,
system out-of-step performance, Substation computer, 75-77
970-971
894-897 block diagram, 76
unit relaying and monitoring,
977-992 protection requirements, hierarchy, 75
comments on SSR relays, 896-897 Subsynchronous resonance, 955
992 representation in the Z plane, SVC protection, 704-708
SSR monitors, 990-992 894-896 Switching stations, see "station,"
SSR protective relays, review of fundamentals, 853-862 Synchro-check relay, 886-887
977-990 definitions, 853-854 Synchro-verifier relay, 887
armature current relay, effect of impedance, 854-855 Synchronous motor, 788
978-982 the swing equation, 858-862 loss of excitation, 788
subsynchronous current two-port representation, loss of synchronism, 788
relay, 982-990 855-857 System disturbance model, 1093-1104
Stability, 853-909 special protection schemes, disturbance classifications,
automatic reclosing, 873-894 902-909 1097-1099
introduction, 873-874 design procedure, 904-905 disturbance distribution,
need for fast reclosing, 875 critical conditions, 904 1096-1097
disturbance considerations, operator control, 905 disturbance joint density, 1104
875-877 recognition triggers, 904 example with 3 bus system,
fault types, 876-877 disturbance events, 903-904 1099-1103
voltage levels, 876 example of an SPS, 905-909 probabilistic disturbance model,
reclosing considerations, SPS characteristics, 902-903 1093-1096
877-881 system transient behavior, 862-873 probabilistic model distribution,
arc deionization, 880-881 effect of power transfer, 1099
definitions, 877-879 864-867 System protection equivalent,
number of reclosures, 877 effect of circuit breaker speed, 172-186
reclosing success, 877 867-868 4 port, 185-186
reclosing relays, 882-888 effect of reclosing, 868 3 port, 184-185
breaker operation, 882-884 relay measurements during 2 port parameters, 178
digital reclosing and transients, 868-873 2-port representation, 174-176
synchro-check relay, stability of test system, 863 2-port equivalent, 176-178
887-888 State, 4-5 for protection studies, 172-186
multishot reclosing relays, abnormal,5 for series faults, 179-180
886 action, 5 general description, 172-173
single-shot reclosing relays, block diagram, 5 line with shunt fault, 178-179
884-886 nonnal,5 multiport, 183-186
1304 Index

System protection equivalent, distribution function, 1143-1148 regulating transformer protection,


(Continued) parallel logic, 1144- 1145 699-700
numerical example, 181-182 sequential logic, 1147-1148 shunt reactor protection, 700-704
open-circuit impedance matrix, series logic, 1143-1144 discussion, 700-701
173-174 standby logic, 1145-1147 dry type reactors, 701-702
series faults, 179-180 probability distribution, 1143 oil immersed reactors, 702-704
two port, 176-177 Transfer trip, 484-489 failure modes, 702-703
System frequency, 807-847 direct overreaching, 487-488 protection practices,
abnormal frequency, 807-847 direct underreaching, 484-486 703-704
effect of overfrequency on permissive overreaching, 488
static var compensator (SVC)
turbines, 808 permissive underreaching, 486-487
protection, 704-708
effect of underfrequency on Transformer fault protection,
discussion, 704-705
turbines, 808-810 philosophy, 680-681
SVC protection requirements,
effect on generators, 808-809 Transformer faults, 674-681
705-708
effect on turbines, 810-813 external,674--675
internal,675-680 typical SVC system, 705
operation, 807
load shedding protection, 834--847 internal, active, 676-680 transformer and line combined
off normal, load shedding, 834 internal, incipient, 675-676 protection, 697-699
off-normal protection, 831-832 Transformer protection, 673-708 examples, 697-698
off-normal turbine protection, discussion, 673-674 non-unit protection schemes,
832-834 magnetizing inrush, 681-684 698
System under frequency protection, current harmonics, 683-684 unit protection schemes,
834-847, also see "load current magnitude, 681-683 698-699
shedding," 835 in parallel banks, 684 transformer faults, 674-681
typical turbine protection, 834-835 protection against active faults, external faults, 674-675
System frequency response model, 687-697 fault protection philosophy,
813-831 differential protection 680-681
effect of connections, 687-690 internal faults, 675-680
damping, 825 current transformer ratios,
active faults described,
disturbance size, 819 688-689
676-680
governor droop, 821-822 delta-wye bank CT
incipient faults, 675-676
high pressure fraction, 823-824 connections, 687-688
Transmission faults, bypassed series
inertia, 822-823 example, 689-690
capacitors, 601-604
reheat time constant, 823 differential protection
discussion, 690-695 Transmission fault, series
mathematical model, 813-831
autotransformer protection, compensated line, parameter
normalization, 819-820
694--695 effects, 604-611
refinements, 827-829
slope of response, 820-821 differential relay problems, Transmission faults, unbypassed series
validation, 825-826 695 capacitors, 578-590
various model comparisons, parallel transformer banks, center line capacitors, 586-589
829-830 694 conclusions, 589-590
System state, see "state" percent slope of differential discussion, 578
relays, 690-692 end-of-line capacitors, bus side
T suppression of magnetizing voltage, 578-585
Threshold (of protective action), 5, inrush, 692-693 end-of-line capacitors, line side
7-9 three-winding transformer voltage, 585-586
Time (of protective action), 7, 471 protection, 693-694 Transmission line, mutual induction,
action, 7 overcurrent protection of 423-453
clearing, 7 transformers, 695-696 long line, 445-453
comparison, 7 ground fault protection of
short line, 423-424
decision, 7 transformers, 696-697
Transmission line fault
operating, of protective equipment, protection against incipient faults,
analysis of, 379-394
471 684-687
Transmission line mutual impedance
Time constant external incipient faults,
684-685 example of 500 kV line, 425-428
of fault current decrement, 149
overheating, 684-685 Transmission protection, 249-278
Time to failure
as a random variable, 1143 overfluxing, 685-686 distance relay protection, 257-268
composite protection system, internal incipient faults, distance relay characteristics,
1148-1152 686-687 257-262
1305

zoned distance relays, 262-265 example of loop DC relay v


effect of fault resistance, coordination, 253 Varistor, fundamcntal frequency
265'-267 example of looped system modcl,598-601
summary of distance concepts, coordination, 255-257 Voltage inversion
267-268 loops with multiple sources,
example, 433
ground fault protection, 270-277 254'-257
in mutually coupled transmission
importance, 270-271 DC relay procedure, 255-257
lines, 431-433
Trip free, 21-22
ground fault characteristics, Voltage profile, on series compensated
Type I networks
271-272 lines, 577-578
dcfincd,439-440
polarization of ground relays, Voltagc transformer, see VT, 30, 32
with fault on one line, 441
272-276 Typc 2 networks Voltage transformer descriptions,
voltage polarization, defincd, 442 30-32
272-273 Typc 3 networks Voltage transformers, 30-32
current polarization, defincd,442-443 graphic symbol for, 18
273-276
types of ground relays, 276-277 U w
introduction, 249-250 Unblocking, 489-493 Wire pilot systems, 475-477
directional comparison, 492-493
overcurrent relay protection,
250-257 Undesired tripping z
defined, 10 Z loci, 284'-293
loops with one source, 252-254
Unit protection line and circle mapping, 286-293
loops with multiple sources,
replica concept, 269 the liZ transformation, 284'-286
254'-257
Unit schemes, 499-509 Z R loci construction, 323-329
summary, 277-278
longitudinal differential, 507-509 k and 1fr circles, example, 328-329
unit protection, 268-270 phase comparison, 499-507 k circles, 324'-326
Transmission DC protection, 253-257 Unrcadincss probability, 1230-1233 Vf circles, 326-327

You might also like